PERFORMANCE

SPECIFICATIONS

USAID Ronald Reagan Building Floor Renovation Design Services

USAID Ronald Reagan Building Floor Renovation Design Services

United States Agency for International Development

FINAL SUBMISSION

12 APRIL 2018

STRATEGIC ANALYSIS FOR THE

United States Agency for

International Development

Final Submittal USAID Performance Specifications April 12, 2018 Page 1

TABLE OF CONTENTS

PERFORMANCE SPECIFICATIONS

OFFICE SPACE

ADMINISTRATOR’S SUITE

ENCLOSED OFFICES

ENCLOSED OFFICES

ENCLOSED OFFICES

ENCLOSED OFFICES

RESTRICTED OFFICE AREA

OPEN WORKSTATIONS

COLLABORATION SPACE

FOCUS ROOM/ PHONE BOOTH

SMALL CONFERENCE ROOM: 4 SEATS

MEDIUM CONFERENCE ROOM: 8-10 SEATS

LARGE CONFERENCE ROOM: 12-14 SEATS

X-LARGE CONFERENCE ROOM: 18-25 SEATS

POINT IV MEETING

RESTRICTED MEDIUM CONFERENCE ROOM: 8-10 SEATS

SUPPORT SPACE

ENROLLMENT/ BADGING

CLASSNET ACCESS

EVENT CENTER

GENERAL OFFICE STORAGE

MOTHER’S ROOM/ WELLNESS ROOM

PRINTER/ COPY/ MAIL DROP

SECURE CONFERENCE ROOM (SCIF)

file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070716 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070717 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070718 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070719 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070720 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070721 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070722 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070723 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070724 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070725 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070726 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070727 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070728 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070729 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070730 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070731 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070732 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070733 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070734 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070735 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070736 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070737 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070738 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070739 file://///ia-global.com/dfsroot/Projects/WashingtonDC/GSA/03GSAA.0060.000%20USAID%20RRB%20DIDs/Project%20Drawings/Design%20Process/1.Program/Room%20Data%20Sheets/2017-11%2010_USAID%20Perf%20Spec%20Final.docx%23_Toc498070739

USAID Performance Specifications April 12, 2018 Page 3

PERFORMANCE SPECIFICATIONS

OVERVIEW

OFFICE SPACEPERFORMANCE

SPECIFICATIONS

OVERVIEW

The performance specifications provided focus on the USAID workspace. The specifications establish a quality level in compliance with GSA’s PBS P-100 Facilities Standards for the Public Buildings Services. The intent is to provide future planners and contractors with a quality level and layout for pricing and constructing. Previous phases of the USAID Renovation project were certified LEED CI Silver, thus establishing a standard for consideration for the performance specifications .

The layouts are designed to be prototypical and provide a “basis of design”. The functions, materials, features, capacities and assemblies listed must be provided. The actual configurations may be adjusted to accommodate the site conditions and specific building envelope influences within the interior and that affect planning and construction.

Refinement of the “typicals” and the specifications as the project is designed is expected and improvements to the specifications or changes based on intended use may be required to meet USAID’s needs over the forecast duration of the project. Technologies, workstyles, materials and funding may affect the long-term implementation of the standards and result in adjustments to specifications and/or layouts.

Performance specifications for the building infrastructure is provided in the Prospectus Development Study (PDS). The PDS tasks include a survey of the building systems and reporting on the current conditions. The report lists the recommended upgrades to bring building systems up to current P-100 design standards and includes costs associated with each upgrade. The survey also assesses conditions known to be code or safety deficiencies and provides solutions to bring the systems up to code or current design and operating standards.

General overview for IT, AV, MEP, and Security requirements can be found in the PDS

The performance specifications include a floor and ceiling plan or “typical” layout in addition to a description using performance criteria to describe the assemblies, materials, features and functions required for each space type. The specification assumes the building infrastructure is able (as defined under the PDS) to meet the utility and infrastructure requirements necessary to support the room features and functions.

The specification is organized by the following space types:

Office

Workstation

Collaboration

Support

PERFORMANCE SPECIFICATIONSThe performance specifications provided focus on the USAID workspace. The specifications establish a quality level in compliance with GSA’s PBS P-100 Facilities Standards for the Public Buildings Services. The intent is to provide future planners and contractors with a quality level and layout for pricing and constructing. Previous phases of the USAID Renovation project were certified LEED CI Silver, thus establishing a standard for consideration for the performance specifications .

The layouts are designed to be prototypical and provide a “basis of design”. The functions, USAID Performance Specifications April 12, 2018 Page 4

USAID Performance Specifications April 12, 2018 Page 5

OFFICE SPACE

Administrator’s Suite

Enclosed OfficesOFFICE SPACE

Administrator’s Suite

USAID Performance Specifications April 12, 2018 Page 6

Administrator’s Suite

Item Specifications

Description Suite for the Administrator and the immediate staff, including the Deputy Administrator.

Space Requirement 7,800 SF

Adjacency Requirements TBD

Ceiling 24x24 high performance (fiberglass) acoustical ceiling tile (ACT) .90 noise reduction coefficient (NRC) minimum. Include drywall, acoustically rated bulkheads, STC 50, for 20% of the ceiling area for glazed partition connections.

Partition Types Provide a slab-to-slab STC 50 assembly with acoustical insulation for all partitions without glazing. Provide an STC 50 assembly above the ceiling from the bulkhead to the structural slab above glazed partitions. For any glazed partitions, provide a double-walled glass glazing system with an STC 44. Glazed partition locations to be determined during the final design.

Front wall: office front glazed aluminum storefront system with privacy film

Flooring Carpet Tile

Wall Finishes Front wall: privacy film on 80% of the glass surface All other walls: Paint Rubber base

Doors Solid core, wood veneer doors, aluminum frame, gaskets and thresholds. Interior doors to service areas such as toilet rooms, pantries, copy areas or storage room do not require gaskets and thresholds.

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, hold open door stops.

Glazing Aluminum Framed Interior Lights

Millwork Provide custom millwork pantry cabinets.

Provide a toilet room vanity cabinet with solid surface counter and undermount porcelain sink.

Mechanical HVAC zoning per P-100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical (4) Wall duplex receptacles 120v 20 amp. Duplex receptacles to be placed 6’ -12’ apart in open areas.

(4) Wall duplex receptacles 120v 20 amp per office.

(6) 120v 20 amp power outlets per workstation

(4) Wall duplex receptacles 120v 20 amp for the Pantry and copy room.

(2) dedicated power outlets 120v 20 amp for the copy equipment in the copy room

(2) dedicated power outlets 120v 20 amp for the refrigerator and an appliance circuit at counter height in the pantry

(1) duplex outlets behind each display device, except for projection screens, provide power and junction box for the screen motor. Display devices and/or projector and projection screen, lighting and window shades controlled by a “one -touch” room scene device flush mounted in the wall or integrated into the room’s AV control system.

Provide floor outlets and recessed raceways for under floor power and data cable to the table via recessed floor mounted wiring devices.

USAID Performance Specifications April 12, 2018 Page 7

Administrator’s Suite

Item Specifications

Lighting - 3-zone lighting system to provide over the conference table, ambient and accent lighting controlled by the one touch scene device. All fixtures LED.

- Provide broadcast LED fixtures permanently mounted in the large conference room.

- High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

- Desk Task Lamp for offices

Telecommunications

Telecommunications (Cont)

- AV connections in the conference rooms to include (2) network cables per display device terminated in the floor LAN closet. Provide 1 cable per 4 seats at each conference table terminated in the floor LAN closet.

- Provide a Plain Old Telephone Line POTS in the Administrator’s and Deputy

Administrator’s office.

- Wireless/ Voice over IP. (3) Voice/ Data cables per desk seat. Provide 1 additional cable drop in the Administrator’s office

- Provide 1 cable outlet for each copier or multi-function device (MFD) installed.

Plumbing Provide a stainless steel sink, garbage disposal, dishwasher and waterline for coffee maker and refrigerator ice machine with water filter.

Provide porcelain tile shower enclosure with terrazzo shower receptor, toilet and undermount lavatory. Ceiling Mounter Water Heater. Core Drilling for Water Feeds & SS to nearest Risers.

Structural Conference rooms shall be column free

Audio Visual - In each conference room, provide audiovisual system with secure video teleconference capabilities and enhanced teleconference audio with ceiling mounted speakers and microphones, mount location determined by room acoustics.

- Provide (2) wall mounted, remote controlled video cameras in addition to the

VTC cameras for video broadcasting from the large conference room.

Provide wireless microphone system and (4) wireless microphones.

- Display devices determined by room size and configuration. System to include desktop sharing functions.

- Provide commercial television feed and 70” minimum LED display in each office, wall mounted, articulating arm to adjust for viewing angles.

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment Cross cut shredder, Four single recycling bins, 22 gallon minimum capacity per bin

Accessories Occupant, Title and Division Identified with a modular sign system allowing names, titles an organization to be changed independently from each other.

Provide (2) portable podiums, one for each conference room.

Provide stainless steel toilet room accessories.

Special Requirements Include an allowance of 40% of the cost for construction of the Administrator’s Suite for suite upgrades to be determined during design.

Provide perforated veneer finished acoustical panels for 50% of the exposed drywall or hard surface of the conference rooms.

Security Provide a distress alarm button at the Administrator’s and Deputy Administrator’s desk and at two of the staff desks in staff area. Provide a card reader to control the entry doors and any secondary doors. Provide door release button at two of the staff positions and within office at each desk.

Other N/A

USAID Performance Specifications April 12, 2018 Page 8

Enclosed Offices

USAID Performance Specifications April 12, 2018 Page 9

USAID Performance Specifications April 12, 2018 Page 10

USAID Performance Specifications April 12, 2018 Page 11

Enclosed Office

Item Specifications

Description Enclosed space assigned to 1 individual

Space Requirement Size varies

Adjacency Requirements To be located in the interior

Ceiling 24x24 high performance (fiberglass) acoustical ceiling tile (ACT) .90 noise reduction coefficient (NRC) minimum

Partition Types Provide an STC 50 assembly on three sides with acoustical insulation Front wall: office front glazed aluminum storefront system with privacy film; special acoustically rated double paned glass partitions with door mat, extra gasketing, and drop bottom

Flooring Carpet Tile

Wall Finishes Front wall: privacy film on 50% of the glass surface All other walls: Paint Rubber base

Doors Solid core wood veneer doors, aluminum frame

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, hold open door stops. Coat hook in offices.

Glazing Aluminum Framed Interior Lights, non-demountable

Millwork N/A

Mechanical HVAC zoning per P-100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical (4) Wall duplex receptacles 120v 20 amp. Duplex receptacles to be placed 6’-12’ apart

Lighting - High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

- Desk Task Lamp

Telecommunications Wireless network/ Voice over IP.

2 cables per staff position

Plumbing N/A

Structural N/A

Audio Visual N/A

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment N/A

Accessories N/A

Special Requirements Occupant, Title and Division Identified with a modular sign system allowing names, titles an organization to be changed independently from each other

Security N/A

USAID Performance Specifications April 12, 2018 Page 12

Restricted Office Area

Item Specifications

Description Single enclosed space assigned to 1 individual or a grouping of enclosed offices isolated form adjacent space by a sound rated partition.

Space Requirement Size varies

Adjacency Requirements

Ceiling 24x24 high performance (fiberglass) acoustical ceiling tile (ACT) .90 noise reduction coefficient (NRC) minimum

Partition Types Provide an STC 50 assembly between restricted and unrestricted areas.

Flooring Carpet Tile

Wall Finishes Paint Rubber base

Doors Solid core wood veneer doors, aluminum frame. Frames gaskets with thresholds.

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, hold open door stops. Coat hook in offices.

Glazing N/A

Millwork N/A

Mechanical HVAC zoning per P-100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical (4) Wall duplex receptacles 120v 20 amp. Duplex receptacles to be placed 6’ -12’ apart for each office. Convenience outlets (1) per 200 SF of open space for maintenance.

Lighting - High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

- Desk Task Lamp in offices.

Telecommunications 2 cables per staff position

Plumbing N/A

Structural N/A

Audio Visual N/A

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment N/A

Accessories N/A

Open WorkstationsOFFICE SPACE

USAID Performance Specifications April 12, 2018 Page 13

Restricted Office Area

Item Specifications

Special Requirements Occupant, Title and Division Identified with a modular sign system allowing names, titles an organization to be changed independently from each other

Security Perimeter of the restricted area enclosed with STC 50 partitions and access controlled via gasketed door with threshold and card reader.

USAID Performance Specifications April 12, 2018 Page 14

Open Workstations

COLLABORATION SPACEOFFICE SPACE

Open Workstations

USAID Performance Specifications April 12, 2018 Page 15

Open Workstations

Item Specifications

Description Panel based systems furniture workstation assigned to 1 individual

Space Requirement Size varies, Panel width and height varies based on location and function.

Adjacency Requirements Located in open office areas

Ceiling 24x24 high performance (fiberglass) acoustical ceiling tile (ACT) .90 noise reduction coefficient (NRC) minimum

Partition Types N/A

Flooring Carpet Tile

Wall Finishes Open office: Paint Rubber base

Doors N/A

Hardware N/A

Glazing N/A

Millwork N/A

Mechanical HVAC zoning per P-100

Electrical (3) Duplex receptacles 120v 20 amp per workstation Workstations shall be powered off column and wall via power-whip. In areas where a wall or column are not within 1’-0” of the furniture infeed raceway or panel, power and data shall be fed through floor poke-through devices.

Lighting - High efficiency LED direct/indirect fixtures. Dual technology occupancy sensors and daylight sensors to regulate light levels with manual override.

Lighting zones to control lights in approximately 1,000 SF zones.

Telecommunications Wireless network/ Voice over IP. 2 cables/ per staff position

Plumbing N/A

Structural N/A

Audio Visual N/A

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment N/A

Accessories Desk Task Lamp with occupancy sensor.

Special Requirements Provide a single panel mounted sign for each workstation to include the workstation number only.

USAID Performance Specifications April 12, 2018 Page 16

COLLABORATION SPACE

Focus Room/ Phone Booth

Small Conference Room: 4

SeatsCOLLABORATION SPACE

USAID Performance Specifications April 12, 2018 Page 17

Description A small focus room utilized by groups of up to two for meetings.

The use and furniture for this room type may vary for different room uses, including a space designated for quiet use, focused work, or quiet breaks. To be determined during the design phase.

Space Requirement 45 SF

Adjacency Requirements Evenly distributed across the open work area for easy access. Located in the interior space between open workstation areas.

Ceiling 100% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum.

Partition Types STC 45, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes Front wall: office front system with privacy film All other walls: Paint Rubber base Walls facing open office areas: paint with dry-erase marker writable wall paint, floor to ceiling. Surfaces prepared to level 5 finish, Gypsum Association (GA) GA- 214-96

Doors Solid Core Wood Doors

Hardware Grade 1 standard duty mortise locks with plated finish. Passage door lever, non-locking, kick-down door stop. Security features are provided by door swing, hinge pin selection, and lock function.

Glazing Aluminum Framed Interior Lights. Apply privacy film band 42” wide starting at 30” above floor.

Millwork N/A

Mechanical HVAC Zoning per P100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (2) Wall duplex receptacles 120v 20 amp

- (1) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet. Mount at 60” AFF to center of monitor

- (1) Wall duplex 18” AFF on short wall.

- Provide 4” double gage Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas.

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

Telecommunications Wireless network, Voice over IP, (6) Data outlets, 3 data cables for general use, 1 data cable per A/V device.

Plumbing N/A

Structural N/A

Audio Visual Additional backing reinforcement (blocking) for 50 lbs. flat panel display. Provide one 40”LED display, wall mounted.

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment N/A

Accessories 24 SF of porcelain steel whiteboard writing surface

Special Requirements Room Number and Room name Identified with a modular sign system

USAID Performance Specifications April 12, 2018 Page 18

USAID Performance Specifications April 12, 2018 Page 19

Small Conference Room: 4 Seats

Medium Conference Room: 8-10

USAID Performance Specifications April 12, 2018 Page 20

Description A small conference room utilized by groups of up to four for meetings.

Space Requirement 96 SF

Adjacency Requirements Evenly distributed across the open work area for easy access. Located in the interior of the space between open workstation areas.

Ceiling 100% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum

Partition Types STC 45, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes - Front wall: office front system with privacy film

- Rubber base

Doors Solid Core Wood Doors

Hardware Grade 1 standard duty mortise locks with plated finish. Passage door lever, non-

Millwork N/A

Mechanical HVAC Zoning per P100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (2) Wall duplex receptacles 120v 20 amp

- (1) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet.

Mount at 60” above finished floor (AFF) to center of monitor

- (1) Wall duplex 18” AFF on short wall.

- Provide 4” double gage Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas.

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

Wireless network, Voice over IP, (3) cables for general use, 1 cable per A/V device, omni-directional speaker phone with supplementary microphones.

Plumbing N/A

Structural N/A

Audio Visual Additional backing reinforcement (blocking) for 50 lbs. flat panel display mounted at 48” AFF. Provide (1) 40-50” LED display, wall mounted.

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment N/A

Accessories 32 square feet of porcelain steel whiteboard writing surface

Special Requirements Digital corridor signage and conference room scheduler integrated with Local Area network (LAN), email and room scheduling system

USAID Performance Specifications April 12, 2018 Page 21

Medium Conference Room: 8-10 Seats

Large Conference Room: 12-14

USAID Performance Specifications April 12, 2018 Page 22

Description A medium-sized conference room utilized by groups of eight to ten for meetings.

Space Requirement 300 SF

Adjacency Requirements Evenly distributed across the open work area for easy access.

Ceiling 80% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum

20% GWB

Partition Types STC 45, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes - Front wall: office front system with privacy film

- Side walls: 50% paint and 50% covered with ½” thick upholstered wall system.

- Rubber base

Doors Solid Core Wood Doors

Hardware Grade 1 standard duty mortise locks with plated finish. Passage door lever, non-

Millwork N/A

Mechanical Provided dedicated HVAC zoning control and CO2 sensor. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (4) Wall duplex receptacles 120v 20 amp (1) on each wall

- (1) Floor core drills containing voice/power/data.

- (2) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet.

Mount at 60” AFF to center of monitor

- (1) Wall duplex voice/data receptacle 18” AFF on short wall.

Provide 4” double gage Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas. Provide ceiling mounted power outlets for projector and projection screen motor.

Equipped with Lutron Lighting Control Panel(s).

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light

Wireless network, Voice over IP, (8) Data drops at the table, (1) Data drop on adjacent walls.

1 cable per A/V device.

Plumbing N/A

Structural N/A

Audio Visual - Additional backing reinforcement (blocking) for 100 lbs. flat panel display

- Projection Screen or display system determined by room dimensions and design guidelines (70” minimum).

- Digital corridor signage and conference room scheduler

- Equipped with AV-Remote/Wireless Control Key Boards

Sound Masking N/A

Equipment

Accessories 48 square feet of porcelain steel whiteboard writing surface

USAID Performance Specifications April 12, 2018 Page 23

Special Requirements Digital corridor signage and conference room scheduler integrated with LAN, email and room scheduling system.

Security N/A

Other Integrated power and data conference tables. Include integrated power and cable raceways for power and data cables, accessible through a concealed channel with access doors in the center of the table. Provide 1 power and 1 data outlet for each 4 persons seated at the table.

USAID Performance Specifications April 12, 2018 Page 24

Large Conference Room: 12-14 Seats

X-Large Conference Room: 18-25

USAID Performance Specifications April 12, 2018 Page 25

Description A large conference room utilized by groups of up to 12-14 for meetings

Space Requirement 500 SF

Adjacency Requirements Evenly distributed across the open work area for easy access.

Ceiling 80% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum

20% GWB

Partition Types STC 45, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes - Front wall: office front system with privacy film

- Side walls: 50% paint and 50% covered with ½” thick upholstered wall system.

- Rubber base

Doors Solid Core Wood Doors

Hardware Grade 1 standard duty mortise locks with plated finish. Passage door lever, non-

Millwork Architectural Millwork Institute (AWI) Custom Grade

Mechanical Provided dedicated HVAC zoning control and CO2 sensor. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (6) Wall duplex receptacles 120v 20 amp (2) on each wall

- (2) Floor core drills containing voice/power/data.

- (2) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet.

Mount at 60” AFF to center of monitor

- (1) Wall duplex voice/data receptacle 18” AFF on short wall.

- Provide 4” double gage Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas. Provide ceiling mounted power outlets for projector and projection screen motor.

- Equipped with Lutron Lighting Control Panel(s).

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light

Wireless network, Voice over IP,

(4) cables, (8) Data outlet at the table,

(1) data outlet at adjacent walls

(1) cable per A/V device, omni-directional speaker phone with supplementary microphones

Plumbing N/A

Structural N/A

Audio Visual - Additional backing reinforcement (blocking) for 100 lbs. flat panel display

- Projection Screen or display system determined by room dimensions and design guidelines

- Digital corridor signage and conference room scheduler

- Equipped with AV-Remote/Wireless Control Key Boards

Sound Masking N/A

Equipment Commented [AJ1]: This reflects FFE; needs redistribution to another category

USAID Performance Specifications April 12, 2018 Page 26

Accessories 72 square feet of porcelain steel whiteboard writing surface

Special Requirements Digital corridor signage and conference room scheduler integrated with LAN, email and room scheduling system.

50% of the exposed drywall or hard surface wall area (excluding the glazed partition), shall be finished with an upholstered acoustical wall system for sound absorption.

Security N/A

Other Integrated power and data conference tables. Include integrated power and cable raceways for power and data cables, accessible through a concealed channel with

USAID Performance Specifications April 12, 2018 Page 27

X-Large Conference Room: 18-25 Seats

Point IV MeetingCOLLABORATION SPACE

USAID Performance Specifications April 12, 2018 Page 28

Description A large conference room utilized by groups of 18-25 for division meetings.

Space Requirement 750 SF

Adjacency Requirements Evenly distributed across the open work area for easy access.

Ceiling 80% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum

20% GWB

Partition Types STC 45, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes - Front wall: office front system with privacy film

- Side walls: 50% paint and 50% covered with ½” thick upholstered wall system.

- Rubber base

Doors Solid Core Wood Doors

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, hold open door stops.

Glazing Aluminum Framed Interior Lights. Apply privacy film band 42” wide starting at 30” above floor.

Millwork AWI Custom Grade

Mechanical Provided dedicated HVAC zoning control and CO2 sensor. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (4) Wall duplex receptacles 120v 20 amp (1) on each wall

- (2) Floor core drills containing voice/power/data.

- (2) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet.

Mount at 60” AFF to center of monitor

- (1) Wall duplex voice/data receptacle 18” AFF on short wall.

- Provide 4” double gage Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas. Provide ceiling mounted power outlets for projector and projection screen motor.

- Equipped with Lutron Lighting Control Panel(s).

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light

(4) cables, (8) data outlets at table

(1) at adjacent walls.

(1) cable per A/V device, omni-directional speaker phone with supplementary microphones

Plumbing N/A

Structural - Additional backing reinforcement (blocking) for 100 lbs. flat panel display

- Projection Screen or display system determined by room dimensions and design guidelines.

- Digital corridor signage and conference room scheduler

Audio Visual Wireless network, Voice over IP, (2) Data drops (1) at adjacent walls.

Provide one cable drop to each AV device in the room.

Provide A/V, lighting and window shade controls in a single touch screen device and interface.

Equipped with AV-Remote/Wireless Control Key Boards

USAID Performance Specifications April 12, 2018 Page 29

Sound Masking N/A

Equipment

Accessories 72 square feet of porcelain steel whiteboard writing surface

Special Requirements Digital corridor signage and conference room scheduler integrated with LAN, email and room scheduling system.

Security N/A

Other Integrated power and data conference tables. Include integrated power and cable raceways for power and data cables, accessible through a concealed channel with

USAID Performance Specifications April 12, 2018 Page 30

Point IV Meeting

Restricted Medium Conference Room: 8-10

USAID Performance Specifications April 12, 2018 Page 31

Description Open, flexible space for holding large meetings, events, training, breakout sessions, and social gatherings. Ease of reconfiguration is essential to altering space based on size, type, duration and other requirements of meeting or event.

Space can accommodate up to 200 people in a theater-style set-up or 150 in a banquet-style set-up.

Space Requirement 1,750 SF

Adjacency Requirements Multi-purpose room shall be adjacent to A-AID suite .

Ceiling 80% ACT, 24x24 high performance (mineral board) ACT .80 NRC minimum

20% GWB

Partition Types Provide an STC 50 assembly on three sides with acoustical insulation Front wall: office front glazed aluminum storefront system with privacy film slab-to-slab.

Flooring Carpet Tile

Wall Finishes Side walls – 50% paint and 50% 1” thick acoustic panel Rubber base Provide recessed solid surface jamb for the operable wall to protect the drywall at the wall seal points.

Doors Solid Core Wood Doors Aluminum frame

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, concealed closers, coordinated hold open door stops.

Glazing Aluminum Framed Interior Lights

Millwork N/A

Mechanical HVAC zoning per P-100. Provide a dedicated four-pipe, chilled water, hot-water air handling unit with variable frequency drive utilizing a VAV control concept.

Unit shall be provided with CO2 sensors for demand controlled ventilation.

Electrical - (8) Wall duplex receptacles 120v 20 amp

- (1) Floor core drills containing power/data per 100 SF of floor space

- (4) AV connections per 600 SF, standard AV wall plate that includes two RJ45, one HDMI, , and power outlet. Mount at 84” AFF to center of monitor.

- Provide 4” double gang Junction box w/ power outlet. Junction shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas.

Lighting - High efficiency LED direct/indirect fixtures. Dual technology sensor office light control with manual override operation option.

- Provide and integrated lighting, window shade, AV control system for the conference space. System shall provide “one-touch” programmed pre-set interface. Systems shall detect room configuration and control one, some or all rooms from a single control panel.

(2) cables, (4) data outlets at adjacent walls.

Provide one cable drop to each AV device in the room.

Plumbing N/A

Structural Provide a concealed, ceiling slab mounted steel superstructure for the movable wall track.

16’-0” Structural floor to Structural Ceiling height Column-free room

Audio Visual - Additional backing reinforcement (blocking) for 100LB flat panel displays

- Recessed Projection Screens, 16:9 format

- Hi-definition 1080p or 4k projector

- Digital corridor signage and conference room scheduler

- (4) Flat Panel Displays

USAID Performance Specifications April 12, 2018 Page 32

- Provide audiovisual system with secure video teleconference capabilities and enhanced teleconference audio with ceiling mounted speakers and microphones, mount location determined by room acoustics. Provide (2) wireless microphones per room. Display devices determined by room size and configuration. System to include desktop sharing functions.

Sound Masking N/A

Equipment One touch scene lighting controls and projection screens. Coordinate with A/V systems.

Accessories 128 SF of porcelain steel whiteboard

Special Requirements Structural acoustic panels: 2” thick acoustic panels, perforated metal finish with 33% open surface area, 1.5 lbs./cubic foot density mineral wool in-fill.

Room Number and Room name Identified with a modular sign system

USAID Performance Specifications April 12, 2018 Page 33

Restricted Medium Conference Room: 8-10 Seats

SUPPORT SPACECOLLABORATION

SPACE

USAID Performance Specifications April 12, 2018 Page 34

Description A restricted use, medium-sized conference room utilized by groups of eight to ten for meetings.

Space Requirement 300 SF

Adjacency Requirements Central location, 1 per floor.

Ceiling 80% ACT, 24x24 high performance (fiberglass) ACT .80 NRC minimum

20% GWB

Partition Types STC 50, slab-to-slab assembly with acoustical insulation

Flooring Carpet Tile

Wall Finishes - Walls: 50% paint and 50% covered with ½” thick upholstered wall system.

- Rubber base

- Paint floors, walls and ceilings with RF rated paint.

Doors STC 50 Door and Frame assembly with threshold.

Hardware Grade 1 standard duty mortise locks with plated finish. Passage door lever, non-locking, kick-down door stop. Security features are provided by door swing, hinge pin selection, and lock function. Provide GSA rated security tumbler lock (Kaba Mas X-10) or equal. Coordinate lock functions to provide single motion exiting.

Glazing N/A

Millwork N/A

Mechanical Provided dedicated HVAC zoning control and CO2 sensor. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air ducts shall be ducted with a “Z” duct.

Electrical - (4) Wall duplex receptacles 120v 20 amp (1) on each wall

- (1) Floor core drills containing voice/power/data.

- (2) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet.

Mount at 60” AFF to center of monitor

- (1) Wall duplex voice/data receptacle 18” AFF on short wall.

Provide 4” junction box w/ power outlet. Junction boxes shall be off-set by a minimum of 2’-0”. Boxes shall never be installed back to back or side to side when serving adjacent areas. Provide ceiling mounted power outlets for projector and projection screen motor.

Equipped with Lutron Lighting Control Panel(s).

All signal conduit serving the room shall be rigid galvanized conduit

Lighting High efficiency LED direct/indirect fixtures. Dual technology sensor office light

Voice over IP, (8) Data drops at the table, (1) Data drop on adjacent walls.

1 cable per A/V device.

Plumbing N/A

Structural N/A

Audio Visual - Additional backing reinforcement (blocking) for 100 lbs. flat panel display

- Projection Screen or display system determined by room dimensions and design guidelines (70” minimum).

- Digital corridor signage and conference room scheduler

- Equipped with AV-Remote/Wireless Control Key Boards

Sound Masking N/A

USAID Performance Specifications April 12, 2018 Page 35

Equipment

Accessories 48 square feet of porcelain steel whiteboard writing surface

Special Requirements Digital corridor signage and conference room scheduler integrated with LAN, email and room scheduling system.

Security N/A

Other Integrated power and data conference tables. Include integrated power and cable raceways for power and data cables, accessible through a concealed channel with

USAID Performance Specifications April 12, 2018 Page 36

SUPPORT SPACE

Enrollment/ Badging

ClassNet AccessSUPPORT SPACE

USAID Performance Specifications April 12, 2018 Page 37

Description Badging processing area for new employees and contractors. Requires a waiting area and badge processing workstations.

Space Requirement 200 SF

Adjacency Requirements Adjacent to Visitor Lobby and Security Main

Ceiling 24x24 high performance ACT .80 NRC minimum

Partition Types Provide an STC 50 assembly on three sides with acoustical insulation Front wall: office front glazed aluminum storefront system with privacy film, slab-to-slab

Flooring Standard VCT in waiting area, carpet in workstations.

Wall Finishes Paint Rubber base

Doors Solid Core Wood Doors Aluminum frame

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, concealed closers, coordinated hold open door stops, astragal.

Low-voltage wiring.

Card access controlled. Card reader controlled doors require wired hinges. Doors must be prepared to accept the mortise lock and low-voltage wiring to control the mortise lock.

Glazing N/A

Millwork N/A

Mechanical HVAC Zoning per P-100. Enclosed staff and meeting spaces shall not be directly connected by ductwork. Connections to the main air supply duct shall be outside of the enclosed space and any connecting ductwork shall require three bends to isolate noise transmission. All return air dust shall be ducted with a “Z” duct.

Electrical - (8) Wall duplex receptacles 120v 20 amp

- (2) Wall junction boxes and for systems furniture whips, one 120v 20 amp circuit per junction box, (8) outlets per workstation.

- (1) Standard AV wall plate that includes two RJ45, one HDMI, and power outlet. Mount at 60” AFF to center of monitor Low-voltage wiring.

Card access controlled. Card reader controlled doors require wired hinges. Doors must be prepared to accept the mortise lock and low-voltage wiring to control the mortise lock.

Lighting All lighting to be high-efficiency LED direct/indirect fixtures.

Telecommunications (1) Standard AV wall plate that includes (2) RJ45, (1) HDMI, and power outlet.

Mount at 60” AFF to center of monitor

- (2) cables, (4) data outlets per staff position

- (2) cables, (4) outlets for office MFD and other network connected equipment

- Wireless network connectivity

Plumbing N/A

Structural N/A

Audio Visual Digital signage – flat panel display (70” minimum)

Sound Masking An integrated sound-masking system shall be provided for all staff areas, including adjacent conference and meeting space. The systems shall provide central control and allow for adjusting speaker volume by zones. The speaker design shall include enclosure design, enclosure color and speaker mounting options. The system shall provide a multi-frequency sound.

Equipment (1) Badge printer per badge operator position, (1) 5-drawer safe, (1) badge camera, per badge operator position.

USAID Performance Specifications April 12, 2018 Page 38

Accessories Include wall length mirror adjacent to photo booth area

Special Requirements Room Number and Room name Identified with a modular sign system

Security Card access controlled.

USAID Performance Specifications April 12, 2018 Page 39

ClassNet Access

Event CenterSUPPORT SPACE

USAID Performance Specifications April 12, 2018 Page 40

Description Shall be built to Secure Compartmentalized Information Facility (SCIF) standards provided by accrediting authority. Used for Classnet activities.

Space Requirement 375 SF

Adjacency Requirements Central location to floor; two (2) per floor

Ceiling 24x24 high performance (fiberglass) ACT for open areas and (mineral board) ACT in Conference rooms and Private offices.

.80 NRC minimum

Partition Types Provide an STC 55 assembly or per accrediting authority’s requirements, slab-to-slab. Provide woven wire mesh or plywood in the wall assembly.

Flooring Carpet in Conference rooms and Private offices.

Wall Finishes Paint Rubber base

Doors Solid Core Metal Doors, with gaskets and thresholds Welded steel hollow metal frame STC 55 rated assembly

Hardware Grade 1 standard duty mortise locks with plated finish, BHMA A156 Series (door hardware). Silencers, concealed closers, coordinated hold open door stops, astragal. Low-voltage wiring.

Card access control. Card reader controlled doors require wired hinges. Doors must be prepared to accept the mortise lock and low-voltage wiring to control the mortise lock.

Threshold Sweeps

Glazing N/A

Millwork N/A

Mechanical - Dedicated 24/7 four-pipe air handling unit with single zone VAV control scheme. Unit shall be powered from emergency power and shall have chem-bio filtration system on outside air supply. Unit shall be sized to support a minimum of 10 watts per square foot of heat rejection.

- Di-electric breaks for all piping, conduit and duct work.

- Provide inspection ports and man-bars for all duct work entering the secure area with an opening 100 square inches or greater.

Electrical Copy/Print:

Provide surface mounted wiremold at counter with outlets every 2 feet for power.

Provide dedicated power outlet for multi-function device (MFD).

Workstations:

- (4) Wall…