Equipment List.xls

XLS spreadsheet 59 KB Posted

Attached to
HVAC MAINTENANCE AND REPAIR SERVICES
Solicitation number
5400028310
Issued by
Greenville County, South Carolina

About this file

The file is an Equipment List Excel spreadsheet detailing HVAC equipment for the South Carolina Department of Employment and Workforce (SCDEW) across multiple regions, including Greenville, Catwaba/Lancaster, Pee Dee/Florence, Marion, Waccamaw/Conway, Kingstree, Beaufort, Lower Savannah/Aiken, Barnwell, Orangeburg, and Santee-Lynches/Sumter. The document provides a comprehensive inventory of heat pump systems, package AC units, and split AC units, primarily manufactured by Trane, Carrier, Goodman, Daikin, York, and Lennox, with detailed information on each unit's model number, serial number, age, and projected replacement date.

The equipment list indicates most units are between 15-20 years old, with many having projected replacement dates around 2015-2023. The document includes specific repair needs and estimated repair costs for various units, ranging from $132 to $6,400, with common issues including compressor contactor replacements, thermostat calibration, and mismatched condensing units and air handlers. The inventory suggests an ongoing maintenance and replacement strategy for HVAC systems across different regional offices, with a focus on tracking equipment age, performance, and potential upgrade requirements.

View the file

Other files

File Type Posted
Amendment 2.pdf PDF
Solicitation.pdf PDF
Amendment 1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Regions 1, 2 & 3

SCDEW EQUIPMENT LISTING BY REGION
Projected Replacement DateCurrent Replacement Cost Estimate (2015)
Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in needRepair Costs
REGION # 1 - GREENVILLE
C/U # 1 - Heat Pump Outdoor UnitTraneTWA12043AAB00AR18382270YA10201815New equipment18-Feb
A/H # 1 - Heat Pump Indoor UnitTraneTWE12043AAA00A01837195BA4) 16X25X1A-5110201815New equipmentFeb-18
C/U # 2 - Heat Pump Outdoor UnitTraneTWA120A300EB3214LNAd10200315T-stat needs moved into the Tax Office for proper control of unit$250.00
A/H # 2 - Heat Pump Indoor UnitTraneTWE120A300EB3242YE45H4) 16X25X1A-5110200315Replaced leaking primary drain pan
C/U # 3 - Heat Pump Outdoor UnitTraneTWA090D30RAB16013K5AYA7.5201815New equipmentMar-19
A/H # 3 - Heat Pump Indoor UnitTraneTWE090D300AB15465RPDBA2) 24X24X1A-517.5201815New equipment19-Mar
C/U # 4 - Heat Pump Outdoor UnitTrane4TWR030D1000AA16083USC5F2201915New equipment19-Mar
A/H # 4 - Heat Pump Indoor UnitTraneTEM4A0B30S31SAA16053YCJ2V1) 16X20X12198815New equipment19-Mar
C/U # 5 - Heat Pump Outdoor UnitTrane2TWB3024A1000AA81126N44F2200815
A/H # 5 - Heat Pump Indoor UnitTrane2TEC3F24B1000AA83526UT1V1) 20X20X12200815
C/U # 6 - Heat Pump Outdoor UnitTraneTWA120D30RBA18024STTYA10201815New equipment18-Apr
A/H # 6 - Heat Pump Indoor UnitTraneTWE120D300AB18043RM2BA2)20X20X2 & 2)16X20X2AX-4110201815New equipment18-Apr
C/U # 7 - Heat Pump Outdoor UnitTrane4TWR4036D1000AB1621505HBF3201615New equipment16-Feb
A/H # 7 - Heat Pump Indoor UnitTraneTEM4A0C36S41SAA162441682V1) 20X20X13201615New equipment16-Feb
C/U # 8 - Heat Pump Outdoor UnitTrane10200315New equipment
A/H # 8 - Heat Pump Indoor UnitTrane2)20X20X2 & 2)16X20X2A-4110200615New equipment
REGION #3- CATWABA/LANCASTER, 705 N. WHITE STREET
RTU # 1 - Package Heat PumpTraneWCD180B300DBK34102363D4) 20X25X2, 2) 20X20X2BX6215199315Replace (2) compressor contactors, disconnect too large$260.00
Disconnect too large and blades will not close. Need to replace$650.00

&R&"Arial,Bold"&8APPENDIX 1

Region 4 & 5

Projected Replacement DateCurrent Replacement Cost Estimate (2015)
Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in needRepair Costs
REGION # 4 - PEE DEE/FLORENCE - 1558 W. EVANS STREET
C/U # 1 - Heat Pump Outdoor UnitCarrier38ARQ012---5013304G5006010200415Replaced compressor June 2013
A/H # 1 - Heat Pump Indoor UnitCarrier40RMQ012---B611HC3304F513274) 16X24X2A-3910200415Leak search evaporator has slow leak$250.00
C/U # 2 - Heat Pump Outdoor UnitCarrier38ARQ012---5013004G2006210200415Replaced compressor June 2013
C/U # 2A - Heat Pump Outdoor UnitCarrier38AQS016---5413504F54760142004152nd of (2) condensers. Replace compressor contactor$132.00
A/H # 2 - Heat Pump Indoor UnitCarrier40RMQ028-B511GC4304X019254)20X24X2, 4) 20X25X22) BX4215200415
REGION # 4 - PEE DEE/MARION - 2413 EAST HWY 76
C/U # 1 - Heat Pump Outdoor UnitTraneTWA090A300FB6114PHFAD7.5200615Replace compressor contactor and service disconnect$680.00
A/H # 1 - Heat Pump Indoor UnitYorkFCHP5090AANEC50133814) 16X25X1A-367.5199415
C/U # 2 - Heat Pump Outdoor UnitTraneTWA090A300FB11015WW3YA7.5201115Compressor contactor needs to be replaced$132.00
A/H # 2 - Heat Pump Indoor UnitTraneTWE090D300AA01486TPABA3) 16X25X1A-497.5201015
REGION # 5- WACCAMAW/CONWAY -
RTU # 1 - Packaged AC UnitTraneTCH600BE0V2BME500C0EF0HHC19E0344617) 16X20X22) BX-9550201920Replace compressor and blower motor contactors$264.00
C/U # 2 - Split AC condensing unitTrane4TTA4042A3000AA212634CA3F3202115Compressor contactor needs to be replaced$132.00
A/H # 2 - Split AC air handling unitTraneTEM4A0C425415BA204978M83V1) 20X20X13202015Mismatched unit, 3 ton condeenser with 3.5 ton air handling unit
REGION # 5- WACCAMAW/KINGSTREE - 530 MARTIN LUTHER KING JR. AVE
C/U # 1 - Heat Pump Outdoor UnitGoodmanGSH1000903AB90727394510200915Replace compressor contactor and thermostat (out of calibration)$298.00
A/H # 1 - Heat Pump Indoor UnitTraneTWE090A300BBL212X6C5H3)16X25X1A-377.5199515Mismatched unit, 7.5 ton air handler and 10 condensing unit
C/U # 2 - Heat Pump Outdoor UnitDaikinDZ4SEA483023031589134202315Replace compressor contactor and thermostat (out of calibration)$298.00
A/H # 2 - Heat Pump Indoor UnitGoodmanAMST48CU140024030195581) 20X20X14202415Mismatched unit, 4 ton condenser and 5 ton air handling unit
C/U # 3 - Heat Pump Outdoor UnitTraneTWA090A300BBL164LLKAH7.5199515Replace compressor contactor and thermostat (out of calibration)$298.00
A/H # 3 - Heat Pump Indoor UnitTraneTWE090A300BBL212KJK5H3)16X25X2A-477.5199515

Region 7 & 8

Projected Replacement DateCurrent Replacement Cost Estimate (2015)
Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in needRepair Costs
REGION # 7 - LOW COUNTRY/BEAUFORT - 164 CASTLE ROCK ROAD
PKG # 1 - Package AC unitTraneTSH240G3R0C160210710658D25202115$250.00
PKG # 2 - Package AC unitTraneTSC060G3R0A030203014705L2) 20x35x25202015
REGION # 8 - LOWER SAVANNAH/AIKEN - 1571 RICHLAND AVE. E.
C/U # 1 - Heat Pump Outdoor UnitTrane4TWA44048A3000AA18222TUX4F4201815NEW EQUIPMENT
A/H # 1 - Heat Pump Indoor UnitTraneTEM4A0C48S41SAA18184P103V3) 20X20X14201815NEW EQUIPMENT
C/U # 2 - Heat Pump Outdoor UnitTrane4TWA40363000AA181522FF4F3201815NEW EQUIPMENT
A/H # 2 - Heat Pump Indoor UnitTraneTEM4A0B36S3SBA182348SJ3V2) 21X21X13201815NEW EQUIPMENT
C/U # 3 - Heat Pump Outdoor UnitTraneTWA09043AAA02B50100232244494A7.5202315
A/H # 3 - Heat Pump Indoor UnitTraneBWB090C400GAC201765762) 21X21X1A-487.5198815Electric auxiliary heat strips will not come on from thermostat$210.00
C/U # 4 - Heat Pump Outdoor UnitTraneTWA036A300A0C212981573198815
A/H # 4 - Heat Pump Indoor UnitTraneTWH736A140A0C224017782) 21X21X13198815T-stat located in conference room but away from return in lobby$223.00
C/U # 5 - Heat Pump Outdoor UnitTrane4TWA3036A3000CA1350PCD4P3201315
A/H # 5 - Heat Pump Indoor UnitTraneTAM4A0A36531SCA133342NKAV2) 21X21X13201315
REGION # 8 - LOWER SAVANNAH/BARNWELL - 248 WALL STREET
PKG # 1 - Package Heat PumpGoodmanGPHM36041AA23021541811) 24X30X15202315
C/U # 2 - Heat Pump Outdoor UnitCarrier38YCC030403304E315932.5200415
A/H # 2 - Heat Pump Indoor UnitCarrierFA4BNF0303404A846871) 20X25X12.5200415
REGION # 8 - LOWER SAVANNAH/ORANGEBURG - 1804 JOE. S. JEFFORDS HWY
PKG # 1 - Gas Package UnitCarrier48P4B0305472XHZFVN5221U4980910) 20X24X22) 5VX53030202115No repairs needed
PKG # 2 - Package AC unitCarrier48TCDA09A2A5A0A0A01012G102934) 20X20X2A-487.5201215No repairs needed

Region 9, 10 & 11

Projected Replacement DateCurrent Replacement Cost Estimate (2015)
Designation/TypeManufacturerModel NumberSerial NumberFiltersV-beltsTonsAgeLifeRepairs found in needRepair Costs
REGION # 11 - SANTEE-LYNCHES/SUMTER - 29 E. CALHOUN STREET
C/U # 1 - Heat Pump Outdoor UnitGoodmanGSH1300361CD13070711583200715Mismatched C/U 3 ton, AH 4 ton
A/H # 1 - Heat Pump Indoor UnitLennoxCBS18-51-3P5189F942212) 21X21X14198915$6,400.00
C/U # 2 - Heat Pump Outdoor UnitTraneTWA090A300BBL21414JAH7.5199715
A/H # 2 - Heat Pump Indoor UnitLennoxCPH17-95V-1NOT AVAILABLE4) 21X21X1AX-327.5198915Replace worn bearings in air handling unit$940.00
C/U # 3 - Heat Pump Outdoor UnitGoodmanGSH1301361CD13070111563200715
A/H # 3 - Heat Pump Indoor UnitLennoxCBS18-41-3PNOT AVAILABLE2) 21X21X13.5198915
C/U # 4 - Heat Pump Outdoor UnitLennoxHP29-048-7Y5806M015774200615
A/H # 4 - Heat Pump Indoor UnitLennoxCPS18-41-3P5189G737662) 21X21X14198915Replace worn bearings in air handling unit$680.00
C/U # 5 - Heat Pump Outdoor UnitCarrier25HBC336A--5001012E003843201215
A/H # 5 - Heat Pump Indoor UnitCarrierFB4CNF0422912A896713) 21X21X13.5201215