ENERGY QAP C16.18-22 FJ1 (PC&S) (AUG 2014).pdf
PDF 93 KB Posted
- Solicitation number
- SPE60524Q0006
- Issued by
-
Defense Logistics Agency Energy
About this file
This document is a Request for Quotation (RFQ) for the delivery of 11,100 gallons of Fuel Oil, Burner (FJ1) to multiple locations at Camp Fuji, Japan. The required delivery dates are August 6-27, 2024. The contract will be a firm fixed-price contract awarded to the lowest priced responsible vendor. Quotes are due by 10:00 AM Ft. Belvoir Time on August 2, 2024. The government may require the vendor to sign the SF1449 contract form within as little as 2 hours of being offered the delivery. Delivery will be F.O.B. destination via tank truck with pump. The government will not assume responsibility for more than a 10% variance in the quantity delivered. Applicable taxes and fees must be included in the quoted price. The contracting agency is the Defense Logistics Agency Energy.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DELIVERY REQUIREMENT.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C16.18-22 FUEL OIL BURNER (PC&S) (JAPAN) (DLA ENERGY AUG 2014) For use in PC&S solicitations/contracts for Japan.
Supplies delivered under this contract shall conform to all in-country environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. In the event the in-country environmental requirement is more stringent than the specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent requirement will be considered to be a nonconforming supply.
(a) FUEL OIL, BURNER Burner fuel oil shall conform to Japanese Standard JIS K 2204(2007).
(1) CLASSIFICATION.
NATIONAL STOCK NUMBER PRODUCT
NOMENCLATURE
PRODUCT CODE POUR POINT
9140-01-408-7183 Burner Fuel Oil, No. 1 FJ1 -2.5oC maximum
(2) SEASONAL REQUIREMENTS.
(i) Mainland Japan (except Hachinoe and Misawa AFB) requires FJ1 with the following seasonal pour point and cold filter plugging point (CFPP) limits:
MONTH POUR POINT COLD FILTER PLUGGING
POINT (CFPP)
June to August 5oC maximum Report November 16th to February 29th -7.5oC maximum -5oC maximum March to May; September to November 15th -2.5oC maximum -1oC maximum
(ii) Hachinoe and Misawa AFB require FJ1 from April 1st to November 14th and FJ3 from November 15th to March 31st of each year in a multiyear contract. The pour point for FJ3 during the months required shall be -30°C maximum and the CFPP shall be -19°C maximum.
Signature
Prepared by:
Quality / Technical Support Office Approval: Prior approval as contract provision
Contracting Approval: Prior approval as contract provision
Legal Approval:
(Only required for E QAPs)
DMM0076
Typewritten Text DISTRIBUTION STATEMENT - A: APPROVED FOR PUBLIC RELEASE. DISTRIBUTION IS UNLIMITED
| 2014-08-28T15:35:36-0400 | |
| ATKINS.RENRICK.L.1024389320 |
File details come from the government source that posted it. Updated .