ELECTRICAL DRWINGS.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25522R0033-0002
About this file
This is an amendment to a solicitation for project 657-19-127JB to renovate space for domiciliary providers in Building 2 at a VA medical center. The amendment provides answers to questions submitted, an updated site visit roster, and revised specifications and drawings. Key details include renovations to electrical, lighting, and systems on the first and second floors, including demolishing existing panels and installing new ones, upgrading receptacles and branch circuits, and installing cabling pathways and connections for systems like fire alarm, nurse call, and security. The project also involves electrical work in the basement and on the ground floor. The response date has not changed from the original solicitation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
COAX PANEL
TO REMAIN
PANEL L1-2
TO BE REMOVED
PANEL L1-3
TO BE REMOVED
PANEL L1-1
TO BE REMOVED
PANEL L1-4
TO BE REMOVED
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:0
A
M
02-ED-111
LIGHTING DEMOLITION PLAN - FLOOR 01
CMTACMTA
SCALE: 1/4" = 1'-0"02-ED-111
1 Lighting Demolition Plan - Floor 01
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO
REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR
EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR
PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.
CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY
MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND
REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN
OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.
F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND
CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE
BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN
ACCORDANCE W ITH NEC REQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT
INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.
K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-
W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED
BREAKERS SHALL BE IN OFF POSITION.
L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.
M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.
N
Revisions: Date:
ADDENDUM #1 1/21/2022
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
J
PO1
PO1
PO1
PO1
PO1
PO1 PO1
PO1 PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO1
PO3
PO3
PO3
PANEL L1-4
TO BE REMOVED
PANEL L1-2
TO BE REMOVED
COAX PANEL
TO REMAIN
PANEL L1-3
TO BE REMOVED
PANEL L1-1
TO BE REMOVED
PO14
PO14
PO14
PANEL LE-1
TO REMAIN
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:0
A
M
02-ED-112
POWER DEMOLITION PLAN - FLOOR 01
CMTACMTA
SCALE: 1/4" = 1'-0"02-ED-112
1 Power Demolition Plan - Floor 01
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO
REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR
EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR
PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.
CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY
MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND
REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN
OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.
F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND
CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE
BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN
ACCORDANCE W ITH NEC REQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT
INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.
K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-
W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED
BREAKERS SHALL BE IN OFF POSITION.
L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.
M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.
N
TAGGED NOTES
PO1 EXISTING HVAC UNIT TO BE RELOCATED, REMOVE
ELECTRICAL POWER CONNECTION AND BRANCH CIRCUIT.
COORDINATE DETAILS WITH MECHANICAL WORK.
PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO
REMAIN.
PO14 REMOVE EXISTING POWER PANEL INDICATED AND
ASSOCIATED PANEL FEEDER COMPLETELY BACK TO SOURCE.
FIELD VERIFY IF PANEL HAS ANY DEVICES, LIGHTS, ETC. ON
CIRCUITS THAT ARE TO REMAIN. RE-ROUTE THESE CIRCUITS
TO EXISTING/NEW PANELS THAT ARE IN THE SAME AREA, AS
REQUIRED, (UTILIZE SPACES/SPARES IN THESE PANELS AS
NECESSARY). CONTRACTOR SHALL CAREFULLY DETERMINE
EXTENT OF WORK PRIOR TO DEMOLITION OF THE
PANEL/PANEL FEEDER. REFER TO PANEL
RELOCATION/DEMOLITION DETAIL AND ELECTRICAL POWER
RISER DIAGRAM.
J J
J J
J J
J
J
J J
J JJ
J
J
PO1
PO1
PO1
PO1
PO1
PO1 PO1
PO1
PO1
PO1
PO1
PO1
PO4
PO3
PO4
COAX PANEL
TO REMAIN
PANEL L2-1
TO BE REMOVED
PO14
PANEL L21-A
TO REMAIN
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:0
A
M
02-ED-122
POWER DEMOLITION PLAN - FLOOR 02
CMTACMTA
SCALE: 1/4" = 1'-0"02-ED-122
1 Power Demolition Plan - Floor 02
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO
REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR
EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR
PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.
CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY
MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND
REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN
OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.
F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND
CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE
BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN
ACCORDANCE W ITH NEC REQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT
INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.
K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-
W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED
BREAKERS SHALL BE IN OFF POSITION.
L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.
M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.
N
TAGGED NOTES
PO1 EXISTING HVAC UNIT TO BE RELOCATED, REMOVE
ELECTRICAL POWER CONNECTION AND BRANCH CIRCUIT.
COORDINATE DETAILS WITH MECHANICAL WORK.
PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO
REMAIN.
PO4 REMOVE EXISTING ADVANCED NETWORK ANNUNCIATION UNIT
AND SALVAGE, STORE. CLEAN AND REINSTALL UNIT PER NEW
WORK PLAN TO LIKE NEW CONDITION.
PO14 REMOVE EXISTING POWER PANEL INDICATED AND
ASSOCIATED PANEL FEEDER COMPLETELY BACK TO SOURCE.
FIELD VERIFY IF PANEL HAS ANY DEVICES, LIGHTS, ETC. ON
CIRCUITS THAT ARE TO REMAIN. RE-ROUTE THESE CIRCUITS
TO EXISTING/NEW PANELS THAT ARE IN THE SAME AREA, AS
REQUIRED, (UTILIZE SPACES/SPARES IN THESE PANELS AS
NECESSARY). CONTRACTOR SHALL CAREFULLY DETERMINE
EXTENT OF WORK PRIOR TO DEMOLITION OF THE
PANEL/PANEL FEEDER. REFER TO PANEL
RELOCATION/DEMOLITION DETAIL AND ELECTRICAL POWER
RISER DIAGRAM.
STRUCTURE ABOVE
1'' C. FOR
STUB DOWN WHERE REQUIRED
OUTLETS AS SHOWN ON PLAN
SUCH CABLING SHALL MEET N.E.C. REQUIREMENTS FOR SUCH INSTALLATIONS.
WHERE OPEN CABLING IS INSTALLED WITHIN ENVIRONMENT AIR PLENUMS,
ROUGHING-IN DETAIL FOR STUB-OUTS
ALL CONDUIT STUB-OUTS SHALL EXTEND TO NEAREST CABLING PATH (J-HOOK
OR CABLE TRAY).
NO SCALE
NOTES:
FLOOR LINE
HEIGHT AS SCHEDULED
S
3/4'' CONDUIT MINIMUM
J
FLEX DOWN
CEILING LINE
INSULATED THROAT BUSHING
NC
SYSTEMS CABLING SLEEVE INSTALLATION DETAIL
NO SCALE
CEILING
STRUCTURE
OBSTRUCTIONS
8"+, TO CLEARLC
FIRE/SMOKE RATED OR UNRATED PARTITION OF
VARIOUS CONSTRUCTIONS-REFER TO
ARCHITECTURAL PLANS OR FIELD VERIFY TYPE
ACCESSIBLE CEILING EACH SIDE OF SLEEVE
USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS, ETC.
PROVIDE HILTI BRAND ''TWIST-TYPE''
CABLING SLEEVES. USE TWO 4'' SLEEVES,
BUT ADD ADDITIONAL SLEEVES AS
NECESSARY SO AS NOT TO EXCEED A
MAXIMUM 40% FILL. MOUNT ABOVE THE
SUSPENDED CEILING AND IN-LINE WITH THE
CABLING PATH AT LOCATIONS INDICATED
AND WHERE REQUIRED FOR CABLING
PATHWAYS.
PROVIDE CAULKING-STYLE FIRE-STOPPING
APPLICATION BETWEEN SLEEVE AND WALL
MATERIAL TO ANCHOR SLEEVE.
NOTE:
CABLING FOR THE FOLLOWING SYSTEMS SHALL BE RAN FULLY IN CONDUIT AND NOT JUST TO
THE CABLING PATHWAYS (FULL CONDUIT ''HOMERUNS''). REFER ALSO TO SPECIFICATIONS
SECTION ''27 05 33, PART 3'' FOR FURTHER INFORMATION.
NURSE CALL
FIRE ALARM FA
ALL SECURITY SYSTEMS CC
T
SOVERHEAD PAGING
STUB OUT 6" ABOVE CEILING OR
TURN OUT OF WALL AND EXTEND TO
WITHIN 12'' OF THE CABLING
PATHWAYS UNLESS NOTED TO BE
RAN FULLY IN CONDUIT BELOW
PHYSIOLOGICAL &
TELEMETRY
PATIENT
MONITORING
DETAIL OF CABLE TRAY PENETRATION THRU RATED W ALL
NO SCALE
IF THE EIGHT 4'' SLEEVES WILL
NOT BE ADEQUATE TO
CONTAIN ALL CABLES AND
STILL LEAVE ADEQUATE
CAPACITY (40% MAXIMUM
FILL), PROVIDE ADDITIONAL
SLEEVES IN WALL ABOVE TOP
LAYER OF SLEEVES.
AFTER ALL CABLES ARE
INSTALLED AND SYSTEMS ARE
COMPLETELY TESTED APPLY A
UL-LISTED FIRE- STOPPING
MATERIAL TO SEAL ENDS OF
SLEEVES TO SAME RATING AS
WALL
CABLE TROUGH TO STOP APPX.
6'' FROM WALL-SLEEVES TO
EXTEND 3'' OVER END OF TROUGH
SLEEVES TO BE 4'' GALV. RIGID
STEEL PIPE WITH FIBRE BUSHINGS
ON EACH END-SPACE 2'' APART
SLEEVES TO EXTEND NO MORE
THAN 12'' BEYOND WALL AND
SHALL BE INSTALLED PER LOCAL
CODES
FIRE-RATED PARTITION
FIBER OPTIC CABLING
DATA/VOICE CABLES
DATA/VOICE CABLES
SPARE SLEEVE OR OTHER
MISC. CABLING
PROVIDE HILTI BRAND ''TWIST-TYPE''
CABLING SLEEVES. USE EIGHT 4'' SLEEVES,
BUT ADD ADDITIONAL SLEEVES AS
NECESSARY SO AS NOT TO EXCEED A
MAXIMUM 40% FILL. MOUNT ABOVE THE
SUSPENDED CEILING AND IN-LINE WITH THE
CABLING PATH AT LOCATIONS INDICATED.
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:0
A
M
02-EJ-504
PANEL SCHEDULES
AuthorChecker
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 138 A
REC 21980 VA 72.75% 15990 VA TOTAL CONNECTED CURRENT: 154 A
LTNG 2612 VA 100.00% 2612 VA TOTAL ESTIMATED DEMAND: 49542 VA
EQUIP 30940 VA 100.00% 30940 VA TOTAL CONNECTED LOAD: 55532 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 153 A 145 A 167 A
TOTAL LOAD (kVA): 18.2 kVA 17.4 kVA 19.9 kVA
SPARE -- -- -- 20 1 53 0.0 0.0 54
SPARE -- -- -- 20 1 51 0.0 0.0 52
SPARE -- -- -- 20 1 49 0.0 0.0 50
3 60 -- -- -- SPD
SPARE -- -- -- 20 1 47 0.0 2.0 48 1 20 3/4" 12 12 Autodoor - Restroom 127, 128
45 4.2 0.5 46 1 20 3/4" 12 12 EQUIP SEC-A
WH - 2 6 10 3/4" 50 2
43 4.2 0.2 44 1 20 3/4" 12 12 REC - Electrical Room 126
41 1.2 2.4 42 1 25 3/4" 10 10 WH - 3
39 1.2 1.2 40IT Data Rack - Second Floor 10 10 3/4" 30 3
37 1.2 1.2 38
35 1.2 1.2 36
3 30 3/4" 10 10 IT Data Rack - Second Floor
33 1.2 1.1 34 1 20 3/4" 12 12 REC - OIT 125IT Data Rack - First Floor 10 10 3/4" 30 3
31 1.2 0.7 32 1 20 3/4" 12 12 REC - Computer 130
WH - 1 10 10 3/4" 25 1 29 2.0 1.2 30
Fan Coil Units - North Quadrant 12 12 3/4" 20 1 27 0.4 1.2 28
Copier - Storage/Copy 111 12 12 3/4" 20 1 25 1.0 1.2 26
3 30 3/4" 10 10 IT Data Rack - First Floor
Copier - Storage/Copy 111 12 12 3/4" 20 1 23 1.0 1.1 24 1 20 3/4" 12 12 REC - Office 120
Fan Coil Units - East Quadrant 12 12 3/4" 20 1 21 0.2 0.4 22 1 20 3/4" 12 12 Fan Coil Units - South Quadrant
Fan Coil Units - West Quadrant 12 12 3/4" 20 1 19 0.4 1.1 20 1 20 3/4" 12 12 REC - Office 115
REC - Computer 130 12 12 3/4" 20 1 17 1.1 1.1 18 1 20 3/4" 12 12 REC - Corridor & Group 129
REC - Multipurpose 131 & Comp 130 12 12 3/4" 20 1 15 1.1 0.7 16 1 20 3/4" 12 12 REC - Computer 130
REC - Office 118 & 121 12 12 3/4" 20 1 13 1.3 0.9 14 1 20 3/4" 12 12 REC - Office 123 & Jan 117
REC - Office 119 & 120 12 12 3/4" 20 1 11 1.1 1.1 12 1 20 3/4" 12 12 REC - Office 120 & 121
REC - Office 115 & 116 12 12 3/4" 20 1 9 1.3 0.7 10 1 20 3/4" 12 12 REC - Corridor
REC - Office 113 12 12 3/4" 20 1 7 1.1 1.1 8 1 20 3/4" 12 12 REC - Office 114 & 115
REC - Office 110 & Storage/Copy 111 12 12 3/4" 20 1 5 1.3 1.1 6 1 20 3/4" 12 12 REC - Office 112
LTG 12 12 3/4" 20 1 3 1.0 1.1 4 1 20 3/4" 12 12 REC - Office 109
LTG - Corridor 12 12 3/4" 20 1 1 0.4 1.2 2 1 20 3/4" 12 12 LTG
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: MDP
VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELEC 126
PANEL: L1-1 MAINS TYPE: 225/3 current study
PANELBOARD AND WIRING SCHEDULE PANEL INTERRUPTING RATING: To be determined by fault
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.
TOTAL ESTIMATED DEMAND CURRENT: 135 A
REC 13040 VA 88.34% 11520 VA TOTAL CONNECTED CURRENT: 139 A
LTNG 1757 VA 100.00% 1757 VA TOTAL ESTIMATED DEMAND: 48547 VA
EQUIP 35270 VA 100.00% 35270 VA TOTAL CONNECTED LOAD: 50067 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL CURRENT (A): 139 A 166 A 118 A
TOTAL LOAD (kVA): 16.3 kVA 19.5 kVA 14.2 kVA
SPARE -- -- -- 20 1 53 0.0 0.0 54
SPARE -- -- -- 20 1 51 0.0 0.0 52
SPARE -- -- -- 20 1 49 0.0 0.0 50
3 60 -- -- -- SPD
SPARE -- -- -- 20 1 47 0.0 0.0 48
SPARE -- -- -- 20 1 45 0.0 0.0 46
SPARE -- -- -- 20 1 43 0.0 0.0 44
3 100 -- -- -- PANEL 'L21-A'
SPARE -- -- -- 20 1 41 0.0 0.0 42 1 20 -- -- -- SPARE
SPARE -- -- -- 20 1 39 0.0 0.0 40 1 20 -- -- -- SPARE
EQUIP SEC-A 12 12 3/4" 20 1 37 0.5 0.0 38 1 20 -- -- -- SPARE
WH - 3 - Kitchenette 10 10 3/4" 25 1 35 2.4 0.3 36 1 20 3/4" 12 12 Autodoors - Restrooms 214 & 215
WH - 3 - Second Floor Men's... 10 10 3/4" 25 1 33 2.4 4.2 34
Projector - Conference 208 12 12 3/4" 20 1 31 0.2 4.2 32 2 50 3/4" 10 6 WH - 2 - Second Floor
29 1.2 1.2 30
27 1.2 1.2 28IT Data Rack - Second Floor 10 10 3/4" 30 3
25 1.2 1.2 26
3 30 3/4" 10 10 IT Data Rack - Second Floor
23 1.2 1.1 24 1 20 3/4" 12 12 REC - OIT 213
21 1.2 1.2 22IT Data Rack - First Floor 10 10 3/4" 30 3
19 1.2 1.2 20
REC - Office 204 12 12 3/4" 20 1 17 1.1 1.2 18
3 30 3/4" 10 10 IT Data Rack - First Floor
Fan Coil Units - East Quadrant 12 12 3/4" 20 1 15 2.5 2.0 16 1 20 3/4" 12 12 Fan Coil Units - West Quadrant
REC - Conference 208 12 12 3/4" 20 1 13 1.1 2.5 14 1 20 3/4" 12 12 Fan Coil Units - North Quadrant
Copier - Copy Room 211 12 12 3/4" 20 1 11 1.0 1.1 12 1 20 3/4" 12 12 REC - Office 204 & 205
Coffee Maker - Kitchenette 209 12 12 3/4" 20 1 9 0.8 0.9 10 1 20 3/4" 12 12 REC - Corridor
REC - Kitchenette 209 & HAC 210 12 12 3/4" 20 1 7 0.5 0.8 8 1 20 3/4" 12 12 Refrigerator - Kitchenette 209
REC - Office 203 & 204 12 12 3/4" 20 1 5 1.1 1.4 6 1 20 3/4" 12 12 REC - Office 202 & Mech 201
REC - Cubicle Bay 207 12 12 3/4" 20 1 3 1.1 0.9 4 1 20 3/4" 12 12 REC - Workstation 208 & Office 204
LTG - Corridor 12 12 3/4" 20 1 1 0.5 1.3 2 1 20 3/4" 12 12 LTG
CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: MDP
VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELEC 212
PANEL: L2-1 MAINS TYPE: 225/3 current study
PANELBOARD AND WIRING SCHEDULE PANEL INTERRUPTING RATING: To be determined by fault
Revisions: Date:
ADDENDUM #1 1/21/2022
J
M
M
M
M
M
M
M
M M M
M
M
M
M
M
M
M
M
M
M
M
M C
J
M
J J J J
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
115OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
VESTIBULE
STAIR 1
ELEV LOBBY
MECH
ELEV
OIT
ELEC
126JAN
GROUP
COMPUTER
MEN
W OMEN
CORRIDOR
CORRIDOR
MULTI-PURPOSE
STAIR 2
S133
STAIR 3
S103
CORRIDOR
STORAGE/COPY
-4L1-1
-5L1-1
-10L1-1
-11L1-1
-12L1-1
-13L1-1
-14L1-1
-17L1-1
-18L1-1
W H-2
W H-3
W H-1 PANEL L1-1
-8L1-1
-19L1-1
PO5
PO5
PO5
-6L1-1
PO5
-7L1-1
PO5
PO5
-20L1-1
PO5
PO5
-9L1-1
PO5
-21L1-1
-22L1-1
PO5 PO5
-27L1-1
PO5
PO5
PO5
PO5
-24L1-1
PO5
PO6
PO6
PO6
PO7
CLG
PO8CLG
PO9
-25L1-1-23L1-1
-29L1-1
-32L1-1
PO6
PO6PO3
PO3
PO3
-44L1-1
-34L1-1
COAX PANEL
-42L1-1
PO12
-43,45L1-1
PO13
PO12
-15L1-1
-16L1-1
PO5
+6' - 6"
-18,20,22L2-1
-19,21,23L2-1
-26,28,30L1-1 -31,33,35L1-1
PO11
PO11
PO11
PO11
PANEL LE-1
TO REMAIN
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:0
A
M
02-EP-111
POWER PLAN - FLOOR 01
CMTACMTA
SCALE: 1/4" = 1'-0"02-EP-111
1 Power Plan - Floor 01
GENERAL NOTES (POWER):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT
NUMBER.
D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS
SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM
SHALL BE MARKED IN ACCORDANCE W ITH NEC 406.3(E).
E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS
SHALL BE COORDINATED W ITH MECHANICAL AND PLUMBING
CONTRACTORS TO ENSURE ACCESS AND W ORKING CLEARANCE IS
MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED
CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE
AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT
NAMEPLATES OR ACCESS PANELS OR THROUGH
ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER
TRADES.
N
TAGGED NOTES
PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO
REMAIN.
PO5 DEVICE TO BE INCLUDED IN THE BID DEDUCT.
PO6 EXISTING RECEPTACLE AND BRANCH CIRCUIT TO BE
REPLACED WITH NEW DEVICE AND WIRING. EXISTING
JUNCTION BOX AND RACEWAY TO BE REUSED.
PO7 PROVIDE CONTROL SWITCH FOR MOTORIZED SCREEN.
COORDINATE EXACT SWITCH REQUIREMENTS WITH SCREEN
INSTALLER.
PO8 PROVIDE 120V ELECTRICAL POWER CONNECTION FOR
MOTORIZED SCREEN. COORDINATE EXACT MOUNTING
LOCATION WITH SCREEN INSTALLER.
PO9 PROVIDE 20A/120V DUPLEX RECEPTACLE FLUSH MOUNTED
WITH THE CEILING FOR CONNECTION TO PROJECTOR.
COORDINATE EXACT MOUNTING LOCATION WITH PROJECTOR
INSTALLER.
PO11 PROVIDE 30A, 208 THREE-PHASE TWIST LOCK RECEPTACLE
(L21-30R). COORDINATE INSTALLATION LOCATION WITH
TELECOMMUNICATIONS CONTRACTOR PRIOR TO ROUGH-IN.
PO12 DISCONNECT SWITCH PROVIDED BY MECHANICAL WORK.
PO13 PROVIDE 30A, 240V SINGLE PHASE DISCONNECT SWITCH.
J J
M M
M
M
M
M
M
M M
M
M
M
M
M
J M
C
J J J J
COPIER
REFRIG.
-3L2-1
-4L2-1
STAIR 3
STAIR 2
OIT
ELEV
HAC
MECH
STORAGE
218A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ELEC
OFFICE
COPY ROOM
STAIR 1
S200
CONFERENCE
MEN
W OMEN
CORRIDOR
CUBICLE BAY
OFFICE
W ORKSTATION
OFFICE
OFFICE
KITCHENETTE
-5L2-1
-6L2-1
COFFEE
MAKER
-7L2-1
-8L2-1
-9L2-1
-10L2-1
-11L2-1
-12L2-1
-13L2-1
PO2
W H-2
W H-3
PO3
PO2
PANEL L2-1
PO5
PO5
-17L2-1
PO5
PO5
PO5
-14L2-1
-16L2-1
-15L2-1
PO7
CLG
PO8
CLG
PO9
PO10
-24L2-1 -25,27,29L2-1
-36,38,40L1-1
COAX PANEL
-31L2-1
-32,34L2-1
PO12
-33L2-1
PO12
W H-3
-35L2-1
+4' - 6"
-26,28,30L2-1 -37,39,41L1-1
PO11 PO11 PO11
PO11
PANEL L21-A
TO REMAIN
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:1
A
M
02-EP-121
POWER PLAN - FLOOR 02
CMTACMTA
SCALE: 1/4" = 1'-0"02-EP-121
1 Power Plan - Floor 02
GENERAL NOTES (POWER):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT
NUMBER.
D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS
SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM
SHALL BE MARKED IN ACCORDANCE W ITH NEC 406.3(E).
E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS
SHALL BE COORDINATED W ITH MECHANICAL AND PLUMBING
CONTRACTORS TO ENSURE ACCESS AND W ORKING CLEARANCE IS
MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED
CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE
AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT
NAMEPLATES OR ACCESS PANELS OR THROUGH
ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER
TRADES.
N
TAGGED NOTES
PO2 NEW LOCATION FOR EXISTING ADVANCED NETWORK
ANNUNCIATION DEVICE. CONNECT TO EXISTING SYSTEM AS
REQUIRED.
PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO
REMAIN.
PO5 DEVICE TO BE INCLUDED IN THE BID DEDUCT.
PO7 PROVIDE CONTROL SWITCH FOR MOTORIZED SCREEN.
COORDINATE EXACT SWITCH REQUIREMENTS WITH SCREEN
INSTALLER.
PO8 PROVIDE 120V ELECTRICAL POWER CONNECTION FOR
MOTORIZED SCREEN. COORDINATE EXACT MOUNTING
LOCATION WITH SCREEN INSTALLER.
PO9 PROVIDE 20A/120V DUPLEX RECEPTACLE FLUSH MOUNTED
WITH THE CEILING FOR CONNECTION TO PROJECTOR.
COORDINATE EXACT MOUNTING LOCATION WITH PROJECTOR
INSTALLER.
PO10 PROVIDE FIRE RATED POKE-THRU TO ACCOMMODATE TWO
DATA AND ONE VOICE JACKS, AND (2) 20A/120V DUPLEX
RECEPTACLES. COORDINATE EXACT MOUNTING LOCATION
WITH OWNER PRIOR TO ROUGH-IN.
PO11 PROVIDE 30A, 208 THREE-PHASE TWIST LOCK RECEPTACLE
(L21-30R). COORDINATE INSTALLATION LOCATION WITH
TELECOMMUNICATIONS CONTRACTOR PRIOR TO ROUGH-IN.
PO12 DISCONNECT SWITCH PROVIDED BY MECHANICAL WORK.
PANEL L2-1
FACP
TS
FS
FACP
N A
C
FIRE
STORAGE
G02
STORAGE/COPY ROOM
G02A
STORAGE
G02B
ELEV
E-00
ELEV EQUIP
G01
CORRIDOR
H002
STORAGE
G03
OIT
G04
STORAGE
G05
CORRIDOR
H003
TRANSFORMER
G09
MECH RM
G08
STORAGE
G07
STORAGE
G07A
TOILET
G05A
HAC
G05B
CORRIDOR
H001
STORAGE
G06
STAIR 1
S001
EXEX
EX
T E
L
EX
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:1
A
M
02-ET-101
SYSTEMS PLAN - FLOOR 00
AuthorChecker
SCALE: 1/4" = 1'-0"02-ET-101
1 Systems Plan - Floor 00
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT
NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND
SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF
EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO
THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).
REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL
REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT
BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.
PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM
CABLING INSTALLATION.
N
ADDITIONAL WORK SCOPE :
THE FOLLOWING SCOPE OF WORK IS TO BE INCLUDED IN PROJECT AND IS NOT SHOWN ON
THESE DRAWINGS.
PROVIDE A FIRE ALARM TAMPER SWITCH CONNECTION TO THE POST INDICATOR VALVE FOR
THE NEW FIRE SPRINKLER SERVICE LOCATED ON SITE. COORDINATE EXACT LOCATION WITH
FIRE SPRINKLER INSTALLER.
SD
F
F
F
S S
S
S S
S
S
S
W AP
W AP
W AP
N A
C
KP
CR
IR
IM
F
F F
F
F F
F
V
V
V
V
V
V
TS
FS
DS
PB
PB
PB PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB PB
PBPB
PB
PB
PB
PB
PP PP
PPPP
ADAD
CC
CC
CC CC
CC
CC
CC
OFFICE
OFFICE
OFFICE
112 OFFICE
113 OFFICE
OFFICE
OFFICE
OFFICE
123OFFICE
OFFICE
OFFICE
OFFICE
VESTIBULE
STAIR 1
ELEV LOBBY
MECH
ELEV
OIT
ELEC
JAN
GROUP
COMPUTER
MEN
W OMEN
CORRIDOR
CORRIDOR
MULTI-PURPOSE
STAIR 2
S133
STAIR 3
S103
CORRIDOR
STORAGE/COPY
T E
L
T E
L
EX
EX
EX
S3
S3
S3
S3 S3
S3
S3
S3
S3
S3
S3
S3
S3
S3
S3
S3
S3
S3S3
S3
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V.
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V .
2D/1V
2D/1V
S4
S4
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
S3
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D
S5
2D/1V
EXIST COAX
PANEL
PANEL L1-1
S7
S7
S7 S7
S7
S1
S1
S1
S1
S1 S1
S1
S9
S8
S10
S4
S11 S11
S11
S11
S11
S11
S11
S11
S11
S11
S11
DATA
RACK (TYP)
S12
S11
S11
S11
S11
S11
S11
S11
S11
-48L1-1
ELEC
S11 S14
S14
S14
S15S15
SEC-A
-46L1-1
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:1
A
M
02-ET-111
SYSTEMS PLAN - FLOOR 01
CMTACMTA
SCALE: 1/4" = 1'-0"02-ET-111
1 Systems Plan - Floor 01
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT
NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND
SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF
EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO
THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).
REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL
REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT
BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.
PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM
CABLING INSTALLATION.
N
TAGGED NOTES
ELE
C
ELECTRICAL NOTES
S1 NEW LOCATION FOR EXISTING CEILING MOUNTED FIRE ALARM
DEVICE. SALVAGED ROM DEMOLITION. CONNECT TO
EXISTING FIRE ALARM SYSTEM AS REQUIRED.
S3 DEVICE TO BE INCLUDED IN THE BID DEDUCT.
S4 PROVIDE (2)-4" CONDUIT SLEEVES THROUGH WALLS
INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO
LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL
PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501.
S5 PROVIDE DATA OUTLET WITH TWO DATA CONNCTIONS FOR
CONNECTION TO PROJECTOR. COORDINATE EXACT
MOUNTING LOCATION WITH PROJECTOR INSTALLER/OWNER.
S7 PROPOSED CABLING PATH - COORDINATE ALL PATHS WITH
PIPING, DUCTWORK, ETC. (NOTE : STUB-UP CONDUITS SHALL
BE ROUTED TO THESE CABLING PATHS). PROVIDE CABLE
TRAY ALONG ALL REQUIRED CABLING PATHS. WHERE
CABLING PATH IS INTERRUPTED BY DUCTWORK, PIPING, ETC,
PROVIDE CABLE TRAY PATH BELOW AS REQUIRED TO
MAINTAIN A CONTINUOUS CABLING PATH - REFER TO
INSTALLATION DETAILS FOR FURTHER REQUIREMENTS.
CABLE TRAY IN OIT ROOMS ARE TO BE INSTALLED AROUND
PERIMETER OF ROOM PER VA OIT DEISGN GUIDE TEMPLATES;
PROVIDE AS REQUIRED.
S8 AUDIO/VIDEO INTERCOM MASTER STATION WITH DOOR
RELEASE FOR CONTROL OF FRONT DOOR. PROVIDE POWER
SUPPLIES & DOOR RELAY CONTACTS, ALL CABLING,
CONNECTORS, RELAYS, ETC. AS REQUIRED FOR A COMPLETE
AND OPERATIONAL SYSTEM. AUDIO/VIDEO INTERCOM UNIT TO
BE AIPHONE#AX-8MV OR APPROVED EQUIVALENT. COLOR TO
BE SELECTED BY COR.
S9 AUDIO/VIDEO INTERCOM REMOTE STATION WITH FLUSH-MTD
S.S. ENCLOSURE. REMOTE STATION TO BE AIPHONE #AX-DVF
OR APPROVED EQUIVALENT.
S10 PROVIDE (4)-4" CONDUIT SLEEVES THROUGH WALLS
INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO
LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL
PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501 FOR
ADDITIONAL DETAILS.
S11 PROVIDE PANIC BUTTON AND ASSOCIATED ROUGH-IN PER
VENDOR REQUIREMENTS. COORDINATE LOCATION WITH
OWNER/VENDOR PRIOR TO ROUGH-IN.
S12 PROVIDE THE FOLLOWING CABLING SYSTEM ROUTED FROM
DATA RACK:
a). TWO 12-STRAND FIBER OPTIC CABLE ASSEMBLY WITH
MULTI-FIBER PUSH-ON CONNECTORS ROUTED TO THE DATA
RACK LOCATED IN THE BASEMENT O.I.T. CLOSET G04.
PROVIDE TWO CASSETTES WITH 12 DUPLEX LC INTERFACES IN
BOTH THE BASEMENT AND NEW O.I.T. CLOSET DATA RACKS
FOR CABLING TERMINATIONS.
b). ONE 100 PAIR COPPER CABLE FROM NEW DATA RACK TO
110 BLOCK(S) INSTALLED IN ADJACENT MECHANICAL ROOM.
CONTRACTOR PROVIDE 110 BLOCKS AND TERMINATIONS AS
REQUIRED.
S14 PROVIDE 360 DEGREE CCTV CAMERA.
S15 PROVIDE CCTV CAMERA FOR STAIRWELL COVERAGE AS
REQUIRED; COORDINATE DETAILS WITH COR.
CRITICAL WIDE AREA NETWORK GENERAL NOTE:
COORDINATE REINSTALLATION OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER.
(DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING.
COORDINATE REW ORK DETAILS W ITH OW NER.)
F
F
F
F
F
S
S
S S
S
S
S
W AP
W AP
W AP
F
CR
DS
DS
CR
CR
F F
V
V
V
FS
TS
SD
PB
PP
PPPP
PP
ADAD
T E
L
STAIR 3
STAIR 2
OIT
ELEV
HAC
MECH
STORAGE
218A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ELEC
OFFICE
COPY ROOM
STAIR 1
S200
CONFERENCE
MEN
W OMEN
CORRIDOR
CUBICLE BAY
OFFICE
W ORKSTATION
OFFICE
OFFICE
KITCHENETTE
S1
S1
S1
S1
S3
S3 S3 S3
S3
S3
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
S4
S4
2D/1V
2D/1V
2D
S5
S6
EXIST COAX
PANEL
PANEL L2-1
S7
S7
S7
S1
S11
EX.
S13
DATA
RACK (TYP)
S12
-36L2-1
2D/1V.
2D/1V
-37L2-1
SEC-A
E IN
I
HANS
ROBERT A.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NA L
S IO ENG
NUMBER
PE-2006009888
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/2
/2
:5
:1
A
M
02-ET-121
SYSTEMS PLAN - FLOOR 02
CMTACMTA
SCALE: 1/4" = 1'-0"02-ET-121
1 Systems Plan - Floor 02
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT
NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND
SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF
EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO
THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).
REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL
REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT
BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.
PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM
CABLING INSTALLATION.
N
TAGGED NOTES
S1 NEW LOCATION FOR EXISTING CEILING MOUNTED FIRE ALARM
DEVICE. SALVAGED ROM DEMOLITION. CONNECT TO
EXISTING FIRE ALARM SYSTEM AS REQUIRED.
S3 DEVICE TO BE INCLUDED IN THE BID DEDUCT.
S4 PROVIDE (2)-4" CONDUIT SLEEVES THROUGH WALLS
INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO
LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL
PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501.
S5 PROVIDE DATA OUTLET WITH TWO DATA CONNCTIONS FOR
CONNECTION TO PROJECTOR. COORDINATE EXACT
MOUNTING LOCATION WITH PROJECTOR INSTALLER/OWNER.
S6 PROVIDE FIRE RATED POKE-THRU TO ACCOMMODATE TWO
DATA AND ONE VOICE JACKS, AND (2) 20A/120V DUPLEX
RECEPTACLES. COVER TYPE AND FINISH TO BE SELECTED BY
COR. COORDINATE EXACT MOUNTING LOCATION WITH COR
PRIOR TO ROUGH-IN.
S7 PROPOSED CABLING PATH - COORDINATE ALL PATHS WITH
PIPING, DUCTWORK, ETC. (NOTE : STUB-UP CONDUITS SHALL
BE ROUTED TO THESE CABLING PATHS). PROVIDE CABLE
TRAY ALONG ALL REQUIRED CABLING PATHS. WHERE
CABLING PATH IS INTERRUPTED BY DUCTWORK, PIPING, ETC,
PROVIDE CABLE TRAY PATH BELOW AS REQUIRED TO
MAINTAIN A CONTINUOUS CABLING PATH - REFER TO
INSTALLATION DETAILS FOR FURTHER REQUIREMENTS.
CABLE TRAY IN OIT ROOMS ARE TO BE INSTALLED AROUND
PERIMETER OF ROOM PER VA OIT DEISGN GUIDE TEMPLATES;
PROVIDE AS REQUIRED.
S11 PROVIDE PANIC BUTTON AND ASSOCIATED ROUGH-IN PER
VENDOR REQUIREMENTS. COORDINATE LOCATION WITH
OWNER/VENDOR PRIOR TO ROUGH-IN.
S12 PROVIDE THE FOLLOWING CABLING SYSTEM ROUTED FROM
DATA RACK:
a). TWO 12-STRAND FIBER OPTIC CABLE ASSEMBLY WITH
MULTI-FIBER PUSH-ON CONNECTORS ROUTED TO THE DATA
RACK LOCATED IN THE BASEMENT O.I.T. CLOSET G04.
PROVIDE TWO CASSETTES WITH 12 DUPLEX LC INTERFACES IN
BOTH THE BASEMENT AND NEW O.I.T. CLOSET DATA RACKS
FOR CABLING TERMINATIONS.
b). ONE 100 PAIR COPPER CABLE FROM NEW DATA RACK TO
110 BLOCK(S) INSTALLED IN ADJACENT MECHANICAL ROOM.
CONTRACTOR PROVIDE 110 BLOCKS AND TERMINATIONS AS
REQUIRED.
S13 PROVIDE (4)-4" CONDUITS ABOVE DUCTWORK AND ROUTE TO
O.I.T. ROOM, AS INDICATED.
CRITICAL WIDE AREA NETWORK GENERAL NOTE:
COORDINATE REINSTALLATION OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER.
(DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING.
COORDINATE REW ORK DETAILS W ITH OW NER.)
| Sheets |
| 02-ED-111 - LIGHTING DEMOLITION PLAN - FLOOR 01 |
| 02-ED-112 - POWER DEMOLITION PLAN - FLOOR 01 |
| 02-ED-122 - POWER DEMOLITION PLAN - FLOOR 02 |
| 02-EJ-504 - PANEL SCHEDULES |
| 02-EP-111 - POWER PLAN - FLOOR 01 |
| 02-EP-121 - POWER PLAN - FLOOR 02 |
| 02-ET-101 - SYSTEMS PLAN - FLOOR 00 |
| 02-ET-111 - SYSTEMS PLAN - FLOOR 01 |
| 02-ET-121 - SYSTEMS PLAN - FLOOR 02 |
File details come from the government source that posted it. Updated .