ELECTRICAL DRWINGS.pdf

PDF 2 MB Posted

Attached to
Z2DA--FCA - Renovate Space for Domiciliary Providers, Building 2 PA:657-19-127JB
Solicitation number
36C25522R0033-0002
Issued by

About this file

This is an amendment to a solicitation for project 657-19-127JB to renovate space for domiciliary providers in Building 2 at a VA medical center. The amendment provides answers to questions submitted, an updated site visit roster, and revised specifications and drawings. Key details include renovations to electrical, lighting, and systems on the first and second floors, including demolishing existing panels and installing new ones, upgrading receptacles and branch circuits, and installing cabling pathways and connections for systems like fire alarm, nurse call, and security. The project also involves electrical work in the basement and on the ground floor. The response date has not changed from the original solicitation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OS

OS

OS

OS

OS OS

OS

OS

OS

OS

OS

COAX PANEL

TO REMAIN

PANEL L1-2

TO BE REMOVED

PANEL L1-3

TO BE REMOVED

PANEL L1-1

TO BE REMOVED

PANEL L1-4

TO BE REMOVED

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:0

A

M

02-ED-111

LIGHTING DEMOLITION PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-ED-111

1 Lighting Demolition Plan - Floor 01

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY

MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN

OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.

F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE W ITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-

W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.

M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.

N

Revisions: Date:

ADDENDUM #1 1/21/2022

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J J

J

J

J

J

PO1

PO1

PO1

PO1

PO1

PO1 PO1

PO1 PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO1

PO3

PO3

PO3

PANEL L1-4

TO BE REMOVED

PANEL L1-2

TO BE REMOVED

COAX PANEL

TO REMAIN

PANEL L1-3

TO BE REMOVED

PANEL L1-1

TO BE REMOVED

PO14

PO14

PO14

PANEL LE-1

TO REMAIN

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:0

A

M

02-ED-112

POWER DEMOLITION PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-ED-112

1 Power Demolition Plan - Floor 01

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY

MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN

OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.

F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE W ITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-

W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.

M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.

N

TAGGED NOTES

PO1 EXISTING HVAC UNIT TO BE RELOCATED, REMOVE

ELECTRICAL POWER CONNECTION AND BRANCH CIRCUIT.

COORDINATE DETAILS WITH MECHANICAL WORK.

PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO

REMAIN.

PO14 REMOVE EXISTING POWER PANEL INDICATED AND

ASSOCIATED PANEL FEEDER COMPLETELY BACK TO SOURCE.

FIELD VERIFY IF PANEL HAS ANY DEVICES, LIGHTS, ETC. ON

CIRCUITS THAT ARE TO REMAIN. RE-ROUTE THESE CIRCUITS

TO EXISTING/NEW PANELS THAT ARE IN THE SAME AREA, AS

REQUIRED, (UTILIZE SPACES/SPARES IN THESE PANELS AS

NECESSARY). CONTRACTOR SHALL CAREFULLY DETERMINE

EXTENT OF WORK PRIOR TO DEMOLITION OF THE

PANEL/PANEL FEEDER. REFER TO PANEL

RELOCATION/DEMOLITION DETAIL AND ELECTRICAL POWER

RISER DIAGRAM.

J J

J J

J J

J

J

J J

J JJ

J

J

PO1

PO1

PO1

PO1

PO1

PO1 PO1

PO1

PO1

PO1

PO1

PO1

PO4

PO3

PO4

COAX PANEL

TO REMAIN

PANEL L2-1

TO BE REMOVED

PO14

PANEL L21-A

TO REMAIN

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:0

A

M

02-ED-122

POWER DEMOLITION PLAN - FLOOR 02

CMTACMTA

SCALE: 1/4" = 1'-0"02-ED-122

1 Power Demolition Plan - Floor 02

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY

MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN

OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.

F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE W ITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-

W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.

M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.

N

TAGGED NOTES

PO1 EXISTING HVAC UNIT TO BE RELOCATED, REMOVE

ELECTRICAL POWER CONNECTION AND BRANCH CIRCUIT.

COORDINATE DETAILS WITH MECHANICAL WORK.

PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO

REMAIN.

PO4 REMOVE EXISTING ADVANCED NETWORK ANNUNCIATION UNIT

AND SALVAGE, STORE. CLEAN AND REINSTALL UNIT PER NEW

WORK PLAN TO LIKE NEW CONDITION.

PO14 REMOVE EXISTING POWER PANEL INDICATED AND

ASSOCIATED PANEL FEEDER COMPLETELY BACK TO SOURCE.

FIELD VERIFY IF PANEL HAS ANY DEVICES, LIGHTS, ETC. ON

CIRCUITS THAT ARE TO REMAIN. RE-ROUTE THESE CIRCUITS

TO EXISTING/NEW PANELS THAT ARE IN THE SAME AREA, AS

REQUIRED, (UTILIZE SPACES/SPARES IN THESE PANELS AS

NECESSARY). CONTRACTOR SHALL CAREFULLY DETERMINE

EXTENT OF WORK PRIOR TO DEMOLITION OF THE

PANEL/PANEL FEEDER. REFER TO PANEL

RELOCATION/DEMOLITION DETAIL AND ELECTRICAL POWER

RISER DIAGRAM.

STRUCTURE ABOVE

1'' C. FOR

STUB DOWN WHERE REQUIRED

OUTLETS AS SHOWN ON PLAN

SUCH CABLING SHALL MEET N.E.C. REQUIREMENTS FOR SUCH INSTALLATIONS.

WHERE OPEN CABLING IS INSTALLED WITHIN ENVIRONMENT AIR PLENUMS,

ROUGHING-IN DETAIL FOR STUB-OUTS

ALL CONDUIT STUB-OUTS SHALL EXTEND TO NEAREST CABLING PATH (J-HOOK

OR CABLE TRAY).

NO SCALE

NOTES:

FLOOR LINE

HEIGHT AS SCHEDULED

S

3/4'' CONDUIT MINIMUM

J

FLEX DOWN

CEILING LINE

INSULATED THROAT BUSHING

NC

SYSTEMS CABLING SLEEVE INSTALLATION DETAIL

NO SCALE

CEILING

STRUCTURE

OBSTRUCTIONS

8"+, TO CLEARLC

FIRE/SMOKE RATED OR UNRATED PARTITION OF

VARIOUS CONSTRUCTIONS-REFER TO

ARCHITECTURAL PLANS OR FIELD VERIFY TYPE

ACCESSIBLE CEILING EACH SIDE OF SLEEVE

USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS, ETC.

PROVIDE HILTI BRAND ''TWIST-TYPE''

CABLING SLEEVES. USE TWO 4'' SLEEVES,

BUT ADD ADDITIONAL SLEEVES AS

NECESSARY SO AS NOT TO EXCEED A

MAXIMUM 40% FILL. MOUNT ABOVE THE

SUSPENDED CEILING AND IN-LINE WITH THE

CABLING PATH AT LOCATIONS INDICATED

AND WHERE REQUIRED FOR CABLING

PATHWAYS.

PROVIDE CAULKING-STYLE FIRE-STOPPING

APPLICATION BETWEEN SLEEVE AND WALL

MATERIAL TO ANCHOR SLEEVE.

NOTE:

CABLING FOR THE FOLLOWING SYSTEMS SHALL BE RAN FULLY IN CONDUIT AND NOT JUST TO

THE CABLING PATHWAYS (FULL CONDUIT ''HOMERUNS''). REFER ALSO TO SPECIFICATIONS

SECTION ''27 05 33, PART 3'' FOR FURTHER INFORMATION.

NURSE CALL

FIRE ALARM FA

ALL SECURITY SYSTEMS CC

T

SOVERHEAD PAGING

STUB OUT 6" ABOVE CEILING OR

TURN OUT OF WALL AND EXTEND TO

WITHIN 12'' OF THE CABLING

PATHWAYS UNLESS NOTED TO BE

RAN FULLY IN CONDUIT BELOW

PHYSIOLOGICAL &

TELEMETRY

PATIENT

MONITORING

DETAIL OF CABLE TRAY PENETRATION THRU RATED W ALL

NO SCALE

IF THE EIGHT 4'' SLEEVES WILL

NOT BE ADEQUATE TO

CONTAIN ALL CABLES AND

STILL LEAVE ADEQUATE

CAPACITY (40% MAXIMUM

FILL), PROVIDE ADDITIONAL

SLEEVES IN WALL ABOVE TOP

LAYER OF SLEEVES.

AFTER ALL CABLES ARE

INSTALLED AND SYSTEMS ARE

COMPLETELY TESTED APPLY A

UL-LISTED FIRE- STOPPING

MATERIAL TO SEAL ENDS OF

SLEEVES TO SAME RATING AS

WALL

CABLE TROUGH TO STOP APPX.

6'' FROM WALL-SLEEVES TO

EXTEND 3'' OVER END OF TROUGH

SLEEVES TO BE 4'' GALV. RIGID

STEEL PIPE WITH FIBRE BUSHINGS

ON EACH END-SPACE 2'' APART

SLEEVES TO EXTEND NO MORE

THAN 12'' BEYOND WALL AND

SHALL BE INSTALLED PER LOCAL

CODES

FIRE-RATED PARTITION

FIBER OPTIC CABLING

DATA/VOICE CABLES

DATA/VOICE CABLES

SPARE SLEEVE OR OTHER

MISC. CABLING

PROVIDE HILTI BRAND ''TWIST-TYPE''

CABLING SLEEVES. USE EIGHT 4'' SLEEVES,

BUT ADD ADDITIONAL SLEEVES AS

NECESSARY SO AS NOT TO EXCEED A

MAXIMUM 40% FILL. MOUNT ABOVE THE

SUSPENDED CEILING AND IN-LINE WITH THE

CABLING PATH AT LOCATIONS INDICATED.

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:0

A

M

02-EJ-504

PANEL SCHEDULES

AuthorChecker

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 138 A

REC 21980 VA 72.75% 15990 VA TOTAL CONNECTED CURRENT: 154 A

LTNG 2612 VA 100.00% 2612 VA TOTAL ESTIMATED DEMAND: 49542 VA

EQUIP 30940 VA 100.00% 30940 VA TOTAL CONNECTED LOAD: 55532 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 153 A 145 A 167 A

TOTAL LOAD (kVA): 18.2 kVA 17.4 kVA 19.9 kVA

SPARE -- -- -- 20 1 53 0.0 0.0 54

SPARE -- -- -- 20 1 51 0.0 0.0 52

SPARE -- -- -- 20 1 49 0.0 0.0 50

3 60 -- -- -- SPD

SPARE -- -- -- 20 1 47 0.0 2.0 48 1 20 3/4" 12 12 Autodoor - Restroom 127, 128

45 4.2 0.5 46 1 20 3/4" 12 12 EQUIP SEC-A

WH - 2 6 10 3/4" 50 2

43 4.2 0.2 44 1 20 3/4" 12 12 REC - Electrical Room 126

41 1.2 2.4 42 1 25 3/4" 10 10 WH - 3

39 1.2 1.2 40IT Data Rack - Second Floor 10 10 3/4" 30 3

37 1.2 1.2 38

35 1.2 1.2 36

3 30 3/4" 10 10 IT Data Rack - Second Floor

33 1.2 1.1 34 1 20 3/4" 12 12 REC - OIT 125IT Data Rack - First Floor 10 10 3/4" 30 3

31 1.2 0.7 32 1 20 3/4" 12 12 REC - Computer 130

WH - 1 10 10 3/4" 25 1 29 2.0 1.2 30

Fan Coil Units - North Quadrant 12 12 3/4" 20 1 27 0.4 1.2 28

Copier - Storage/Copy 111 12 12 3/4" 20 1 25 1.0 1.2 26

3 30 3/4" 10 10 IT Data Rack - First Floor

Copier - Storage/Copy 111 12 12 3/4" 20 1 23 1.0 1.1 24 1 20 3/4" 12 12 REC - Office 120

Fan Coil Units - East Quadrant 12 12 3/4" 20 1 21 0.2 0.4 22 1 20 3/4" 12 12 Fan Coil Units - South Quadrant

Fan Coil Units - West Quadrant 12 12 3/4" 20 1 19 0.4 1.1 20 1 20 3/4" 12 12 REC - Office 115

REC - Computer 130 12 12 3/4" 20 1 17 1.1 1.1 18 1 20 3/4" 12 12 REC - Corridor & Group 129

REC - Multipurpose 131 & Comp 130 12 12 3/4" 20 1 15 1.1 0.7 16 1 20 3/4" 12 12 REC - Computer 130

REC - Office 118 & 121 12 12 3/4" 20 1 13 1.3 0.9 14 1 20 3/4" 12 12 REC - Office 123 & Jan 117

REC - Office 119 & 120 12 12 3/4" 20 1 11 1.1 1.1 12 1 20 3/4" 12 12 REC - Office 120 & 121

REC - Office 115 & 116 12 12 3/4" 20 1 9 1.3 0.7 10 1 20 3/4" 12 12 REC - Corridor

REC - Office 113 12 12 3/4" 20 1 7 1.1 1.1 8 1 20 3/4" 12 12 REC - Office 114 & 115

REC - Office 110 & Storage/Copy 111 12 12 3/4" 20 1 5 1.3 1.1 6 1 20 3/4" 12 12 REC - Office 112

LTG 12 12 3/4" 20 1 3 1.0 1.1 4 1 20 3/4" 12 12 REC - Office 109

LTG - Corridor 12 12 3/4" 20 1 1 0.4 1.2 2 1 20 3/4" 12 12 LTG

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: MDP

VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELEC 126

PANEL: L1-1 MAINS TYPE: 225/3 current study

PANELBOARD AND WIRING SCHEDULE PANEL INTERRUPTING RATING: To be determined by fault

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS. SPARE BREAKERS TO BE 20A/1P.

TOTAL ESTIMATED DEMAND CURRENT: 135 A

REC 13040 VA 88.34% 11520 VA TOTAL CONNECTED CURRENT: 139 A

LTNG 1757 VA 100.00% 1757 VA TOTAL ESTIMATED DEMAND: 48547 VA

EQUIP 35270 VA 100.00% 35270 VA TOTAL CONNECTED LOAD: 50067 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL CURRENT (A): 139 A 166 A 118 A

TOTAL LOAD (kVA): 16.3 kVA 19.5 kVA 14.2 kVA

SPARE -- -- -- 20 1 53 0.0 0.0 54

SPARE -- -- -- 20 1 51 0.0 0.0 52

SPARE -- -- -- 20 1 49 0.0 0.0 50

3 60 -- -- -- SPD

SPARE -- -- -- 20 1 47 0.0 0.0 48

SPARE -- -- -- 20 1 45 0.0 0.0 46

SPARE -- -- -- 20 1 43 0.0 0.0 44

3 100 -- -- -- PANEL 'L21-A'

SPARE -- -- -- 20 1 41 0.0 0.0 42 1 20 -- -- -- SPARE

SPARE -- -- -- 20 1 39 0.0 0.0 40 1 20 -- -- -- SPARE

EQUIP SEC-A 12 12 3/4" 20 1 37 0.5 0.0 38 1 20 -- -- -- SPARE

WH - 3 - Kitchenette 10 10 3/4" 25 1 35 2.4 0.3 36 1 20 3/4" 12 12 Autodoors - Restrooms 214 & 215

WH - 3 - Second Floor Men's... 10 10 3/4" 25 1 33 2.4 4.2 34

Projector - Conference 208 12 12 3/4" 20 1 31 0.2 4.2 32 2 50 3/4" 10 6 WH - 2 - Second Floor

29 1.2 1.2 30

27 1.2 1.2 28IT Data Rack - Second Floor 10 10 3/4" 30 3

25 1.2 1.2 26

3 30 3/4" 10 10 IT Data Rack - Second Floor

23 1.2 1.1 24 1 20 3/4" 12 12 REC - OIT 213

21 1.2 1.2 22IT Data Rack - First Floor 10 10 3/4" 30 3

19 1.2 1.2 20

REC - Office 204 12 12 3/4" 20 1 17 1.1 1.2 18

3 30 3/4" 10 10 IT Data Rack - First Floor

Fan Coil Units - East Quadrant 12 12 3/4" 20 1 15 2.5 2.0 16 1 20 3/4" 12 12 Fan Coil Units - West Quadrant

REC - Conference 208 12 12 3/4" 20 1 13 1.1 2.5 14 1 20 3/4" 12 12 Fan Coil Units - North Quadrant

Copier - Copy Room 211 12 12 3/4" 20 1 11 1.0 1.1 12 1 20 3/4" 12 12 REC - Office 204 & 205

Coffee Maker - Kitchenette 209 12 12 3/4" 20 1 9 0.8 0.9 10 1 20 3/4" 12 12 REC - Corridor

REC - Kitchenette 209 & HAC 210 12 12 3/4" 20 1 7 0.5 0.8 8 1 20 3/4" 12 12 Refrigerator - Kitchenette 209

REC - Office 203 & 204 12 12 3/4" 20 1 5 1.1 1.4 6 1 20 3/4" 12 12 REC - Office 202 & Mech 201

REC - Cubicle Bay 207 12 12 3/4" 20 1 3 1.1 0.9 4 1 20 3/4" 12 12 REC - Workstation 208 & Office 204

LTG - Corridor 12 12 3/4" 20 1 1 0.5 1.3 2 1 20 3/4" 12 12 LTG

CIRCUIT DESCRIPTION WIRE GND C OCP P CKT A B C CKT P OCP C GND WIRE CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: MDP

VOLTAGE: 208Y/120V,3P,4W SPD: Yes LOCATION: ELEC 212

PANEL: L2-1 MAINS TYPE: 225/3 current study

PANELBOARD AND WIRING SCHEDULE PANEL INTERRUPTING RATING: To be determined by fault

Revisions: Date:

ADDENDUM #1 1/21/2022

J

M

M

M

M

M

M

M

M M M

M

M

M

M

M

M

M

M

M

M

M

M C

J

M

J J J J

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

115OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

VESTIBULE

STAIR 1

ELEV LOBBY

MECH

ELEV

OIT

ELEC

126JAN

GROUP

COMPUTER

MEN

W OMEN

CORRIDOR

CORRIDOR

MULTI-PURPOSE

STAIR 2

S133

STAIR 3

S103

CORRIDOR

STORAGE/COPY

-4L1-1

-5L1-1

-10L1-1

-11L1-1

-12L1-1

-13L1-1

-14L1-1

-17L1-1

-18L1-1

W H-2

W H-3

W H-1 PANEL L1-1

-8L1-1

-19L1-1

PO5

PO5

PO5

-6L1-1

PO5

-7L1-1

PO5

PO5

-20L1-1

PO5

PO5

-9L1-1

PO5

-21L1-1

-22L1-1

PO5 PO5

-27L1-1

PO5

PO5

PO5

PO5

-24L1-1

PO5

PO6

PO6

PO6

PO7

CLG

PO8CLG

PO9

-25L1-1-23L1-1

-29L1-1

-32L1-1

PO6

PO6PO3

PO3

PO3

-44L1-1

-34L1-1

COAX PANEL

-42L1-1

PO12

-43,45L1-1

PO13

PO12

-15L1-1

-16L1-1

PO5

+6' - 6"

-18,20,22L2-1

-19,21,23L2-1

-26,28,30L1-1 -31,33,35L1-1

PO11

PO11

PO11

PO11

PANEL LE-1

TO REMAIN

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:0

A

M

02-EP-111

POWER PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-EP-111

1 Power Plan - Floor 01

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS

SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM

SHALL BE MARKED IN ACCORDANCE W ITH NEC 406.3(E).

E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS

SHALL BE COORDINATED W ITH MECHANICAL AND PLUMBING

CONTRACTORS TO ENSURE ACCESS AND W ORKING CLEARANCE IS

MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED

CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE

AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT

NAMEPLATES OR ACCESS PANELS OR THROUGH

ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER

TRADES.

N

TAGGED NOTES

PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO

REMAIN.

PO5 DEVICE TO BE INCLUDED IN THE BID DEDUCT.

PO6 EXISTING RECEPTACLE AND BRANCH CIRCUIT TO BE

REPLACED WITH NEW DEVICE AND WIRING. EXISTING

JUNCTION BOX AND RACEWAY TO BE REUSED.

PO7 PROVIDE CONTROL SWITCH FOR MOTORIZED SCREEN.

COORDINATE EXACT SWITCH REQUIREMENTS WITH SCREEN

INSTALLER.

PO8 PROVIDE 120V ELECTRICAL POWER CONNECTION FOR

MOTORIZED SCREEN. COORDINATE EXACT MOUNTING

LOCATION WITH SCREEN INSTALLER.

PO9 PROVIDE 20A/120V DUPLEX RECEPTACLE FLUSH MOUNTED

WITH THE CEILING FOR CONNECTION TO PROJECTOR.

COORDINATE EXACT MOUNTING LOCATION WITH PROJECTOR

INSTALLER.

PO11 PROVIDE 30A, 208 THREE-PHASE TWIST LOCK RECEPTACLE

(L21-30R). COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR PRIOR TO ROUGH-IN.

PO12 DISCONNECT SWITCH PROVIDED BY MECHANICAL WORK.

PO13 PROVIDE 30A, 240V SINGLE PHASE DISCONNECT SWITCH.

J J

M M

M

M

M

M

M

M M

M

M

M

M

M

J M

C

J J J J

COPIER

REFRIG.

-3L2-1

-4L2-1

STAIR 3

STAIR 2

OIT

ELEV

HAC

MECH

STORAGE

218A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ELEC

OFFICE

COPY ROOM

STAIR 1

S200

CONFERENCE

MEN

W OMEN

CORRIDOR

CUBICLE BAY

OFFICE

W ORKSTATION

OFFICE

OFFICE

KITCHENETTE

-5L2-1

-6L2-1

COFFEE

MAKER

-7L2-1

-8L2-1

-9L2-1

-10L2-1

-11L2-1

-12L2-1

-13L2-1

PO2

W H-2

W H-3

PO3

PO2

PANEL L2-1

PO5

PO5

-17L2-1

PO5

PO5

PO5

-14L2-1

-16L2-1

-15L2-1

PO7

CLG

PO8

CLG

PO9

PO10

-24L2-1 -25,27,29L2-1

-36,38,40L1-1

COAX PANEL

-31L2-1

-32,34L2-1

PO12

-33L2-1

PO12

W H-3

-35L2-1

+4' - 6"

-26,28,30L2-1 -37,39,41L1-1

PO11 PO11 PO11

PO11

PANEL L21-A

TO REMAIN

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:1

A

M

02-EP-121

POWER PLAN - FLOOR 02

CMTACMTA

SCALE: 1/4" = 1'-0"02-EP-121

1 Power Plan - Floor 02

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS

SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM

SHALL BE MARKED IN ACCORDANCE W ITH NEC 406.3(E).

E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS

SHALL BE COORDINATED W ITH MECHANICAL AND PLUMBING

CONTRACTORS TO ENSURE ACCESS AND W ORKING CLEARANCE IS

MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED

CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE

AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT

NAMEPLATES OR ACCESS PANELS OR THROUGH

ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER

TRADES.

N

TAGGED NOTES

PO2 NEW LOCATION FOR EXISTING ADVANCED NETWORK

ANNUNCIATION DEVICE. CONNECT TO EXISTING SYSTEM AS

REQUIRED.

PO3 EXISTING ADVANCED NETWORK ANNUNCIATION SYSTEM TO

REMAIN.

PO5 DEVICE TO BE INCLUDED IN THE BID DEDUCT.

PO7 PROVIDE CONTROL SWITCH FOR MOTORIZED SCREEN.

COORDINATE EXACT SWITCH REQUIREMENTS WITH SCREEN

INSTALLER.

PO8 PROVIDE 120V ELECTRICAL POWER CONNECTION FOR

MOTORIZED SCREEN. COORDINATE EXACT MOUNTING

LOCATION WITH SCREEN INSTALLER.

PO9 PROVIDE 20A/120V DUPLEX RECEPTACLE FLUSH MOUNTED

WITH THE CEILING FOR CONNECTION TO PROJECTOR.

COORDINATE EXACT MOUNTING LOCATION WITH PROJECTOR

INSTALLER.

PO10 PROVIDE FIRE RATED POKE-THRU TO ACCOMMODATE TWO

DATA AND ONE VOICE JACKS, AND (2) 20A/120V DUPLEX

RECEPTACLES. COORDINATE EXACT MOUNTING LOCATION

WITH OWNER PRIOR TO ROUGH-IN.

PO11 PROVIDE 30A, 208 THREE-PHASE TWIST LOCK RECEPTACLE

(L21-30R). COORDINATE INSTALLATION LOCATION WITH

TELECOMMUNICATIONS CONTRACTOR PRIOR TO ROUGH-IN.

PO12 DISCONNECT SWITCH PROVIDED BY MECHANICAL WORK.

PANEL L2-1

FACP

TS

FS

FACP

N A

C

FIRE

STORAGE

G02

STORAGE/COPY ROOM

G02A

STORAGE

G02B

ELEV

E-00

ELEV EQUIP

G01

CORRIDOR

H002

STORAGE

G03

OIT

G04

STORAGE

G05

CORRIDOR

H003

TRANSFORMER

G09

MECH RM

G08

STORAGE

G07

STORAGE

G07A

TOILET

G05A

HAC

G05B

CORRIDOR

H001

STORAGE

G06

STAIR 1

S001

EXEX

EX

T E

L

EX

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:1

A

M

02-ET-101

SYSTEMS PLAN - FLOOR 00

AuthorChecker

SCALE: 1/4" = 1'-0"02-ET-101

1 Systems Plan - Floor 00

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND

SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF

EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO

THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).

REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL

REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT

BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.

PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM

CABLING INSTALLATION.

N

ADDITIONAL WORK SCOPE :

THE FOLLOWING SCOPE OF WORK IS TO BE INCLUDED IN PROJECT AND IS NOT SHOWN ON

THESE DRAWINGS.

PROVIDE A FIRE ALARM TAMPER SWITCH CONNECTION TO THE POST INDICATOR VALVE FOR

THE NEW FIRE SPRINKLER SERVICE LOCATED ON SITE. COORDINATE EXACT LOCATION WITH

FIRE SPRINKLER INSTALLER.

SD

F

F

F

S S

S

S S

S

S

S

W AP

W AP

W AP

N A

C

KP

CR

IR

IM

F

F F

F

F F

F

V

V

V

V

V

V

TS

FS

DS

PB

PB

PB PB

PB

PB

PB

PB

PB

PB

PB

PB

PB

PB PB

PBPB

PB

PB

PB

PB

PP PP

PPPP

ADAD

CC

CC

CC CC

CC

CC

CC

OFFICE

OFFICE

OFFICE

112 OFFICE

113 OFFICE

OFFICE

OFFICE

OFFICE

123OFFICE

OFFICE

OFFICE

OFFICE

VESTIBULE

STAIR 1

ELEV LOBBY

MECH

ELEV

OIT

ELEC

JAN

GROUP

COMPUTER

MEN

W OMEN

CORRIDOR

CORRIDOR

MULTI-PURPOSE

STAIR 2

S133

STAIR 3

S103

CORRIDOR

STORAGE/COPY

T E

L

T E

L

EX

EX

EX

S3

S3

S3

S3 S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3S3

S3

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V.

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V .

2D/1V

2D/1V

S4

S4

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

S3

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D

S5

2D/1V

EXIST COAX

PANEL

PANEL L1-1

S7

S7

S7 S7

S7

S1

S1

S1

S1

S1 S1

S1

S9

S8

S10

S4

S11 S11

S11

S11

S11

S11

S11

S11

S11

S11

S11

DATA

RACK (TYP)

S12

S11

S11

S11

S11

S11

S11

S11

S11

-48L1-1

ELEC

S11 S14

S14

S14

S15S15

SEC-A

-46L1-1

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:1

A

M

02-ET-111

SYSTEMS PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-ET-111

1 Systems Plan - Floor 01

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND

SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF

EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO

THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).

REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL

REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT

BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.

PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM

CABLING INSTALLATION.

N

TAGGED NOTES

ELE

C

ELECTRICAL NOTES

S1 NEW LOCATION FOR EXISTING CEILING MOUNTED FIRE ALARM

DEVICE. SALVAGED ROM DEMOLITION. CONNECT TO

EXISTING FIRE ALARM SYSTEM AS REQUIRED.

S3 DEVICE TO BE INCLUDED IN THE BID DEDUCT.

S4 PROVIDE (2)-4" CONDUIT SLEEVES THROUGH WALLS

INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO

LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL

PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501.

S5 PROVIDE DATA OUTLET WITH TWO DATA CONNCTIONS FOR

CONNECTION TO PROJECTOR. COORDINATE EXACT

MOUNTING LOCATION WITH PROJECTOR INSTALLER/OWNER.

S7 PROPOSED CABLING PATH - COORDINATE ALL PATHS WITH

PIPING, DUCTWORK, ETC. (NOTE : STUB-UP CONDUITS SHALL

BE ROUTED TO THESE CABLING PATHS). PROVIDE CABLE

TRAY ALONG ALL REQUIRED CABLING PATHS. WHERE

CABLING PATH IS INTERRUPTED BY DUCTWORK, PIPING, ETC,

PROVIDE CABLE TRAY PATH BELOW AS REQUIRED TO

MAINTAIN A CONTINUOUS CABLING PATH - REFER TO

INSTALLATION DETAILS FOR FURTHER REQUIREMENTS.

CABLE TRAY IN OIT ROOMS ARE TO BE INSTALLED AROUND

PERIMETER OF ROOM PER VA OIT DEISGN GUIDE TEMPLATES;

PROVIDE AS REQUIRED.

S8 AUDIO/VIDEO INTERCOM MASTER STATION WITH DOOR

RELEASE FOR CONTROL OF FRONT DOOR. PROVIDE POWER

SUPPLIES & DOOR RELAY CONTACTS, ALL CABLING,

CONNECTORS, RELAYS, ETC. AS REQUIRED FOR A COMPLETE

AND OPERATIONAL SYSTEM. AUDIO/VIDEO INTERCOM UNIT TO

BE AIPHONE#AX-8MV OR APPROVED EQUIVALENT. COLOR TO

BE SELECTED BY COR.

S9 AUDIO/VIDEO INTERCOM REMOTE STATION WITH FLUSH-MTD

S.S. ENCLOSURE. REMOTE STATION TO BE AIPHONE #AX-DVF

OR APPROVED EQUIVALENT.

S10 PROVIDE (4)-4" CONDUIT SLEEVES THROUGH WALLS

INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO

LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL

PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501 FOR

ADDITIONAL DETAILS.

S11 PROVIDE PANIC BUTTON AND ASSOCIATED ROUGH-IN PER

VENDOR REQUIREMENTS. COORDINATE LOCATION WITH

OWNER/VENDOR PRIOR TO ROUGH-IN.

S12 PROVIDE THE FOLLOWING CABLING SYSTEM ROUTED FROM

DATA RACK:

a). TWO 12-STRAND FIBER OPTIC CABLE ASSEMBLY WITH

MULTI-FIBER PUSH-ON CONNECTORS ROUTED TO THE DATA

RACK LOCATED IN THE BASEMENT O.I.T. CLOSET G04.

PROVIDE TWO CASSETTES WITH 12 DUPLEX LC INTERFACES IN

BOTH THE BASEMENT AND NEW O.I.T. CLOSET DATA RACKS

FOR CABLING TERMINATIONS.

b). ONE 100 PAIR COPPER CABLE FROM NEW DATA RACK TO

110 BLOCK(S) INSTALLED IN ADJACENT MECHANICAL ROOM.

CONTRACTOR PROVIDE 110 BLOCKS AND TERMINATIONS AS

REQUIRED.

S14 PROVIDE 360 DEGREE CCTV CAMERA.

S15 PROVIDE CCTV CAMERA FOR STAIRWELL COVERAGE AS

REQUIRED; COORDINATE DETAILS WITH COR.

CRITICAL WIDE AREA NETWORK GENERAL NOTE:

COORDINATE REINSTALLATION OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER.

(DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING.

COORDINATE REW ORK DETAILS W ITH OW NER.)

F

F

F

F

F

S

S

S S

S

S

S

W AP

W AP

W AP

F

CR

DS

DS

CR

CR

F F

V

V

V

FS

TS

SD

PB

PP

PPPP

PP

ADAD

T E

L

STAIR 3

STAIR 2

OIT

ELEV

HAC

MECH

STORAGE

218A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ELEC

OFFICE

COPY ROOM

STAIR 1

S200

CONFERENCE

MEN

W OMEN

CORRIDOR

CUBICLE BAY

OFFICE

W ORKSTATION

OFFICE

OFFICE

KITCHENETTE

S1

S1

S1

S1

S3

S3 S3 S3

S3

S3

2D/1V

2D/1V

2D/1V 2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

S4

S4

2D/1V

2D/1V

2D

S5

S6

EXIST COAX

PANEL

PANEL L2-1

S7

S7

S7

S1

S11

EX.

S13

DATA

RACK (TYP)

S12

-36L2-1

2D/1V.

2D/1V

-37L2-1

SEC-A

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:5

:1

A

M

02-ET-121

SYSTEMS PLAN - FLOOR 02

CMTACMTA

SCALE: 1/4" = 1'-0"02-ET-121

1 Systems Plan - Floor 02

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND

SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF

EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO

THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).

REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL

REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT

BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.

PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM

CABLING INSTALLATION.

N

TAGGED NOTES

S1 NEW LOCATION FOR EXISTING CEILING MOUNTED FIRE ALARM

DEVICE. SALVAGED ROM DEMOLITION. CONNECT TO

EXISTING FIRE ALARM SYSTEM AS REQUIRED.

S3 DEVICE TO BE INCLUDED IN THE BID DEDUCT.

S4 PROVIDE (2)-4" CONDUIT SLEEVES THROUGH WALLS

INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO

LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL

PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501.

S5 PROVIDE DATA OUTLET WITH TWO DATA CONNCTIONS FOR

CONNECTION TO PROJECTOR. COORDINATE EXACT

MOUNTING LOCATION WITH PROJECTOR INSTALLER/OWNER.

S6 PROVIDE FIRE RATED POKE-THRU TO ACCOMMODATE TWO

DATA AND ONE VOICE JACKS, AND (2) 20A/120V DUPLEX

RECEPTACLES. COVER TYPE AND FINISH TO BE SELECTED BY

COR. COORDINATE EXACT MOUNTING LOCATION WITH COR

PRIOR TO ROUGH-IN.

S7 PROPOSED CABLING PATH - COORDINATE ALL PATHS WITH

PIPING, DUCTWORK, ETC. (NOTE : STUB-UP CONDUITS SHALL

BE ROUTED TO THESE CABLING PATHS). PROVIDE CABLE

TRAY ALONG ALL REQUIRED CABLING PATHS. WHERE

CABLING PATH IS INTERRUPTED BY DUCTWORK, PIPING, ETC,

PROVIDE CABLE TRAY PATH BELOW AS REQUIRED TO

MAINTAIN A CONTINUOUS CABLING PATH - REFER TO

INSTALLATION DETAILS FOR FURTHER REQUIREMENTS.

CABLE TRAY IN OIT ROOMS ARE TO BE INSTALLED AROUND

PERIMETER OF ROOM PER VA OIT DEISGN GUIDE TEMPLATES;

PROVIDE AS REQUIRED.

S11 PROVIDE PANIC BUTTON AND ASSOCIATED ROUGH-IN PER

VENDOR REQUIREMENTS. COORDINATE LOCATION WITH

OWNER/VENDOR PRIOR TO ROUGH-IN.

S12 PROVIDE THE FOLLOWING CABLING SYSTEM ROUTED FROM

DATA RACK:

a). TWO 12-STRAND FIBER OPTIC CABLE ASSEMBLY WITH

MULTI-FIBER PUSH-ON CONNECTORS ROUTED TO THE DATA

RACK LOCATED IN THE BASEMENT O.I.T. CLOSET G04.

PROVIDE TWO CASSETTES WITH 12 DUPLEX LC INTERFACES IN

BOTH THE BASEMENT AND NEW O.I.T. CLOSET DATA RACKS

FOR CABLING TERMINATIONS.

b). ONE 100 PAIR COPPER CABLE FROM NEW DATA RACK TO

110 BLOCK(S) INSTALLED IN ADJACENT MECHANICAL ROOM.

CONTRACTOR PROVIDE 110 BLOCKS AND TERMINATIONS AS

REQUIRED.

S13 PROVIDE (4)-4" CONDUITS ABOVE DUCTWORK AND ROUTE TO

O.I.T. ROOM, AS INDICATED.

CRITICAL WIDE AREA NETWORK GENERAL NOTE:

COORDINATE REINSTALLATION OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER.

(DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING.

COORDINATE REW ORK DETAILS W ITH OW NER.)

Sheets
02-ED-111 - LIGHTING DEMOLITION PLAN - FLOOR 01
02-ED-112 - POWER DEMOLITION PLAN - FLOOR 01
02-ED-122 - POWER DEMOLITION PLAN - FLOOR 02
02-EJ-504 - PANEL SCHEDULES
02-EP-111 - POWER PLAN - FLOOR 01
02-EP-121 - POWER PLAN - FLOOR 02
02-ET-101 - SYSTEMS PLAN - FLOOR 00
02-ET-111 - SYSTEMS PLAN - FLOOR 01
02-ET-121 - SYSTEMS PLAN - FLOOR 02

File details come from the government source that posted it. Updated .