EF-1_Updated with EXP Motor.pdf

PDF 460 KB Posted

Attached to
(PROJ: 573-19-616) BB Correct Electrical Deficiencies (3-Year Test) Federal contract opportunity
Solicitation number
36C24823R0042
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This document contains technical specifications and certifications for an exhaust fan and roof curb to be provided under a federal contract opportunity. The exhaust fan is a belt drive centrifugal roof exhaust fan model GB-097-4 with a motor enclosure rated for explosion proof use. The fan produces 100 CFM at 0.3 inches water gauge static pressure while operating at 919 RPM and drawing 0.04 horsepower. The roof curb is model GPF-19 with dimensions of 18.5 inches tall, 19 inches wide, and 19 inches long. Both products are certified for high wind and hurricane conditions up to 150 pounds per square foot by Miami-Dade County and the Florida Product Approval program. Relevant options and accessories are specified including a standard curb cap, thermal overload protection for the motor, and a NEMA-rated switch.

The related federal contract opportunity is a special notice for project 573-19-616 to correct electrical deficiencies at a Department of Veterans Affairs medical center on a three-year test basis. Proposals are due by December 5, 2022 at 1:00 PM. The solicitation number is 36C24823R0042 and was issued by the Veterans Health Administration Veterans Integrated Service Network 8.

View the file

Other files for this federal contract opportunity

Other files attached to (PROJ: 573-19-616) BB Correct Electrical Deficiencies (3-Year Test), newest first.
File Type Posted
RFI 7 Breaker List from 3 Year Test.pdf PDF
SITE VISIT SIGN IN SHEET.pdf PDF
RESPONSES - RFIs 36C24823R0042.pdf PDF
SF30 - RFI -36C24823R0042 0001_1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR, ADAPTER, AND/OR

HINGE BASE.

19.00 SQ

1.75

23.70

Ø 24.40

42.20

(18.50)

Model: GB-097-4 Belt Drive Centrifugal Roof Exhaust Fan Previously: GB-071-4

Dimensional Quantity 1

Weight w/o Acc's (lb) 61

Weight w/ Acc's (lb) 67

Weight w/ Acc's and Curb (lb) 103

Max T Motor Frame Size 56

Standard Curb Cap Size (in.) 19 x 19 Roof Opening (in.) 15.5 x 15.5

Performance Requested Volume (CFM) 100

Actual Volume (CFM) 100

Total External SP (in. wg) 0.3

Fan RPM 919

Operating Power (hp) 0.04

Elevation (ft) 105

Airstream Temp.(F) 70

Air Density (lb/ft3) 0.075

Drive Loss (%) 50.0

Tip Speed (ft/min) 2,690 Static Eff. (%) 26 Misc Fan Data

Fan Eff. Index (FEI) - Outlet Velocity (ft/min) 104

Motor Motor Mounted Yes

Size (hp) 1/4

Voltage/Cycle/Phase 115/60/1

Enclosure EXP

Motor RPM 1725

Efficiency Rating Standard

Windings 1 NEC FLA* (Amps) 5.8

Min. Circuit Ampacity (MCA) 7.25 Max. Overcurrent Protection (MOP) 15

Short Circuit Current Rtg (SCCR) 5 kA

Notes:

All dimensions shown are in units of in.

*NEC FLA, MCA and MOP are for reference only – based on tables 430.248 or 430.25 of National Electric Code 2020. Actual motor FLA may vary, for sizing thermal overload, consult factory.

MCA and MOP values shown only account for the motor, not accessories (damper actuator, field supplied VFD, etc).

LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5 ft - dBA levels are not licensed by AMCA International Sones - calculated using ANSI/AMCA 301 at 5 ft

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

Inlet 62 58 58 50 46 39 33 30 54 42 3.0

11/16/2022Printed Date:

VA GainesvilleJob:

EF-1Mark:

GB-097-4Model:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 1 of 7 C:\Users\tedwards\Documents\CAPS\Jobs\Tom Edwards Jobs\VA Gainesville.gfcj

Model: GB-097-4 Belt Drive Centrifugal Roof Exhaust Fan Standard Construction Features:

- Aluminum housing - Backward inclined aluminum wheel - Curb cap with prepunched mounting holes - Motor and drives isolated on shock mounts - Birdscreen - Ball bearing motors - Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball bearing pillow blocks - Bearings meet or exceed temperature rating of fan - Static resistant belts - Corrosion resistant fasteners - Sizes 141 and larger have internal Lifting lugs

Spark B construction was selected.

Greenheck has included options and accessories for this product that meet the intent of AMCA 99 - spark resistant construction guidelines. Greenheck recommends, but does not require, an EXP motor for this product line. If an EXP motor is not selected, the engineer of record must determine if this is acceptable for the application. The resulting fan construction in no way implies a guarantee of safety for any level of spark resistance. Spark resistant construction does not prevent ignition of explosive gasses or vapors due to catastrophic failure or from any airstream material that may exist within in a system.

Selected Options & Accessories:

Motor with Thermal Overload Standard Curb Cap Size - 19 Square Spark B Construction UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-7 and 9, Toggle, Shipped with Unit, Division1 Wiring Junction Box Mounted & Wired High Wind Rated (+/- 150 PSF Rating) Florida Product Approval #FL13225.1 & Miami-Dade NOA #21-1129.02 Birdscreen: Aluminum, nom. 86% Free Area Unit Warranty: 1 Yr (Standard) Selected Sub Marks See individual submittals for full details

GPF-19-G18

11/16/2022Printed Date:

VA GainesvilleJob:

EF-1Mark:

GB-097-4Model:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 2 of 7

Assembly Drawing Type: Belt Drive Centrifugal Roof Exhaust Fan

RECOMMENDED EXHAUST DUCT SIZE

MAXIMUM ROOF OPENING

OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR, ADAPTER, AND/OR

HINGE BASE.

DUCT DIMENSIONS ARE LARGEST POSSIBLE DUCT TO FIT THROUGH CURB.

CONSULT SYSTEM DESIGN ENGINEER FOR RECOMMENDED DUCT SIZE.

19.00 SQ

1.75

23.70

Ø 24.40

42.20

(18.50)

15.50

SQ

12.00

SQ

Notes: All dimensions shown are in units of in..

11/16/2022Printed Date:

VA GainesvilleJob:

EF-1Mark:

GB-097-4Model:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 3 of 7

GB-097-4 Min/Max Fan Curve

Performance Requested

Volume

(CFM)

Actual Volume

(CFM)

Total External SP (in. wg)

Fan

RPM

Operating Power (hp)

100 100 0.3 919 0.04

11/16/2022Printed Date:

VA GainesvilleJob:

EF-1Mark:

GB-097-4Model:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 4 of 7

21.75 21.75

18.50

17.75 17.75 Model: GPF Roof Curb Standard Construction Features:

- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in.

aluminum - Straight Sided without a cant - 2 in. or 5 in. mounting flange - 1 in.

thick 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in

0.5 in. increments. Notes: - The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in.. - The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size. - The Roof Opening Dimension may or may not be the same as the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. - Security bars are optional and must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded to the frame and the frame is welded to the curb.

General

Tag Qty Model Sizing

Method Undersizing

(in.)

Weight

(lb) Shipped

Assembled Union Label

1 GPF-19 Nominal 1.25 35 Yes No Preference

Dimensions

Curb Height

(in.)

Nominal Outside Width (in.)

Nominal Outside Length

(in.)

Actual Outside Width (in.)

Actual Outside Length

(in.)

Actual Inside Width (in.)

Actual Inside Length

(in.)

Flange Width (in.)

Flange Length

(in.)

Hinge Base

Width* (in.)

Hinge Base

Length* (in.)

18.5 19 19 17.75 17.75 14.25 14.25 21.75 21.75 18 18 *May not be applicable

Accessories

Material Security

Bars Liner Insulation

(in.)

Insulation R Value

Galvanized No No 1 R4.3

11/16/2022Printed Date:

VA GainesvilleJob:

EF-1Mark:

GPF-19-G18Model:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 5 of 7

February 25, 2022

Subject: Greenheck High Wind Certified Models

To whom it may concern:

Greenheck has tested and certified a number of models to meet the Miami Dade Building Code Compliance Office hurricane and high wind standards. In addition all products are also certified by the Florida Building Council with a Florida Product Approval number for use in areas of Florida not governed by the Miami Dade regulations. All products are tested and certified by an independent third party for use in high wind and hurricane areas.

The chart below lists the applicable information for each of the certified models. A complete certification report can be found on the Miami-Dade website for the Notice of Acceptance (NOA) numbers (www.miamidade.gov) or the Florida Building Code website for the FLPA numbers (www.floridabuilding.org).

Fan Model Available Sizes Protocols Tested

Miami-Dade NOA FLPA Number Max. Wind

Load - PSF

G/GB 060-300

TAS-201

TAS-202

TAS-203

21-1129.02 FL13225.1 150

CUE/CUBE 060-300 21-1129.02 FL13225.1 150

FGI/FGR

Intake 54x54

Relief 66x66

21-1122.09 FL12917.1

Steel - 70

Aluminum - 40

R Series Rooftop

Prop

Unfiltered 18-48

Filtered 18-42

21-1122.09 FL12917.1

Steel - 70

Aluminum - 40

RSF 90-200 21-1122.10 FL41062.1 40

11/16/2022Printed Date:

VA GainesvilleJob:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 6 of 7

Roof Curb Model: GPF

Roof Curb Configuration:

ID #: Tag: Qty: Curb Cap W x L: Actual W x L: Flange W: Flange L: Height: Step Hgt: Damper Tray W x L:

2 EF-1 1 19 x 19 17.75 x 17.75 27.75 27.75 18 N/A x

Notes: All dimensions shown are in units of in.

Standard Construction Features:

- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 2 in. or 5 in. mounting flange - 1 in. thick 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.

Notes:

- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..

- The minimum roof opening dimension should be at least 2.5

in. more than the damper dimension or recommended duct size.

- The Roof Opening Dimension may or may not be the same as the Structural Opening Dimension.

- Damper Tray is optional and must be specified. Tray size is same as damper size.

- Security bars are optional and must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded to the frame and the frame is welded to the curb.

11/16/2022Printed Date:

VA GainesvilleJob:

Generated by: tedwards@stanweaver.comCAPS 4.39.1057 Page 7 of 7

File details come from the government source that posted it. Updated .