E GA College Student Services Lighting Upgrad.pdf
PDF 2 MB Posted
- Solicitation number
- PE-57200-RFQ-2025-000000007
- Issued by
- Douglas County, Georgia
About this file
This document appears to be a set of plans and specifications for a LED lighting retrofit project at the East Georgia State College Student Center in Swainsboro, Georgia. The project involves replacing the existing lighting fixtures with new LED fixtures throughout the student center building. The plans provide details on the types of fixtures to be installed, including 2x4 LED volumetric selectable troffers, 2x4 LED flat panels, 2x2 LED volumetric selectable troffers, 4' linear strip lights, recessed downlights, and emergency lighting. The project is being overseen by Chatham Engineering Company, LLC. No specific bid due dates or award information is provided in the document.
The document also includes general notes and requirements for the electrical work, including specifications for wiring, conduit, devices, and grounding. Contractors are instructed to field verify existing conditions and maintain the existing electrical system to the extent possible. Warranty requirements and lighting fixture installation details are also outlined.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pre Bid Sign In Sheet PN 0000_2513.docx | DOCX document | |
| P _ 0000_2513 Student Services Interior Light.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
20-NOV-2024
E:\E GA College LED Lighting Bldg B - 24086.00\CADD\E1.dgn
CADD PLOT
20-NOV-2024
13:37 bmoye
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
S W
A
IN
S B
O R
O
G E
O R
G
IA
24086.00
JV
BM
P
-2
J A
M B
U
IL
D
IN
G B
S T
U D
E N
T C
E N
T E
R L
E D L
IG
H T
IN
G R
E T R
O
E A S
T G
E O
R G
IA
S
T A T E C
O L L E
G E
R
L E
A S
D
F O
C
N S T R
U C
T
IO
N
TYPE DESCRIPTION
LEGEND
SYMBOL
A-1,3,5 ADJACENT TO ARROW INDICATES HOME-RUN OF CIRCUITS 1,3,5 TO PANEL A. 3,5 OR A-3,5 ADJACENT
TO ARROW INDICATES CIRCUIT CONTINUATION. MARKS ACROSS RACEWAY RUNS INDICATE THE NUMBER OF NO. 12
CONDUCTORS. UNLESS NOTED, NO MARKS INDICATES TWO NO. 12 CONDUCTORS. EQUIPMENT GROUNDING CONDUCTORS
ARE NOT SHOWN, SEE GENERAL NOTES. IF INDICATED ADJACENT TO OUTLET, NUMERAL AND LOWER CASE LETTER 1 a
3,5
A-1,3,5
DESCRIPTION
INDICATES CIRCUIT CONNECTION AND SWITCHLEG DESIGNATION RESPECTIVELY.
ALL SYMBOLS INDICATED HEREIN MAY NOT NECESSARILY BE USED ON THE PLANS.
CEILING OUTLET AND FIXTURE
CEILING OUTLET AND FIXTURE - EGRESS/EMERGENCY LIGHTING
XA
CEILING OR WALL OUTLET AND FIXTURE
CEILING OR WALL OUTLET AND FIXTURE - EGRESS/EMERGENCY LIGHTING
OUTLET AND EXIT LIGHT - LETTERS INDICATE FIXTURE TYPE. PROVIDE ARROWS INDICATED
OUTLET AND STRIP FIXTURE - MOUNTING AS INDICATED IN FIXTURE SCHEDULE
SINGLE CIRCUIT OCCUPANCY SENSOR SWITCH - MT. 48" UP
SINGLE POLE TOGGLE SWITCH - MT. 48" UP
THREE-WAY TOGGLE SWITCH - MT. 48" UP
FOUR-WAY TOGGLE SWITCH - MT. 48" UP
RACEWAY INSTALLED CONCEALED IN/OR BELOW FLOOR SLAB OR BELOW GRADE
RACEWAY INSTALLED CONCEALED IN WALLS AND/OR ABOVE CEILING
RACEWAY INSTALLED EXPOSED
A1
B
WALLWASH LIGHT OUTLET AND FIXTURE
2 X 4 LED VOLUMETRIC SELECTABLE TROFFER
VST24-5L/6L/7L-U-CCTS ALESCO - ILP
A#E SAME AS ABOVE W/ INTEGRAL BATTERY
VST24-5L/6L/7L-U-CCTS-EM10 ALESCO - ILP
VST24-5L/6L/7L-U-CCTS ALESCO - ILP
2 X 4 LED VOLUMETRIC SELECTABLE TROFFERA2
7000L LED
LUMEN LEVEL / CCT
6000L LED
4000K, 55W
4000K, 51W
4400L LED
4000K, 38W
2 X 4 LED FLAT PANEL
VPAN24-33L/44L/55L-U-CCTS ALESCO - ILP
SAME AS ABOVE W/ INTEGRAL BATTERY
VPAN24-33L/44L/55L-U-CCTS-EM10 ALESCO - ILP
C 4400L LED
4000K, 38W
2 X 4 LED FLAT PANEL
SAME AS ABOVE W/ INTEGRAL BATTERY
VPAN24-33L/44L/55L-U-CCTS-NSF ALESCO - ILP
VPAN24-33L/44L/55L-U-CCTS-NSF-EM10 ALESCO - ILP
D
BE
CE
DE SAME AS ABOVE W/ INTEGRAL BATTERY
VST22-2L/3L/4L-U-CCTS ALESCO - ILP
2 X 2 LED VOLUMETRIC SELECTABLE TROFFER 3000L LED
4000K, 24W
VST22-2L/3L/4L-U-CCTS-EM10 ALESCO - ILP
G
GE SAME AS ABOVE W/ INTEGRAL BATTERY
3000L LEDALESCO - LUXILLUMINAIRE 8' LINEAR PENDANT
EOS4.0-P-DI-BAT-1000-XBT-500-8-40K-8-1-UNV-S1-W-HC-24-WF,WC 4000K
EOS4.0-P-DI-BAT-1000-XBT-500-8-40K-8-1-UNV-S1-W-HC-24-WF,WC-EB
XA
INDICATED ON DRAWINGS W/ INTEGRAL BATTERY. WHITE HOUSING.
4000L LED
4000K, 38W
H 4' STRIP LIGHT
VS4-3L/4L/5L-U-CCTS-FRL ALESCO - ILP
2000L LED
4000K, 26W
I 8" ROUND RECESSED DOWNLIGHT
LEM-90-40-KDIM010UNV-MD + ADR8CC GREEN CREATIVE
4000L LED
4000K, 49W
J 6" ROUND RECESSED DOWNLIGHT
LEL-90-40-KDIM010UNV-MD + ADR6CC GREEN CREATIVE
2000L LED
4000K, 49W
K 6" ROUND RECESSED DOWNLIGHT
LEM-90-40-KDIM010UNV-MD + ADR6CC + ADWAW GREEN CREATIVE
EXIT SIGN LED
ELU
E1
SCHEDULES
LEGEND, NOTES, &
F 3300L LED
4000K, 30W
NOTES
FIXTURE SCHEDULE NOTES:
LIGHTING FIXTURE SCHEDULE - NOTE LF-2
M LF-3
2 X 2 LED FLAT PANEL
VPAN22-22L/33L/44L-U-CCTS ALESCO - ILP
LED EMERGENCY LIGHT
TCL-2-W-SD EVENLITE
LED
IE
HE SAME AS ABOVE W/ INTEGRAL BATTERY
SAME AS ABOVE W/ INTEGRAL BATTERY
VS4-3L/4L/5L-U-CCTS-FRL-EM6 ALESCO - ILP
LEM-90-40-KDIM010UNV-MD-EM + ADR8CC GREEN CREATIVE
JE SAME AS ABOVE W/ INTEGRAL BATTERY
LEL-90-40-KDIM010UNV-MD-EM + ADR6CC GREEN CREATIVE
4000L LED
4000K, 29WWTZ4-4L-U-40-SAFL-CT-BABA + SS ILP
4' LINEAR VAPOR TIGHT W/ STAINLESS STEEL LATCHES
DEMO NOTES
REMOVE ALL DEMOLISHED EQUIPMENT/FIXTURES FROM SITE.D1.
LF-4
LF-4
LF-4
LF-4
4400L LED
4000K, 38W
4400L LED
4000K, 38W
3000L LED
4000K, 24W
3000L LED
4000K
4000L LED
4000K, 38W
2000L LED
4000K, 26W
4000L LED
4000K, 49W
LF-1,5
LF-5
LF-5
LF-5
LF-5
LF-5
LF-5
LF-5
LF-4,5
EVENLITE - CCDS-EM-R1-WW-CN-SD
PROVIDE ARROWS, MOUNTING, & SINGLE FACE AS
LF-5. CONNECT ALL EMERGENCY AND EXIT LIGHTING TO CONSTANTLY ENERGIZED CIRCUIT.
LF-4. CONTRACTOR TO FIELD-VERIFY EXISTING HOLE IN CEILING SIZE PRIOR TO ORDERING FIXTURES.
LF-3. PROVIDE 0°F DRIVERS FOR ALL EXTERIOR FIXTURES.
MANUFACTURERS ARE ACCEPTABLE TO BE PROVIDED ONCE REVIEWED BY ENGINEER.
LF-2. FIXTURES SHOWN INDICATE TYPE AND QUALITY OF FIXTURES REQUIRED. OTHER
ABOVE DOORS MOUNT 8'-0" AFF TO BOTTOM.
AS CLOSE TO DOOR FRAME AS POSSIBLE. FOR PENDANT AND WALL MOUNTED LIGHTS NOT
SHOWN ABOVE DOORS, MOUNT DIRECTLY ABOVE DOORS BETWEEN CEILING AND DOOR FRAME
FACE WALL MOUNT, PROVIDE END BRACKETS NECESSARY. FOR WALL MOUNTED UNITS
PENDANT MOUNTED ( ), WALL ( ) OR END ( ) MOUNTED AS REQUIRED. FOR DOUBLE
LF-1. PROVIDE DIRECTIONAL ARROWS AS SHOWN ON PLANS. PROVIDE CEILING MOUNTED ( ),
SIDE VIEW END VIEW
STRUCTURE, TYP.
ATTACHMENT TO STRUCTURE.
CHAINS SHALL HAVE SUFFICIENT
SLACK TO ALLOW LIFTING AND
SHIFTING OF FITURE ONE TILE,
DIRECTION.
SIDE-TO-SIDE, IN EITHER
FIXTURE, TYP.
CHAINS SHALL BE OF EQUAL
LENGTH AND SHALL HANG
PERPENDICULAR TO POINT OF
A.T. CEILING, TYP.
SIZE 12 JACK CHAIN TYPICAL.
TWICE THE WEIGHT OF THE FIXTURE.
SUCH THAT THE ASSEMBLY WILL SUPPORT
ATTACH CHAINS TO FIXTURE AND STRUCTURE
AND ATTACH FIXTURE TO TRAPEEZE.
FIXTURE, PROVIDE TRAPEEZE BELOW OBSTRUCTION
CHAIN TO STRUCTURE, PERPENDICULAR TO
WHERE OBSTRUCTION PROHIBITS ATTACHING
CEILINGS ONLY.
APPLICABLE TO ACOUSTICAL TILE
IS SIMILAR FOR OTHER FIXTURE TYPES.
NOTE: 2 X 4 FIXTURE DEPICTED. INSTALLATION
E1
SCALE: SCHEMATIC ONLY
DETAIL - SAFETY CHAIN INSTALLATION
ALTERNATES
T-EX (15 kVA, 480V-208Y/120V, 3PH, 4W)
T-D (75 kVA, 480V-208Y/120V, 3PH, 4W)
T-CK (150 kVA, 480V-208Y/120V, 3PH, 4W)
T-B (75 kVA, 480V-208Y/120V, 3PH, 4W)
T-A (30 kVA, 480V-208Y/120V, 3PH, 4W)
TRANSFORMERS. VERIFY EXACT LOCATION OF TRANSFORMERS IN FIELD.
EXISTING TRANSFORMERS AND RECONNECT EXISTING FEEDERS TO NEW
NEW AS LISTED BELOW. DISCONNECT EXISTING FEEDERS FROM
CONTRACTOR TO REPLACE EXISTING DRY-TYPE TRANSFORMERS WITH
ALTERNATE #1:
GENERAL NOTES
NOT LESS ONE YEAR FROM THE DATE OF THE SUBSTANTIAL COMPLETION.
DEFECTS AND WILL CONFORM TO THE CONTRACT DOCUMENTS. THIS WARRANTY SHALL EXTEND
THE CONTRACTOR SHALL WARRANT TO THE OWNER THAT ALL WORK SHALL BE FREE FROM 1.
WARRANTYI.
EXISTING CHAINS. SEE DETAIL 1 THIS SHEET.
CORNER ATTACHED TO STRUCTURE. PROVIDE SIZE 12 SAFETY CHAIN FOR FIXTURES WITHOUT
VERIFY EXISTING SAFETY CHAINS AND RECONNECT ON ALL GRID TYPE FIXTURES AT EACH 3.
SHALL BE U.L. LISTED AND LABELED AS SUITABLE FOR DAMP LOCATIONS.
FIXTURES INSTALLED IN DAMP AREAS AS CLASSIFIED BY ARTICLE 100 OF THE N.E.C. 2.
SYSTEM SPECIFIED.
SELECT IN ACCORDANCE WITH THE DRAWINGS. PROVIDE FLANGE OR GRID TYPE FOR CEILING1.
H. LIGHTING FIXTURES
BY LEGRAND, COOPER, OR LEVITON ARE ACCEPTABLE.
20 AMP, 277V SWITCHES SHALL BE HUBBELL 1223. EQUIVALENT SWITCHES MANUFACTURED
SINGLE POLE, 20 AMP, 277 VOLT TOGGLE SWITCHES SHALL BE HUBBELL 1221. THREEWAY,A.
WIRING DEVICESG.
DEVICE PLATES SHALL BE STAINLESS STEEL.3.
2. ALL DEVICES SHALL BE IVORY FINISH.
TERMINAL.
SCREW TYPE CONNECTIONS AND TOGGLE OPERATOR. PROVIDE TYPE WITH GROUND SCREW
WALL SWITCHES SHALL BE SPECIFICATION GRADE, QUIET MECHANICAL, A.C. TYPE WITH1.
F. DEVICES
GROUND DEVICES AND ASSOCIATED OUTLET BOXES TO GROUNDING CONDUCTORS.3.
INSTALL A GREEN INSULATED GROUNDING CONDUCTOR IN ALL RACEWAY SYSTEMS.2.
EQUIPMENT ENCLOSURES, JUNCTION AND OUTLET BOXES.
GROUND ALL NONCURRENT CARRYING PARTS OF ELECTRICAL SYSTEM, I.E. RACEWAY, 1.
GROUNDINGE.
AWG TYPE TFFN (90 DEGREES C).
CONNECTIONS BETWEEN FIXTURE JUNCTION BOX AND FIXTURE SHALL BE MADE WITH NO.16 3.
IN ANY ONE CONDUIT UNLESS NOTED OTHERWISE ON PLAN SHEETS.
NOT MORE THAN THREE BRANCH CIRCUITS OF OPPOSITE PHASES, SHALL BE INSTALLED 2.
MATCH EXISTING SYSTEM.
LARGER) 90 DEGREES C TYPE THHN/THWN OR XHHN WITH COLOR CODED INSULATION TO
CONDUCTORS SHALL BE SOLID COPPER (FOR NO.10 SMALLER) OR STRANDED (FOR NO.8 & 1.
CONDUCTORS - 600 VOLTSD.
WITH APPROPRIATE DEVICE PLATES TO MATCH DEVICE UTILIZIED.
OUTLET BOXES FOR DEVICES SHALL BE 4•" SQUARE, 2-„" DEEP WITH TILE TYPE COVERS3.
DEEP WITH COVER INSTALLED ADJACENT TO FIXTURE.
OUTLET BOXES FOR FLUSH MOUNTED LIGHTING FIXTURES SHALL BE 4•" SQUARE, 2-„" 2.
PROVIDE OUTLET BOXES FOR EACH LIGHT FIXTURE AND DEVICE.1.
OUTLET BOXESC.
WALL RATING.
SEAL ALL CONDUIT PENETRATIONS THROUGH RATED WALLS TO MAINTAIN INTEGRITY OF7.
NOT EXCEED 18" IN LENGTH.
TYPE. FLEX CONNECTIONS TO MECHANICAL EQUIPMENT SHALL BE SEALTITE AND SHALL
CONNECTIONS SHALL NOT BE LESS THAN •". CONNECTORS SHALL BE INSULATED THROAT
CONDUIT MAY BE USED FOR CONNECTION TO LIGHTING FIXTURES. ALL OTHER FLEX
MOUNTED LIGHTING FIXTURES SHALL NOT EXCEED SIX FEET IN LENGTH. 3#8" FLEXIBLE
CORRESPONDING FLUSH MOUNTED LIGHTING FIXTURES. FLEX CONNECTIONS TO FLUSH
FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION FROM JUNCTION BOX TO 6.
EMT COUPLINGS SHALL BE STEEL RAINTIGHT, COMPRESSION TYPE.5.
EMT CONNECTORS SHALL BE INSULATED THROAT, STEEL, RAINTIGHT, COMPRESSION TYPE.4.
SUPPORT CONDUIT SYSTEM IN ACCORDANCE WITH N.E.C. 3.
PULL WIRE IN EMPTY CONDUIT SYSTEMS.
CONDUIT SYSTEMS SHALL BE COMPLETE WITH BOXES, FITTINGS AND SUPPORTS. INSTALL2.
AND SHALL BE STEEL, ZINC-COATED INSIDE AND OUT.
1. ELECTRICAL METALLIC TUBING 'EMT' SHALL BE USED IN CEILING SPACE AND WALLS,
CONDUIT SYSTEMSB.
AND EQUIPMENT ENCLOSURES WITH PAINT SPECIFICALLY FOR THAT PURPOSE.
SCRATCHED OR MARRED SURFACES OF LIGHTING FIXTURES, PANELBOARD, CABINET TRIMS,
REMOVE OIL, DIRT, GREASE, AND FOREIGN MATERIALS FROM ALL EQUIPMENT. TOUCH UP6.
FOR THE INSTALLATION OF ELECTRICAL WORK.
5. PROVIDE ALL CUTTING AND PATCHING TO EXISTING WALLS, FLOORS, ETC., REQUIRED
GEORGIA AMENDMENTS AND ALL STATE ORDINANCES.
CODE (2020), LIFE SAFETY CODE (2018), INTERNATIONAL BUILDING CODE (2018),
INSTALLATION SHALL CONFORM WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL 4.
SHALL BE U.L. LABELED.
MATERIALS, DEVICES, ETC., SHALL BE NEW AND CONFORM TO THE SPECIFICATIONS AND 3.
MAKE OPERABLE, THE ITEM OR SYSTEMS SPECIFIED.
FURNISH LABOR, MATERIAL AND EQUIPMENT NECESSARY TO INSTALL COMPLETE AND 2.
COUNTS PRIOR TO BID.
FIELD REVIEW ALL FIXTURES AND DEVICES AND VERIFY ALL SWITCH LOCATIONS AND
CONNECTIONS IN EXISTING CONTROLS UNLESS OTHERWISE NOTED. CONTRACTOR SHALL
LED EQUIVALENTS, ADD SWITCHES, AND ADD EMERGENCY LIGHTING UNITS. MAINTAIN
THE SCOPE OF THIS PROJECT IS TO REPLACE THE EXISTING LIGHTING FIXTURES TO 1.
GENERALA.
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
20-NOV-2024
E:\E GA College LED Lighting Bldg B - 24086.00\CADD\E2.dgn
CADD PLOT
20-NOV-2024
13:37 bmoye
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
S W
A
IN
S B
O R
O
G E
O R
G
IA
24086.00
JV
BM
P
-2
J A
M B
U
IL
D
IN
G B
S T
U D
E N
T C
E N
T E
R L
E D L
IG
H T
IN
G R
E T R
O
E A S
T G
E O
R G
IA
S
T A T E C
O L L E
L E
A S
N S T R
U C
T
IO
N
SCALE: 1 / 8 " = 1' - 0"
FLOOR PLAN - ELECTRICAL 1
E2
A2 A2
A2 A2 A2 A2
A2 A2
A2 A2
A2 A2
A2A2 A2
A2
A2
A2 A2
A1
A1
A1
A2
A2
A1
A1
A2
A2
A1
A1 A1
A1
A1 A1
A2
A1
A1
A2
A1 A1
A2
A2
A1 A1
C C
C C
A1
A1A1
B
B
A2
A2
A2
A2
A2 A2
A2 A1
A1 A1
A1
A2
A2
A2
A2
A2
A2
A1
A1
A1
A1
B
B
A1 A1
A1 A1
A1 A1
A1 A1
DE D DE
D
DE
D
DED
D D
D DE
DD
G GE G GE G GE
I
I
I
I
I
K
K
K
K
K
K
H H
H
H
H
H HE
H
H
H
H
I
A2 A2
A2A2
A2
A1 A1
A2
A2A2
A2A2A2
A2
A2
A1 A1
I
I
I
I
A1
A1
A1
A1 A1
A1 A1
A1
A1
A1
A2
B
B
BE
B
A1
A1 A1
A1A1
A1
A2 A2
A2
A2
A2
A2
I I IE I IE
I
IE
I
I
IE
I
A2 A2
A2
I I IE
A2
A2
GG GE
A2
XA
XA
XA
XA
XA
XA
XA
XA
XA
XA
XA
XA
E2
BUILDING
STUDENT SERVICES
TO SHEET E3
A2E
A2E
A2E
A1E
A2E
A2EA2E
A1E
A2E
A2E
A2E
A2EA2E
A2E
A2
A2
A2
A2
A2
A2
XA
I
XA
A2
A2E
A2
A2
XA
NOTE 2 NOTE 2
NOTE 2 NOTE 2
NOTE 2 NOTE 2 NOTE 2
NOTES
A2E
A2E
A2E
3 3
NOTE 3
NOTE 3 NOTE 3
OF THE OCCUPANCY SENSOR AND WIRING IN FIELD.
FIXTURES TO NEW LIGHT SWITCH SHOWN. VERIFY THE EXACT LOCATION
3. REMOVE EXISTING OCCUPANCY SENSOR IN SPACE. RECONNECT LIGHTING
GREEN CREATIVE CAT# 9PLO/8CCTS/HYB/PF
EXISTING TO REMAIN. RELAMP FIXTURE ONLY. 2.
CONTRACTOR TO FIELD VERIFY EXISTING FIXTURES PRIOR TO ORDERING.1.
NOTE 3
NOTE 3
DN
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
20-NOV-2024
E:\E GA College LED Lighting Bldg B - 24086.00\CADD\E3.dgn
CADD PLOT
20-NOV-2024
13:35 bmoye
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
S W
A
IN
S B
O R
O
G E
O R
G
IA
24086.00
JV
BM
P
-2
J A
M B
U
IL
D
IN
G B
S T
U D
E N
T C
E N
T E
R L
E D L
IG
H T
IN
G R
E T R
O
E A S
T G
E O
R G
IA
S
T A T E C
O L L E
L E
A S
N S T R
U C
T
IO
N
SCALE: 1 / 8 " = 1' - 0"
FLOOR PLAN - ELECTRICAL 1
E3
CE
C
C
C
CE
C C
CE
C
CE
C
B
B
B BE
B BE
B B B
A2
A2
BE
B
BE
I
I
I
I
IE
I I
IE
I I IE
I
I
I IE I
IE
I
JE
J
JE J
J
J JE
J
JE
F
H
H
XC
XA
H
HE
H
HE
H
ELU
ELU
ELU
ELU
ELU
ELU
ELU
E3
CENTER, JAM
STUDENT ACTIVITIES
TO SHEET E2
M
M M
M
BBBBB
XA
NOTE 2 NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTES
OF THE OCCUPANCY SENSOR AND WIRING IN FIELD.
FIXTURES TO NEW LIGHT SWITCH SHOWN. VERIFY THE EXACT LOCATION
3. REMOVE EXISTING OCCUPANCY SENSOR IN SPACE. RECONNECT LIGHTING
GREEN CREATIVE CAT# 9PLO/8CCTS/HYB/PF
EXISTING TO REMAIN. RELAMP FIXTURE ONLY.2.
CONTRACTOR TO FIELD VERIFY EXISTING FIXTURES PRIOR TO ORDERING.1.
| E1 |
| E1 |
| E0.1.dgn |
| BDR, CHATHAM 24X36.dgn |
| E2 |
| E2 |
| SCRNBGRD, J-317 A2-01.dwg, Model |
| BDR, CHATHAM 24X36.dgn |
| E3 |
| E3 |
| SCRNBGRD, J-317 A2-01.dwg, Model |
| BDR, CHATHAM 24X36.dwg |
File details come from the government source that posted it. Updated .