Ship Check Comments and Changes DTMA94Q1600002 – Pipes and Pumps PR No: MAPR617160143 CLIN No 1 – SR No 5189810 – MSW Pump (3) renewal Pages #14 to #16 Job as written does not provide enough information and dimensions and does not agree with the present installed pump Marine Surveyor Suggestion: Cancel this job until proper information is available CLIN No 2 – SR No 5190854 – Sanitary Flushing Pumps (2) renewal Pages #16 to #18
1) Contractor needs to supply 1/4NPT connections for Pump Suction and Discharge Pressure gages
2) Pump information for installation = http://www.gouldspumps.com/ittgp/medialibrary/goulds/website/Literature/Instruction%20and%20Operation%20Manuals/Alphabetical/InstallationOperationMaintenance_iframeNM3196.pdf?ext=.pdf
3) Page #18 – Disregard following statement:
“Contractor to disable only one (1) sanitary flushing pump at a time………..”
Both pumps can be out of service at one time
CLIN No 3 – SR No 0301930 – Air Supply for ME Clutch Panels Pages #18 to #20
1) Discussions with attending contractors are in agreement that piping to be “welded” 316 stainless steel pipe and fittings
2) System sketch to accompany this write-up for the Air supply to ME Clutch Control panels = See below
Jim Sundfors Marine Surveyor
MARAD DPO
11-9-15 image1.emf