Amendment_0003_-_NY_ERFO_FIIS_2013-1(7).pdf
PDF 9 MB Posted
- Attached to
- Fire Island National Seashore Federal contract opportunity
- Solicitation number
- DTFH71-16-B-00031
About this file
Bid Opening date is scheduled for June 30 2016 at 2 00 p.m. EST.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Results_of_Bid_-_Schedule_A_-_NY_ERFO_FIIS_2013-1(7).pdf | ||
| Amendment_0002_-_NY_ERFO_FIIS_2013-1(7).pdf | ||
| Amendment_0001_-_NY_ERFO_FIIS_2013-1(7).pdf | ||
| VETS-4212_-_Form.pdf | ||
| Subcontract_plan.doc | DOC document | |
| IFB_Solicitation_-_NY_ERFO_FIIS_2013-1(7).pdf | ||
| Supplemental_Specifications.pdf | ||
| Report_3_As-built.pdf | ||
| FP14_Eng.pdf | ||
| Report_1_NEPA.pdf | ||
| ADV_Bidder's_Qualifications_Form.doc | DOC document | |
| Report_2_Load_Letter.pdf | ||
| Plans_-_NY_ERFO_FIIS_2013-1(7).pdf | ||
| Synopsis_-_NY_ERFO_FIIS_2013-1(7).doc | DOC document |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(x)
DTFH7116B00031
x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
x
Sterling VA 20166-6511
EFLHD-CO
21400 Ridgetop Circle Construction Office Eastern Federal Lands Highway Div.
Federal Highway Administration
Sterling VA 20166-6511
EFLHD-AC
21400 Ridgetop Circle Acquisitions Office Eastern Federal Lands Highway Div.
Federal Highway Administration
SEE BLOCK 1406/23/20160003
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
05/23/2016
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not, is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
NY ERFO FIIS 2013-1(7)
The purpose of this Amendment is to:
1) Replace the Bid Schedule Page B-1 to add a pay item for Treated Timber Piles, In Place
(Lay Piles).
2) Revise the Special Contract Requirements (J Pages) as follows:
a) Section 108 to revise the restrictions for no work days.
b) Section 551 to add requirements for lay piles and clarify measurement and payment for lay piles.
Continued ...
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA
FAR (48 CFR) 53.243
NSN 7540-01-152-8070
Previous edition unusable
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
NAME OF OFFEROR OR CONTRACTOR
2 35
CONTINUATION SHEET
REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF
(A) (B) (C) (D) (E) (F)
DTFH7116B00031/0003
c) Section 637 to clarify requirements for providing boat access for the CO.
3) Revise the Plans to replace 18 plan sheets to update and clarify work requirements.
4) Provide Pre-Bid Meeting Minutes.
5) Provide a summary of responses to questions/clarifications submitted by potential bidders via email.
6) Reschedule the Bid Opening date to June 30, 2016 at 2:00 p.m. EST.
NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)
Sponsored by GSA
FAR (48 CFR) 53.110
Amendment No. 0003
Amendment Info
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
Amendment No. 0003 Project NY ERFO FIIS 2013-1(7)
Fire Island National Seashore Watch Hill Marina
Solicitation: DTFH71-16-B-00031
The purpose of this Amendment is to:
1) Replace the Bid Schedule Page B-1 to add a pay item for Treated Timber Piles, In Place (Lay Piles).
2) Revise the Special Contract Requirements (J Pages) as follows:
a) Section 108 to revise the restrictions for no work days.
b) Section 551 to add requirements for lay piles and clarify measurement and payment for lay piles.
c) Section 637 to clarify requirements for providing boat access for the CO.
3) Revise the Plans to replace 18 plan sheets to update and clarify work requirements.
4) Provide Pre-Bid Meeting Minutes.
5) Provide a summary of responses to questions/clarifications submitted by potential bidders via email.
6) Reschedule the Bid Opening date to June 30, 2016 at 2:00 p.m. EST.
B Pages Info
Solicitation B Pages changes
Delete the Bid Schedule page B-1 and substitute the amended Bid Schedule page B-1.
1) Added pay item 55101-2300 Treated Timber Pile, In Place (Lay Piles).
B I D S C H E D U L E Schedule A
Project No: NY ERFO FIIS 2013-1(7)
Name: FIRE ISLAND NATIONAL SEASHORE
Item No. Quantity Unit Unit Price Amount
15101-0000
Line A0020 ALL LPSM $
15201-0000
Line A0040 ALL LPSM $
15701-0000
Line A0060 ALL LPSM $
20304-1000
Line A0080 ALL LPSM $
55101-2300
Line A0100 3,850 LNFT $ $
55101-2300
Line A0120 625 LNFT $ $
55701-2000
Line A0140 61 MFBM $ $
55701-3000
Line A0160 58 MFBM $ $
55706-2000
Line A0180 ALL LPSM $
63601-3000
Line A0200 ALL LPSM $
63701-0000
Line A0220 1 EACH $ $
64501-0000
Line A0240 ALL LPSM $
64605-0000
Line A0260 ALL LPSM $
Schedule A Bid Total:
Submitted by:
MOBILIZATION
CONSTRUCTION SURVEY AND STAKING
SOIL EROSION CONTROL (SILT CURTAIN)
REMOVAL OF STRUCTURES AND OBSTRUCTIONS
TREATED TIMBER PILE, IN PLACE
TREATED TIMBER PILE, IN PLACE (LAY PILES)
FIXTURE (EXTINGUISHERS)
STRUCTURAL TIMBER AND LUMBER, TREATED
STRUCTURAL TIMBER AND LUMBER, COMPOSITE
STRUCTURAL TIMBER AND LUMBER, TREATED (ELECTRICAL SHED)
SYSTEM INSTALLATION, ELECTRICAL
FIELD OFFICE
LOCATE UTILITIES
Amendment No. 0003
Amend 0003
B-1
Construction activities at the project site cannot begin any earlier than September 6, 2016. All work must be completed no later than September 1, 2017.
Does the Bidder claim the Price Evaluation Preference for HUBZone Small Business Concerns as defined in FAR Clause 52.219-4?
Yes No
Bonnie.Dubose Text Box
Bonnie.Dubose Text Box
Bonnie.Dubose Line
Bonnie.Dubose Line
SCR Info Changes
Special Contract Requirements (J Pages) changes
1. Delete the third paragraph of Subsection 108.01 of the SCR, page J-3, and substitute the following:
No work will be permitted on Saturdays, Sundays, or National legal holidays.
2. Add the following Subsection 551.06 to the SCR, page J-10:
Provide 12-inch diameter, 25-foot long treated timber replacement piles for lay piles where directed by the CO.
4. Add the following to Subsection 551.10 of the SCR, page J-10:
Prior to removal of lay piles, identify to the CO the piles that require removal, but that cannot be removed and reset in good condition.
5. Add the following to Subsection 551.18 of the SCR, page J-11:
Measure only identified piles by CO for removal. Do not measure removal and resetting timber lay piles. Piles removed prior to CO approval and that cannot be reset will be considered to have been damaged by Contractor operations and will not be measured for payment. Timber mooring piles required to be removed for Contractor operations will not be measured for payment.
6. Add the following after the first sentence to Subsection 637.03(d) of the SCR, page J-17:
Provide transportation to and from the Watch Hill Ferry Terminal, Patchogue, NY at the beginning and end of each work day.
Plans Changes Info
Plans changes
Delete Plan Sheets A03, A05, A06, C01, D01, D04, D05, D06, D07, D09, D16, D22, D23, D24, D25, D26, R04, and R07, and substitute the amended Plan Sheets A03, A05, A06, C01, D01, D04, D05, D06, D07, D09, D16, D22, D23, D24, D25, D26, R04, and R07.
1) Sheet A03 updated to provide additional text description for electrical symbol list.
2) Sheet A05 updated to provide general construction note 7 for lay piles.
3) Sheet A06 updated to provide note 2 and revise notes 1 and 8 for electrical abbreviations.
4) Sheet C01 updated to add pay item and quantity for lay piles.
5) Sheet D01 updated to provide notes 5 & 6 and sheeting limits call outs to place signs and fencing to prevent pedestrian access.
6) Sheet D04 updated to revise note 1 for coordination with National Park Services.
7) Sheet D05 updated to provide notes 10, 11, & 12 for electrical one-line diagram. Revise circuit breaker and feeder 1.
8) Sheet D06 updated to revise note 1 for lighting fixtures and lighting poles.
9) Sheet D07 updated to revise note 1 for lighting fixtures and lighting poles and additional text description to pole call outs.
10) Sheet D09 updated to delete metal ladder.
11) Sheet D16 updated to revise conduit type on notes 3 and 4 for electrical details and conduit call outs.
12) Sheet D22 updated to provide note 3 for electrical panel schedules, add power to shunt trips circuit breakers, and add spare breakers.
13) Sheet D23 updated to provide note 3 for electrical panel schedules, add power to shunt trips circuit breakers, and add spare breakers.
14) Sheet D24 updated to provide note 3 for electrical panel schedules, add power to shunt trips circuit breakers, and add spare breakers.
15) Sheet D25 updated to provide note 3 for electrical panel schedules and add power to shunt trips circuit breakers.
16) Sheet D26 updated to provide note 4 for electrical panel schedules, add power to shunt trips circuit breakers, add surge protection device (SPD), and add spare breaker.
17) Sheet R04 updated to provide note 11 for finger piers proposed work and revise section
B-B for finger pier typical section.
18) Sheet R07 updated to provide post size and spacing on detail.
Note number within diamond to be specific to area/item indicated on sheet. Note number without diamond is a general note and pertains to all conditions where it may apply.
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION
Branch circuit and conduit(s) routed in deck
Power feeder and conduit(s) trenched minimum 24" below grade.
Conduit turned down
Conduit turned up
Light lines indicate existing to remain
Heavy lines indicate new
New panelboard
Existing panelboard to be demolished
Fused 3 or 4 pole disconnect switch with solid neutral. as indicated on the sheets. Numerals denotes switch/fuse size
60AS
40AF
Unfused 3 or 4 pole disconnect switch with solid neutral. as indicated on the sheets. Numeral denotes switch size.
60AS
Junction box (wall or ceiling mounted).
Ground.
Pull box/Splice box. Provide NEMA 6 pull boxes.
WP
Manhole.
Marine grade duplex receptacle. NEMA 5-20R, mounting height is indicated on sheets. (WP-weatherproof), (GFI-ground fault interrupter).
Branch circuit and conduit(s) trenched minimum 24" below grade.
Lighthouse style pedestal with base extension and with
Side A = 50A, 120V, 1P &
Side B = 50A, 120V, 1P Receptacles.
Transformer.
Empty conduit for future fiber optical cable trenched minimum
24" below grade. Provide pull string and electrical true tape.
Electrical meter.
Lighthouse style pedestal with base extension and with
Side A = 50A, 208V, 1P & 50A, 120V, 1P &
Side B = 50A, 208V, 1P & 50A, 120V, 1P Receptacles.
Only one (1) receptacle per side is to be used per boat slip.
Existing equipment to be removed.
Photo sensor similar to Tork photo electric controls 5400 series, model 5403, Nema 3R enclosure, two (2) 3/4" knockouts at bottom.
Receptacle 3-prong turn-lock meets the requirements of EEI-Nema.
Adjustable over full 360° for proper photoelectric control orientation.
Voltage range 105-130V, 60 Hz, contact rating per pole, 3000 watts.
16' pole, lighting fixture mounted on square metal pole on deck.
Lighting fixture shall be similar to CIMARRON LED CL1S manufactured by Spaulding or approved equal lighting model
CL1S-A-16L-1-3K-5M-XX-PRU-BS (bird shield) with metal square pole model SSA-16-40-A-CX-XX. Refer to sheet for pole height locations.
12' pole, lighting fixture mounted on square metal pole on deck.
Lighting fixture shall be similar to CIMARRON LED CL1S manufactured by Spaulding or approved equal lighting model
CL1S-A-16L-1-3K-5M-XX-PRU-SCO-BS (bird shield) with metal square pole model SSA-12-40-A-CX-XX.
Refer to sheet for pole height locations.
Lighting fixture mounted on round metal pole on deck. Lighting fixture shall be similar to VAPORTITE LED manufactured by HUBBELL or approved equal Outdoor lighting model
VWGL-1-VGL-YW-WALL-11-250-120-4100-757-70-3.6 with metal round post similar to manufactured by Spaulding lighting model
RSA-10-45-C-P2-XX.
Lighting fixture mounted on round metal pole and concrete base.
Lighting fixture shall be similar to VAPORTITE LED manufactured by
HUBBELL or approved equal Outdoor lighting model
VWGL-1-VGL-YW-WALL-11-250-120-4100-757-70-3.6 with metal round post similar to manufactured by Spaulding lighting model
RSA-10-45-C-P2-XX. Concrete base provided by others.
Lighting fixture mounted on wood post supported by deck railing.
Lighting fixture shall be similar to VAPORTITE LED manufactured by
HUBBELL or approved equal Outdoor lighting model
VWGL-1-VGL-YW-WALL-11-250-120-4100-757-70-3.6.
SYMBOL DESCRIPTION
Metal Ladder from deck to basin
GFI
Wall mounted Single Pole Lighting Control Switch.S
Line voltage Thermostat with automatic switch over between
Heating and Cooling (Set 65°F in Winter and 85°F in Summer).
ELECTRICAL SYMBOL LIST
A03
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Added text description
LEA 06/16/16
AutoCAD SHX Text ,1
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text T
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 1:36 PM | FILENAME: 5836-A03.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
A05
GENERAL NOTES
GENERAL NOTES:
SPECIFICATIONS:
Construction:
Standard Specifications for Construction of Roads and Bridges on
Federal Highway Projects, FP-14, US Customary units
Special Contract Requirements
AASHTO LRFD Guide Specifications for the Design of Pedestrian
Bridges, 2009 with 2015 Interims
AASHTO LRFD Bridge Design Specifications, 7th Edition with 2015
Interims
NFPA 70 2014 National Electric Code
MATERIALS:
Timber:
Use composite plastic lumber conforming to the requirements of
Subsection 716.03 for all decking.
Use treated Southern Pine No. 1 conforming to the requirements of
Section 557 - Timber Structures for all other timber. The American
Wood Protection Association (AWPA) use category designation for rails, posts, and cross ties that are in ground contact is UC5A. Use
ACQ preservative for sand retention barrier timber, railings, and all electrical shed timber except shed piles. Treat all other timber with
CCA preservative. Acceptable preservative types and minimum preservative retention rates (lbs of preservative per cubic foot of timber) are:
Preservative Type UC5A Min. Retention
Alkaline Copper Quat (ACQ) 0.60
Chromated Copper Arsenate (CCA) 2.50
Use waterborne preservatives.
All timber dimensions shown on the plans are nominal unless noted otherwise. Use standard dressed dimensions for sawn lumber as specified by the Southern Pine Inspection Bureau (SPIB) grading rules, latest edition.
Treat all cuts, abrasions or other disturbances to the surfaces of treated wood in accordance with Section 557 - Timber Structures.
Connectors:
Use galvanized steel for tie-back connections, tie rod connections, and hardware in contact with tie-backs and tie rod connections.
Use stainless connectors and hardware at all other locations.
Use threaded rod, thru bolts, or carriage bolts conforming to ASTM
A320, Grade B8, Class 2 for all bolt connections.
Use Ogee or dock washers, lock washers, and nuts on each end.
Use nuts conforming to the requirements of ASTM A194 Grade 8, Stainless AISI 304.
Use washers conforming to the requirements of SS304.
Do not use nails as a connector unless otherwise noted in these plans or Special Contract Requirements. Countersink all screws.
Tie Rods
Use deformed or plain round tie rods conforming to ASTM A615, Grade 60. Hot-dip galvanize tie rods in conformance with ASTM
A153 with a minimum thickness of 3.9 mils (0.1 millimeters).
Electrical:
See electrical sheets for electrical notes.
SCALE:
The scales shown on these plans are valid for printing on 11x17 paper.
ELEVATIONS:
Elevations indicated on these plans are based on NAVD 88.
GENERAL SCOPE OF WORK:
1. Remove the existing marina decking, install new bulkhead, install new timber posts, reinforce and supplement existing stringers, and replace existing decking. Replace sand retention barrier. Provide all new materials for the proposed marina rehabilitations unless otherwise noted.
2. Remove and reset all anchor cleats. Fasten cleats to underlying timber framing via lag screws through composite decking.
3. Replace electrical and lighting components as described on the electrical drawings in accordance with the National Electrical
Code at the locations shown.
4. Coordinate with all utilities that have facilities within the project area prior to the start of construction. Contact "Dig Safely" at
811 at least two full working days prior to any excavation or pile installation to determine the presence and/or location of any underground utilities.
5. Prepare, submit for approval, and properly implement a soil erosion plan in accordance with the requirements of Section 157
- Soil Erosion and Sediment Control.
6. Install fire extinguishers in accordance with NFPA 303, 6.2.1.1 at a maximum spacing of 150 feet O.C. along the marina, and no more than 75 feet from any boardwalk terminus. Mount 20 pound ABC fire extinguisher in a weatherproof housing to timber posts.
7. Salvage ladders to concessionaire.
GENERAL CONSTRUCTION NOTES:
1. The dimensions and elevations shown on these plans have been obtained from limited field investigations. Field measure all existing components impacted by the new work to ensure consistency with the proposed modifications. Bring any discrepancies in dimensions, character or extent of the existing components to the attention of the CO before advancing the work.
2. Develop the full capacity of the structural members in all connections in accordance with the latest edition of the National
Design Specification for Wood Construction and Supplement
(NDS). Design and detail all connections and framing not otherwise detailed on the plans. Submit details of any required connections and framing not otherwise detailed on the plans to the CO for review and approval prior to beginning any work.
3. Tighten thru-bolt connections so that washers just start to press into the wood substrate.
4. Repair damage to existing components or structures caused by contractor operations as directed by the CO.
5. Access the site by boat or barge. Obtain special use driving permits to access site when bay ice conditions prevent boat or barge access.
6. Set benchmark for electrical datum plane at El. 4.00 at location directed by CO.
7. Remove and reset existing timber lay piles as necessary to provide access for the construction of the Timber Bulkhead at no cost to the government. Prior to removal, identify to the CO the lay piles that require removal but that cannot be removed and reset in good condition. Provide 12-inch diameter, 25-foot long treated timber replacement piles for select lay piles where directed by the CO. Piles removed prior to CO approval and that cannot be reset will be considered to have been damaged by contractor operations and will not be paid for. Reset lay piles after completion of the bulkhead. Timber mooring piles required to be removed for contractor operations will not be paid for.
AMENDMENT NO. 3
General Construction Note 7 added
VHB 06/16/16
DESCRIPTION BY
REVISIONS
NO.
ELECTRICAL ABBREVIATIONS
A
Ampere
KW Kilowatt
AF
Ampere Frame
LTG
Lighting
AFF Above Finished Floor MCB Main Circuit Breaker
AT
Ampere Trip
KCMIL Thousand Circular Mils
BKR Breaker MTD Mounted
C Conduit MTG
Mounting
CB Circuit Breaker N Normal
CKT Circuit NIC Not in Contract
CO
Contracting Officer
NTS Not to Scale
DIA Diameter
PH, P, Ø
Phase
DISC Disconnect PSEG LI
Public Service Electric & Gas Long Island
E,EX Existing
PWR Power
ETR
Existing to Remain
RGC
Rigid Galvanized Conduit
FDR Feeder RMC
Rigid Metallic Conduit
FIIS Fire Island RTRC
Reinforced Thermosetting Resin Conduit
FINS Fire Island National Seashore SCC Short Circuit Current
FT Feet or Foot SS Stainless Steel
G,GND
Ground TYP
Typical
GFI
Ground Fault Interupter
UON Unless Otherwise Noted
GSC Galvanized Steel Conduit V
Voltage
HZ Hertz W Wire
KAIC
Kilo-Amps Interrupting Capacity
WOS Without Substitution
KVA
Kilovolt Ampere
WP
Weatherproof
GENERAL NOTES:
1. Perform all work in accordance with the adopted edition national electric code in particular to Article 555, accepted standards established by O.S.H.A, pertinent NFPA codes such as NFPA 303 and rules and regulations of all local, NY State and federal authorities having jurisdiction. Provide owner with certificate of inspection.
2. Per NFPA 303 the electrical service is to be turned off from the power source when the water reaches the mark for the electrical datum plane.
3. Return all demolished items as switchboard, panelboards, circuit breakers and conductors to the CO. Coordinate exact location with the CO.
4. Do all necessary cutting and rough patching. Including but not limited to: finish painting and patching, masonry and concrete foundations for equipment.
5. Electrical sheets indicate the size and general location of work.
Do not used scaled dimensions.
6. Prepare and furnish to the CO "as-built" plans.
7. Provide temporary light and power at construction areas.
8. Test and adjust all parts of the work and associated equipment to work properly and be in perfect operating condition. Conduct megger tests between phases and between each phase and ground of all feeders, and panelboards. Correct defects disclosed by these tests. Submit copies of the report to the CO for approval.
9. Eliminate splices in conductors wherever possible. Only where approved by the CO, provide watertight splices in readily accessible junction boxes. Splice boxes in non-accessible locations are not permitted. In unfinished areas (e.g.
equipment rooms, electrical equipment rooms, etc.) conduits run exposed.
10. Properly clean-up and store all materials, tools and equipment after each work period.
11. Provide approved fire stopping and/or watertight compound at all penetrations through fire rated floors, walls and partitions to maintain fire rating of floor, walls or partitions.
12. Provide waterproofing at all conduits penetration into pull boxes, panelboards, disconnect switches, transformers, wireways, etc., internal and external of conduit(s).
13. Maintain power and lighting throughout. All required interruptions shall be as directed by CO.
14. Coordinate the location of all electrical equipment, raceways, etc. so as to avoid interference with piping, building steel, etc.
a. Maintain adequate access to all junction, termination and pull boxes.
b. Maintain adequate access to all equipment for operation, maintenance and repairs.
15. Provide submittals showing proposed work for approval by the
CO prior to installation, according to Subsection 104.03(a).
16. Support wall mounted electrical equipment (i.e. panelboards, junction boxes, disconnect switches, etc.) by strut channel secured to floor and ceiling. Unless wall is of masonry type which is of suitable construction to support weight of equipment, or except as otherwise noted or specified.
17. Survey existing electrical equipment, devices and raceways whether or not shown on the sheets, which may interfere with the work. Determine the source of power and the load it serves. Disconnect and remove completely or relocate and reconnect existing equipment, devices and raceways as directed by the CO.
18. Turn over to the CO existing equipment indicated to be removed, unless otherwise directed.
19. Provide expansion fittings in all conduit and electrical raceway runs.
20. Prior commencing work coordinate with PSEG LI for all electrical requirements, including shut down replacement of transformer secondary feeders and the installation of the
Electric Meters.
21. Submit for approval short circuit calculations prior purchasing of equipment.
A06
ELECTRICAL ABBREVIATIONS
AND GENERAL NOTES
Added note #2 and revision 1 and 8
LEA 06/16/16
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:21 AM | FILENAME: 5836-A06.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
C01
TABULATION OF QUANTITIES
Line Item
No.
Pay Item
Number
Pay Item Description
Unit
Sheet and Description
A05 D01 R04 R04 R05 R06 R12 R07 R15 R16/R17
Electrical
Key Plan
General
Notes
Marina Plan
Proposed
Section A
(Perimeter
Bulkhead)
Proposed
Section B
(Finger Pier
Bulkhead)
Proposed
Section C
(Perimeter
Bulkhead)
Proposed
Section D
(Bulkhead
Wall at Ferry
Dock)
Ferry Railing
Sand
Retention
Barrier Detail
Panelboard
Pile
Foundaiton
Electrical
Shed Details
1 & 2
Marina
Electrical
Key Plan
A0020 15101-0000 MOBILIZATION LPSM ALL
A0040 15201-0000 CONSTRUCTION SURVEY AND STAKING LPSM ALL
A0060 15701-0000 SOIL EROSION CONTROL LPSM ALL
A0080 20304-1000
REMOVAL OF STRUCTURES AND
OBSTRUCTIONS
LPSM ALL
A0100 55101-2300
TREATED TIMBER PILE, IN PLACE
LNFT
3,850
A0120 55101-2300
TREATED TIMBER PILE, IN PLACE (LAY
PILES)
LNFT 625
A0140 55701-2000
STRUCTURAL TIMBER AND LUMBER,
TREATED
MFBM 2 23 6 2 1 1 23 4
A0160 55701-3000
STRUCTURAL TIMBER AND LUMBER,
COMPOSITE
MFBM 4 38 9 7 1
A0180 55706-2000
STRUCTURAL TIMBER AND LUMBER,
TREATED (ELECTRICAL SHED)
LPSM ALL
A0200 63601-3000
SYSTEM INSTALLATION, ELECTRICAL
LPSM ALL
A0220 63701-0000 FIELD OFFICE EACH 1
A0240 64501-0000 LOCATE UTILITIES LPSM ALL
A0260 64605-0000
FIXTURE (EXTINGUISHERS)
LPSM ALL
SUMMARY OF QUANTITIES - SCHEDULE A
Estimated
Quantities
Bid Schedule
ALL
ALL
ALL
ALL
3,850
ALL
ALL
ALL
ALL
AMENDMENT NO. 3
Quantity for lay piles added
VHB 06/16/16
DESCRIPTION BY
REVISIONS
NO.
Repair electrical systems and rehabilitate marina boardwalks (Typ.)
B a s i n
D
B a s
C
VISITOR
CENTER
B a s
A a s
Coordinate with PSEG LI to verify condition of underground electrical line and if it is active. Not all conduits are shown.
B
B
C
Replace existing bulkhead
(approximately 3850 lnft)
C
B
B
A
A
A
A
A
Demolish bocce courts
Replace sand retention barrier
(approximately 1200 lnft)
Replace electrical shed
O p e r a i l i n g
O p e n i n g
O p e n i n g x u m p o u t
19'-9" x 2'-6" Bumpout
O p e n i n g
O p e n i n g
T y p
S t a i r s
13'-0" x 2'-6" Bumpout
O p e n i n g
R a m p
9'-9" x 11'-3" Bumpout
O p e n i n g
13'-2" x 2'-6" Bumpout
R a m p
7'-8" x 8'-3" Bumpout
13'-6" x 2'-6" Bumpout
A
O p e n i n g
8'-0" x
10'-0"
Bumpout
O p e n i n g
W a l k w a y
W a l k w a y
R a m p
8'-0"
Path
Tie-pile (Typ.)
E
E
F
H
E
F
H
F
H
E
FH
E
E
F
H
Ferry railing
Switchback ramp
R a m p
D
D
Replace decking (approximately 3000 sqft)
See Detail G
E
IM
HM
LZ
HM
SM
Notes:
1. MLW and MHW and Limit of LZ located on Vertical bulkhead wall within Marina.
2. See Typical Existing Sections sheets and Typical
Rehabilitation Sections sheets for sections.
3. Install RPZ valves at all fire hose locations.
4. Request antenna to be lowered if wires prevent work access. Antenna has 3 support wires approximately
10'± from base attached to concrete footings that are to not be disturbed.
5. Dimensions shown are existing.
6. Install boom and buoy visible at night across mouth of marina entrance during construction to mark closure.
Bulkhead wall (Typ.)
See Section E
See Section D (20'-0" T&G sheeting)
O p e n i n g
Shed boardwalk
C
C
Antenna (See Note 4)
2" Tide gauge conduit to remain
40'±
E
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
Limits of 20'-0" T&G sheeting
Limits of 20'-0"
T&G sheeting
MARINA PLAN
NY
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
FIRE ISLAND NATIONAL SEASHORE
120485
201456
A M v h b p r o j w a t t s n p s n e r t r a n s t e c h s u p p t e c h f i i s c a d d e w a d o c k s m i c r o s t a m a r i n a s w a t c h h i l l w a t c h h i l l m a p d w g
195093
213699
D01
0 100 200 Feet
AMENDMENT NO. 3
Notes 5, 6 & 20' sheeting limits added
VHB 06/16/16
DESCRIPTION BY DATE
REVISIONS
NO.
Existing PSEGLI Primary feed to remain.
Grade
Level
Existing 300KVA
PSEGLI Transformer
Existing CT cabinet and
Incoming service section
Existing Concession
Distribution Main Switch
Existing Switch Board
Distribution section
Spare
Existing time clock
Existing
Concession meter
Existing FINS meter
Existing Panelboard located in existing storage closet at bathroom area
Concession site lighting panel
Existing pull box
Existing Panelboard outdoor enclosure
NOTES:
1. Salvage switchboard, panelboards, circuit breakers, conductors in accordance with
Specification section 203. Coordinate delivery location with the CO, National Park
Services, 166 West Ave., Patchogue NY
11772.
D04
ELECTRICAL DEMOLITION
ONE-LINE DIAGRAM
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Revised note #1
LEA 06/16/16
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
2000AS
AutoCAD SHX Text
2000AF
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
FINS
AutoCAD SHX Text Main
AutoCAD SHX Text Panel
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'E'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'F'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'D'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'A'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'H'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'G'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'B'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'C'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'I'
AutoCAD SHX Text
CON
AutoCAD SHX Text
CESSION
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
FINS
AutoCAD SHX Text Site
AutoCAD SHX Text Lighting
AutoCAD SHX Text Panel
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:21 AM | FILENAME: 5836-D04.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
Existing PSEGLI Primary feed to remain.
Grade
Level
Existing 300kVA PSEGLI
Transformer
13.2kV-120/208V
Incoming service and CT compartment
Switchboard main and digital metering section
1200A, 120/208V, 3 phase, 4 wire, 65,000 AIC, Nema 4X Stainless Steel
Spare
Marina meter
Panelboard weatherproof enclosure
(Typ.)
Spare
PSEGLI Primary feeder
225kVA PSEGLI
Transformer
13.2kV-120/208V
400AS/175AF
POWER FEEDER LEGEND
TAG
FEEDER
SIZE
GROUND
WIRE SIZE
CONDUIT
SIZE
4#350KCMIL
#3/0
4"
4#400KCMIL #2 3"
4#300KCMILL #3 3"
4#500KCMIL #1 4"
4#4/O
#4
2 1/2"
4#400KCMIL
#1/0 3 1/2"
NUMBER
OF SETS
3#500KCMIL #3 3"
4#4/0
#4
2 1/2"
4#500KCMIL #1 4" 2
Coordinate electrical meters with PSGELI and the CO in the field prior to commencing any work.
Electrical contractor is responsible to provide feeder oversize lugs at switchboard and at panelboards as required.
Provide surge protection device rated for 240kA peak surge current per phase, in a NEMA 4X enclosure.
Provide NEMA 4x splice box at underside of shed.
Provide NEMA 4x splice box adjacent to panelboard.
Refer to grounding details #3 on sheet D18.
Coordinate work with PSEGLI requirements.
Cable to be 15kV, (3)-1/0 awg with concentric neutral in 5" conduit.
Ground neutral conductor at disconnect switch.
The demand calculated load for this main distribution board is based on the connected loads for each panelboard connected with the demand factor per
NEC section 555.12 as follows:
Total connected load
=(1037.6)(30%)(90%)
=280.15kVA
The connected load for this distribution board is as follows:
Total connected load = 600 amps = 155.2kVA
Provide 100% rated main circuit breaker.
NOTES:
Shed
Level
NEMA 4X Stainless Steel
112.5kVA Transformer
208V-480V (Delta-Wye)
NEMA 4X Stainless Steel
112.5kVA Transformer
480V-120/208V
(Delta-Wye)
Existing Panelboard located in existing storage closet at bathroom area
Existing
800A, 120/208V, 3 phase, 4 wire, 65,000 AIC, Nema 4X Stainless
Steel
Concession meter
(Typ.)
Spare
Incoming service and
CT compartment
Switchboard main and digital metering section
Panelboard weatherproof enclosure
Spare
Splice box #2
Splice box #3
Splice box #1
Splice box #4
Splice box #5
3#250KCMIL
4#300KCMIL
4#2/0
3#350KCMIL
4#4/0
4#2
4#3/0
4#350KCMIL
4#250KCMIL
#4
#6
#1/0
#8
#2
#6
#4
#4
#4 3"
3"
2 1/2"
2 1/2"
2 1/2"
3 1/2"
4"
2"
2"
TAG
FEEDER
SIZE
GROUND
WIRE SIZE
CONDUIT
SIZE
NUMBER
OF SETS
D05
ELECTRICAL ONE-LINE
DIAGRAM
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Added notes, revised C.B. and feeder 1
LEA 06/16/16
AutoCAD SHX Text
600AF
AutoCAD SHX Text %%u400AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'A3'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'A2'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'A1'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'B2'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'B1'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'C2'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'C1/D3'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'D1'
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 'D2'
AutoCAD SHX Text
400AF
AutoCAD SHX Text
%%U400AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
SPD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u175AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
600AF
AutoCAD SHX Text %%u225AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
600AF
AutoCAD SHX Text %%u225AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
400AF
AutoCAD SHX Text %%u175AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
400AF
AutoCAD SHX Text %%u400AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u175AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
600AF
AutoCAD SHX Text %%u300AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
600AF
AutoCAD SHX Text %%u250AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u250AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
AutoCAD SHX Text
1200AF
AutoCAD SHX Text %%u1200AT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FIIS
AutoCAD SHX Text Main
AutoCAD SHX Text Panel
AutoCAD SHX Text
CON
AutoCAD SHX Text
CESSION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u200AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
SPD
AutoCAD SHX Text
400AF
AutoCAD SHX Text %%u400AT
AutoCAD SHX Text 2P
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u200AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
800AF
AutoCAD SHX Text %%u800AT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
250AF
AutoCAD SHX Text %%u250AT
AutoCAD SHX Text 3P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 1:36 PM | FILENAME: 5836-D05.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Approximate location of existing PSEG LI transformer
A
B
I
Basin D
Basin C
Existing pull box
C
D06
1. Demolish all existing devices indicated to be demolished such as pedestals, panelboards, panelboard enclosures, feeders, branch circuits, lighting fixtures, lighting poles and conduits back to the origination point.
Demolition of existing shed housing existing electrical switchboard and equipment is by others.
Electrical contractor to demolished electrical equipment in shed. Coordinate all required shutdowns with PSEGLI and the CO in advance.
Demolish a total of thirty-three (33) existing pedestals and branch circuits and conduits back to the origination point.
Approximate location of existing transformer secondary. Electrical contractor to coordinate shutdown with the CO and PSEGLI, prior to demolition of existing feeder.
NOTES:
REFER TO SHEET D07 FOR CONTINUATION
ELECTRICAL DEMOLITION POWER &
LIGHTING PLAN SHEET 1 OF 3
WATCH HILL VISITOR'S CENTER MARINA ELECTRICAL DEMOLITION POWER & LIGHTING PLAN
SCALE: 1" = 50'-0"
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Revised note #1
LEA 06/16/16
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:21 AM | FILENAME: 5836-D06.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
F
E
Basin B
Basin A
D
Existing 12' Pole
Existing 16' Pole
H
G
D07
1. Demolish all existing devices indicated to be demolished such as pedestals, panelboards, panelboard enclosures, feeders, branch circuits, lighting fixtures, lighting poles and conduits back to the origination point.
Demolish a total of Forty-one (41) existing pedestals and branch circuits and conduits back to the origination point.
NOTES:
ELECTRICAL DEMOLITION POWER &
LIGHTING PLAN SHEET 2 OF 3
WATCH HILL VISITOR'S CENTER MARINA ELECTRICAL DEMOLITION POWER & LIGHTING PLAN
SCALE: 1" =50'-0"
R E F E R
T O
S H
E E T
D
F O
R
C O
N T I N
U A T I O
N
REFER TO SHEET D06 FOR CONTINUATION
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Revised note #1
LEA 06/16/16
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:21 AM | FILENAME: 5836-D07.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Approximate location of existing
300 KVA PSEG LI
transformer
C2
(Typ.)
D2
D1
Basin D
Basin C
C1/D3
C1/D3#30
D2#10
D2#10 D2#10
D2#10
D2#10
C1/D3#30
C1/D3#30
C1/D3#30
(Typ.)
(Typ.)
(Typ.)
MH-1
MH-2
(Typ.)
Bathroom area
Restaurant
Approximate location of new
225KVA PSEGLI
Transformer
BRANCH CIRCUIT LEGEND
TAG
CIRCUIT
SIZE
GROUND
WIRE SIZE
CONDUIT
SIZE
2#10
#10
3/4"
D09
Provide secondary conductors from existing
PSEG LI transformer to the new main distribution ct cabinet. Refer to sheet D16 for additional information. Coordinate this scope of work in advance with the CO and PSEG LI prior to commencing any work.
Shed housing, electrical main distribution comprised of the ct cabinet, two (2) main circuit breakers and distribution section(s) on the 2nd level of newly constructed shed. Refer to sheet
D16 for additional information, and to sheet
D18 for grounding information and details.
Provide new outdoor enclosure (wp) for new panelboard. Provided weep holes to discharge condensation. Refer to sheet D17 "typical electrical panelboard detail" for additional information.
Provide trenching for panelboard feeder conductors in conduit as indicated on sheet
D18 , from panelboard to distribution section(s) located on 2nd floor of newly constructed shed.
Refer to note 2 above. Trench conduits minimum of 24 inches below grade. No splices are allowed for any feeder conductor run.
Route panelboard feeder conductors and conduit(s) to the main distribution section(s) located on the 2nd floor of the newly constructed shed. Refer to sheet D05 and D16 for additional information.
Provide photo sensor mounted on the side of the panelboard outdoor enclosure.
Provide conduit(s) and feeder(s) from the FIIS panel to the bathroom area existing electrical panelboard. Existing panelboard located in existing storage closet. Storage closet door shall be reversed to swing out. Reverse door prior to electrical contractor commencing the of work.
Coordinate termination point via splice box #5 with the CO in the field. Refer to sheet D05 for additional information.
Provide conduit(s) and feeder(s) from the 800A main distribution board to the concession restaurant area existing power connection point.
Coordinate termination point via splice box #4 with the CO in the field. Refer to sheet D05 for additional information.
Provide one (1) #8 AWG insulated ground conductor in 3/4 inch conduit at metal ladder.
Ladder grounding conductor shall be independent of any other electrical system grounding. Refer to sheet D18 detail #5.
Provide transformer concrete pad as per
PSEG-LI latest requirements. Coordinate exact location with the CO, prior to commencing any work. Install pad at grade.
Coordinate work with PSEGLI requirements.
NOTES:
REFER TO SHEET D10 FOR CONTINUATION
ELECTRICAL POWER & LIGHTING
PLAN SHEET 1 OF 3
WATCH HILL VISITOR'S CENTER MARINA ELECTRICAL POWER & LIGHTING PLAN
SCALE: 1" = 50'-0"
TYPICAL CIRCUIT LEGEND:
Number denotes branch circuit #10 from panel D2.
Letter/Number denotes panel D2.
D2#10
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Removed metal ladder
LEA 06/16/16
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text D19
AutoCAD SHX Text B
AutoCAD SHX Text D19
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:21 AM | FILENAME: 5836-D09.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
Service to existing panel in storage closet at bathroom area
FIIS PANEL
(TYP.)
SHED SECTION B-B
SCALE: 1/4"=1'-0"
Service to panel A3
Step-Up
Transformer
112.5kVA
400A/175AF
disc. switch
Splice box
#1
Panel FIIS
CKT#3
WP
GFI
Panel FIIS CKT#8, 10, 12
FIIS
Panel
PSEG LI
CT Compartment and 800AT/800AF
Main Distribution
Distribution
Section
PSEG LI
CT Compartment and 1200AT/1200AF
Main Distribution
Step-Up
Transformer 112.5kVA
400A/175AF
disc. switch
WP
GFI
Panel FIIS
CKT#3
SPD
A
A
B
B
SHED PLAN VIEW
SCALE: 1/8"=1'-0"
Distribution Section
Panel FIIS
CKT#7
Panel FIIS
CKT#7
Panel FIIS
CKT#5
SPD
Electrical secondary from existing 300kVA PSEG LI transformer
Service to panel A2
Service to panel A1
Service to panel B2
Service to panel B1
(TYP.)
PSEGLI
electrical meter
Section 2 Section 1
SHED SECTION A-A
SCALE: 1/4"=1'-0"
Main CB
SPD
Splice box #3
Splice box
#2
3'-6"
Transition between rigid galvanized steel
PVC coated conduit and
PVC or RTRC conduit.
(TYP.)
PVC or RTRC conduit (TYP.)
Service to panelboard D2
Rigid galvanized steel
PVC coated conduit (TYP.)
Splice box
#1
Service to restaurant concession existing power
Section 2 Section 1
Electrical secondary from 225kVA
PSEG LI transformer
PSEGLI
electrical meter
Main CB
SPD
Service to panel C1/D3
Service to panel C2
Service to panel D1
Refer to sheet D05 for electrical conduit and conductor information.
Coordinate electrical meters location with PSEGLI and CO in the field prior to commencing any work.
Provide rigid galvanized steel PVC coated conduits from the main distribution panelboard to below grade level. Transition to PVC or
RTRC conduit for the remainder of the conduit route.
Provide ridig galvanized steel PVC coated conduits for the entire conduit route.
5. Refer to sheet D18 for trenching details.
Provide two (2) chain hung lighting fixtures similar to Mercury
Lighting L501-4-4200-35K-HTA-UXX-
UNI-SSL-HB. Provide all accessories required for a complete installation. Provide one (1) lighting control switch. Circuit lighting fixtures to panel FIIS CKT#1.
Provide one (1) wall mounted fan forced unit heater similar to TPI
Corporation 5100 Series, 208V, 3-phase, 2.5kw. Provide wall mounted bracket installed per manufacturer requirements.
Provide 2 square foot fixed louver with 50% free area. Provide
120V, motorized damper and interlock with operation of exhaust fan. Provide bird screen.
Roof mounted mushroom type exhaust fan similar to Greenheck
Model G-085-D, 1/20HP, 120V, 500 CFM, 0.25" static pressure.
Provide bird screen and roof curb.
NOTES:
ELECTRICAL DETAILS
D16
NY
NY ERFO FIIS2013-1(7)
U.S. DEPARTMENT OF TRANSPORTATION
FEDERAL HIGHWAY ADMINISTRATION
EASTERN FEDERAL LANDS HIGHWAY DIVISION
STERLING, VIRGINIA
STATE PROJECT SHEET NO.
NPS
NO.
NO.
PMIS
FIRE ISLAND NATIONAL SEASHORE
120485
201456
195093
213699
AMENDMENT NO. 3
DESCRIPTION BY DATE
REVISIONS
NO.
WATCH HILL MARINA
Revised conduit type
LEA 06/16/16
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text | PROJECT: 5836 | PLOTBY: BBONILLA | PLOTDATE: 6/17/2016 9:22 AM | FILENAME: 5836-D16.dwg |
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PANEL: D1
Nema 3R
Location:
Basin 'D' - West side
Mounting:
Floor on concrete pad, Inside weather proof enclosure
Service:120/208v 3ph 4w w/ground bus Mains: MCB 250 Amps
Bus rating: 400a Short circuit rating: 22 KA RMS SYM ckt. bkr. Branch circuit Branch circuit ckt. bkr.
Amps
Trip
Pole
Designation
Volt
Amps
No No
Volt
Amps
Designation
Pole
Amps
Trip
* 125 2 Pedestal PD-1
10400 1 2 0
Spare
2 125 *
10400 3 4 0
* 125 2 Pedestal PD-2
10400 5 6 0
Spare
2 125 *
10400 7 8 0
* 125 2 Pedestal PD-3
10400 9 10 0
Power to Shunt trip breakers
1 20
10400 11 12 0
Spare
1 20
* 125 2 Pedestal PD-4
10400 13 14 0
Spare
1 20
10400 15 16 0
Spare
1 20
* 125 2 Pedestal PD-5
10400 17 18 0
Space
10400 19 20 0
Space
* 125 2 Pedestal PD-6
10400 21 22 0
Space
10400 23 24 0
Space
30 3
Panel Surge Protection
0 25 26 0
Space
0 27 28 0
Space
0 29 30 0
Space
Subtotal:
Phase A Phase B Phase C
41,600 41,600 41,600
Total:
124,800
Provide Shut Trip Circuit Breaker
PANEL: D2
Nema 3R
Location:
Basin 'D' - North side
Mounting:
Floor on concrete pad, Inside weather proof enclosure
Service:120/208v 3ph 4w w/ground bus Mains: MCB 250 Amps
Bus rating: 400A Short circuit rating: 22 KA RMS SYM ckt. bkr. Branch circuit Branch circuit ckt. bkr.
Amps
Trip
Pole
Designation
Volt
Amps
No No
Volt
Amps
Designation
Pole
Amps
Trip
* 125 2 Pedestal PD-7
10400 1 2 0
Spare
2 125 *
10400 3 4 0
* 125 2 Pedestal PD-8
10400 5 6 0
Spare
2 125 *
10400 7 8 0
* 125 2 Pedestal PD-9
10400 9 10 55
Pole Lighting (Via Photo cell)
1 20
10400 11 12 0
Power to Shunt trip breakers
1 20
* 125 2 Pedestal PD-10
10400 13 14 0
Spare
1 20
10400 15 16 0
Spare
1 20
* 125 2 Pedestal PD-11
10400 17 18 0
Spare
1 20
10400 19 20 0
Space
* 125 2 Pedestal PD-12
10400 21 22 0
Space
10400 23 24 0
Space
30 3
Panel Surge Protection
0 25 26 0
Space
0 27 28 0
Space
0 29 30 0
Space
Subtotal:
Phase…