Amend 1 - DTFASA-17-R-00153 Fresno CA ATCT Fire-Life Safety Upgrade.pdf

PDF 61 KB Posted

Attached to
DTFASA-17-R-00153 - Fresno Airport Air Traffic Control Tower (ATCT) Fire-Life-Safety Upgrades, Fresno, CA
Solicitation number
DTFASA-17-R-00153
Issued by

About this file

Amend 1 - DTFASA-17-R-00153 Fresno CA ATCT Fire-Life Safety Upgrade (pdf)

View the file

Other files

File Type Posted
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
Amend 2 - DTFASA-17-R-00153 Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
RFO - DTFASA-17-R-00153 - Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
Amend 1 - DTFASA-17-R-00153 Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
General Decision - CA170029 01-20-2017 CA29.pdf PDF
RFO - DTFASA-17-R-00153 - Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
General Decision - CA170029 01-20-2017 CA29.pdf PDF
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
RFO - DTFASA-17-R-00153 - Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
Amend 1 - DTFASA-17-R-00153 Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
RFO - DTFASA-17-R-00153 - Fresno CA ATCT Fire-Life Safety Upgrade.pdf PDF
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
Tech Spec - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS SPECS).1-10-2017 FAT FLS SPECS —
Drawings - DTFASA-17-R-00153 - Fresno CA ATCT FireLife Safety Upgrade (1-10-2017 FAT FLS DWGs).1-10-2017 FAT FLS DWGs —
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OMB Control No. 2120-0595 (SF-30) FAA Template No. 11 (Reverse) (8/97)

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES 1 1

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

0001 2/17/2017

6. ISSUED BY 7. ADMINISTRATED BY (If other than Item 6) Federal Aviation Administration Acquisition Management Branch, AAQ-530 1601 Lind Ave SW Renton WA 98057

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

9A. AMENDMENT OF SOLICITATION NO.

DTFASA-17-R-00153

9B. DATED (SEE ITEM 11)

January 20, 2017

10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. AWARD DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is NOT extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation on as amended, by one of the following methods:

(a) By completing Item 8 and 15, and returning 1 copies of the amendment; (b) acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDG- MENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hours and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS, IT MODIFIES THE CONTRACT/ORDER NO. AS

DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT/ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is required to sign this document and return 1 copy to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

The above referenced solicitation for the Fresno Airport Air Traffic Control Tower (ATCT) Fire-Life-Safety Upgrades is amended as follows: Reference the RFO document at Section J, SA34 TECHNICAL SPECIFICATION, the project Technical Specification is changed at Section 28 30 00 specifically as described in Attachment 1 to this amendment, comprised of 4 total pages. Any section or subsection of the technical specification not specifically addressed by this amendment remains unchanged.

ALL OTHER TERMS AND CONDITIONS REMAIN UNCHANGED.

Except as provided herein, all terms and conditions of the referenced document in Item 9A or 10A, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR 15C. DATE SIGNED

16C. DATE SIGNED

(Signature of person authorized to sign)

BY

(Signature of Contracting Officer)

Attachment 1 to Amendment No. 1

The referenced solicitation for the Fresno Airport Air Traffic Control Tower (ATCT) Fire- Life-Safety Upgrades is amended as follows. Reference the RFO document at Section J, SA34 TECHNICAL SPECIFICATION, the project Technical Specification is changed at Section 28 30 00 specifically as described below. Any section or subsection of the technical specification not specifically addressed by this amendment remains unchanged.

SECTION 28 30 00

PART 1 - GENERAL

1.3 QUALITY ASSURANCE

B. Contractor Qualifications

1. The contractor must be a manufacturer-authorized representative of any proposed product. Some examples of manufacturers of known acceptable products are listed below. All proposed products are subject to FAA approval.

a. Edwards Systems Technologies (UTC Fire & Security).

b. Notifier (a division of Honeywell International, Inc.).

c. Siemens Fire Safety Systems (a division of Siemens Industry, Inc.).

d. SimplexGrinnell LP (a division of Tyco International, Ltd.).

Part 2 – PRODUCTS

2.1 GENERAL

A. Listed Equipment

2. All equipment and system components must be the standard product of a single manufacturer.

Some examples of manufacturers of known acceptable products are listed below. All proposed products are subject to FAA approval.

a. Edwards Systems Technologies

b. Notifier

c. Siemens Fire Safety Systems

d. SimplexGrinnell LP.

2.2 FIRE ALARM CONTROL UNIT

A. Listed below are some examples of manufacturers and products which are known to meet the specification. All proposed products are subject to FAA approval.

1. Edwards System Technologies

a. Model EST3X

2. Notifier

a. Model NFS2-3030

3. Siemens Fire Safety Systems

a. Model XLS

4. SimplexGrinnell LP

a. Model 4100ES

B. The fire alarm control unit must be designed and eqipped to provide the following:

7. Digital Alarm Communicator Transmitter (DACT)

a. Listed below are some examples of manufacturers and their DACT products which are known to meet the specification. All proposed products are subject to FAA approval.

1) Edwards System Technologies

a) 3-Modcom

2) Notifier

a) UDACT

3) Siemens Fire Safety Systems

a) MDACT

4) SimplexGrinnell LP

a) 4100-6052

2.4 REMOTE ANNUNCIATOR PANELS

A. Listed below are some examples of manufacturers and their remote annunciator panel products which are known to meet the specification. All proposed products are subject to FAA approval.

1. Edwards System Technologies

a. 3-LCD

2. Notifier

a. LCD-80

3. Siemens Fire Safety Systems

a. SSD

4. SimplexGrinnell LP

a. 4603-9101

2.5 MANUAL FIRE ALARM BOXES

A. Listed below are some examples of manufacturers and their manual fire alarm box products which are known to meet the specification. All proposed products are subject to FAA approval.

1. Edwards System Technologies

a. SIGA-278

2. Notifier

a. NBG-12LX

3. Siemens Fire Safety Systems

a. HMS-D

4. SimplexGrinnell LP

a. 4099-9003

2.6 SMOKE DETECTORS

A. Spot-type smoke detectors

1. Listed below are some examples of manufacturers and their spot-type smoke detector products which are known to meet the specification. All proposed products are subject to FAA approval.

a. Edwards System Technologies

1) SIGA-PS

b. Notifier

1) FSP-851

c. Siemens Fire Safety Systems

1) HFP-11

d. SimplexGrinnell LP

1) 4098-9714

B. Duct Smoke Detectors

1. Listed below are some examples of manufacturers and their duct smoke detector products which are known to meet the specification. All proposed products are subject to FAA approval.

a. Edwards System Technologies

1) SIGA-DH

b. Notifier

1) InonovairFlex

c. Siemens Fire Safety System

1) AD-HR

d. SimplexGrinnell LP

1) 4098-9755

2.7 HEAT DETECTORS

A. Listed below are some examples of manufacturers and their heat detector products which are known to meet the specification. All proposed products are subject to FAA approval.

a. Edwards System Technologies

1) SIGA-DH

b. Notifier

1) InnovairFlex

c. Siemens Fire Safety System

1) AD-HR

d. SimplexGrinnell LP

1) 4098-9755

END OF AMENMDMENT/ATTCHEMENT

Amend 1 - (SF 30) spec clarified
spec clarifications attach