ENGINEERING SERVICES
OPERATIONS
RCAG
COVER SHEET
SECURITY FENCE
NCROCKY MOUNT-WILSON RGNL AIRPORTROCK MOUNT
JW
PROJECT ENGINEER MGR: ENGINEERING CENTER
03/17/2022 18064037
RWI-18064037-G001
02/15/202218064037CONSTRUCTION, DT #1970503/17/2022
rw i- -g
.d g n
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
C O
N S
T R
U
IO
/0
/2
:5
:2
P
M lo tt e d b y
V
-C
A E
G -E
D
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
IS
T OF TRANSPO
T A
IC
OF
STATES
IT
TM
EN
AVIA
I
LAR
TRAT
SI
NI
ROCKY MOUNT, NORTH CAROLINA
REMOTE COMMUNICATIONS AIR TO GROUND (RCAG)
FOR OFFICIAL USE ONLY
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
rwi-18064037-g001
2022-04-12T08:12:27-0400
HENRY B NEWCOMB
2022-04-12T07:36:38-0400
JOHN R WEST
INDEX SHEET
RWI-18064037-G002
SCALE
DETAIL, ELEVATION OR SECTION IS/ARE LOCATED
SHEET NUMBER(S) WHERE CALLOUT(S) TO PLAN,
ELEVATION REFERENCE LETTER
SECTION REFERENCE LETTER
DETAIL REFERENCE NUMBER
(PLAN, DETAIL / ELEVATION, SECTION)
REFERENCE NUMBER/LETTER
ELEVATION IS LOCATED
SHEET NUMBER WHERE
DETAIL IS LOCATED
SECTION IS LOCATED
:2 lo tt e
SYMBOLS LEGEND
SUBTITLE REFERENCE
ELEVATION CALLOUT REFERENCE
DETAIL CALLOUT REFERENCE
SECTION CALLOUT REFERENCE
X
XXXX
XXXXXXXXXXX
SCALE: X=XXX
DRAWING PREFIXES
EXXX - ELECTRICAL
CXXX - CIVIL
GXXX - GENERAL
DRAWING LIST
DRAWING TITLE DRAWING NUMBER
ABBREVIATIONS
COVER SHEET
INDEX SHEET
RWI-18064037-G001
RWI-18064037-G002
RWI-18064037-C001
RWI-18064037-C002
RWI-18064037-E001 GROUNDING LAYOUT
FENCE DETAILS
NEW SITE PLAN
RWI-18064037-E002 GROUNDING DETAILS
rwi-18064037-g002
2022-04-12T08:13:08-0400
HENRY B NEWCOMB
2022-04-12T07:36:49-0400
JOHN R WEST
NEW SITE PLAN
RWI-18064037-C001
-c
.6
.0
60.0'
94.3'
63.7'
.3
.3
62.0'
.7
.2
NEW AT SAME LOCATION
ALL SIDES AND REPLACE WITH
DEMOLISH EXISTING FENCE
WOODEN GARAGE
GUY TOWER
LATTICE TOWER
LATTICE TOWER
GUY TOWER
64.0'
:3 lo tt e
SITE LOCATION
PRICE LANE
OAK LEVEL RD
L
IN
SCALE: 1" = 20'
20' 40'020'
STAINLESS STEEL.
8) CONTRACTOR SHALL PROVIDE QTY 2 STANLEY BEST INTERCHANGEABLE CORE PADLOCKS 21B772
QUANTITY OF 17.
7) CONTRACTOR SHALL PROVIDE TIES AND INSTALL GOVERNMENT FURNISHED SECURITY SIGNAGE.
SECURITY FENCE CLEARANCES.
RESTORING SITE CONDITIONS THE CONTRACTOR SHALL GRADE AREAS SO THAT THEY COMPLY WITH
6) CONTRATOR IS RESPONSIBLE TO RESTORE ANY DISTURBED AREAS TO ITS ORIGINAL CONDITION. WHEN
AS SHOWN IN THE DRAWINGS AND FAA'S LIGHTNING PROTECTION STANDARD.
5) CONTRACTOR SHALL REVIEW GROUNDING DETAILS PRIOR TO WORK AND SHALL INSTALL ALL GROUNDING
LOCATION OF EXISTING FENCE.
4) CONTRACTOR SHALL PROVIDE AND INSTALL NEW 8' SECURITY FENCE AND 1' BARB WIRE AND INSTALL IN
BARB WIRE.
3) CONTRACTOR SHALL DEMOLISH AND LEGALLY DISPOSE OF ALL EXISTING 5' SECURITY FENCE AND 1'
DEMOLITION AND EXCAVATION.
2) CONTRACTOR IS RESPONSIBLE FOR CONTACTING NORTH CAROLINA DIGSAFE PRIOR TO ANY FENCE POST
THE OPERATIONS OF THE FACILITY.
THROUGH THE COR, SO THAT WORK MAY BE SCHEDULED AS EFFICIENTLY AS POSSIBLE AND NOT DISRUPT
1) THE RWI RCAG SITE IS AN OPERATIONAL FACILITY. THE CONTRACTOR SHALL COORDINATE ALL WORK
NOTES:
209.10'
.5
206.47'
.0
GRAVEL
GRASS
0.9889 ACRES
43,077 SQ. FT.
RCAG SITE AREA
AVEL
VICINTY MAP
NOT TO SCALE
SITE PLAN
SCALE: 1"=20'C001
rwi-18064037-c001
2022-04-12T08:13:33-0400
HENRY B NEWCOMB
2022-04-12T07:39:34-0400
JOHN R WEST
FENCE DETAILS
RWI-18064037-C002
12" DIA.
6'
:4 lo tt e x xx x x x x x x xxxxxx
OUTSIDEINSIDE
C002
FENCE - SIDE VIEW
TOP WITH 45° ANGLE BEND
OUTRIGGER TYPE LINE POST
#6 GAUGE
TENSION WIRE,
HIGH CARBON
POST FOOTING
TYPICAL LINE
FINISH SURFACE
0.125" X 1 1/4"
BAND
BRACE & TRUSS
BRACE RAIL 1 5/8" PIPE
1/4" X 3/4" STRETCHER BAR
FABRIC TO FINISH SURFACE
1" MAX. FROM BOTTOM OF
POST FOOTING
TYPICAL END, CORNER, PULL
MIN 12"
6" ABOVE GRADE
BOLTED CONNECTION
TRUSS BAND
TERMINAL POST TOP
OUTRIGGER TYPE
12" DIA. MIN.16" DIA. MIN.
AT 15" O.C.
9 GAUGE TIE WIRES
COPPER BOND STRAP
FLEXIBLE TINNED
1" X 1/8"
CONNECTION
WELD
EXOTHERMIC
12"
#6 GAUGE
TENSION WIRE,
HIGH CARBON
OF TOP AND BOTTOM
AT 14" O.C. MAX. AND WITHIN 4"
1/8" X 1" STRETCHER BAR BAND
STRAIGHT CUP
RAIL END
CONDUCTOR
#4/0 BARE GROUND
(TYP)
2' BELOW GRADE
TOP OF CONCRETE
(2 7/8" DIA.)
LINE POST
(4" DIA.)
END,PULL POST
TIGHTENERS & FITTINGS
WITH ADJUSTABLE
3/8" DIA. ROD BRACE
THAN 100' APART
CORNERS AND NOT MORE
EACH GATE OR GATE LEAF
CLAD GROUND ROD (TYP)
3/4"X10' LONG COPPER
(4" DIA.)
CORNER POST
10'- 0"
(TYP.)
10'- 0"
(TYP.)
NOTE 8
SEE
HEIGHT
FENCE
9'-0"
POST
LINE
PIECE)
(ONE
HEIGHT
FABRIC
8'-0"
SPACED NOT MORE THAN 4" APART
4 POINT ALUMINUM BARBS
DOUBLE STRAND, WITH 14 GAUGE
3 STRANDS BARBED WIRE, 12 GAGE
TIE WIRES AT 15" O.C.
WITH 9 GAUGE GALVANIZED
FABRIC FASTENED TO RAIL
TWISTED AND BARBED FINISH
TOP AND BOTTOM SELVAGE HAS
FABRIC #9 WIRE- 2" MESH
4" OD END POSTS
3'-6" MIN.
P.C. CONC.GRASS SURFACE
STEEL PIPE
1" ID
SAND/GRAVEL
(INDUSTRY STANDARD)
1/2" DIA. DROP ROD
P.C. CONC.
OF POSTS
OUTSIDE
FABRIC ON
CLEARANCE
MAX. 1"
STONE
CRUSHED
WIRE ARM
BARBED
14" O.C. MAX.
FABRIC CLIPS
RAIL AS SPECIFIED (TYP)
TOP TENSION WIRE OR
WIRE (TYP.)
3 STRANDS OF BARBED
SPECIFIED (TYP)
WIRE OR RAIL AS
BOTTOM TENSION
HINGES (TYP)
BRACE RAIL (TYP)
FABRIC
CHAIN-LINK
WIRE (TYP.)
3 STRANDS OF BARBED
DROP ROD
GATE FRAME
ASSEMBLY
LATCH
16" DIA. MIN.
RODS (TYP)
3/8" DIA. TRUSS
OUTWARD
45°
1. ARM 18" LONG
2. BARBED WIRE SPACED 6" APART
BARBED WIRE ARM
DIAMETER
(INCHES)
1 5/8" (SCH.40)
2 1/2" (SCH.40)
3" (SCH.40)
4" (SCH.40)
OUTSIDE
DIMENSIONS
1.660
2.375
2.875
4.000
WALL
THICKNESS
.140
.154
.203
.226
WEIGHT
PER FOOT
(POUNDS)
2.27
3.65
5.79
9.11
SECTION
MODULUS
(CU.INCHES)
.235
.561
1.06
2.39
MIN. YIELD
STRESS
(PSI)
30,000
MIN. TENSILE
STRESS
(PSI)
48,000
POSTS PHYSICAL PROPERTIES
ACCORDANCE WITH ASTM-F1083 (FORMERLY ASTM-120).
1. ALL POSTS CONFORM TO ASTM A53 GRADE A AND GALVANIZED WITH 2.0 OUNCES OF HOT DIPPED ZINC IN
STANDARD
TRUSS ROD (TYP)
BRACE RAIL (TYP)
GRADE LINE
CONTENT.
COLD GALVANZING COMPOUND OR EQUAL. MINIMUM 95% METALLIC ZINC
9. CONTRACTOR SHALL REPAIR ANY DAMAGED GALVANIZED SURFACES WITH ZRC
OF FENCING OR GATES. ALL FABRIC TIES ARE DOUBLE WRAPPED.
TO ALLOW PROPER OPERATION OF COMPONENTS, BUT PREVENT DISASSEMBLY
8. CONTRACTOR SHALL PEEN THREADS ON ALL HARDWARE IN SUCH A MANNER
7. TOP OF 3/4" X 10' COPPER CLAD GROUND RODS ARE 1 FOOT BELOW GRADE.
6. ALL CONCRETE FOUNDATIONS ARE FORMED FULL DEPTH.
CLASS 2 (2.0 OZ. PER SQUARE FOOT OF SURFACE AREA).
5. FENCE FABRIC HEIGHT IS 96" AND GALVANIZED CONFORMING TO ASTM A392,
4" SLUMP AND 3/4" MAXIMUM SIZE AGGREGATE.
4. ALL CONCRETE COMPRESSIVE STRENGTHS ARE 4000 PSI AT 28 DAYS WITH
THE POSTS SHOWN. ALL HOLLOW POSTS ARE CAPPED.
CAPABLE OF WITHSTANDING 110 MPH WIND LOADS MAY BE SUBSTITUTED FOR
3. ROLLED OR EXTRUDED SECTIONS OR TUBING OF STEEL OR ALUMINUM
THE FENCING.
2. ALL POSTS AND STRUCTURAL SUPPORTS ARE LOCATED ON INNER SIDE OF
1. ALL FERROUS METAL IS HOT DIPPED GALVANIZED PER ASTM A-153.
16" DIA. MIN.
LATCH ASSEMBLY
DROP ROD FOUNDATION
DROP ROD ASSEMBLY
DOUBLE SWING GATE
rwi-18064037-c002
2022-04-12T08:14:12-0400
HENRY B NEWCOMB
2022-04-12T07:39:41-0400
JOHN R WEST
GROUNDING LAYOUT
RWI-18064037-E001
-e
SEE NOTE 5
SEE NOTE 2 AND DETAIL 3/E002.
TYPICAL FENCE POST GROUND.
SEE NOTE 3
lo tt e
7. SPECIFIES LOCATION TO BOND ACROSS BARB WIRE.
6. SPECIFIES LOCATION OF A GROUND ROD.
QUALITY #6 IN SERIES.
5. WHERE BARB WIRE TERMINATES AT CORNERS AND GATES, BOND ACROSS TERMINATION WITH SAME
AND OTHER APPLICABLE SECTIONS IN 19F.
4. CONTRACTOR SHALL GROUND AND BOND FENCE IN ACCORDANCE WITH 19F 5.3.8.1 FENCE GROUNDING, AND 19F 5.3.8.2.
3. GROUND FENCE POSTS AT EACH SIDE OF OVERHEAD POWER IN ACCORDANCE WITH DETAIL 4/E002
2. GROUND RODS AT EACH CORNER OF FENCE LINE AND AT MAXIMUM 100' SPACING.
LAYOUT AND REVIEW WITH COR AND 19F LIGHTNING PROTECTION GROUNDING STANDARD.
1. LOCATIONS OF GROUNDING SHOWN ON E001 IS APPROXIMATE. CONTRACTOR SHALL VERIFY FIELD
GROUNDING LAYOUT1
E001 NOT TO SCALE
rwi-18064037-e001
2022-04-12T08:14:55-0400
HENRY B NEWCOMB
2022-04-12T07:39:49-0400
JOHN R WEST
GROUNDING DETAILS
RWI-18064037-E002
SEE NOTE 4
EXOTHERMIC WELD (TYP)
BOLT CONNECTOR OR EQUAL.
WITH BURNDY KSU TYPE SPLIT
BOND BARB WIRE TO CONDUCTOR
2'.
TO FENCE FABRIC EVERY
CONDUCTOR SECURED
BARE COPPER
#6 AWG TINNED
SIDES OF FENCE
AT BOTH
1.5/2-3.5/32WC24
JUMPER FGA
PREFAB GATE
NEW HARGER
:0 lo tt e
14'-0"
(INTERWOVEN)
#6 GAUGE WIRE 1
HORIZONTAL BRACE
GATE FRAME GATE FRAME
BOTTOM
WIRE
GATE FRAME
BOTH SIDES OF FENCE
1.5/2-3.5/32WC24 AT
GATE JUMPER FGA
NEW HARGER PREFAB
#4/0 BC
SHEET)
(SEE DETAIL 2, THIS
#4/0 BARE COPPER
TO EES.
FROM FENCE POST
WELD BARE 4/0
EXOTHERMICALLY
BOTTOM
WIRE
Y
1'-6" O
SONOTUBE
AT GATE POSTS
CONNECTOR OR EQUAL.
BURNDY KSU TYPE SPLIT BOLT
WIRE TO CONDUCTOR WITH
(SEE 19F 5.3.8.1(F). BOND
TINNED COPPER CONDUCTOR
#6 AWG BARE STRANDED
GRADE
TO POST DIAMETER
HARGER CPC SIZED
BONDING CLAMP
(AT EACH GROUND ROD)
WELDS AT EACH END
CONDUCTOR WITH EXOTHERMIC
4/0 AWG STRANDED COPPER
100FT)
INTERVALS NO GREATER THAN
CORNERS, GATES AND
STEEL GROUND ROD (AT
10' X 3/4" COPPER CLAD
(AT EACH GROUND ROD)
WELDS AT EACH END
CONDUCTOR WITH EXOTHERMIC
4/0 AWG STRANDED COPPER
THAN 100FT)
INTERVALS NO GREATER
CORNERS, GATES AND
STEEL GROUND ROD (AT
10' X 3/4" COPPER CLAD
GRADE
CONNECTION, TYPE XA/XB
EXOTHERMIC WELD
TYPE GY
CONNECTION,
EXOTHERMIC WELD
TENSION WIRE
WELDED GATE POST
EXOTHERMICALLY
CONDUCTOR
4/0 AWG GROUND
(SIM.)
SINGLE GATE
DOUBLE GATE
COPPER
#4/0 BARE
GROUND ROD
3/4" X 10' LBRACE
HORIZONTAL
SEE NOTE 4
2 GATE GROUNDING PLAN
E002 NOT TO SCALE
E002
GROUNDING DETAIL
FENCE POST OVERHEAD POWER
1 DOUBLE GATE DETAIL
6 GROUND CONDUCTOR DETAIL @ GATE
4) BOND BARB WIRE AT FENCE END ADJACENT TO GATE AS SHOWN IN DETAIL 3.
SET OF BONDED BARB WIRE IN SERIES USING #6 TINNED STRANDED CONDUCTOR.
3) BOND ACROSS TERMINATION POINTS OF BARB WIRE AT CORNERS. CONNECT
FRAME VIA HARGER CPC BONDING CLAMPS.
CONTINUOUSLY THOUGH GATE FABRIC AND MECHANICALLY BONDED TO GATE
2) INSTALL HORIZONTAL #6 AWG BARE STRANDED TINNED COPPER THREADED
1) SEE SHEET E001 FOR GROUNDING LAYOUT.
IN DETAIL 3
SERIES AS SHOWN
BOND BARB WIRE IN
5 GROUND ROD DETAIL
E002 NOT TO SCALEE002
FENCE POST GROUNDING DETAIL
SEE NOTE 2
rwi-18064037-e002
2022-04-12T08:15:31-0400
HENRY B NEWCOMB
2022-04-12T07:39:54-0400
JOHN R WEST