This is Addendum No. 1 to bid solicitation DRM 2024-57 #8 issued by the Massachusetts Executive Office of Public Safety and Security, Department of Correction, Division of Resource Management for an Emergency Notification System at MCI Framingham in Framingham, MA. The addendum modifies the specifications with four items: 1) The contractor must install communication cable between the alert beacon and LED marquee in rigid conduit to prevent tampering, 2) One CAT6 cable must be run to rapid response console locations and terminated on a red colored jack using a single gang bell box with security bit screws, 3) The contractor must incorporate work related to specification section 02 80 00, and 4) The contractor must follow recommendations from the attached asbestos and RCRA-8 paint survey report dated January 30, 2025.

The addendum includes detailed information about asbestos-containing materials (ACMs) and RCRA-8 metals found in paint throughout the facility, based on testing performed by Arcadis U.S. Inc. The survey identified ACMs in floor tiles and associated mastics in various buildings, with chrysotile content ranging from <1% to 3%. RCRA-8 metals testing of paint samples revealed detectable levels of various metals including lead, chromium, cadmium and others, requiring specific handling and disposal procedures as outlined in specification section 02 80 00. The report includes detailed requirements for worker protection, containment controls, work procedures, air sampling, clean-up and waste disposal.

View the file

Other files

File Type Posted
Bid Intent Form~28.doc DOC document
Bidder Checklist~64.doc DOC document
Prevailing Wage Payroll Report Form~74.pdf PDF
Updated Plan Holders List~4.docx DOCX document
Prevailing Wage Statement of Compliance~73.pdf PDF
SDP plan form 3 - reporting~46.xlsx XLSX spreadsheet
Bid Results~62.doc DOC document
Bid Package~2.pdf PDF
Where to get plans and specs~50.docx DOCX document
Site Visit Sign in Framingham.pdf PDF
Prevailing Wages~32.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRM 2024-57 #8

Addendum No. 1

COMMONWEALTH OF MASSACHUSETTS

EXECUTIVE OFFICE OF PUBLIC SAFETY AND

SECURITY

DEPARTMENT OF CORRECTION

DIVISION OF RESOURCE MANAGEMENT

DRM 2024-57 #8

Emergency Notification System MCI Framingham

Framingham, MA

January 31, 2025

ADDENDUM No. 1

The attention of bidders submitting proposals for the subject project at MCI

Framingham, located in Framingham, MA, is called to the following addendum to the Specifications and or Drawings. The items set forth herein, whether of omission, addition, substitution, or clarification are all to be included in and form a part of the proposal submitted.

A: SCOPE MODIFICATION AND ADDITIONAL CLARIFICATION

ITEM NO. DESCRIPTION

Item #1. Attention is directed to Appendix D, LED Marquee Installation Guide. In

Section 4.4, with regard to the communication cable between the alert beacon and the LED marquee, the contractor shall be responsible for installing the cable between these two devices.

This cable shall be installed in rigid conduit to prevent tampering. The contractor is responsible for installing the rigid conduit per the specifications.

Item #2. At the rapid response console locations, the contractor shall homerun one (1)

CAT6 cable to these locations. The contractor shall terminate these cables on a red colored jack, using a single gang bell box that is 2 5/8” deep with a stainless-steel dual port faceplate fastened with security bit screws.

Item #3. The contractor shall incorporate all work related to the attached specification section 02 80 00 into their scope of work.

Item #4. The contractor shall incorporate attached Path of Construction Asbestos and

RCRA-8 Paint Survey Report for MCI Framingham prepared by Arcadis U.S., Inc. dated January

30th, 2025. The contractor shall follow all recommendations contained in the above-mentioned report and all applicable OSHA Safety and Health Regulations.

Arcadis U.S., Inc.

One Federal Street

Suite 3800

Boston, Massachusetts 02110 www.arcadis.com

Page:

1/5

Mr. Steve Lemmo

Massachusetts Department of Correction

Division of Resource Management

50 Maple Street Milford, Massachusetts 01757

Subject:

Path of Construction Asbestos and RCRA-8 Paint Survey Report

Emergency Notification System Project

MCI Framingham

99 Loring Drive

Framingham, Massachusetts 01701

Dear Mr. Lemmo:

Arcadis U.S., Inc. (Arcadis) conducted a path of construction (POC) Asbestos and

Resource Conservation and Recovery Act (RCRA) 8 metals in paint survey at MCI

Framingham located at 99 Loring Drive in Framingham, Massachusetts (site).

The survey included an inspection of the following areas:

Old Administration Building

Townline Building

Laurel Building

HSU Building

Smith Building

The objective of the survey was to ascertain the general presence and location of asbestos-containing materials (ACMs) and RCRA-8 metals in paint that may be impacted during the planned Emergency Notification System installation project.

On January 22, 2025, Mr. Brandon Wabble with Arcadis visited the site to conduct the survey. A copy of his asbestos accreditations is provided in Attachment A.

ENVIRONMENT

Date:

January 30, 2025

Contact:

Gregory Donovan

Phone:

617.778.8212

Email:

greg.donovan@arcadis.com

Our ref:

30263340 arcadis.com

Mr. Steve Lemmo

January 30, 2025

Page:

2/5

Asbestos-Containing Materials Survey

Asbestos Survey Methodology

Arcadis conducted the path of construction asbestos survey for compliance with the United States

Environmental Protection Agency (USEPA) National Emissions Standards for Hazardous Air Pollutants

(NESHAPs), Occupational Safety and Health Administration (OSHA) Asbestos in General Industry

Standard (29 CFR 1910.1001), OSHA Asbestos in Construction Standard Title 29 CFR Part 1926.1101, the Massachusetts Department of Environmental Protection 310 CMR 7.15, and the Massachusetts

Department of Labor Standards 454 CMR 28.00.

This was accomplished by initially conducting a visual inspection of the planned path of construction areas then collecting samples of suspect ACM based on these observations. Arcadis conducted the asbestos survey in general accordance with ASTM International (ASTM) E2356 Standard Practice for

Comprehensive Building Asbestos Surveys. ASTM E2356 meets the applicable requirements of current

USEPA NESHAP Standard 40 Code of Federal Regulations (CFR) 61, Subpart M (Asbestos), USEPA

Asbestos Hazard Emergency Response Act (AHERA) 40 CFR 763, Subpart E, and Occupational Safety and Health Administration (OSHA) asbestos survey and/or sampling regulations.

The survey included an inspection of the areas within the POC providing a general sense of the overall location, type, quantity, and condition of suspect ACMs present. It was thorough in that most accessible functional spaces were inspected, and bulk samples taken of suspect materials observed.

Suspect materials were divided into "Homogeneous Areas" (HAs) (i.e., building materials that were determined by the inspector to be homogeneous based on their color, texture, and assumed date of installation). A representative number of samples were collected from each HA.

Bulk material samples were collected and assigned their own unique identification number, placed in 4-mil plastic bags, and tightly sealed for transport under a chain-of-custody protocol to EMSL Analytical, Inc. in

Indianapolis, Indiana.

Asbestos Analytical Methodology

Bulk samples were analyzed for asbestos (reported in percent of type of asbestos) using Polarized Light

Microscopy with Dispersion Staining (PLM/DS) in accordance with the USEPA Method 600/R-93/116.

Percentage estimates of each material's composition are based on the analyst's best visual judgment following PLM/DS analysis, and examination with a stereoscope.

EMSL is a member of the American Industrial Hygiene Association (AIHA), National Voluntary Laboratory

Accreditation Program (NVLAP). The laboratory analytical reports are provided as Attachment B.

January 30, 2025

Page:

3/5

Resource Conservation and Recovery Act 8 Paint Survey

RCRA-8 Metals Survey Methodology

Arcadis conducted a path of construction RCRA-8 metal in paint survey for compliance with USEPA RCRA

(Standard 40 CFR 240-280) and OSHA Safety and Health Regulations for Construction (Standard 29 CFR

1926).

Suspect RCRA-8 metal-containing paint was identified based upon a visual inspection of painted building components in the path of construction then collecting paint chip samples based on these observations.

Paint chip samples were collected and assigned their own unique identification number, placed in 4-mil plastic bags, and tightly sealed for transport under a chain-of-custody protocol to EMSL in Indianapolis, Indiana.

RCRA-8 Metals Analytical Methodology

Paint chip samples were analyzed for total metal content (reported in milligrams per kilogram [mg/Kg]) by

Inductively Coupled Plasma (ICP) Atomic Emission Spectrometry in accordance with USEPA Method

SW-846 3050B/6010D, and Mercury by Cold Vapor Atomic Absorption (CVAA) SW-846 7471B. EMSL conformed to QA/QC procedures established by their accreditation manual. The laboratory analytical reports are provided in Attachment C.

SURVEY FINDINGS

Asbestos

Arcadis identified thirty (30) HAs, of which, sixty-five (65) suspect ACM bulk samples were collected and submitted for laboratory analysis. Details regarding the material description, material location, condition, friability, asbestos content, and estimated quantity of each HA identified during the POC asbestos survey is presented in the Homogeneous Areas Summary Table provided in Table 1. Approximate sampling locations are shown on the Figures.

Massachusetts Department of Environmental Protection defines ACM as a material containing more than or equal to 1% asbestos by weight. The following HAs are confirmed ACM:

Old Administration Building

HA-12: 9” Beige with Black Streaks Floor Tile

HSU Building

HA-21: 9” Light and Dark Brown Patterned Floor Tile

HA-23: 9” Tan and Brown Floor Tile

The following HA has been determined to contain trace amounts of asbestos, i.e. one percent or less (1% or <1%) by laboratory analysis and their disturbance is regulated by OSHA:

HSU Building

HA-22: Black Mastic Associated with HA-21

January 30, 2025

Page:

4/5

The remaining bulk samples collected by Arcadis as part of the survey were reported by the laboratory as

“None Detected” for asbestos.

RCRA-8 Metals

Eight (8) composite RCRA-8 metals in paint chip samples were collected and submitted for laboratory analysis. Detectable concentrations of RCRA-8 metals were identified in the following paint chips collected:

RCRA-1: White/Beige/Blue Paint on Brick Walls in Old Administration Building

RCRA-2: White Paint on Gypsum Board Walls in Old Administration Building

RCRA-3: White Paint on Gypsum Board Walls in Old Administration Building

RCRA-4: Gray Paint on Brick Walls in Old Administration Building

RCRA-5: White Paint on Metal Ceiling in Townline Building

RCRA-6: Blue/White Paint on Concrete Walls in Laurel Building

RCRA-7: Gray/White Paint on Plaster Wall in Smith Building

RCRA-8: Gray/White Paint on Plaster Wall in Old Administration Building

Details regarding the sample description, sample location, analyte, and results are presented in the RCRA-8 Metals in Paint Summary provided in Table 2. Approximate sampling locations are shown on the Figures.

RECOMMENDATIONS

Asbestos-Containing Materials

As presented in Table 1, and the laboratory data provided in Attachment B, results of the asbestos survey identified confirmed ACMs at the site.

ACMs identified at the site that may be disturbed during construction activities, must be removed by a licensed asbestos abatement contractor utilizing industry standard work procedures in accordance with all federal, state, and local regulations governing asbestos.

If other suspect materials, not referenced in this survey report, are identified during construction activities, Arcadis recommends that these materials be considered ACM until they are inspected by an appropriately licensed asbestos inspector and proven otherwise.

Asbestos waste must be disposed at an asbestos waste receiving facility that is duly permitted by the state and/or local municipality in which it resides.

RCRA-8 Metals

As presented in Table 2, and the laboratory data provided in Attachment C, the results of the RCRA-8 metals in paint survey identified detectable concentrations of RCRA-8 metals in samples collected.

Arcadis recommends that the general contractor and any sub-trades be advised of the presence of

RCRA-8 metals in the paint and the requirements for compliance with RCRA Standards (Title 40 CFR 240-

280) and OSHA Safety and Health Regulations for Construction (Standard 29 CFR 1926). Compliance with OSHA is required for any detectable levels of metals in paint that may potentially be disturbed.

January 30, 2025

Page:

5/5

Any work that could disturb known or suspect RCRA-8 metal-containing paint should be conducted in a way to minimize and control dust, and the contractor should perform a thorough cleanup.

If other suspect paints, not referenced in this survey report, are identified during renovation or demolition activities, Arcadis recommends that these materials be managed as RCRA-8 metal-containing paint until they are sampled and proven otherwise.

Arcadis recommends that construction waste streams containing paint generated during the planned construction activities be tested via Toxicity Characteristic Leaching Procedure for waste disposal characterization prior to disposal.

CLOSING

Thank you for your time and consideration on this project. Please do not hesitate to call if you have questions regarding the results of this POC survey or if you require additional information.

Sincerely, Arcadis U.S., Inc.

Gregory Donovan

Certified Project Manager

TABLES

Table 1 Homogeneous Areas Summary

Table 2 RCRA-8 Metals in Paint Summary

FIGURES

A-01 HSU 1st Foor Sample Locations

A-02 HSU 2nd Floor Sample Locations

A-03 Laurel and Towline Sample Locations

A-04 Smith Building 1st Foor Sample Locations

A-05 Smith Building 2nd Foor Sample Locations

A-07 Old Administration Building 1st Floor Sample Locations

A-08 Old Administration Building 2nd Floor Sampe Locations

ATTACHMENTS

A Asbestos Accreditations

B Laboratory Analytical Report – Asbestos

C Laboratory Analytical Report – RCRA-8 Metals

January 30, 2025

Page:

6/5

TABLES

Table 1

Homogeneous Areas Summary

Emergency Notification System Project

MCI Framingham

99 Loring Drive

Framingham, Massachusetts 01757

HA No. Building Material Description Material Location Sample Number Condition Friability Asbestos

Content Notes

Old Administration

Building Gray Brick Mortar Floors 1-3 Throughout 1A, 1B Good Non-Friable NAD

Old Administration

Building Gypsum Board 3rd Floor Industries 2A, 2B Good Non-Friable NAD

Old Administration

Building

12" White with Black Streaks

Floor Tile 3rd Floor Industries 3A, 3B Good Non-Friable NAD

Old Administration

Building

Beige Mastic Associated with HA-

3rd Floor Industries 4A, 4B Good Non-Friable NAD

Old Administration

Building White Plaster Wall Skim Coat 3rd Floor Library 5A, 5B, 5C Good Non-Friable NAD

Old Administration

Building Gray Plaster Wall Base Coat 3rd Floor Library 6A, 6B, 6C Good Non-Friable NAD

Old Administration

Building White Gypsum Board 3rd Floor College Classroom 7A, 7B Good Friable NAD

Old Administration

Building 12" Beige Patterned Floor Tile 3rd Floor College Classroom 8A, 8B Good Non-Friable NAD

Old Administration

Building

Beige/Brown Mastic Associated with HA-8 3rd Floor College Classroom 9A, 9B Good Non-Friable NAD

Old Administration

Building White Plaster Wall Skim Coat 2nd Floor Cells 10A, 10B, 10C Good Non-Friable NAD

Old Administration

Building Gray Plaster Wall Base Coat 2nd Floor Cells 11A, 11B, 11C Good Non-Friable NAD

Emergency Notification System Project

MCI Framingham

99 Loring Drive

Framingham, Massachusetts 01757

HA No. Building Material Description Material Location Sample Number Condition Friability Asbestos

Content Notes

Old Administration

Building

9" Beige with Black Streaks

Floor Tile 2nd Floor CPO Hallway 12A, 12B Good Non-Friable 2% Chrysotile

Old Administration

Building

Black Mastic Associated with HA-

2nd Floor CPO Hallway 13A, 13B Good Non-Friable NAD

Old Administration

Building 12" Brown Speckled Floor Tile 2nd Floor Classroom 92 14A, 14B Good Non-Friable NAD

Old Administration

Building

Beige Mastic Associated with HA-

2nd Floor Classroom 92 15A, 15B Good Non-Friable NAD

Old Administration

Building Gray Plaster Wall Base Coat 1st Floor Classroom 16A, 16B, 16C Good Non-Friable NAD

Old Administration

Building

White Joint Compound

Associated with Gypsum Board 2nd Floor Copier Room 17A, 17B Good Friable NAD

18 Townline Building Gray Concrete Block Mortar Throughout 18A, 18B Good Non-Friable NAD

19 Laurel Building Gray Concrete Block Mortar Throughout 19A, 19B Good Non-Friable NAD

20 HSU Building Beige Fiber Reinforced Plastic

Panel Mastic 1st Floor Shower, Restrooms 20A, 20B Good Non-Friable NAD

21 HSU Building 9" Light and Dark Brown

Patterned Floor Tile 1st FloorThroughout 21A, 21B Good Non-Friable 3% Chrysotile

22 HSU Building Black Mastic Associated with

HA-21

1st Floor Throughout 22A, 22B Good Non-Friable <1% Chrysotile

Emergency Notification System Project

MCI Framingham

99 Loring Drive

Framingham, Massachusetts 01757

HA No. Building Material Description Material Location Sample Number Condition Friability Asbestos

Content Notes

23 HSU Building 9" Tan and Brown Floor Tile 2nd Floor Hallway 23A, 23B Good Non-Friable 3% Chrysotile

24 HSU Building Black Mastic Associated with HA-

2nd Floor Hallway 24A, 24B Good Non-Friable NAD

25 HSU Building Gray Concrete Block Mortar 1st Floor Hallway 25A, 25B Good Non-Friable NAD

26 Smith Building 12" Orange and White Patterned

Floor Tile 1st and 2nd Floor Hallways 26A, 26B Good Non-Friable NAD

27 Smith Building Black Mastic Associated with HA-

1st and 2nd Floor Hallways 27A, 27B Good Non-Friable NAD

28 Smith Building 1' x 1' Ceiling Tile 1st Floor Office 28A, 28B Good Friable NAD

29 Smith Building 2' x 2' Fissured Ceiling Tile 2nd Floor Gallery 29A, 29B Good Friable NAD

30 Smith Building Gypsum Ceiling 1st Floor Visitation 30A, 30B Good Friable NAD

NAD = No Asbestos Detected

Notes:

Table 2

RCRA-8 Metals in Paint Summary

Emergency Notification System Project

MCI Framingham

99 Loring Drive

Framingham, Massachusetts 01701

Sample ID Building Sample Description Sample Location Arsenic Barium Cadmium Chromium Lead Selenium Silver Units

RCRA-1

Old Administration

Building

White/Beige/Blue Paint on Brick Wall

3rd Floor Hallway, Industries 12 830 51 58 13000 <4.0 1.7 mg/Kg

RCRA-2

Old Administration

Building

White Paint on Gypsum

Board Wall 3rd Floor Industries <4.0 52 <0.80 2.3 23 <8.0 <0.80 mg/Kg

RCRA-3

Old Administration

Building

White Paint on Gypsum

Board Wall 2nd Floor Classroom <2.0 20 <0.40 4.1 20 <4.0 <0.40 mg/Kg

RCRA-4

Old Administration

Building

Gray Paint on Brick

Wall 2nd Floor Pool Room <2.0 510 <0.40 530 72000 <4.0 1.1 mg/Kg

RCRA-5 Townline Building White Paint on Metal

Ceiling

1st Floor Common

Area <4.0 <20 <0.81 2.2 7.8 <8.1 <0.81 mg/Kg

RCRA-6 Laurel Building Blue/White Paint on

Concrete Wall

1st Floor Common

Area <2.0 1100 0.45 2.3 24 <4.0 <0.40 mg/Kg

RCRA-7 Smith Building Gray/White Paint on

Plaster Wall 1st Floor Hallway <2.0 220 <0.40 5.6 4.0 <4.0 <0.40 mg/Kg

RCRA-8

Old Administration

Building

Gray/White Paint on

Plaster Wall Chapel <2.0 560 0.50 8.1 6800 <4.0 <0.40 mg/Kg

Acronyms and Abbreviations:

mg/Kg = milligram per kilogram

FIGURES

ATTACHMENT A

Asbestos Accreditations

Inspector Certifications

Inspector Brandon Wabble

Certification Asbestos Inspector

Certified By The Commonwealth of Massachusetts Department of Labor Standards

Certification Number AI000377

Expiration Date July 26, 2025

ATTACHMENT B

Laboratory Analytical Report – Asbestos

EMSL Analytical, Inc.

6340 CastlePlace Dr. Indianapolis, IN 46250

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162501105EMSL Order:

Customer ID: ACAD78AJ

Customer PO: 30263340

Project ID:

Attention: Phone:Greg Donovan (617) 778-8212

Fax:ARCADIS U.S., Inc.

Received Date:126 N Jefferson Street 01/24/2025 9:51 AM

Analysis Date:Suite 400 01/24/2025 - 01/25/2025

Collected Date:Milwaukee, WI 53202

Project: 30263340

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

1A

162501105-0001

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray Brick Mortar

HA: 1

1B

162501105-0002

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray Brick Mortar

HA: 1

2A

162501105-0003

None DetectedGypsum

Non-fibrous (Other)

90%

8%

Cellulose

Glass

2%

<1%

White

Non-Fibrous

Homogeneous

Gypsum Board

HA: 2

2B

162501105-0004

None DetectedGypsum

Non-fibrous (Other)

90%

8%

Cellulose

Glass

2%

<1%

White

Non-Fibrous

Homogeneous

Gypsum Board

HA: 2

3A

162501105-0005

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

12' White w/ Black

Streak Floor Tile

HA: 3

3B

162501105-0006

None DetectedNon-fibrous (Other)100%Gray/White

Non-Fibrous

Homogeneous

12' White w/ Black

Streak Floor Tile

HA: 3

4A

162501105-0007

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige Mastic

Associated w/ HA-3

HA: 4

4B

162501105-0008

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige Mastic

Associated w/ HA-3

HA: 4

5A

162501105-0009

None DetectedQuartz

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 5

5B

162501105-0010

None DetectedQuartz

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 5

5C

162501105-0011

None DetectedQuartz

Non-fibrous (Other)

20%

80%

White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 5

6A

162501105-0012

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 6

Initial report from: 01/27/2025 08:11:02

Page 1 of 5ASB_PLM_0008_0002 - 2.31 Printed: 1/27/2025 8:11 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162501105EMSL Order:

Customer ID: ACAD78AJ

Customer PO: 30263340

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

6B

162501105-0013

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 6

6C

162501105-0014

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 6

7A

162501105-0015

None DetectedGypsum

Non-fibrous (Other)

20%

5%

Cellulose75%Brown/White

Fibrous

Heterogeneous

White Gypsum Board

HA: 7

7B

162501105-0016

None DetectedGypsum

Non-fibrous (Other)

30%

5%

Cellulose65%Brown/White

Fibrous

Heterogeneous

White Gypsum Board

HA: 7

8A

162501105-0017

None DetectedNon-fibrous (Other)100%Beige

Non-Fibrous

Homogeneous

12' Beige Patterned

Floor Tile

HA: 8

8B

162501105-0018

None DetectedNon-fibrous (Other)100%Beige

Non-Fibrous

Homogeneous

12' Beige Patterned

Floor Tile

HA: 8

9A

162501105-0019

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige Brown Mastic

Associated w/HA-8

HA: 9

9B

162501105-0020

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige Brown Mastic

Associated w/HA-8

HA: 9

10A

162501105-0021

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 10

10B

162501105-0022

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 10

10C

162501105-0023

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Plaster Wall

Skim Coat

HA: 10

11A

162501105-0024

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 11

11B

162501105-0025

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 11

11C

162501105-0026

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 11

12A

162501105-0027

2% ChrysotileNon-fibrous (Other)98%Beige

Non-Fibrous

Homogeneous

9" Beige w/ Black

Streaks Floor Tile

Page 2 of 5ASB_PLM_0008_0002 - 2.31 Printed: 1/27/2025 8:11 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162501105EMSL Order:

Customer ID: ACAD78AJ

Customer PO: 30263340

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

HA: 12

12B

162501105-0028

Positive Stop (Not Analyzed)9" Beige w/ Black

Streaks Floor Tile

HA: 12

13A

162501105-0029

None DetectedNon-fibrous (Other)100%Tan/Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-12

HA: 13

13B

162501105-0030

None DetectedNon-fibrous (Other)100%Tan/Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-12

HA: 13

14A

162501105-0031

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

12" Brown Sparkled

Floor Tile

HA: 14

14B

162501105-0032

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

12" Brown Sparkled

Floor Tile

HA: 14

15A

162501105-0033

None DetectedQuartz

Non-fibrous (Other)

10%

90%

Tan/Black

Non-Fibrous

Homogeneous

Beige Mastic

Associated w/ HA-14

HA: 15

15B

162501105-0034

None DetectedQuartz

Non-fibrous (Other)

10%

90%

Tan/Black

Non-Fibrous

Homogeneous

Beige Mastic

Associated w/ HA-14

HA: 15

16A

162501105-0035

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray/White

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 16

16B

162501105-0036

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray/White

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 16

16C

162501105-0037

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Hair<1%Gray/White

Non-Fibrous

Homogeneous

Gray Plaster Wall

Base Coat

HA: 16

17A

162501105-0038

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Joint

Compound

Associated w/

Gypsum Board

HA: 17

17B

162501105-0039

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

White Joint

Compound

Associated w/

Gypsum Board

HA: 17

18A

162501105-0040

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray CMU Mortar

HA: 18

18B

162501105-0041

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray CMU Mortar

HA: 18

Page 3 of 5ASB_PLM_0008_0002 - 2.31 Printed: 1/27/2025 8:11 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162501105EMSL Order:

Customer ID: ACAD78AJ

Customer PO: 30263340

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

19A

162501105-0042

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray CMU Mortar

HA: 19

19B

162501105-0043

None DetectedQuartz

Non-fibrous (Other)

20%

80%

Gray

Non-Fibrous

Homogeneous

Gray CMU Mortar

HA: 19

20A

162501105-0044

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige FRP Mastic

HA: 20

20B

162501105-0045

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Beige FRP Mastic

HA: 20

21A

162501105-0046

3% ChrysotileNon-fibrous (Other)97%Brown

Non-Fibrous

Homogeneous

9' Light & Dark Brown

Patterned Floor Tile

HA: 21

21B

162501105-0047

Positive Stop (Not Analyzed)9' Light & Dark Brown

Patterned Floor Tile

HA: 21

22A

162501105-0048

<1% ChrysotileNon-fibrous (Other)100%Gray/Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-21

Result includes a small amount of inseparable attached material

HA: 22

22B

162501105-0049

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-21

HA: 22

23A

162501105-0050

3% ChrysotileNon-fibrous (Other)97%Brown

Non-Fibrous

Homogeneous

9" Tan & Brown

Patterned Floor Tile

HA: 23

23B

162501105-0051

Positive Stop (Not Analyzed)9" Tan & Brown

Patterned Floor Tile

HA: 23

24A

162501105-0052

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-23

HA: 24

24B

162501105-0053

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-23

HA: 24

25A

162501105-0054

None DetectedQuartz

Non-fibrous (Other)

15%

85%

Gray

Non-Fibrous

Homogeneous

Gray CMU Mortar

HA: 25

25B

162501105-0055

None DetectedQuartz

Non-fibrous (Other)

15%

85%

Gray

Fibrous

Homogeneous

Gray CMU Mortar

HA: 25

Page 4 of 5ASB_PLM_0008_0002 - 2.31 Printed: 1/27/2025 8:11 AM

Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com

162501105EMSL Order:

Customer ID: ACAD78AJ

Customer PO: 30263340

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

26A

162501105-0056

None DetectedNon-fibrous (Other)100%Pink

Non-Fibrous

Homogeneous

12" Orange & White

Patterned Floor Tile

HA: 26

26B

162501105-0057

None DetectedNon-fibrous (Other)100%Pink

Non-Fibrous

Homogeneous

12" Orange & White

Patterned Floor Tile

HA: 26

27A

162501105-0058

None DetectedNon-fibrous (Other)95%Cellulose5%Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-26

HA: 27

27B

162501105-0059

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Black Mastic

Associated w/ HA-26

HA: 27

28A

162501105-0060

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

50%

30%

Gray/White

Fibrous

Homogeneous

1x1 Ceiling Tile

HA: 28

28B

162501105-0061

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

50%

30%

Gray/White

Fibrous

Homogeneous

1x1 Ceiling Tile

HA: 28

29A

162501105-0062

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

60%

20%

Gray/White

Fibrous

Homogeneous

2x2 Fissured Ceiling

Tile

HA: 29

29B

162501105-0063

None DetectedPerlite

Non-fibrous (Other)

15%

5%

Cellulose

Min. Wool

60%

20%

Gray/White

Fibrous

Homogeneous

2x2 Fissured Ceiling

Tile

HA: 29

30A

162501105-0064

None DetectedGypsum

Non-fibrous (Other)

85%

5%

Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Gypsum Ceiling

HA: 30

30B

162501105-0065

None DetectedGypsum

Non-fibrous (Other)

35%

5%

Cellulose

Glass

60%

<1%

Brown/White

Fibrous

Heterogeneous

Gypsum Ceiling

HA: 30

Analyst(s)

Paul Rihm (62) Asbestos Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0, AZ0939, CA 2575, CO AL-15132, TX 300262, A2LA Accredited - Certificate #2845.25

Page 5 of 5ASB_PLM_0008_0002 - 2.31 Printed: 1/27/2025 8:11 AM

OrderID: 162501105

O r d e r I D

P a g e f d e r I D

P a g e d e r I D

P a g e d e r I D

P a g e d e r I D

P a g e d e r I D

P a g e d e r I D

P a g e d e r I D

P a g e

ATTACHMENT C

Laboratory Analytical Report – RCRA-8 Metals

Project Name:

Customer PO:

EMSL Sales Rep:

Reported:

ARCADIS U.S., Inc. [ACAD78J]

25 Braintree Hill Office Park, Suite 200

Braintree, MA 02184

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

Greg DonovanAttention:

(617) 778-8212 greg.donovan@arcadis.com

30265332 TASK NO., 01

Received: 01/24/2025 12:47

01/29/2025 18:01

Christopher Brandt

EMSL Order ID: 162551033

LIMS Reference ID: CD51033

EMSL Customer ID: ACAD78J

MA DOC- FRAMING HIM, MA

Analytical Results

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g) Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: RCRA-1/WHITE/BEIGE/BLUE, BRICK, WALL Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-01

1Arsenic M101/29/25 JW 01/29/25 JW12 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5035

1Barium M101/29/25 JW 01/29/25 JW830 mg/kg 9.9 mg/kg SW846 3050B SW-846 6010D0.5035

1Cadmium M101/29/25 JW 01/29/25 JW51 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5035

1Chromium M101/29/25 JW 01/29/25 JW58 mg/kg 0.99 mg/kg SW846 3050B SW-846 6010D0.5035

25Lead M101/29/25 JW 01/29/25 JW13000 mg/kg 50 mg/kg SW846 3050B SW-846 6010D0.5035

1Selenium M101/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5035

1Silver 01/29/25 JW 01/29/25 JW1.7 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5035

Sample Comments:

Client Sample ID: RCRA-2/WHITE/GYPSUM BOARD, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-02

1Arsenic 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.25

1Barium 01/29/25 JW 01/29/25 JW52 mg/kg 20 mg/kg SW846 3050B SW-846 6010D0.25

1Cadmium 01/29/25 JW 01/29/25 JW<0.80 mg/kg 0.80 mg/kg SW846 3050B SW-846 6010D0.25

1Chromium 01/29/25 JW 01/29/25 JW2.3 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.25

1Lead 01/29/25 JW 01/29/25 JW23 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.25

1Selenium 01/29/25 JW 01/29/25 JW<8.0 mg/kg 8.0 mg/kg SW846 3050B SW-846 6010D0.25

1Silver 01/29/25 JW 01/29/25 JW<0.80 mg/kg 0.80 mg/kg SW846 3050B SW-846 6010D0.25

Sample Comments:

Client Sample ID: RCRA-3/WHITE/GYPSUM BOARD, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-03

1Arsenic 01/29/25 JW 01/29/25 JW<2.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5063

1Barium 01/29/25 JW 01/29/25 JW20 mg/kg 9.9 mg/kg SW846 3050B SW-846 6010D0.5063

1Cadmium 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5063

1Chromium 01/29/25 JW 01/29/25 JW4.1 mg/kg 0.99 mg/kg SW846 3050B SW-846 6010D0.5063

1Lead 01/29/25 JW 01/29/25 JW20 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5063

1Selenium 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5063

1Silver 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5063

Sample Comments:

Client Sample ID: RCRA-4/GRAY, BRICK, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-04

1Arsenic 01/29/25 JW 01/29/25 JW<2.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5

1Barium 01/29/25 JW 01/29/25 JW510 mg/kg 10 mg/kg SW846 3050B SW-846 6010D0.5

1Cadmium 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5

125Chromium 01/29/25 JW 01/29/25 JW530 mg/kg 120 mg/kg SW846 3050B SW-846 6010D0.5

125Lead 01/29/25 JW 01/29/25 JW72000 mg/kg 250 mg/kg SW846 3050B SW-846 6010D0.5

1Selenium 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5

1Silver 01/29/25 JW 01/29/25 JW1.1 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5

Sample Comments:

[TOC_1]Sample Results[TOC]

EMSL Sales Rep:

Reported:

ARCADIS U.S., Inc. [ACAD78J]

25 Braintree Hill Office Park, Suite 200

Braintree, MA 02184

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

Greg DonovanAttention:

(617) 778-8212 greg.donovan@arcadis.com

30265332 TASK NO., 01

Received: 01/24/2025 12:47

01/29/2025 18:01

Christopher Brandt

EMSL Order ID: 162551033

LIMS Reference ID: CD51033

EMSL Customer ID: ACAD78J

MA DOC- FRAMING HIM, MA

Analytical Results

(Continued)

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g) Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: RCRA-5/WHITE, METAL, CEILING, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-05

1Arsenic 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.2472

1Barium 01/29/25 JW 01/29/25 JW<20 mg/kg 20 mg/kg SW846 3050B SW-846 6010D0.2472

1Cadmium 01/29/25 JW 01/29/25 JW<0.81 mg/kg 0.81 mg/kg SW846 3050B SW-846 6010D0.2472

1Chromium 01/29/25 JW 01/29/25 JW2.2 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.2472

1Lead 01/29/25 JW 01/29/25 JW7.8 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.2472

1Selenium 01/29/25 JW 01/29/25 JW<8.1 mg/kg 8.1 mg/kg SW846 3050B SW-846 6010D0.2472

1Silver 01/29/25 JW 01/29/25 JW<0.81 mg/kg 0.81 mg/kg SW846 3050B SW-846 6010D0.2472

Sample Comments:

Client Sample ID: RCRA-6/BLUE/WHITE, CONCRETE, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-06

1Arsenic 01/29/25 JW 01/29/25 JW<2.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5038

1Barium 01/29/25 JW 01/29/25 JW1100 mg/kg 9.9 mg/kg SW846 3050B SW-846 6010D0.5038

1Cadmium 01/29/25 JW 01/29/25 JW0.45 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5038

1Chromium 01/29/25 JW 01/29/25 JW2.3 mg/kg 0.99 mg/kg SW846 3050B SW-846 6010D0.5038

1Lead 01/29/25 JW 01/29/25 JW24 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5038

1Selenium 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5038

1Silver 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5038

Sample Comments:

Client Sample ID: RCRA-7/GRAY/WHITE, PLASTER, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-07

1Arsenic 01/29/25 JW 01/29/25 JW<2.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5032

1Barium 01/29/25 JW 01/29/25 JW220 mg/kg 9.9 mg/kg SW846 3050B SW-846 6010D0.5032

1Cadmium 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5032

1Chromium 01/29/25 JW 01/29/25 JW5.6 mg/kg 0.99 mg/kg SW846 3050B SW-846 6010D0.5032

1Lead 01/29/25 JW 01/29/25 JW4.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5032

1Selenium 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5032

1Silver 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5032

Sample Comments:

Client Sample ID: RCRA-8/GRAY/WHITE, PLASTER, WALL, INTACT Date Sampled: 01/23/25

Matrix: Solid LIMS Reference ID: CD51033-08

1Arsenic 01/29/25 JW 01/29/25 JW<2.0 mg/kg 2.0 mg/kg SW846 3050B SW-846 6010D0.5041

1Barium 01/29/25 JW 01/29/25 JW560 mg/kg 9.9 mg/kg SW846 3050B SW-846 6010D0.5041

1Cadmium 01/29/25 JW 01/29/25 JW0.50 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5041

1Chromium 01/29/25 JW 01/29/25 JW8.1 mg/kg 0.99 mg/kg SW846 3050B SW-846 6010D0.5041

10Lead 01/29/25 JW 01/29/25 JW6800 mg/kg 20 mg/kg SW846 3050B SW-846 6010D0.5041

1Selenium 01/29/25 JW 01/29/25 JW<4.0 mg/kg 4.0 mg/kg SW846 3050B SW-846 6010D0.5041

1Silver 01/29/25 JW 01/29/25 JW<0.40 mg/kg 0.40 mg/kg SW846 3050B SW-846 6010D0.5041

Sample Comments:

EMSL Sales Rep:

Reported:

ARCADIS U.S., Inc. [ACAD78J]

25 Braintree Hill Office Park, Suite 200

Braintree, MA 02184

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

Greg DonovanAttention:

(617) 778-8212 greg.donovan@arcadis.com

30265332 TASK NO., 01

Received: 01/24/2025 12:47

01/29/2025 18:01

Christopher Brandt

EMSL Order ID: 162551033

LIMS Reference ID: CD51033

EMSL Customer ID: ACAD78J

MA DOC- FRAMING HIM, MA

CertificationsAnalyte

Certified Analyses included in this Report

SW-846 6010D in Solid

16-A2LA ChemistryArsenic

16-A2LA ChemistryBarium

16-A2LA ChemistryCadmium

16-A2LA ChemistryChromium

16-A2LA ChemistryLead

16-A2LA ChemistrySelenium

16-A2LA ChemistrySilver

[TOC_1]Certified

Analyses[TOC]

List of Certifications

Code Description Number Expires

16-MO 10180Missouri Drinking Water 03/31/2026

16-NYDOH 12130New York Potable Water, Metals Solid and Hazardous Waste - Asbestos 04/01/2025

16-AIHA ELLAP 157245EMSL Analytical, Inc. Indianapolis, IN AIHA-LAP, LLC ELLAP Accredited 06/01/2025

16-AIHA IHLAP 157245EMSL Analytical, Inc. Indianapolis, IN AIHA-LAP, LLC IHLAP Accredited 06/01/2025

16-CA ELAP 2575California Metals in DW, Chemistry and Bulk Asbestos in Hazardous Waste 06/30/2025

16-A2LA Food 2845.11A2LA Food Microbiology 01/31/2026

16-A2LA Chemistry 2845.25A2LA Environmental and Chemistry 01/31/2026

16-IN Metals/Asbestos C-49-09Indiana Lead and Metals and Asbestos in Drinking Water 12/31/2026

16-OHDOH E10040Ohio - Lead in Paint Chips, Wipes, Soil and Air 05/03/2025

16-FLDOH E871170Florida Asbestos and Metals in Drinking Water, PCBs 06/30/2025

16-NJDEP IN002New Jersey Metals, Organics and Inorganics in DW PCBs 06/30/2025

16-IN Colilert/HPC M-49-06Indiana Colilert and HPC 12/31/2026

Please see the specific Field of Testing (FOT) on www.emsl.com <http://www.emsl.com> for a complete listing of parameters for which EMSL is certified.

[TOC_1]Certifications[TOC]

Notes and Definitions

Item Definition

M1 The spike recovery for this QC sample is outside of established control limits possibly due to sample matrix interference.

Laboratory Control Samples(LCS/LCSD) recovery were acceptable.

(Dig) For metals analysis, sample was digested.

[2C] Reported from the second channel in dual column analysis.

DF Dilution Factor

MDL Method Detection Limit.

ND Analyte was NOT DETECTED at or above the detection limit.

NR Spike/Surrogate showed no recovery.

Q Qualifier

RL Reporting Limit

Wet Sample is not dry weight corrected.

[TOC_1]Qualifiers, Definitions and Disclaimer[TOC]

EMSL Sales Rep:

Reported:

ARCADIS U.S., Inc. [ACAD78J]

25 Braintree Hill Office Park, Suite 200

Braintree, MA 02184

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

Greg DonovanAttention:

(617) 778-8212 greg.donovan@arcadis.com

30265332 TASK NO., 01

Received: 01/24/2025 12:47

01/29/2025 18:01

Christopher Brandt

EMSL Order ID: 162551033

LIMS Reference ID: CD51033

EMSL Customer ID: ACAD78J

MA DOC- FRAMING HIM, MA

Measurement of uncertainty and any applicable definitions of method modifications are available upon request. Per EPA NLLAP policy, sample results are not blank corrected.

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. QC sample results are within quality control criteria and met method specifications unless otherwise noted. All results for soil samples are reported on a dry weight basis, unless otherwise noted.

Aleks Kuchenbrod Laboratory Manager or other approved signatory

PROJECT NO. DRM 2024-57 #8

M.C.I. FRAMINGHAM – EMERGENCY NOTIFICATION SYSTEM

FRAMINGHAM, MA

RCRA-8 METAL CONTAINING PAINT HANDLING January 30, 2025

028000 - 1 of 13

SECTION 028000

RCRA-8 METAL CONTAINING PAINT HANDLING

PART 1 - GENERAL

1.1 GENERAL PROVISIONS

A. Attention is directed to the CONTRACT and GENERAL CONDITIONS and all Sections within Division 01 – GENERAL REQUIREMENTS, which are hereby made a part of this Section of the Specifications.

1.2 DEFINITIONS

A. The following definitions shall be applicable to this Section:

“Site”: Refers to the various buildings located at the Massachusetts Correctional Institution (MCI) Framingham located at 99 Loring Drive in Framingham, Massachusetts 0702 as described by the Contract Documents and Drawings.

“Owner": Refers to the Massachusetts Department of Correction (DOC) and their designated, authorized personnel.

“Consultant”: Refers to Arcadis U.S., Inc. and their designated, authorized personnel.

“Contractor”: Refers to the General Contractor and all Subcontractors who are performing remediation, renovation, demolition, construction and site restoration work outlined by the Contract Documents. Contractor as referenced, applies to ALL trades (including Filed Subcontractors) working at the site.

1.3 DESCRIPTION OF WORK

A. The Contractor shall be made aware that lead and other RCRA-8 metals are confirmed or assumed to be present within painted components throughout the Site which will be impacted by the Emergency Notification System Project. All work under this Section shall be performed to minimize the quantity of hazardous waste generated, protect the health and safety of all site personnel and building occupants, the welfare of the public, and avoid adverse environmental impacts.

B. The Contractor shall be required to comply with all aspects of the Occupational Safety and Health Administration (OSHA) Regulations pertaining to lead and other RCRA-8 metals with regards to disturbance of these materials when performing their work.

C. It shall be the sole responsibility of the Contractor for compliance with this Section, including all costs associated with, but not limited to:

028000 - 2 of 13

• Compliance with OSHA 29 CFR 1926.62 Lead Regulations.

• Compliance with OSHA 29 CFR 1926.1118 Arsenic Regulations

• Compliance with OSHA 29 CFR 1926.1126 Chromium Regulations.

• Compliance with OSHA 29 CFR 1926.1127 Cadmium Regulations.

• Compliance with OSHA 29 CFR 1926.1126 Chromium Regulations.

• USEPA’s Renovation, Repair and Painting Final Rule (RRP) (40 CFR 745)

• RCRA Regulations Title 40 CFR Parts 239 - 282

• Development and implementation of a Compliance Program.

• Development and implementation of a Respiratory Program.

• Development and implementation of a Medical Monitoring Program.

• Development and implementation of a Hazard Communication Program.

• Performance of any Negative Exposure Assessments required.

• Providing all medical examinations required.

• Providing all equipment required (Including appropriate PPE)

• Providing all engineering controls and associated work practices.

• Disposing of all materials in accordance with local, state and federal regulations.

D. Due to the age of the buildings, previous painting history, and the results of Arcadis’

RCRA-8 Paint Testing Report dated January 30, 2025, the Contractor shall assume that all painted surfaces contain lead and other RCRA-8 metals. The Contractor must comply with this Section as well as all local, state and federal regulations governing the removal, transport, and disposal of RCRA-8 metals in paint.

E. In the absence of analytical testing results, Contractor shall assume that paints and coatings impacted by the Emergency Notification System project contain RCRA-8 metals. The abatement, removal, handling, containerization, and disposal/recycling of wastes shall be in accordance with this Section.

F. It should be noted that the abatement of RCRA-8 metal containing paint by a licensed

Lead Abatement Contractor shall not be required for performance of the abatement and demolition work outlined under this Contract. The building is not considered a residence where children under the age of six (6) reside, therefore, abatement of lead-containing components will not be required as per Massachusetts Department of Public Health (DPH) "Child Lead Poisoning and Prevention Regulations. However, compliance with the OSHA Lead in Construction Standard is required under this Contract.

G. OSHA regulates activities that disturb the lead and other RCRA-8 metals by the use of manual techniques. Regulated activities include but are not limited to abrasive blasting, welding, drilling, cutting, burning on structures, manual scraping or sanding, and manual demolition of components. The work practices described in this Section are intended to adequately protect the workers from exposure to lead, and other RCRA-8 metals, provide a safe workplace, and protect the environment. It shall be the Contractors responsibility to comply with this Section as well as any other provisions/requirements outlined by OSHA and other applicable regulations.

H. Materials and Equipment: The work of this Section, without limiting the generality thereof, includes the furnishing of labor, materials, tools, equipment, services and

028000 - 3 of 13 incidentals necessary to safely accomplish tasks which will disturb lead and other RCRA-8 metals.

I. Approvals and Inspections: Temporary facilities, work procedures, equipment, materials, services, and agreements must fully comply with EPA, OSHA, RCRA, and NIOSH recommendations, standards and guidelines, as well as any other applicable federal, state, and local regulations. Where there exists an overlap of these regulations and guidelines, the most stringent shall apply.

J. Toxicity Characteristic Leaching Procedure Testing: All materials which are determined to be hazardous waste or regulated waste for lead and other RCRA-8 metals shall be disposed of by the Contractor as specified herein. On behalf of the Owner the Consultant shall perform representative Toxicity Characteristic Leaching Procedure (TCLP) tests of painted waste debris to ensure the material is properly profiled for disposal. This shall also include all testing required by the disposal or recycling facility. The Contractor shall provide 48 hours’ notice to the Owner and Consultant, once waste has been packaged for transport and disposal, that abatement waste is ready to be tested. No additional waste will be permitted to enter that waste stream following collection of TCLP samples. All costs associated with TCLP testing to profile the waste material shall be borne by the Owner. If the material is found to be hazardous waste or regulated waste, the Contractor shall provide appropriate drums/containers for use. The Contractor shall properly handle and transport all hazardous waste or regulated waste material into the drums/containers provided.

K. Disposal: The Contractor shall dispose of painted debris and associated materials in accordance with Part 3.6 of this Section. All costs associated with proper disposal of the waste materials (whether hazardous or regulated) shall be borne by the Owner.

The costs for non-hazardous materials shall be included under the Base Bid. All materials, whether hazardous, non-hazardous or regulated shall be disposed of in accordance with all laws, this contract, and any or all other applicable federal, state county or local regulations and guidelines. It shall be the sole responsibility of the Contractor to assure compliance with all laws and regulations relating to waste disposal.

1.4 SITE WORK DEFINITIONS

A. Action Level: Action Level as defined by OSHA shall refer to employee exposure, without regard to the use of respirators, to an airborne concentration of lead, and other RCRA-8 metals calculated as an eight (8)-hour time-weighted average (TWA).

B. Competent Person: Competent Person shall refer to a person who is capable of identifying existing and predictable hazards in the surroundings or working conditions and who has authorization to take prompt corrective measures to eliminate them.

C. HEPA Filter: HEPA Filter shall refer to a filter capable of filtering out monodispersive particles of 0.3 microns or greater diameter from a body of air at 99.97 percent efficiency or greater.

028000 - 4 of 13

D. Lead and RCRA-8 Metals Paint: Shall refer to paint found or assumed to contain lead and other RCRA-8 metals in any concentration as indicated in this Section.

E. Permissible Exposure Limit (PEL): PEL shall refer to employee exposure, without regard to the use of respirators, to an airborne concentration of lead and other RCRA- 8 metals calculated as an eight (8) hour time-weighted average.

1.5 PERMITS AND INSPECTIONS

A. Notifications/Approvals: The Contractor shall make, in proper and timely fashion, any necessary notifications to relevant local, state, and federal authorities and shall obtain and comply with the provisions of all permits or applications required by the work specified, as well as make all required submittals required under those auspices.