Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- RFP CSD 260000002650 2
- Issued by
- Kalamazoo County, Michigan
About this file
Summary: Drawings.pdf - ADA Sidewalks and Parking Construction
This is a technical drawings file related to a Michigan invitation to bid for the construction of ADA (Americans with Disabilities Act) compliant sidewalks and parking facilities. The drawings document appears to contain the detailed specifications, site plans, and construction details necessary for contractors to understand the scope of work, spatial requirements, and technical standards for the proposed improvements. The file serves as a primary reference document for bidders to develop accurate cost estimates and construction methodologies for the ADA sidewalk and parking lot project.
The drawings establish the technical baseline for all bid submissions and would typically include dimensional information, material specifications, accessibility compliance details per ADA Standards for Accessible Design, grading plans, drainage considerations, and any utility locations or conflicts that contractors must account for during construction. These technical documents are essential for ensuring all bidders are responding to identical project requirements and that the completed work will meet all applicable accessibility standards and local construction codes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum No. 1 (9.22.26) (1).pdf | ||
| Technical Specifications.pdf | ||
| Project Manual (Dated 9.9.26).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
NOT TO SCALE
T1.0 TITLE SHEET
C1.0
C3.0
DETAILS
C2.0
ISSUED FOR: CONSTRUCTION DOCUMENTS
C4.0
SITE LAYOUT & UTILITY PLAN
EXISTING CONDITIONS & DEMO PLAN
GRADING & SESC PLAN
CIVIL ENGINEER:
AR ENGINEERING, LLC.
5725 VENTURE PARK DRIVE, SUITE A
KALAMAZOO, MI 49008
TEL. (269) 250-5991 FAX. (866) 569-0604
DATE
42°05'18.5"N 84°16'47.9"W
SHEET INDEX
0 CONSTRUCTION DOCUMENTS
REVISIONS
09/09/26 lm
No. ISSUED FOR: DATE: BY:No. SHEET TITLE
C O
LU
M
B
IA
C E
N
TR
A L
SE
N
IO
R
H
IG
H S
C H
O O
L B
A
LL
F
IE
LD
S
9/ 9/
LOCATION MAP
NOT TO SCALE
N
11775 HEWITT RD
SECTION 26, T.04S, R.01E
COLUMBIA TOWNSHIP
JACKSON COUNTY, MI
SITE DEVELOPMENT PLANS
SEPTEMBER 9, 2026
PARCEL #: 000-19-26-301-001-00
BEG AT W 1/4 POST OF SEC 26 TH E ALG E&W 1/4 LN 1870.66 FT TH S 0DEG 23' 15''W 937.46 FT TH S 89DEG 14'30''E TO N&S 1/4 LN TH S ALG SD 1/4 LN 1134.3 FT TH N 77DEG 24'40"W 505.75 FT TH S 28DEG 42'15"E 535.5 FT TO CEN OF CEMENT CITY RD TH S 50DEG 38'30"W 272.58 FT ALG CEN OF SD RD TH N 39DEG 21'30"W 132 FT TH S 50DEG 38'30"W 214.5 FT TH S 39DEG 21'30"E 132 FT TO CEN OF CEMENT CITY RD THS 50DEG 38'30"W 524.05 FT ALG CEN OF SD RD TO THE CEN LN OF HEWITT RD TH N 30DEG 11'30"W 1943.04 FT ALG CEN OF SD RD TH N 30DEG 33'45"W 1636.18 FT ALG CEN LN OF SD RD TO THE
E&W 1/4 LN TH E ALG SD 1/4 LN 204.66 FT TO BEG SECS 26,27 & 35 T4S R1E 106.32A
LEGAL DESCRIPTION
AARON FELSKE. P.E.
OWNERS:
COLOMBIA SCHOOL DISTRICT
11775 HEWITT RD
BROOKLYN, MI 49230
(517) 592-6634
DEVELOPER:
TMP ARCHITECTURE
1191 WEST SQUARE LAKE RD
BLOOMFIELD HILLS, MI 48302
TEL. (248) 338-4561
COLUMBIA CENTRAL
SENIOR HIGH SCHOOL
BALL FIELDS
H
EW
ITT RD
CEMENT C
ITY RD
DALCHAR DRM
APLE LN
CEMENT C
ITY RD
C
AM
E
LO
T C T
WILKSHIRE DR
NOTTINGHAM DR
BARBARA DR
KIRKLEY DR
AMBLER DR
AutoCAD SHX Text
SITE LOCATION
AaronFelske Pen AarmFelzu
AaronFelske Pen 9-10
AaronFelske Pen -26
EM
HH
CHH
R
W
Ø10"
Ø8"
Ø8"
Ø10"
Ø12"
Ø12"
Ø8"
Ø12"
Ø12"
Ø12"
Ø12"
Ø10"
Ø10"
Ø8"
Ø12"
Ø12"
Ø10"
32'
WV
MH
CP 50
CP 51
CP 52
BM
BM
BASEBALL DUGOUT
GRAVEL
TREELINE
SCOREBOARD
SCOREBOARD
FLAGPOLE
BOLLARD (TYP.)
BLEACHERS ON
CONCRETE PAD
CONCRETE PAD
PRESS BOX
BATTING CAGE ON
CONCRETE PAD
SCOREBOARD DONATED BY
ATHLETIC BOOSTERS SIGN
FOUL POLE ON
CONCRETE BASE
FOUL POLE ON
CONCRETE BASE
HANDICAP
PARKING SIGN
SCOREBOARD
6' CHAINLINK FENCE
SOFTBALL DUGOUT
BLEACHERS
SOFTBALL DUGOUT
BASEBALL DUGOUT
SOFTBALL DUGOUT
BENCH
4' CHAINLINK FENCE
POWER POLE (TYP.)
GUY WIRE (TYP.)
18' CHAINLINK FENCE
6' CHAINLINK FENCE
10' CHAINLINK FENCE
6' CHAINLINK FENCE
6' CHAINLINK FENCE
6' CHAINLINK FENCE
6' CHAINLINK FENCE
10' CHAINLINK FENCE
10' CHAINLINK FENCE
10' CHAINLINK FENCE
10' CHAINLINK FENCE
18' CHAINLINK FENCE
18' CHAINLINK FENCE
18' CHAINLINK FENCE
18' CHAINLINK FENCE
OVERHEAD DOOR
MH-A
RISER
ELECTRICAL
METER
WATER WELL
BALL FIELD
BALL FIELD
BALL FIELD
BALL FIELD
6" CLEANOUT
WATER VALVE
BM-2
BM-1
C1.0
E X
IS
TI
N G
C O
N D
IT
IO
N S
D
E M
O P
LA
N
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
AF
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: NLP
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
26026017
09/09/2026
43210
/0
9/
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
LM
PR
O
JE
C
T:
C
LI
EN
T:
C O
LU
M
BI
A
SE
N
IO
R
H
IG
H S
C H
O O
L C
O
LU
M
BI
A
SC
H O
O L
D
IS
TR
IC
T
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
BR
O
O
KL
YN
, M
I
SE
C
TI
O N
6, T
S, R
E.
ST
ATE OF MICHIGAN
L I C E N S E D P R O F E S S I O N A L E N G
I N E E
R
AARON
MICHAEL
FELSKE
No.
6201045105
AARON FELSKE, P.E.
No. 6201045105
REMOVE
LIMITS OF CONSTRUCTION
P PROTECT
GRAVEL REMOVAL
P
DEMOLITION NOTES LEGEND
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: AR ENGINEERING, LLC
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES
AND REGULATIONS IN FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL
PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY
APPLICATIONS, BONDS, AND OTHER FEES REQUIRED FOR PROPOSED WORK. THIS
SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE REQUIRED BY THE
COLUMBIA TOWNSHIP, MICHIGAN AND JACKSON COUNTY.
10. CONTACT MISS DIGG "811" FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM
OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE
THE CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO
ARE NOT PART OF THE "MISS DIG" ALERT SYSTEM. THE CONTRACTOR SHALL
CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT THOSE UTILITIES
NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
11. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
12. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO
DEMOLITION.
13. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL
SPECIFICATIONS AND GEOTECHNICAL REPORT FOR THIS SITE BY [INSERT NAME].
14. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR
TO COMMENCEMENT OF WORK.
15. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO
ADJACENT ROADWAYS. CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
16. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST
BE SEEDED TO ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS
TO BE SEEDED AND MULCH BLANKETS APPLIED IMMEDIATELY TO PROVIDE A
STABLE BASE AND AVOID EXCESSIVE EROSION.
17. REVIEW ALL THE REMOVALS AND PROTECTION WITH OWNER PRIOR TO
COMMENCING CONSTRUCTION. INSTALL TEMPORARY SNOW FENCE AROUND ALL
TREES REQUIRING PROTECTION. SNOW FENCE SHALL BE PLACED AT EDGE OF DRIP
LINE.
18. SAWCUT ALL CURB, SIDEWALK, AND PAVEMENTS PRIOR TO REMOVAL. ADDITIONAL
SAWCUT MAY BE NECESSARY PRIOR TO REPLACEMENT TO ENSURE CLEAN EDGE.
19. ALL REMOVALS SHALL BE TAKEN OFF-SITE AND DISPOSED OF PROPERLY. NO
STOCKPILE OR BURNING OF DEBRIS IS ALLOWED.
20. ALL REMOVALS SHALL BE TO THE LIMITS INDICATED ABOVE UNLESS OTHERWISE
DIRECTED BY THE ENGINEER. UNAUTHORIZED REMOVALS AND SUBSEQUENT
REPLACEMENT SHALL BE AT THE CONTRACTOR'S EXPENSE.
21. REMOVE, STORE, AND RESET ANY EXISTING SIGNS AS DIRECTED BY THE
ENGINEER/OWNER.
22. REMOVE ALL TREES TO THE CLEARING LIMITS AS SHOWN. REMOVE ALL EXISTING
TREES, STUMPS AND BRUSH FROM THE SITE AS NECESSARY TO CONSTRUCT THE
IMPROVEMENTS.
23. THE CONTRACTOR SHALL DEMOLISH AND REMOVE ANY ITEMS REMAINING FROM
THE EXISTING BUILDING, IN ITS ENTIRETY, INCLUDING WALLS, FOUNDATIONS AND
FOOTINGS. ALL BUILDING DRAINS AND UTILITY LEADS SHALL BE LOCATED AND
PROPERLY PLUGGED. UTILITY LEAD WORK SHALL BE COORDINATED WITH THE
APPROPRIATE UTILITY COMPANY.
24. BACKFILL EXCAVATED AREAS WITH CLEAN GRANULAR FILL COMPACTED TO 95% OF
THE MATERIAL UNIT WEIGHT BY MODIFIED PROCTOR.
25. CONTROL SHALL BE MAINTAINED OVER THE SITE AND OPERATION TO ELIMINATE
HAZARDS TO THE PUBLIC. NAILS OR OTHER TIRE PUNCTURING ITEMS SHALL NOT
BE DROPPED ON STREETS, ALLEYS AND ADJACENT PROPERTY. PUBLIC STREETS,
CURBS AND SIDEWALKS SHALL BE PROTECTED FROM DAMAGE. THE PERSON
ENGAGED IN THE DEMOLITION WORK SHALL BE LIABLE FOR ANY AND ALL DAMAGE
TO CURBS, STREETS, SIDEWALKS AND OTHER PUBLIC OR PRIVATE PROPERTY AND
FOR ANY BODILY INJURY OCCURRING AS A RESULT OF THE DEMOLITION WORK.
1 inch = ft.
50 10075
N
REMOVE EXISTING
HANDICAP SIGNS
R
R
R
R
R
R
REMOVE & REPLACE
YARD DRAIN WITH
ROUND CATCH BASIN
FOR STORM
P
KEEP EXISTING TREES
BENCHMARK INFORMATION
BM-1: ELEV: 1004.61
SET "X" IN THE NORTHWEST BOLT OF FOUL POLE BASE LOCATED
±429' NORTHEAST OF CENTERLINE OF HEWITT RD AND ±438'
NORTHWEST OF CENTERLINE OF CEMENT CITY RD.
BM-2: ELEV: 1005.93
SET MAG NAIL IN SOUTHWEST CORNER OF CONCRETE BLEACHER
PAD LOCATED ±95' NORTHEAST OF CENTERLINE OF HEWITT RD
AND ±165' NORTHEAST OF CENTERLINE OF CEMENT CITY RD.
REMOVE EXISTING FENCE.
APPROX. 54 LFT
R
R
REMOVE EXISTING GRAVEL PATH
YD-1, 18" CPP STRUCTURE
RIM = 1003.28
NNW 6" PVC (INV. = 1000.98)
SUMP = 998.08
STORM STRUCTURE INFORMATION
SANITARY STRUCTURE INFORMATION
MH-A, CONC. STRUCTURE
RIM = 1004.53
SSE 4" PVC (INV. = 1002.23)
EXISTING GRAVEL DEPTH IS UNKNOWN.
REMOVE GRAVEL TO DEPTH
NECESSARY TO CONSTRUCT NEW
CONCRETE AND SAND SUBBASE
SECTION.
REMOVED GRAVEL MAY BE DEPOSITED
ON SITE BY SPREADING IN THE GRAVEL
PARKING LOT AND LEVELING.
COORDINATE LOCATION OF GRAVEL
DISPOSAL WITH OWNER.
TEMPORARILY REMOVE ANY LOOSE
BENCHES/BLEACHERS/EQUIPMENT IN
ORDER TO PLACE NEW CONCRETE WALKS
EXISTING GRAVEL DEPTH IS UNKOWN. REMOVE GRAVEL
TO DEPTH NECESSARY TO CONSTRUCT NEW CONCRETE
AND SAND SUBBASE SECTION.
NOTE NEW BASIN LOCATIONS WILL PROVIDE LOW SPOTS
AROUND THE BUILDING, SO ADDITIONAL REMOVAL MAY
BE NECESSARY TO CONSTRUCT THE NEW CONCRETE PROFILE
6" INVERT OUT
997.73
CHH
R
W
Ø10"
Ø8"
Ø8"
Ø10"
Ø12"
Ø12"
Ø8"
Ø12"
Ø12"
Ø12"
Ø12"
Ø10"
Ø10"
Ø8"
Ø12"
Ø12"
Ø10"
32'
WV
MH
CB
CB-1
CB-2
44' - 8" N12 HDPE @ 0.30%
CB
CB-4
49' - 8" N12 HDPE @ 0.30%
CB47' - 8" N12 HDPE @ 0.30%
CB
CB
CB
16' - 6" N12 HDPE @ 0.30%
CB
H
EW
ITT R
D
(66' PU
BLIC
R.O .W
./ASPH
ALT)
CEMENT C
ITY R
D
(66' P
UBLIC
R .O
.W ./A
SPHALT
CB-1, 2' DIA. EJIW 5105
RIM = 1003.95
8" HDPE N
CB-2, 2' DIA. EJIW 5105
RIM = 1003.95
8" HDPE S
8" HDPE W
CB-3, 2' DIA. EJIW 5105
RIM = 1003.92
12" HDPE N
6" HDPE NW
CB-4, 2' DIA. EJIW 5105
RIM = 1003.88
8" HDPE E
8" HDPE S
1001.26
1001.13 1001.13
1001.12 1001.12
1000.98 1000.98
C2.0
S
IT
E L
A Y
O U
T
U
TI
LI
TY
P
LA
N
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
AF
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: NLP
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
26026017
09/09/2026
43210
/0
9/
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
LM
PR
O
JE
C
T:
C
LI
EN
T:
C O
LU
M
BI
A
SE
N
IO
R
H
IG
H S
C H
O O
L C
O
LU
M
BI
A
SC
H O
O L
D
IS
TR
IC
T
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
BR
O
O
KL
YN
, M
I
SE
C
TI
O N
6, T
S, R
E.
AARON FELSKE, P.E.
No. 6201045105
GENERAL NOTES
1. DIMENSIONS HEREIN TAKE PRECEDENCE OVER SCALE AND
COMPUTER MODEL. CONTRACTOR TO VERIFY ALL
DIMENSIONS IN FIELD.
2. SLOPE GRADES UNIFORMLY BETWEEN ELEVATIONS SHOWN.
ALL PEDESTRIAN WALKWAYS SHALL COMPLY WITH ADA
REQUIREMENTS.
3. IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS BECOME
APPARENT, THESE SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER PRIOR TO CONSTRUCTION OF
ANYTHING AFFECTED SO THAT CLARIFICATION OR REDESIGN
MAY OCCUR.
1. PROPERTY INFORMATION:
PARCEL #S: 000-19-26-301-001-00
SITE AREA: 4,631,299 SF (106.32AC)
OWNER: COLUMBIA SCHOOL DISTRICT
11775 HEWITT RD
BROOKLYN, MI 49230
ARCHITECT: TMP ARCHITECTURE
259 E. MICHIGAN AVE
SUITE 308
KALAMAZOO, MI 49007
PHONE: (248) 338-4561
E-MAIL: INFO@TMP-ARCHITECTURE.COM
2. ZONING:
PROPERTY CURRENTLY ZONED:
RR - RURAL RESIDENTIAL DISTRICT
ABUTTING PROPERTY CURRENTLY ZONED:
NORTH: RR - RURAL RESIDENTIAL DISTRICT
SOUTH: RR - RURAL RESIDENTIAL DISTRICT
EAST: RR - RURAL RESIDENTIAL DISTRICT
WEST: RR - RURAL RESIDENTIAL DISTRICT
PROPOSED LAND USE = SCHOOL
*PERMITTED USE IN RURAL RESIDENTIAL DISTRICT
3. LOT:
MINIMUM LOT SIZE: 20,000 SFT
MINIMUM LOT WIDTH: 90 FT
LOT SIZE: 4,631,299 SFT / 106.32 ACRES
LOT DIMENSIONS: IRREGULAR
4. LANDSCAPING:
LANDSCAPING WILL BE LIMITED TO MINOR EDGE
REPAIRS IN GRASS AREAS ADJACENT TO CONCRETE
INSTALLATIONS OR CONSTRUCTION TRAFFIC.
5. STORM WATER DETENTION REQUIRED:
STORM WATER WILL CONTINUE TO UTILIZE THE
EXISTING STORM WATER COLLECTION AND
DISPOSAL SYSTEM ON SITE.
A. CONCRETE PAVEMENT (SEE DETAIL SHEET).
B. PAINT/ STRIPING (SEE DETAIL SHEET)
C. SUGGESTED PARKING LOT STRIPING TO OPTIMIZE
VEHICLE PARKING (NOT PART OF CONTRACT)
D. HANDICAP PARKING SIGN (6)
E. PROPOSED BLEACHER
HD CONCRETE PARKING PAD
CONCRETE PAVEMENT AND SIDEWALK
(SEE DETAIL ON C5.0)
SITE DATA
SITE PLAN NOTES LEGEND
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: AR ENGINEERING, LLC
1 inch = ft.
50 10075
N
11' 11'
11'
11'
11' 11'
18'
5'
10'
15'
15'
14'
15'
13'
8'
8'
8'
R
R5'
R35'
R25'
R19'
R10'
R5' R13'
R2 5'
R2 5'
R2 5'
R25
R2 5'
R2 5'
R 25'
R 25'
A
B
C
D
24'
24'
24'
26'
11'
18' 18' 11'
11'
18' 18' 11'
11'
18'
18'
11'11'
18'
11'
18'
1. SOILS EXPOSED IN THE BASE OF ALL SATISFACTORY FOUNDATION EXCAVATIONS SHOULD BE PROTECTED AGAINST ANY DETRIMENTAL CHANGES IN CONDITION SUCH AS FROM DISTURBANCE, RAIN AND FREEZING. SURFACE RUN-OFF WATER SHOULD BE DRAINED AWAY FROM THE EXCAVATION AND NOT ALLOWED TO POND. IF POSSIBLE, ALL FOOTING CONCRETE SHOULD BE POURED THE SAME DAY THE EXCAVATION IS MADE. IF THIS IS NOT PRACTICAL, THE FOOTING EXCAVATIONS SHOULD BE
ADEQUATELY PROTECTED.
2. REMOVE ALL SUBGRADE GRADE MATERIAL THAT MAY BE SOFTENED BY RAINS, FREEZING, OR
CONSTRUCTION TRAFFIC, ETC. AND REPLACE WITH COMPACTED GRANULAR FILL.
3. STORM SEWER SHALL BE CORRUGATED HDPE PIPE WITH SMOOTH INTERIOR WALL, BY ADS OR EQUAL.
LEACHING BASINS AND MANHOLES ARE TO BE REINFORCED CONCRETE WITH RIM AND SLOTTED
GRATING (AS SHOWN). STORM SEWER & LEACHING BASINS ARE TO BE WRAPPED WITH FILTER FABRIC.
4. SANITARY SEWER PIPE MAY BE PVC SDR 3034 MATERIAL.
5. ALL WATER SERVICE LINES SHALL BE 1" TYPE K COPPER PIPE OR PE AND SHALL BE BROUGHT TO WITHIN 5' OF BUILDING, WITH COMPRESSION FITTINGS OR MECHANICAL FITTINGS OTHER THAN
FLARED ENDS.
6. PROVIDE MINIMUM 5' COVER FROM FINISHED GRADE FOR ALL WATER SERVICE LINES. IF COVER CANNOT BE MAINTAINED DUE TO SITE CONDITIONS OR INVERT ELEVATIONS THE ENTIRE LENGTH OF THE EXTERIOR PIPE MUST BE PROTECTED WITH 2" RIGID INSULATION BOARD ON THE TOP AND SIDES.
7. PROVIDE MINIMUM 5' COVER FROM FINISHED GRADE FOR ALL SANITARY SEWER LINES. IF COVER CANNOT BE MAINTAINED DUE TO SITE CONDITIONS OR INVERT ELEVATIONS THE ENTIRE LENGTH OF THE EXTERIOR PIPE MUST BE PROTECTED WITH 2" RIGID INSULATION BOARD ON THE TOP AND SIDES.
8. MAINTAIN 10 FOOT MINIMUM HORIZONTAL SEPARATION BETWEEN THE SEWER AND WATER MAIN
UTILITIES. PROVIDE 18" MINIMUM VERTICAL SEPARATION WHERE UTILITIES CROSS.
9. THE CONTRACTOR SHALL INSTALL A PEDESTRIAN FENCE AROUND ALL EXCAVATIONS TO BE LEFT OPEN
OVERNIGHT AS REQUIRED.
10. EXTERIOR CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH OF 4000 PSI AND SHALL HAVE
LIMESTONE AGGREGATE AND SHALL HAVE 4 - 6 % AIR ENTRAINMENT WITH A BROOM FINISH.
11. EXPANSION JOINTS IN CONCRETE PAVEMENT AND WALLS SHALL BE 1/2" ASPHALT IMPREGNATED FULL DEPTH 40' O.C. MAXIMUM & AT SIDEWALK INTERSECTIONS. CRACK CONTROL SCORING AT SIDEWALK
WIDTH DIMENSION AND @ 10'-0" O.C. IN DRIVES.
GENERAL NOTES
SITE MATERIALS & CONSTRUCTION NOTES
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS IN
FORCE AT TIME OF CONSTRUCTION.
2. ELECTRICAL WORK SHALL BE PERFORMED BY A STATE OF MICHIGAN LICENSED ELECTRICIAN ACCORDING TO THE N.F.P.A. NATIONAL ELECTRICAL CODE AS MODIFIED BY THE STATE OF MICHIGAN.
FURNISH AND INSTALL ALL MATERIALS AND LABOR TO PROVIDE A COMPLETE WORKING SYSTEM.
3. ALL PLUMBING WORK SHALL BE PERFORMED BY A STATE OF MICHIGAN LICENSED PLUMBER
ACCORDING TO THE INTERNATIONAL PLUMBING CODE AS MODIFIED BY THE STATE OF MICHIGAN AND LOCAL HEALTH DEPARTMENT. FURNISH AND INSTALL ALL MATERIALS AND LABOR TO PROVIDE A FULL
WORKING SYSTEM.
4. ALL MECHANICAL WORK SHALL BE PERFORMED ACCORDING TO THE INTERNATIONAL MECHANICAL CODE AS MODIFIED BY THE STATE OF MICHIGAN AND THE MICHIGAN ENERGY CODE. FURNISH AND
INSTALL ALL MATERIALS AND LABOR TO PROVIDE A FULL WORKING SYSTEM.
5. ALL WORK SHALL CONFORM TO THE MICHIGAN HANDICAPPED ACCESSIBILITY CODE AND THE
AMERICANS WITH DISABILITIES ACT.
6. WATER SERVICE PRESSURE TESTING AND CHLORINATION SHALL BE PER EGLE AND COLUMBIA
TOWNSHIP REQUIREMENTS.
7. SANITARY SEWER INSTALLATION AND TESTING MUST MEET THE REQUIREMENTS OF COLUMBIA
TOWNSHIP AND EGLE.
8. ALL REGULATORY SIGNAGE (IF SPECIFIED) SHALL BE PER THE MICHIGAN DEPARTMENT OF
TRANSPORTATION (MDOT).
9. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER FEES REQUIRED
FOR PROPOSED WORK.
10. CONTACT "MISS DIG 811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "MISS DIG" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT
THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
11. ANY SANITARY SEWER, SANITARY SEWER SERVICE LEADS, WATER MAIN, WATER SERVICES, OR STORM SEWER WHICH IS DAMAGED BY THE CONTRACTOR DURING HIS OPERATIONS SHALL BE REPAIRED TO
THE OWNERS SATISFACTION, AND AT THE CONTRACTORS EXPENSE. IF ANY ELEMENTS OF THE
SANITARY SEWER SYSTEM ARE DAMAGED AND NEED REPAIRED, IT MUST MEET COLUMBIA TOWNSHIP
SPECIFICATIONS.
12. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE ELECTRICAL TRANSFORMER PAD PER THE
UTILITY COMPANY SPECIFICATIONS.
13. THE TELEPHONE UTILITY COMPANY SHALL PROVIDE UNDERGROUND TELEPHONE TO THE BUILDING AT
THE OWNERS EXPENSE.
14. REFER TO ELECTRICAL DRAWINGS FOR UNDERGROUND ELECTRICAL REQUIREMENTS FOR SITE
LIGHTING & SITE DETAILS SHEETS FOR THE FIXTURE AND & POLE SPECIFICATIONS.
15. DESIGN, INSTALLATION AND SPECIFICATION FOR IMPROVEMENTS RELATED TO GAS, TELEPHONE, ELECTRIC AND CABLE TELEVISION SERVICES SHALL BE COORDINATED BY THE CONTRACTOR.
16. CONTRACTOR SHALL COORDINATE TELEPHONE, ELECTRIC, AND CABLE TELEVISION CONDUITS WITH
THE APPROPRIATE UTILITY PRIOR TO PAVEMENT INSTALLATION.
17. CONTRACTOR IS TO UNCOVER AND CONFIRM ALL TAP LOCATIONS. LOCATION DISCREPANCIES ARE TO
BE BROUGHT TO THE ENGINEERS ATTENTION FOR RESOLUTION.
18. THE CONTRACTOR IS TO PROVIDE THE WATER SERVICE PIPING FROM THE BUILDING TO THE EXISTING MAIN. THE CONTRACTOR SHALL MAKE THE CONNECTION TO THE SHUT OFF VALVE, THE CONTRACTOR
SHALL COORDINATE SERVICES WITH THE VILLAGE.
19. CONTRACTOR/OWNER SHALL OBTAIN UTILITY CONNECTION PERMITS AND SETTLE APPLICABLE UTILITY
ASSESSMENTS PRIOR TO EXTENSION OF PUBLIC UTILITIES ONSITE.
20. MANHOLE AND CATCH BASIN STRUCTURES SHALL BE PRECAST AND HAVE A MAXIMUM OF 2 ADJUSTING RINGS FOR FINISH GRADE ADJUSTMENT. STORM STRUCTURES MUST ALL HAVE A SUMP OF TWO FEET.
21. ALL WATER MAIN TO HAVE A BURIAL DEPTH AS REQUIRED BY EGLE FOR THE SPECIFIC REGION OF WORK
IN JACKSON COUNTY.
22. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
23. THE CONTRACTOR SHALL REVIEW THE GEOTECHNICAL REPORT.
24. DRIVEWAY LAYOUT AND CONNECTION TO HEWITT RD SHALL COMPLY WITH ALL ASPECTS OF THE MDOT /
COUNTY ROAD COMMISSION DRIVE PERMITS, RESPECTIVELY.
25. GEOTEXTILE FABRIC SHALL BE PLACED UNDER ALL APPLICATIONS OF RIP RAP OUTFALLS AND
SPILLWAYS.
STORM STRUCTURE DATA
BENCHMARK INFORMATION
BM-1: ELEV: 1004.61
SET "X" IN THE NORTHWEST BOLT OF FOUL POLE BASE LOCATED
±429' NORTHEAST OF CENTERLINE OF HEWITT RD AND ±438'
NORTHWEST OF CENTERLINE OF CEMENT CITY RD.
BM-2: ELEV: 1005.93
SET MAG NAIL IN SOUTHWEST CORNER OF CONCRETE BLEACHER
PAD LOCATED ±95' NORTHEAST OF CENTERLINE OF HEWITT RD
AND ±165' NORTHEAST OF CENTERLINE OF CEMENT CITY RD.
11'
18'
CONCRETE CONTRACTOR TO SUBMIT PROPOSED JOINT LAYOUT
PLAN TO ENGINEER FOR APPROVAL. GENERALLY FOLLOW MDOT
DETAIL R-29-J FOR SPACING AND INTENT FOR CRACK CONTROL.
STRAIGT SIDEWALKS AREAS TO MATCH WIDTH OF WALK. MAX 100 SFT
PER AREA. PLACE CONTROL/ISOLATION POINTS AT MAX 50' SPACING.
SEE DETAIL ON C4.0.
PLACE EXPANSION JOINT MATERIAL AT EDGE OF
EXISTING CONCESSIONS BUILDING PAD WHEN FORMING NEW
SIDEWALK AREA TO SEAL AREA BETWEEN NEW AND EXISTING.
EXISTING TRIM/SIDING IN SOME AREAS IS PRESENT BELOW THE
EDGE OF THE FLOOR SLAB, AND WILL REQUIRE REMOVAL/TRIMMING
IN ORDER TO PLACE SURROUNDING CONCRETE FLUSH WITH FLOOR SLAB.
E
E
6" INVERT OUT
997.73
EX. 6" NW 1000.98
OUTFALL 6" 997.73
(MATCH EX.)
(MATCH EX.)
(MATCH EX.)
PLACE 6" N12 HDPE STUB FROM CB3
TO FENCE LINE FOR FUTURE USE INSIDE FIELD
CHH
R
W
Ø10"
Ø8"
Ø8"
Ø10"
Ø12"
Ø12"
Ø8"
Ø12"
Ø12"
Ø12"
Ø12"
Ø10"
Ø10"
Ø8"
Ø12"
Ø12"
Ø10"
32'
WV
MH
CP 50
CP 51
CP 52
BM
BM
CB
EM
HH
CHH
R
W
32'
WV
MH
CP 50
CP 51
CP 52
BM
BM
CB
CB
CB
CB
CB
CB
1004.22 M.E.
1004.64 M.E.
1004.69 M.E.
1004.23 M.E.
1004.38 M
.E.
1005.12 M
.E.
1004.24 M
.E.
1003.73 M
.E.
1003.73 M
.E.
1004.32 M
.E.
1005.46 M
.E.
1005.94 M
.E.
1005.55 M
.E.
1005.95 M
.E.
1005.17 M
.E.
1004.35 M.E.
1004.13 M.E.
1004.79 M.E.
1005.75 M
.E.
1005.36 M.E.
1005.99 M
.E.
1005.74 M.E.
1005.39 M
.E.
1005.91 M
.E.
1005.94 M.E.
1005.82 M
.E.
1005.86 M.E.1005.87 M.E.
1005.87 M
.E.
1005.84 M.E.
1005.89 M
.E.
1005.52 M
.E.
1005.52 M
.E.
1005.93 M
.E.
1005.76 M.E.
1004.79 M
.E.
1005.42 M
.E.
1005.48 M
.E.
1003.45 M
.E.
1003.48 M
.E.
00 10
01 10
10031004
06 10
32'
WV
MH
CB
32'
WV
MH
CB-1
CB-2
44' - 8" N12 HDPE @ 0.30%
CB CB-4
49' - 8" N12 HDPE @ 0.30%
CB
47' - 8" N12 HDPE @ 0.30%
CB
CB
CB
16' - 6" N12 HDPE @ 0.30%
CB
1003.95
1003.95
1003.92
1003.88
1004.18 M
.E.
1004.18 M.E.
1004.26 M.E.
1004.25 M
.E.
1004.33 M.E.
1004.24 M
.E.
1004.14 M
.E.
1004.12 M
.E.
1004.50 M
.E.
1004.66 M.E.
1004.51 M.E.
1004.48 M.E.
1004.30 M.E.
1004.17 M
.E.
1004.73 M
.E.
C3.0
G R
A D
IN
G
S
E S
C P
LA
N
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
AF
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: NLP
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
26026017
09/09/2026
43210
/0
9/
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
LM
PR
O
JE
C
T:
C
LI
EN
T:
C O
LU
M
BI
A
SE
N
IO
R
H
IG
H S
C H
O O
L C
O
LU
M
BI
A
SC
H O
O L
D
IS
TR
IC
T
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
BR
O
O
KL
YN
, M
I
SE
C
TI
O N
6, T
S, R
E.
AARON FELSKE, P.E.
No. 6201045105
SOIL EROSION & SEDIMENT CONTROL NOTES
3P
4T
8P
14T
26T
29T
3T
33T
LIMITS OF CONSTRUCTION
SILT FENCE
GRADING NOTES LEGEND
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: AR ENGINEERING, LLC
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND
REGULATIONS IN FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT
COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER
FEES REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO
THOSE REQUIRED BY THE MICHIGAN DEPARTMENT OF TRANSPORTATION.
3. CONTACT MISS DIGG "811" FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48 HOURS
BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "MISS DIG" ALERT
SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE
THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. MATCH EXISTING GRADES AROUND PERIMETER WITH SLOPES AS SHOWN.
6. ALL SPOT ELEVATIONS ARE TOP OF PAVEMENT GRADES AT EDGE OF METAL (EOM) UNLESS
OTHERWISE NOTED.
7. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO MASS GRADING.
8. ALL EARTHWORK SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS AND
GEOTECHNICAL REPORT.
9. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR TO
COMMENCEMENT OF WORK.
10. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO ADJACENT
ROADWAYS. CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
11. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST BE SEEDED TO ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS TO BE SEEDED AND MULCH BLANKETS APPLIED IMMEDIATELY TO PROVIDE A STABLE BASE AND AVOID EXCESSIVE EROSION.
1 ALL CONSTRUCTION METHODS SHALL BE DONE IN COMPLIANCE WITH MDOT-EGLE. THE
OWNER SHALL BE RESPONSIBLE FOR OBTAINING A "SOIL EROSION PERMIT" FROM THE
GOVERNING AUTHORITY AND A "PERMIT BY RULE/NOTICE OF COVERAGE" FROM THE
GOVERNING AUTHORITY, IF APPLICABLE, PRIOR TO START OF CONSTRUCTION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL REQUIREMENTS OF THE
"SOIL EROSION PERMIT" AND FOR ALL CERTIFIED STORM WATER INSPECTION SERVICE
REQUIRED BY THE "PERMIT BY RULE." EROSION CONTROL MEASURES SHOWN ON THE PLANS
ARE THE MINIMUM REQUIREMENTS AND SHALL NOT RELIEVE THE CONTRACTOR'S
RESPONSIBILITY FOR PROVIDING ALL REQUIRED EROSION CONTROL MEASURES.
2. AVOID UNNECESSARY DISTURBING OR REMOVING OF EXISTING VEGETATED TOPSOIL OR EARTH
COVER, THESE COVER AREAS ACT AS SEDIMENT FILTERS.
3. ALL TEMPORARY SOIL EROSION PROTECTION SHALL REMAIN IN PLACE UNTIL REMOVAL IS
REQUIRED FOR FINAL CLEAN UP AND APPROVAL.
4. GEOTEXTILE SILT FENCE SHALL BE INSTALLED AS REQUIRED WHEN CROSSING CREEKS OR
WHEN ADJACENT TO WETLANDS OR SURFACE WATER BODIES TO PREVENT SILTATION AND
ELSEWHERE AS DIRECTED BY THE ENGINEER. SEEDING AND/OR SODDING SHALL BE INSTALLED
ON CREEK BANKS IMMEDIATELY AFTER CONSTRUCTION TO PREVENT EROSION.
5. MAINTENANCE, CLEANING, AND REMOVAL OF THE VARIOUS SEDIMENT CONTROL MEASURES
SHALL BE INCLUDED IN THE VARIOUS EROSION CONTROL ITEMS.
ALL SOIL EROSION AND SEDIMENTATION CONTROL MEASURES SHALL BE PER MDOT STANDARD
DETAILS. "P" DENOTES PERMANENT MEASURE AND "T" DENOTES TEMPORARY MEASURE. SOIL
EROSION CONTROL PLANS DENOTE MINIMUM EROSION MEASURES REQUIRED AS DESCRIBED
BELOW.
DENOTES PERMANENT SEEDING. ALL DISTURBED AREAS NOT PAVED OR GRAVELED SHALL BE
RESTORED. PLACE TOPSOIL SURFACE, SALV, 3 INCH, MDOT SEEDING, MIXTURE TUF APPLIED AT A RATE OF 220 LB/ACRE, FERTILIZER, CHEMICAL NUTRIENT, CL A APPLIED AT A RATE OF 228
LB/ACRE; MULCH AT A RATE OF 2 TON/ACRE AND MULCH ANCHORING. (APPLIES TO ENTIRE
PROJECT)
DENOTES TEMPORARY SEEDING. TEMPORARY SEEDING SHALL BE PLACED AT LOCATIONS
DETERMINED BY THE ENGINEER IN THE FIELD AND SHALL INCLUDE CEREAL RYE SEED APPLIED
AT A RATE OF 70 LB/ACRE AND MULCH.
DENOTES DUST CONTROL. DUST CONTROL MAY BE REQUIRED ON THE SUBGRADE
CONSTRUCTION AND WILL INCLUDE APPLYING FRESH WATER TO BE INCLUDED IN THE ITEM OF
EMBANKMENT. DUST CONTROL ON THE AGGREGATE BASE COURSE WILL BE ACCOMPLISHED
BY APPLYING FRESH WATER (INCLUDED IN THE ITEM OF AGGREGATE BASE, 6 INCH) AND
APPLYING DUST PALLIATIVE, APPLIED, CACL₂ (TON) AS DIRECTED BY THE PROJECT ENGINEER.
DENOTES AGGREGATE COVER/PERMANENT PAVEMENT RESTORATION
DENOTES GRAVEL ACCESS APPROACH. APPROACH SHALL BE INSTALLED TO PROVIDE STABLE
ACCESS TO ROADWAYS AND MINIMIZE DUST AND TRACKING OF MATERIALS ONTO PUBLIC
STREETS AND HIGHWAYS. THE APPROACH SHALL BE A MINIMUM OF 12' WIDE, 6" DEEP, AND
CONSIST OF 2"-4" AGGREGATE.
DENOTES TEMPORARY SILT FENCE. SILT FENCE SHALL BE INSTALLED AT CREEK CROSSINGS,
ADJACENT TO ALL WETLANDS AND SURFACE WATERS, AND OTHER LOCATIONS AS DIRECTED
BY THE ENGINEER. EACH SILT FENCE SHALL BE INSTALLED GENERALLY ALONG THE SAME
CONTOUR ELEVATION.
DENOTES INLET PROTECTION FABRIC DROP. SHALL BE INSTALLED AT EXISTING AND PROPOSED STORM SEWER INLETS TO PROVIDE SETTLING AND FILTERING OF SILT LADEN WATER PRIOR TO
ENTRY INTO THE DRAINAGE SYSTEM.
DENOTES MULCH BLANKET OR MATTING. SHALL BE NORTH AMERICAN GREEN DS150, OR
APPROVED EQUAL. MULCH BLANKETS SHALL BE PLACED ON ALL 1:3 SLOPES OR GREATER, IN
AND AROUND DITCH BOTTOMS WHERE THERE IS NO BIOSWALE BY CONTRACTOR RESPONSIBLE
FOR RESTORING THAT AREA.
1 inch = ft.
50 10075
N
SEE CONCESSION BLOW-UP
FOR GRADES
BENCHMARK INFORMATION
BM-1: ELEV: 1004.61
SET "X" IN THE NORTHWEST BOLT OF FOUL POLE BASE LOCATED
±429' NORTHEAST OF CENTERLINE OF HEWITT RD AND ±438'
NORTHWEST OF CENTERLINE OF CEMENT CITY RD.
BM-2: ELEV: 1005.93
SET MAG NAIL IN SOUTHWEST CORNER OF CONCRETE BLEACHER
PAD LOCATED ±95' NORTHEAST OF CENTERLINE OF HEWITT RD
AND ±165' NORTHEAST OF CENTERLINE OF CEMENT CITY RD.
4T 8P
4T 8P
4T
8P
29T
CONCESSION BLOW-UP
C3.0 - 140105 SCALE 1:20
PROPOSED ALTERNATE
DRAINAGE ARROW
29T
29T
29T
EXISTING BUILDING
F.F. 1004.45
RESET SANITARY RIM TO
MATCH NEW CONCRETE
WALK
PROPOSED
HIGH POINT
PROPOSED
HIGH POINT
PROPOSED
HIGH POINT
PROPOSED
HIGH POINT
C4.0
D E
TA
IL
S
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
AF
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: NLP
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
26026017
09/09/2026
43210
/0
9/
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
LM
PR
O
JE
C
T:
C
LI
EN
T:
C O
LU
M
BI
A
SE
N
IO
R
H
IG
H S
C H
O O
L C
O
LU
M
BI
A
SC
H O
O L
D
IS
TR
IC
T
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
BR
O
O
KL
YN
, M
I
SE
C
TI
O N
6, T
S, R
E.
AARON FELSKE, P.E.
No. 6201045105
1/4" WIDE TOOLED
CONTROL JOINT
1" DEEP MIN.
(CONTRACTOR TO
SUBMIT JOINT LAYOUT
PLAN TO ENGINEER
FOR APPROVAL -
REFERENCE MDOT
DETAIL R-29-J)
CONCRETE SIDEWALK
03003 NOT TO SCALE
NOTES
1. *TRANSVERSE SIDEWALK SLOPES ARE 2% MAXIMUM.
2. IN ORDER TO MEET SITE CONDITIONS, IF THE TRANSVERSE SLOPE IS REQUIRED TO BE
LESS THAN 1.5%, LONGITUDINAL DRAINAGE MUST BE PROVIDED.
3. **SAWN CONTROL JOINTS WILL NOT BE ACCEPTED UNLESS APPROVED BY OWNER
4. USE MINIMUM 6" CONCRETE AND 6" BASE THROUGH DRIVEWAYS
1/2" WIDE EXPANSION JOINT
MATERIAL W/ SEALANT.
PROVIDE EXPANSION JOINT IN
PLACE OF CONTROL JOINTS AT
50'-0" MAX. & WHERE REQ'D AS
ISOLATION JOINT.
4"
V A
R
IE
S (S
E E
P
LA
N
MATCH
SIDEWALK WIDTH
10' MAX.
1/2" EXP. JT. W / SEALANT (TYP.)
MEDIUM BROOM FINISH
PERPENDICULAR TO TRAFFIC
1/4 " WIDE TOOLED**
CONTROL JOINTS
*2% MAX
4" TOOLED
RADIUS EDGE
(TYP.)
VARIES
(SEE PLAN)
6"
TYP.
PLAN VIEW
PROFILE A-A VIEW SECTION B-B VIEW
4" FIBER-REINFORCED 4,000 PSI CONCRETE
FiberForce 750 @ 5lb PER CYD (OR EQUAL)
W/ MEDIUM BROOM FINISH
(UNLESS NOTED OTHERWISE).
A A
B B
4" MDOT CLASS II COMPACTED
GRANULAR MATERIAL BASE 4" MDOT CLASS II COMPACTED
GRANULAR MATERIAL BASE
DIVIDE SIDEWALK INTO SQUARE
UNITS WITH AREAS OF AT LEAST 16
SFT BUT NO MORE THAN 100 SFT.
PLACE JOINTS AS NEAR TO
PERPENDICULAR AS POSSIBLE
WITH SIDEWALK EDGE. MINIMIZE
NARROW OR POINTED PIECES.
STANDARD STATE APPROVED
ACCESSIBLE SIGNAGE INSTALLED
ON A METAL SIGN POST AT THE
PROPER HEIGHT REQUIRED.
PROVIDE ADDITIONAL
SIGNAGE BELOW THE
ACCESSIBLE SIGN AS
REQUIRED PER REGULATIONS.
BOLT SIGNS TO HEAVY
DUTY GALVANIZED STEEL
SIGN POST
HEAVY DUTY
U-CHANNEL
GALVANIZED STEEL
SIGN POST
GROUND GRADE
AT SIDEWALK
2.
5'
M
IN
7'
M
IN
CONCRETE SURROUND
AROUND PIPE COLUMN
6" DIAMETER CONCRETE FILLED
STEEL PIPE BOLLARD WITH
PLASTIC COVER (COLOR PER OWNER)
BOLT SIGNS TO GALVANIZED
METAL 1" DIA. PIPE COLUMN
PROVIDE ADDITIONAL SIGNAGE
BELOW THE HANDICAPPED SIGN AS
REQUIRED PER REGULATIONS
STANDARD STATE APPROVED
HANDICAPPED SIGNAGE INSTALLED
ON A METAL COLUMN AT THE
PROPER HEIGHT REQUIRED.
2' -0
1'-6" MIN.
2' -6
5' -0
M
IN
ACCESSIBLE PARKING
SIGN
08002 NOT TO SCALE HANDICAP PARKING SIGN
08002 NOT TO SCALE
15'-0"
'-0
11'-0" 5'-0" 11-0"
5' -0
4" PARKING SPACE STRIPE,
BLUE COLOR
4" PAINTED STRIPES - H.C. BLUE
COLOR @ 24" O.C. AT 45 DEGREES.
BOLLARD WITH HANDICAP
PARKING SIGN, AS REQUIRED
CONC. SIDEWALK
(BROOM FINISH)
BOLLARD WITH
HANDICAP
PARKING SIGN,
AS REQUIRED
NOTE:
ALL HANDICAPPED RAMP AND ACCESS
AISLES SHALL MEET ALL CODES AND
ADAAG REGULATIONS.
HANDICAP PARKING
08001 NOT TO SCALE
2% MAX.
PAVEMENT
SLOPE IN ALL
DIRECTIONS
STANDARD HANDICAP PARKING
SYMBOL PAINTED ON PAVEMENT,
BLUE COLOR
FLOW
4" MIN. 4" MIN
NOTE:
INLETS SHALL BE
CONSTRUCTED IN
ACCORDANCE WITH ASTM
SPECIFICATION C-478
ALL PIPE SHOULD BE
INSTALLED WITH
FLEXIBLE RUBBER
BOOTS AT STRUCTURES
AND O-RING GASKETS AT
ALL JOINTS
EXTRUDIBLE PRE-FORMED
PLASTIC GASKET MATERIAL
AT ALL JOINTS
E.J.I.W. FRAME #1130 WITH TYPE M1
ADA RATED GRATE, OR E.J.I.W. 1020
FRAME WITH M3 ADA RATED GRATE
PRECAST CONCRETE
ADJUSTING RINGS
(2 MAX, 8" MAX)
PRECAST REINFORCED
CONCRETE
V A
R
IE
S
S E
E P
LA
N
24" DIA. 3"3"
2' S
U M
P
24" STORM INLET
06011 NOT TO SCALE
SUMP
LEAD
HD CONCRETE SECTION
04002 NOT TO SCALE
6x6-W2.9xW2.9 WWF AT
PAVEMENT MID-DEPTH
NOTES:
EXISTING SUBGRADE - PROOF ROLL AND REPLACE ALL
DEFICIENT/SUSPECT AREAS.
CONCRETE MIX SHALL USE CRUSHED LIMESTONE - NO
GRAVEL OR SLAG.
BROOM FINISH SURFACE AND APPLY CURING
COMPOUND (ASTM C3098 TYPE 2) AT 1 GAL/25 SFT
1.0' MIN.
TOPSOIL
8" - 4,000 PSI FIBER REINFORCED CONCRETE
FiberForce 750 @ 5lb PER CYD (OR EQUAL)
IN SITU SOIL
8" COMPACTED (98%)
MDOT CLASS II GRANULAR MATERIAL
18" COMPACTED (95%) SUBBASE
MDOT CLASS II GRANULAR MATERIAL
File details come from the government source that posted it. Updated .