This document provides details for a federal contract opportunity to upgrade the fire suppression and annunciation system at the Richmond VA Medical Center. The Department of Veterans Affairs is soliciting proposals to provide all labor, materials, and supervision necessary to reconfigure and update the current diesel fire pump and building systems. Work includes demolition, architectural, electrical, plumbing, mechanical, and structural improvements to comply with VA construction standards. The contract period is 275 calendar days with an estimated value between $500,000 and $1,000,000. The solicitation is designated as a service-disabled veteran owned small business set aside and will be available on May 4, 2021, with proposals due around 30 days later. A site visit is scheduled for May 17, 2021 and all questions must be emailed to the specified point of contact.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Upgrade Fire Suppression-Annunciation System, newest first.
File Type Posted
36C24621B0006 0003.docx DOCX document
36C24621B0006 0002.docx DOCX document
36C24621B0006_1.docx DOCX document
WAGE DETERMINATION.pdf PDF
Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA OF WORK

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

PROJECT SITE MAPPROJECT LOCATION MAP

PROJECT IMAGE

/1 /2

:4

:5

A M

GI001

ENG. PROJECT COVER

1 1RK AKS

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

UPGRADE FIRE SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249

VA PROJECT #: 652-18-100 APOGEE PROJECT #: 18-170

DRAWING LIST

No. Description Dwg of Dwg

GI001 ENG. PROJECT COVER 1 1

STRUCTURAL

S-001 GENERAL NOTES & SCHEDULES 1 3

S-101 PLANS 2 3

S-201 SECTIONS & DETAILS 3 3

ARCHITECTURAL

A-101 FIRST FLOOR PLAN 1 2

A-301 SECTIONS AND DETAILS 2 2

CIVIL

C-501 DEMO, SITE, PAVING, AND UTILITY PLAN 1 2

C-502 CONSTRUCTION DETAILS 2 2

FIRE PROTECTION

F-001 FIRE PROTECTION GENERAL INFORMATION 1 3

F-101 FIRST FLOOR FIRE PROTECTION PLANS 2 3

F-501 FIRE PROTECTION DETAILS AND SCHEDULES 3 3

ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 4

E-101 ELECTRICAL NEW WORK PLAN 2 4

E-501 ELECTRICAL DETAILS 3 4

E-601 ONE-LINE DIAGRAM 4 4

DocuSign Envelope ID: 79D23206-AF43-48F6-9A0A-D9DB532986A3

12/17/2020

F

SD

7 8 9 10 11 12

C

D

E

F

G

2 LAYERS OF FIRE RATED GYPSUM

WALL BOARD EACH SIDE OF 16 GA

STEEL STUD PARTITION @ 16"OC,

TYPICAL.

TOP OF WALLS UP TO

BOTTOM OF ROOF,

SEAL TO MAINTAIN

FIRE RATING.

6'-0" X 7'-0" HM 90

MIN RATED DOOR

AND FRAME

TOP OF WALLS UP TO

BOTTOM OF ROOF,

SEAL TO MAINTAIN

FIRE RATING.

NEW 2 HR RATED WALL TO

EXTEND FROM TOP OF

EXISTING CMU WALL TO

UNDERSIDE OF STRUCTURE.

A-301

A-301

7'-10" 6'-3"

VIF

17'-2"

4' -1

3'

-6

/2

2' -2

AL

IG

N

MIN.

4'-6"

3 3

A-301

SIM.

5 5

## KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

4/

0:

:3

AM

A-101

FIRST FLOOR PLAN

1 2DMM, LW GTS

UPGRADE FIRE

SUPPRESSION AND

ANNUNICATION SYSTEM

H.H MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

Scale: 1/4" = 1'-0"

1 FIRST FLOOR PLAN 0 4 8 16

N O

R

TH

TRUE

N

KEY PLAN

SCALE: NO SCALE

1 SAW CUT, REMOVE AND REPLACE CONCRETE SLAB

FOR NEW UG PIPE.

1 NEW FIRE PUMP PACKAGE UNIT, SEE SHEET

F-501 FOR CORRESPONDING DETAILS AND

INFORMATION.

2 EXISTING SIAMESE CONNECTIONS TO REMAIN.

3 EXISTING TRANSFORMER

4 12" PIPE, COORDINATE WITH ENGINEERS'

DRAWINGS.

5 EXISTING ELECTRICAL EQUIPMENT.

F

SE

E

SC

H

ED

U

LE

SCHEDULE

SEE

2" 2"

SCHEDULE

SEE

SE

E

SC

H

ED

U

LE

2"

DOOR AND

FRAME - SEE

DOOR SCHEDULE

CAULK BOTH

SIDES OF DOOR -

CONTINUOUS

(2) 2x METAL

STUDS TO FORM

HEADER

SEE DOOR

SCHEDULE

6" 2 LAYERS OF

FIRE RATED

GYPSUM WALL

BOARD BOTH

SIDES

DOOR AND

FRAME - SEE

DOOR

SCHEDULE

CAULK BOTH

SIDES OF DOOR -

CONTINUOUS

(2) 2x METAL

STUDS TO

FORM JAMB

6"

2 LAYERS FIRE

RATED GYPSUM

WALL BOARD

BOTH SIDES

T.O. SLAB

0"

T.O. RETAINING WALL

10' - 0"

T.O. JOIST ROOF LOW

POINT

27' - 0"

SEAL WALL AROUND

JOISTS TO MAINTAIN FIRE

RATING PER U.L. DETAIL

W-L-1065

SLIP TRACK, SEE

STRUCTURAL DRAWINGS

2 LAYERS OF 5/8" FIRE

RATED GYPSUM WALL

BOARD BOTH SIDES

6" METAL STUD FRAMING

EXISTING CMU

RETAINING WALL TO

REMAIN

'-0

SEAL BOTH SIDES

T.O. SLAB

0"

T.O. RETAINING WALL

10' - 0"

T.O. JOIST ROOF LOW

POINT

27' - 0"

SLIP TRACK, SEE

STRUCTURAL DRAWINGS

2 LAYERS OF 5/8" FIRE

RATED GYPSUM WALL

BOARD BOTH SIDES

6" METAL STUD FRAMING

SEAL BOTH SIDES

NOTE: SEAL ALL PENETRATIONS

THROUGH WALL TO MAINTAIN 2 HOUR

FIRE RATING PER U.L. DETAIL W-L-1065

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

4/

0:

:3

AM

A-301

SECTIONS AND DETAILS

2 2DMM, LW GTS

UPGRADE FIRE

SUPPRESSION AND

ANNUNICATION SYSTEM

H.H MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

DOOR SCHEDULE

Level

DOOR DOOR FRAME HEAD

DETAIL NO.

JAMB

DETAIL NO. LBL

HDWR

SET REMARKSNO. WIDTH HEIGHT THICK MAT'L FINISH ELEV MAT'L FINISH ELEV

T.O. SLAB 01 6' - 0" 7' - 0" 1 3/4" HM PT F HM PT 1 H1 J1 90MIN HW-12G PAINT DOOR AND FRAME TO MATCH EXISTING.

PROVIDE ADO.

Scale: 1/4" = 1'-0"

D1 DOOR ELEVATION

Scale: 1/4" = 1'-0"

F1 FRAME ELEVATION

Scale: 1 1/2" = 1'-0"

H1 HEAD DETAIL @ METAL STUD

Scale: 1 1/2" = 1'-0"

J1 JAMB DETAIL @ METAL STUD

Scale: 1/2" = 1'-0"

1 SECTION THRU EXISTING CMU WALL

Scale: 1/2" = 1'-0"

2 TYPICAL WALL SECTION

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

SIDEWALK

SIDEWALK

S

I

D

E

W

A

L

K

F

E

N

C

E

FENCE

CONC.

CONC.

C O

N C

CONC.

CONC.

DRAIN MH

TOP 178.66'

ELEC. BOX

POW

PO

W

INV. 173.12'

173.84'

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SSSS

SS

SS

SS

SS

SS

SS

SS

SS

SS

170.09'

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

I N

V

171.27'

12"

C O

N C

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

ELEC.BOX WI RISER

CONNECTIONS

DRAIN

MH

TOP

178.40'

BUILDING

FF=179.04'

ELEC.

BOXES

H/C

RAMP

INV. 170.30'

SAN. MH

TOP 178.00'

INV. 170.36'

SAN. MH

TOP 177.85'

CURB &

GUTTER

EDGE OF

CONCRETE

SAN. MH

TOP 177.75'

SAN. MH

TOP 177.93' INV.

170.15'

STEPS

BUILDING

FF=179.39'

SIAMESE

HYDRANTS

SAN. MH

TOP 178.75'

ELEC.

BOXES

EDGE OF

CONCRETE

BUILDING

FF=178.99'

FILLER

CAPS

ELEC.

BOX

CURB &

GUTTER

PEDESTRIAN

CROSSING

CURB &

GUTTER

CALL

BOX

BUILDING

FF=178.21'

12"

PINE

PAVED

AREA

TRANSFORMER

ON CONC. PAD

BENCHMARK

'X' ON CORNER

OF CONC. PAD

ELEV.=178.15'

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

W W

W W

W W

W W

W W

W W

W W

W W

W W

UG/E UG/E UG/E UG/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

WW

WWWWWWWWWW

W W

W W

W W

W W

W W

W

W

W

W

W

W

W

W

W

W

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/EUG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

GAS

GAS

GAS

GAS

GAS

GAS

GAS

UG/E UG/E UG/E UG/E UG/E UG/E

UG

/E

UG

/E

UG

/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/T UG/T UG/T UG/T UG/T UG/T

UG

/T

UG

/T

UG

/T

UG/T

UG/T

UG/T

UG/T

UG/T

UG/E UG/E UG/E UG/E UG/E UG/E

UG/E

UG/E

UG/E

UG/E UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/EUG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

LOD

LOD

LOD

LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD

LOD

LODLODLODLODLODLOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LODLOD

LODLOD

EXISTING BOLLARD

(TO BE REMOVED, TYP.)

EXISTING FIRE HYDRANT

(TO REMAIN, TYP.)

EXISTING ASPHALT PAVEMENT

(TO BE SAWCUT, REMOVED, AND

REPLACED FOR PROPOSED WATER LINE)

EXISTING SEWER LINE

(TO REMAIN, TYP.)

EXISTING UNKNOWN UTILITY

(TO REMAIN)

EXISTING CONCRETE SIDEWALK

(TO BE SAWCUT, REMOVED, AND

REPLACED FOR PROPOSED WATER LINE)

EXISTING WATER LINE

(TO REMAIN, TYP.)

EXISTING UNDERGROUND ELECTRICAL LINE

(TO REMAIN, TYP.)

EXISTING SEWER MANHOLE

(TO REMAIN)

66.89'

29.35'

27.01'

3.01'

EXISTING CURB AND GUTTER

(TO BE SAWCUT, REMOVED, AND REPLACED)

EXISTING WATER SERVICE

(TO REMAIN)

EXISTING TRANSFORMER

(TO REMAIN)

EXISTING GAS LINE

(TO REMAIN)

4'

EXISTING MANHOLE AND SEWER LINE

(TO REMAIN)

EXISTING UNDERGROUND

PHONE LINE

(TO REMAIN)

EXISTING FENCE

(TO REMAIN)

EXISTING ELECTRICAL LINE

(TO REMAIN)

EXISTING WATER LINE

(TO REMAIN)

EXISTING FIRE

HYDRANT

(TO REMAIN)

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

OHP

SIDEWALK

SIDEWALK

S

I

D

E

W

A

L

K

F

E

N

C

E

FENCE

CONC.

CONC.

C O

N C

CONC.

CONC.

ELEC. BOX

POW

PO

W

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SSSS

SS

SS

SS

SS

SS

SS

SS

SS

SS

170.09'

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

I N

V

171.27'

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

ELEC.BOX WI RISER

CONNECTIONS

BUILDING

FF=179.04'

ELEC.

BOXES

H/C

RAMP

INV. 170.30'

SAN. MH

TOP 178.00'

INV. 170.36'

SAN. MH

TOP 177.85'

CURB &

GUTTER

EDGE OF

CONCRETE

SAN. MH

TOP 177.75'

SAN. MH

TOP 177.93' INV.

170.15'

STEPS

BUILDING

FF=179.39'

SAN. MH

TOP 178.75'

ELEC.

BOXES

EDGE OF

CONCRETE

BUILDING

FF=178.99'

ELEC.

BOX

CURB &

GUTTER

PEDESTRIAN

CROSSING

CURB &

GUTTER

CALL

BOX

BUILDING

FF=178.21'

12"

PINE

PAVED

AREA

TRANSFORMER

ON CONC. PAD

BENCHMARK

'X' ON CORNER

OF CONC. PAD

ELEV.=178.15'

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

W W

W W

W W

W W

W W

W W

W W

W W

W W

UG/E UG/E UG/E UG/E

UG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

WW

WWWWWWWWWW

W W

W W

W W

W W

W W

W

W

W

W

W

W

W

W

W

W

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/EUG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

GAS

GAS

GAS

GAS

GAS

GAS

GAS

UG/E UG/E UG/E UG/E UG/E UG/E

UG

/E

UG

/E

UG

/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/T UG/T UG/T UG/T UG/T UG/T

UG

/T

UG

/T

UG

/T

UG/T

UG/T

UG/T

UG/T

UG/T

UG/E UG/E UG/E UG/E UG/E UG/E

UG/E

UG/E

UG/E

UG/E UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/E

UG

/E

UG

/E

UG

/E

UG

/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/EUG/EUG/EUG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

UG/E

66.89'

27.01'

3.01'

PROPOSED ELECTRICAL FIRE PUMP IN ENCLOSURE

(SEE FIRE PROTECTION PLANS FOR DETAILS)

PROPOSED 12' X 24' LEVEL CONCRETE PAD FOR

PROPOSED ELECTRIC FIRE PUMP

(REFERENCE STRUCTURAL PLANS PER PAD DETAILS)

C-502

REMOVABLE POST

BOLLARD (TYPE A)

(TYP.)

C-502

UTILITY TRENCH PATCH

(TYP.)

PROPOSED CURB

AND GUTTER

(TO MATCH EXISTING)

PROPOSED CONCRETE SIDEWALK

(TO MATCH EXISTING)

PROPOSED SOD

(TYP.)

PROPOSED 8" DIP FIRE WATER LINE

CONTRACTOR SHALL REFER TO FIRE PLANS

FOR DETAILS AT THE BUILDING

PROPOSED POST INDICATOR VALVE

(SEE FIRE PROTECTION PLANS FOR DETAILS)

CONTRACTOR SHALL REFER TO FIRE PLANS

FOR FIRE PUMP CONNECTIONS

PROPOSED 12" DIP FIRE WATER LINE

PROPOSED WATER SERVICE CONNECTION

WITH 12"X8"X12" TAPPING SLEEVE

29.35' 4'

PROPOSED ELECTRICAL DUCT BANK

(SEE ELECTRICAL PLANS FOR DETAILS)

24'

PROPOSED ELECTRICAL DUCT BANK

(SEE ELECTRICAL PLANS FOR DETAILS)

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of

Construction and Facilities

Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

A

M

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-100

18-170

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

GRADING AND DRAINAGE PLAN LEGEND

EXISTING CONTOURS

PROPOSED CONTOURS

EXISTING SPOT ELEVATION

PROPOSED SPOT ELEVATION

PROPOSED TOP OF CURB / BOTTOM OF CURB

SPOT ELEVATION

TC

BC

XXXX.XX

XXXX.XX

XXXX.XX

XXXX.XX

XXXX

XXXX

SCALE: 1" = 20'

C-501

DEMOLITION PLAN

SCALE: 1" = 20'

C-501

SITE, PAVING, AND UTILITY PLAN

SITE AND PAVING PLAN LEGEND

PROPOSED HEAVY DUTY ASPHALT PAVING

PROPOSED CONCRETE SIDEWALK PAVING

PROPOSED CONCRETE PAVING

PROPOSED LANDSCAPING

PROPERTY LINE

DEMOLITION PLAN LEGEND

CONCRETE SIDEWALK AND/OR CURB & GUTTER TO BE

REMOVED

ASPHALT PAVING TO BE REMOVED

LANDSCAPING TO BE REMOVED

PROPERTY LINE

LIMITS OF DISTURBANCE

LOD LOD LOD

GENERAL NOTES:

1. CONTRACTOR TO PROVIDE TEMPORARY FENCING IN THE FORM

OF A 6' HIGH GALVANIZED CHAIN LINK FENCE AROUND THE

PROPOSED IMPROVEMENTS.

2. ALL NEW WORK SHOWN IN THESE SHEETS SHALL COMPLY WITH

APPLICABLE STATE, FEDERAL, AND LOCAL BUILDING AND UTILITY

INSTALLATION CODES.

3. ALL MATERIALS AND CONSTRUCTION METHODS SHALL BE IN

ACCORDANCE WITH DEPARTMENT OF VETERAN AFFAIRS

TECHNICAL INFORMATION LIBRARY STANDARD SPECIFICATIONS.

4. THERE MAY BE ADDITIONAL UTILITIES NOT SHOWN ON THESE

PLANS. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR

LOCATIONS SHOWN, AND IT SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR TO FIELD VERIFY THE LOCATIONS OF ALL UTILITIES

WITHIN THE LIMITS OF CONSTRUCTION AND TO NOTIFY THE OWNER

IN CASE OF DISCREPANCIES THAT AFFECT THE CONSTRUCTION

PROJECT.

5. THE CONTRACTOR IS RESPONSIBLE FOR NOTIFICATION OF AND

LIAISON WITH VETERAN AFFAIRS IN THE PROCESS OF LOCATION

AND RELOCATION OF AND TIE-IN TO VETERAN AFFAIRS' UTILITIES.

6. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE THAT MAY

OCCUR TO ANY ADJACENT STRUCTURES OR PROPERTY, OR ANY

EXISTING STRUCTURES WITHIN LIMITS OF CONSTRUCTION THAT

ARE DESIGNATED ON THE PLANS TO REMAIN, AND SHALL REPAIR

OR REPLACE SUCH DAMAGED PROPERTY TO THE VETERAN

AFFAIRS' SATISFACTION AT NO COST TO THE VETERAN AFFAIRS.

7. THE CONTRACTOR SHALL NOT DEVIATE FROM THESE PLANS

AND SPECIFICATIONS WITHOUT THE PRIOR WRITTEN CONSENT OF

THE ENGINEER.

8. CONTRACTOR IS RESPONSIBLE FOR CONTACTING

DEPARTMENT OF VETERAN AFFAIRS AND ALL EXISTING UTILITY

PROVIDERS BEFORE REMOVING ANY/ALL UTILITIES FROM THEIR

EXISTING LOCATION ON THE SITE. THE CONTRACTOR SHALL

PERFORM ALL UTILITY DEMOLITION OR RELOCATION ACTIVITIES IN

ACCORDANCE WITH THE EXISTING UTILITIES SPECIFICATIONS,

MATERIALS, AND REQUIREMENTS.

9. THE CONTRACTOR SHALL SEQUENCE THE WORK AND PROVIDE

TEMPORARY MEASURES AS NECESSARY TO MAINTAIN ACCESS TO

THE SITE THROUGH ALL ENTRANCES AT ALL TIMES DURING

CONSTRUCTION. TEMPORARY PROVISIONS MAY INCLUDE, BUT ARE

NOT LIMITED TO: BARRICADES, FLASHING LIGHTS, FLAGMAN,

TEMPORARY PAVEMENT, AND DIRECTIONAL SIGNAGE AS

NECESSARY TO ACCOMPLISH THE WORK.

10. CONTRACTOR SHALL CONSIDER COORDINATION ASPECTS OF

CRANES AND CONSTRUCTION EQUIPMENT OPERATIONS DURING

DEMOLITION ACTIVITY.

11. COORDINATE WITH DEPARTMENT OF VETERAN AFFAIRS CODES

ENFORCEMENT DIVISION AS REQUIRED DURING ALL DEMOLITION

AND NEW CONSTRUCTION ACTIVITIES.

12. ALL ITEMS DESIGNATED FOR REMOVAL SHALL BE LEGALLY

DISPOSED OF, OFF SITE.

13. CONTRACTOR TO POT HOLE EXISTING WATER LINE,

UNDERGROUND ELECTRICAL LINES, GAS LINE, UNDERGROUND

TELEPHONE, FIBER OPTIC, AND ANY OTHER UTILITY LINES DURING

DEMOLITION ACTIVITIES AND COORDINATE FIELD LOCATIONS AND

DEPTHS OF THESE UTILITIES WITH ENGINEER FOR PROPOSED

UTILITY CROSSINGS AND PROPOSED PAVEMENT OVER EXISTING

LINES. THESE LINES MAY REQUIRE RELOCATION.

14. THE CONTRACTOR SHALL PROVIDE DUST CONTROL AND SHALL

PROTECT ADJACENT PAVEMENTS FROM SOIL ACCUMULATION

DURING CONSTRUCTION.

15. ADDITIONAL EROSION CONTROL DEVICES MAY BE REQUIRED

BY THE ENGINEER OR OTHER INSPECTORS AS DETERMINED BY

FIELD CONDITIONS.

16. STORM DRAINAGE STRUCTURES AND CONDUITS SHALL BE

PROTECTED FROM SEDIMENTATION AS REQUIRED BY STATE OR

LOCAL CODES.

17. A SUBSURFACE UTILITY LOCATION LEVEL B INVESTIGATION

WAS PERFORMED FOR THE SITE, UTILIZING GROUND PENETRATING

RADAR AND AN ELECTROMAGNETIC PIPE LOCATOR (SEE SHEET

V-101). EVERY EFFORT WAS MADE TO LOCATE ANY AND ALL

UNDERGROUND UTILITIES ON SITE, BUT THERE MAY BE ADDITIONAL

UTILITIES NOT SHOWN ON THESE PLANS. THE ENGINEER ASSUMES

NO RESPONSIBILITY FOR THE LOCATIONS SHOWN. THE

CONTRACTOR IS REQUIRED TO PERFORM THERE OWN

SUBSURFACE UTILITY LOCATION PRIOR TO CONSTRUCTION.

CONTRACTOR SHALL NOTIFY THE ENGINEER IN CASE OF

DISCREPANCIES THAT AFFECT THE CONSTRUCTION PROJECT.

CONTRACTOR IS REQUIRED TO POTHOLE ALL UTILITIES CROSSINGS

WITH THE PROPOSED IMPROVEMENTS. CONTRACTOR SHALL

NOTIFY THE ENGINEER IN CASE OF DISCREPANCIES THAT AFFECT

THE CONSTRUCTION PROJECT.

GENERAL NOTES:

1) ALL PROPOSED DIMENSIONS USED TO SHOW THE GEOMETRIC

LAYOUT OF THE PROPOSED PARKING LOT ARE SHOWN AT THE FACE

OF CURB. ALL PROPOSED DIMENSIONS USED TO SHOW THE

GEOMETRIC LAYOUT OF THE PROPOSED BUILDING LOCATION ARE

GIVEN AT THE OUTSIDE FACE OF THE BUILDING CORNERS. ALL

CURB RADII ARE GIVEN AT THE FACE OF CURB.

2) CONTRACTOR SHALL NOTIFY VETERANS AFFAIRS OF ANY

DISCREPANCIES BETWEEN THE EXISTING CONDITIONS IN THE FIELD

AND THE SURVEY SHOWN ON THE PLANS BEFORE PROCEEDING

WITH ANY NEW CONSTRUCTION.

3) CONTRACTOR IS RESPONSIBLE FOR CORRECT HORIZONTAL

AND VERTICAL ALIGNMENT OF ALL TIES BETWEEN PROPOSED AND

EXISTING PAVEMENTS, CURB AND GUTTER, SIDEWALKS, WALLS,

AND UTILITIES.

4) MAXIMUM CUT OR FILL SLOPE= 2H:1V.

5) THRUST BLOCKING TO BE PROVIDED AT ALL HORIZONTAL AND

VERTICAL BENDS ALONG THE PROPOSED FIRE WATER LINE.

GENERAL NOTES:

1) ALL SPOT ELEVATIONS SHOWN ARE AT THE EDGE OF

PAVEMENT UNLESS OTHERWISE NOTED.

SITE NOTES:

1) THE CONTRACTOR SHALL CLEAN OUT ACCUMULATED SILT IN

STORM WATER CONVEYANCE CHANNELS AND PIPES AT END OF

CONSTRUCTION WHEN DISTURBED AREAS HAVE BEEN STABILIZED.

2) IN ALL AREAS OF FILL OR OTHERWISE DISTURBANCE OF

EXISTING CONDITIONS, UNLESS OTHERWISE NOTED, THE

CONTRACTOR SHALL FULLY AND COMPLETELY REMOVE AND

LEGALLY DISPOSE OFF-SITE, ALL PLANT MATERIALS INCLUDING BUT

NOT LIMITED TO ROOT SYSTEMS, CONCRETE, REINFORCED

CONCRETE, ASPHALT DEBRIS, UNDERBRUSH, TOPSOIL, AND OTHER

DELETERIOUS MATERIAL. THE SUBGRADE TO REMAIN SHALL BE

COMPACTED TO 95% STANDARD PROCTOR MAXIMUM DRY DENSITY

FOLLOWING FULL REMOVAL OF THESE MATERIALS.

3) EXTREME CAUTION SHALL BE USED WHEN WORKING WITHIN

THE VICINITY OF THE EXISTING OVERHEAD POWER LINES.

CONTRACTORS SHALL NOTIFY/COORDINATE WITH VETERANS

AFFAIRS PRIOR TO CONSTRUCTION.

LEGEND

EXISTING FENCE LINE

PROPERTY LINE

EXISTING OVERHEAD POWER LINE

EXISTING UNDERGROUND POWER LINE

EXISTING UNDERGROUND TELEPHONE LINE

EXISTING GAS LINE

EXISTING SANITARY SEWER LINE

EXISTING WATER LINE

EXISTING STORM LINE

EXISTING UNKNOWN UTILITY LINE

PROPOSED FIRE WATER LINE

W W W

SS SS SS

GAS GAS GAS

UG/T UG/T

UG/E UG/E

OHP OHP OHP

N

TRUE NORTH

0 2010 40

N

TRUE NORTH

0 2010 40

N

KEY PLAN

SCALE: NO SCALE

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of

Construction and Facilities

Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

A

M

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-100

18-170

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

TYPE 3 UTILITY TRENCH PATCH

NOT TO SCALE

C-502

REMOVABLE POST BARRICADE

NOT TO SCALE

C-502

REMOVABLE POST BARRICADE - STRAP DETAIL

NOT TO SCALE

C-502

UTILITY TRENCHING SCHEMATIC DETAIL

NOT TO SCALE

C-502

C-502

CONCRETE POST BARRICADES

NOT TO SCALE

THRUST BLOCKING FOR HIGH PRESSURE SYSTEM

NOT TO SCALE

C-502

THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA

13. IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE

PROTECTION WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS

DRAWING IS “FOR INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE

PROTECTION CONTRACTOR TO BASE THE DESIGN OF THE FIRE PROTECTION

SYSTEM ON. THE CONTRACTOR SHALL VERIFY THE EXACT CONDITIONS THAT THIS

DRAWING REPRESENTS, INCLUDING ANY PERCEIVED CONCEALED SPACES, AND THE

BUILDING TYPE AND CONSTRUCTION AS OUTLINED IN THE INTERNATIONAL BUILDING

CODE, PRIOR TO THE START OF WORK. REFER TO THE INTERNATIONAL BUILDING

CODE, ESPECIALLY CHAPTERS 6 (TYPES OF CONSTRUCTION) AND CHAPTER 9 (FIRE

PROTECTION SYSTEMS), NFPA 13 (CHAPTER 8), AND THE PROJECT SPECIFICATIONS

FOR OTHER FIRE PROTECTION REQUIREMENTS.

FIRE PROTECTION GENERAL NOTES

FIRE PROTECTION CONTRACTOR

SEMI-RECESSED SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

FIRE LINE

FPC

FL

TAMPER SWITCH

FLOW SWITCH

CONCEALED SPRINKLER HEAD

PENDANT SPRINKLER HEAD CHECK VALVE

GATE VALVE

EXTERIOR ALARM GONG (WATER ACTIVATED)

TEST AND DRAIN ASSEMBLY

ORDINARY HAZARD

GROUP 1 OCCUPANCY

SIDEWALL SPRINKLER HEAD

FIRE DEPARTMENT CONNECTION (FDC)

NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT

FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

KEYNOTE

DETAIL OR SECTION MARK

SHOWN ON DRAWING

DETAIL MODULE NUMBER POINT OF NEW CONNECTION

LIMIT OF DEMOLITION

BACKFLOW PREVENTER

FIRE PROTECTION DEMOLITION GENERAL NOTES

A. LOCATIONS SHOWN FOR EXISTING FIRE PROTECTION PIPE AND EQUIPMENT ARE APPROXIMATE. THE CONTRACTOR IS

TO FIELD VERIFY THE EXACT LOCATIONS OF EXISTING FIRE PROTECTION LINES AND EQUIPMENT INCLUDING RISERS AND

VALVES PRIOR TO THE START OF WORK.

B. COORDINATE WITH VA FOR ANY SHUTDOWNS OR PLANNED INTERRUPTIONS OF THE FIRE PROTECTION SERVICE. THE CONTRACTOR SHALL GIVE THE OWNER THREE (3) DAYS NOTICE PRIOR TO THE PLANNED SHUTDOWN OR

INTERRUPTION.

C. COORDINATE DEMOLITION OF FIRE PROTECTION PIPING WITH OTHER PIPING WHICH IS NOT TO BE REMOVED. PROTECT

OTHER PIPING WHICH IS NOT TO BE REMOVED FROM DAMAGE, DIRT, AND DEBRIS.

D. ALL FIRE PROTECTION RELATED EQUIPMENT AND PIPING WHICH IS REMOVED FROM THE BUILDING IS TO BE TAKEN

OFFSITE AND DISPOSED OF.

BUILDING AND OCCUPANT SAFETY -

INTERRUPTION OF FIRE PROTECTION SERVICE

A. DURING THE TIME THAT THE FIRE PROTECTION RENOVATION WORK IS BEING PERFORMED, AND THE FIRE PROTECTION SYSTEM IS DOWN AND OUT OF COMMISSION, THE FIRE PROTECTION CONTRACTOR SHALL HAVE SUFFICIENT PERSONNEL ONSITE TO KEEP A “FIRE WATCH” ON THE FACILITY. COORDINATE THIS WITH VA COR.

B. A FIRE PROTECTION WATCH IS IMPLEMENTED TO ENSURE THE FIRE SAFETY OF A BUILDING IN THE EVENT OF ANY ACT, OR SITUATION INSTIGATING AN INCREASED RISK TO PERSONS OR PROPERTY. THE TERM “FIRE WATCH” IS USED TO DESCRIBE A DEDICATED PERSON OR PERSONS WHO’S SOLE RESPONSIBILITY IS TO LOOK FOR FIRES WITHIN AN

ESTABLISHED AREA.

C. FIRE WATCH PERSONNEL ARE TO KEEP WATCH FOR FIRES IN THE GENERAL AREA OF PERFORMANCE, THE PERSONS

PERFORMING THE FIRE WATCH ARE NOT PERMITTED TO PERFORM ANY OTHER DUTIES.

D. FIRE WATCH PERSONNEL ARE TO HAVE FIRE EXTINGUISHING EQUIPMENT READILY AVAILABLE AND TO BE TRAINED IN ITS

USE.

E. THE QUANTITY OF PERSONNEL INVOLVED IN THE FIRE WATCH IS TO BE ADEQUATE SUCH THAT EACH FLOOR, LEVEL, AND

ROOM OF THE FIRE AREA IS COVERED. COORDINATE THIS WITH VA COR.

T&D

TS

FS

ORDINARY HAZARD

GROUP 2 OCCUPANCY

A. THESE FIRE PROTECTION DRAWINGS ARE DIAGRAMMATIC IN NATURE. SPRINKLER HEAD TYPES AND APPROXIMATE LOCATIONS HAVE BEEN ESTABLISHED. THE FIRE PROTECTION LAYOUT INDICATED IS FOR REFERENCE ONLY. FINAL SYSTEM LAYOUT AND PIPE ROUTING SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR AND SHALL TAKE INTO CONSIDERATION THE BUILDING STRUCTURE, ARCHITECTURAL FEATURES AND SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES. THE FIRE PROTECTION CONTRACTORS SHALL PROVIDE WORKING DRAWINGS IN

ACCORDANCE WITH NFPA 13 FOR REVIEW AND APPROVAL BY COR.

B. ADJUST SPRINKLERS TO BE PLACED IN THE CENTER OF THE CEILING TILE IT IS SHOWN IN.

C. MODIFICATION TO EXISTING SPRINKLER SYSTEMS SHALL RESULT IN A COMPLETE AND WORKING WET PIPE SPRINKLER

SYSTEM THAT IS IN COMPLIANCE WITH CONTRACT DOCUMENTS AND NFPA 13.

D. ALL WORK SHALL BE CONDUCTED IN ACCORDANCE WITH NFPA 13, THE DEPARTMENT OF VETERANS AFFAIRS, FIRE PROTECTION DESIGN MANUAL 7TH EDITION AND ALL OTHER APPLICABLE CODES AND STANDARDS.

E. LIGHT HAZARD OCCUPANCIES: OFFICE AND CUSTOMARY ACCESS AREAS. LIGHT HAZARD SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM DENSITY OF 0.10 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST

REMOTE 1500 SQ.FT.

F. ORDINARY HAZARD GROUP 1 OCCUPANCIES: MECHANICAL ROOMS, TRANSFORMER ROOMS, ELECTRICAL SWITCHGEAR ROOMS AND ELECTRICAL CLOSETS. ORDINARY HAZARD GROUP 1 SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM DENSITY OF 0.15 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ.FT.

G. ORDINARY HAZARD GROUP 2 OCCUPANCIES: STORAGE ROOMS, TRASH ROOMS, CLEAN AND SOILED LINEN ROOMS AND KITCHENS. ORDINARY HAZARD GROUP 2 SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM

DENSITY OF 0.20 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ.FT.

H. PRIOR TO THE OPERATION (OPENING OR CLOSING) OF ANY VALVES CONTROLLING WATER TO THE DOMESTIC OR FIRE SYSTEMS, NOTIFICATION SHALL BE GIVEN TO THE COR AND APPROVAL MUST BE OBTAINED BEFORE BEGINNING OF

WORK.

I. PROVIDE PIPING OFFSETS AS REQUIRED TO AVOID DUCTWORK, STRUCTURE, OTHER TRADES OR OTHER

OBSTRUCTIONS.

J. ALL PIPE SHALL BE INSTALLED ABOVE CEILINGS IN AREAS WITH FINISHED CEILINGS AND CORRESPONDING SPRINKLER HEADS SHALL BE RECESSED. IN AREAS WITH EXPOSED STRUCTURE, PIPING SHALL BE EXPOSED AND PAINTED TO MATCH ADJACENT SURFACES. IN NO CASE SHALL ANY EXPOSED SPRINKLER PIPING BE INSTALLED BELOW THE BOTTOM

HORIZONTAL PLANE OF LIGHTING FIXTURES.

K. NEW ZONE PIPING SHALL BE HYDRAULICALLY CALCULATED WITH THE AVAILABLE SUPPLY AND RESIDUAL PRESSURE AS SHOWN IN THE SPECIFICATIONS. PERFORM HYDRAULIC CALCULATIONS UTILIZING THE AREA/DENSITY METHOD. DESIGN AREA REDUCTIONS ARE PERMITTED WHEN USING QUICK RESPONSE SPRINKLERS. MINIMUM DESIGN AREA IS 1500 SQ.FT.

INCLUDE AN ALLOWANCE FOR A 250 GPM HOSE STREAM AT THE BASE OF THE RISER. SHOP DRAWINGS SHALL BE PREPARED AND SEALED STAMPED BY A REGISTERED PROFESSIONAL ENGINEER IN THE FIELD OF FIRE PROTECTION.

L. VERIFY ALL DISTANCES, HEIGHTS AND DIMENSIONS OF THE BUILDING AND ITS SYSTEMS PRIOR TO THE START OF WORK.

M. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS EXCEPT WHERE SPECIFICALLY PROHIBITED (E.G., HIGH TEMPERATURE AREAS AS DEFINED IN NFPA 13). ALL SPRINKLERS SHALL BE UL LISTED AND FM APPROVED.

N. ALL VALVES SHALL BE READILY ACCESSIBLE FOR OPERATION.

O. CONTRACTOR SHALL PROVIDE LOW POINT DRAINS AS REQUIRED BY NFPA 13. ALL LOW POINTS SHALL BE MARKED WITH

A SIGN INDICATING "AUXILIARY DRAIN".

P. TEST SPRINKLER SYSTEM, CONTROLS, PIPING AND MONITORING IN ACCORDANCE WITH NFPA 25.

Q. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR BURNED.

R. CONTRACTOR SHALL PRESSURE TEST RISERS AFTER NEW FIRE PUMP IS INSTALLED.

FP FIRE PUMP

AUTOMATIC AIR

RELEASE VALVE

M FLOWMETER JP JOCKEY PUMP

SANITARY SEWERSAN

A. CONTRACTOR SHALL COMPLY WITH THE OWNER'S WRITTEN DUST AND NOISE CONTROL REQUIREMENTS

B. EXISTING AIR QUALITY REQUIREMENTS AND OTHER UTILITY REQUIREMENTS FOR OCCUPIED AREAS SHALL BE

MAINTAINED.

C. RENOVATION AREAS SHALL BE ISOLATED FROM OCCUPIED AREAS DURING CONSTRUCTION USING AIRTIGHT BARRIERS.

PROVIDE EXHAUST AIRFLOW IN A MANNER THAT SHALL BE SUFFICIENT TO MAINTAIN NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE. COORDINATE TEMPORARY BARRIERS WITH INTERIM LIFE SAFETY MEASURES.

D. FIRE PROTECTION SYSTEM REVISIONS SHALL BE PROPERLY PERFORMED TO LIMIT WATERBOURNE OPPORTUNISTIC

PATHOGENS.

E. DOUBLE-BAGGING IS REQUIRED FOR CONSTRUCTION DEBRIS. COMPLY WITH OWNER'S DESIGNATED ROUTE FOR

REMOVAL.

DUST AND NOISE CONTROL MEASURES

CONSTRUCTION PHASING

PHASE - 1 ( REQUIRE EXISTING FIRE PUMP SHUTDOWN)

1. INSTALL NEW ELECTRICALLY DRIVEN FIRE PUMP WITH ENCLOSURE AS PER ARCHITECTURAL/CIVIL DRAWINGS.

2. INSTALL SUCTION AND DISCHARGE PIPING TO PUMP AS PER FIRE PROTECTION DRAWINGS.

3. INSTALL FIRE PUMP CONTROL PANEL AND ELECTRICAL POWER TO FIRE PUMP PER ELECTRICAL DRAWINGS.

4. TEST AND COMMISSION FIRE PUMP, AND PUT IN OPERATION.

PHASE - 2

1. RELOCATE DIESEL TANK SERVING EXISTING FIRE PUMP WITH IN BUILDING 501.

2. RE-ORIENT GATE VALVES TO ACCOMMODATE ARCHITECTURAL MODIFICATIONS.

3. PROVIDE ARCHITECTURAL MODIFICATIONS PER ARCHITECTURAL DRAWINGS.

4. TEST AND COMMISSION FIRE PUMP AND PUT IN OPERATION AS BACK UP TO PRIMARY ELECTRICALLY DRIVEN PUMP.

PHASE - 3

1. TEST BOTH FIRE PUMPS PER NFPA REQUIREMENTS TO BE WITNESSED BY VA AND LOCAL FIRE AUTHORITY.

2. TEST PUMP CONTROLS AND CHANGEOVER FROM PRIMARY TO SECONDARY PUMP.

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:3

:4

A M

F-001

FIRE PROTECTION GENERAL

INFORMATION

1 3RK AKS

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA

13. IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE

PROTECTION WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS

DRAWING IS “FOR INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE

PROTECTION CONTRACTOR TO BASE THE DESIGN OF THE FIRE PROTECTION

SYSTEM ON. THE CONTRACTOR SHALL VERIFY THE EXACT CONDITIONS THAT THIS

DRAWING REPRESENTS, INCLUDING ANY PERCEIVED CONCEALED SPACES, AND THE

BUILDING TYPE AND CONSTRUCTION AS OUTLINED IN THE INTERNATIONAL BUILDING

CODE, PRIOR TO THE START OF WORK. REFER TO THE INTERNATIONAL BUILDING

CODE, ESPECIALLY CHAPTERS 6 (TYPES OF CONSTRUCTION) AND CHAPTER 9 (FIRE

PROTECTION SYSTEMS), NFPA 13 (CHAPTER 8), AND THE PROJECT SPECIFICATIONS

FOR OTHER FIRE PROTECTION REQUIREMENTS.

8 9

D

E

F L

F L

F L

F L

D C

W

FIRE SUPPRESSION SERVICE TO BULDING 500

6" x 2 1/2" x 2 1/2" SIDEWALK

FIRE DEPARTMENT SIAMESE

6" x 2 1/2" x 2 1/2" SIDEWALK

HOSE HEADER

S A

N

4" SAN

4" SAN

S A

N

S A

N

4" SAN

S A

N

6" SAN

EXISTING FIRE PUMP CONTROLLER

EX FP

7 8 9

D

E

FP-1

D C

W

F L

F L

FIRE SUPPRESSION SERVICE TO BULDING 500

F L

S A

N

4" SAN 6" SAN

S A

N

EUH-1

*JP-1 IS WITHIN PUMP

ENCLOSURE.

EX FP

F L

F L

12" FL UP

PIV

8" HOSE VALVE

TEST HEADER

PRV

## DEMOLITION KEY NOTES:

# NEW WORK KEYNOTES

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:3

:4

A M

F-101

FIRST FLOOR FIRE PROTECTION

PLANS

2 3RK AKS

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

01 FP-1 IS WITHIN SKID-MOUNTED EXTERNAL FIRE

RATED ENLCOSURE.

02 DEISEL TANK TO BE RELOCATED AS SHOWN.

RECONNECT TO EXISTING FIRE PUMP (EX FP).

03 PROVIDE CHECK VALVE IN VERTICAL POSITION.

04 12" LINE FROM OUTDOOR FIRE PUMP DISCHARGE

ROUTED BELOW SLAB TO CONNECT TO EXISTING

FIRE MAIN SUPPLY TO BUILDING 500. SEE

STRUCTURAL AND CIVIL DRAWINGS FOR EXACT

LOCATIONS.

05 THIS DOOR SHALL REMAIN OPEN DURING FIRE

PUMP OPERATION TO PROVIDE VENTILATION.

PROVIDE ELECTRIC DOOR CLOSER AND

INTERLOCK WITH PUMP CONTROL PANEL TO OPEN

DOOR WHENEVER MAIN PUMP TURNS ON.

06 MODIFY EXISTING SPRINKLER PIPING TO PROVIDE

SPRINKLER COVERAGE IN NEW PUMP ROOM IN

ACCORDANCE WITH NFPA13 AS AN EXTRA

HAZARD GROUP 2 OCCUPANCY CLASSIFICATION.

07 PROVIDE INTERLOCK BETWEEN EX FP AND FP-1.

SEQUENCE OF OPERATIONS SHALL BE AS

FOLLOWS: 1. ON CALL FOR FIRE PUMP FP-1

STARTS. 2. IF FIRE PUMP FAILS TO START IN 10

SECONDS, EX FP SHALL START. 3. IN NO CASE

SHALL TWO PUMPS START SIMULTANEOUSLY.

08 FOR EXACT LOCATION OF FIRE PUMP ENCLOSURE

AND POST INDICATOR VALVE, SEE C-501.

N

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

FIRE PUMP AREA WITHIN BUILDING 501 DEMOLITION

01 GATE VALVES IN VERTICAL SECTION OF PIPING TO

BE RE-ORIENTED TO MAKE ROOM FOR NEW WALL.

02 EXISTING DIESEL TANK TO BE RELOCATED AS

SHOWN.

Scale: 1/4" = 1'-0"

FIRE PUMP AREA WITHIN BUILDING 501 AND NEW PUMP

PIPING PLAN

D. WHEN THE DIESEL PUMP INSIDE THE BUILDING IS IN

OPERATION, THE DOOR TO THE OUTSIDE SHALL BE

OPEN.

C. DIESEL REMOVED FROM TANK BY VA PRIOR TO TANK

RELOCATIOM.

B. PROVIDE SPRINKLER COVERAGE TO NEW FIRE PUMP

ROOM.

A. EXISTING PIPING BELOW SLAB IS SHOWN FOR

COORDINATION PURPOSES BASED ON RECORD

DRAWINGS. ANY DAMAGE TO EXISTING PIPING OR

CONDUIT SHALL BE REPAIRED AT NO COST TO VA.

0 2 4 8

N O

R T

H

TRUE

Scale: No Scale

PHOTO OF EXISING DIESEL ENGINE AND TANK

Scale: No Scale

PHOTO OF EXISTING FIRE PUMP AREA

Scale: No Scale

PHOTO OF EXISTING FIRE PUMP PIPING CONDITIONS

0 2 4 8

N O

R T

H

TRUE

T

NOTES:

1. SKID SHALL BE FILLED WITH CONCRETE AT INSTALLATION. THE

BASE PLATE OF PUMP AND DRIVER SHALL BE GROUTED PER

INSTALAITON INSTRUCTIONS.

2. PIPING TO THE PUMP ENCLOSURE SHOULD NOT BE ANCHORED

RIGIDLY UNTIL FINAL FIT-UP IS COMPLETE.

3. TAMPER SWITCHES SHALL BE PROVIDED ON ALL BUTTERFLY

VALVES, WIRING PROVIDED BY OTHERS.

4. LOCATION OF EQUIPMENT WITHIN ENCLOSURE IS APPROXIMATE.

5. ELECTRICAL SERVICE SHOWN ON ELECTRICAL DRAWINGS.

6. FINAL ORIENTATION AND LAYOUT OF INLET AND OUTLET

LOCATIONS, DOOR LOCATION, ELECTRICAL CONNECTION, PUMP

ROTATION, FDC, TEST DRAIN, AND LIGHTING SHALL BE PER SITE

CONDITIONS. SEE PLANS.

FP

M

TO SYSTEM

METER CONTROL VALVE

TO HOSE HEADER

JP

BYPASS (IF OF VALUE)

NOTES:

1. THE DISTANCE FROM THE FLOWMETER TO EITHER ISOLATION VALVE

SHALL BE AS RECOMMENDED BY THE METER MANUFACTURER.

2. THERE SHALL BE A DISTANCE OF NOT LESS THAN 5 DIAMETERS OF

SUCTION PIPE FOR TOP OR BOTTOM SUCTION CONNECTION TO THE

FIRE PUMP SUCTION FLANGE. THERE SHOULD BE A DISTANCE OF

NOT LESS THAN 10 DIAMETERS OF SUCTION PIPE FOR SIDE

CONNECTIONS (NOT RECOMMENDED) TO THE FIRE PUMP SUCTION

FLANGE.

3. AUTOMATIC AIR RELEASE SHALL BE PROVIDED IF PIPING FORMS AN

INVERTED "U", TRAPPING AIR.

4. OS&Y GATE VALVE OR INDICATING BUTTERFLY VALVE.

FROM SUPPLY

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:3

:4

A M

F-501

FIRE PROTECTION DETAILS AND

SCHEDULES

3 3RK AKS

UPGRADE FIRE

SUPPRESSION AND

ANNUNCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

Scale: No Scale

FP-1, 1500 GPM ELECTRICALLY DRIVEN FIRE PUMP ENCLOSURE

Scale: No Scale

FIRE PUMP PIPING ARRANGEMENT (PER NFPA-20)

ELECTRIC UNIT HEATER SCHEDULE

TAG TYPE

MIN.

CAPACITY

POWER

REMARKS

AMP PHASE VOLT

EUH-1 ELECTRIC 5 kW 6 3 480 1, 2

HYDRONIC FIRE PUMP SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG

SERVED

SYSTEM TYPE

CIRCULATING FLUID

MIN % EFF

ELECTRICAL MOTOR

REMARKS

FLUID FLOW HEAD NPSH TEMPERATURE

NOMINAL

POWER

PHASE VOLT RPM

SPEED

CONTROL

FP-1 OUTSIDE BUILDING 501 BLDG 500 FIRE PROTECTION HORIZONTAL, SPLIT CASING WATER 1500 GPM 160 psig 60 61 % 200 hp 3 460 3570 VARIABLE 1, 2, 3, 4, 5, 6, 8, 9, 10, 12

JP-1 OUTSIDE BUILDING 501 BLDG 500 FIRE PROTECTION IN LINE JOCKEY WATER 60 GPM 170 psig 60 70 % 20 hp 3 460 1750 VARIABLE 5, 11

REMARKS:

1. PROVIDE PUMP WITH 2 HR ENCLOSURE RATED FOR OUTDOOR INSTALLATION.

2. PUMP SHALL BE ELECTRICALLY POWERED.

3. FIRE PUMP ENCLOSURE SHALL INCLUDE VENTILATION, HEAT, AND DRAIN.

4. PROVIDE REDUCED PRESSURE BACKFLOW PREVENTOR DETECTOR ASSEMBLY.

5. PROVIDE JOCKEY PUMP PIPED PER NFPA WITH ALL CONTROLS AND ACCESSORIES.

6. SUCTION PRESSURE AT PUMP INLET MIINIMUM 40 PSIG.

7. PROVIDE SOFT START FIRE PUMP CONTROLLER.

8. FIRE PUMP CONTROLLER SHALL HAVE MODBUS COMMUNICATION CAPABILITIES.

9. BASIS OF DESIGN IS PATTERSON FIRE PUMP (SERIES 8x6) WITH ENCLOSURE AND ACCESSORIES.

10. BASIS OF DESIGN IS PATTERSON HORIZONTAL SPLIT CASE PUMP (8X6).

11. BASIS OF DESIGN FOR FIRE PUMP CONTROLLER IS FIRETROL MODEL-FTT1930-AM200B.

REMARKS:

1. PROVIDE WALL MOUNTED THERMOSTAT.

2. BASIS OF DESIGN IS QMARK INDUSTRIAL UNIT HEATER ( IUH SERIES).

ELECTRICAL ABBREVIATIONS LIST

SS STAINLESS STEEL

STD STANDARD

SWBD SWITCHBOARD

TYP TYPICAL

UTIL UTILITY

V VOLT

VA VOLT-AMPERES

W WATT

W/ WITH

W/O WITHOUT

XFMR TRANSFORMER

XFR TRANSFER

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NTS NOT TO SCALE

PB PULL BOX OR PUSHBUTTON

PF POWER FACTOR

PH PHASE

PNL PANEL

PWR POWER

QTY QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

SEC SECONDARY

SF SQUARE FEET/FOOT

SPEC SPECIFICATION

SP SPARE

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

AMP AMPERE

APPROX APPROXIMATELY

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BFF BELOW FINISHED FLOOR

BLDG BUILDING

C CONDUIT

CALC CALCULATED

CAP CAPACITY

CB CIRCUIT BREAKER

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CONN CONNECTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CU COPPER

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DISC DISCONNECT

DS SAFETY DISCONNECT SWITCH

DWG DRAWING

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EX EXISTING

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GALV GALVANIZED

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

HP HORSEPOWER

IMC INTERMEDIATE METAL CONDUIT

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LF LINEAR FEET/FOOT

LRA LOCKED ROTOR AMPS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MSBD MAIN SWITCHBOARD

MT MOUNT

c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED

PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND

WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE

BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL

PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE

WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND

THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED

MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO

AVOID CONFLICT DURING CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE. EQUIPMENT SHALL HAVE PERMANENT PHELONIC LABELS SECURE WITH SCREW TO THE EXTERIOR OF THE DISCONNECTS, PANELBOARDS, ETC. WITH APPROPRIATE IDENTIFICATION.

RED LETTERING ON WHITE FOR EMERGENCY ESSENTIAL/CRITICAL POWER; BLACK LETTERING ON

WHITE FOR NORMAL POWER.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO

INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR

MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE

ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT". THE OVERCURRENT

PROTECTIVE DEVICE SHALL COORDINATE WITH ALL UPSTREAM DEVICES TO ENSURE 100%

SELECTIVITY.

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR

EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE

DEVICE'S SCREW TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT

UNLESS NOTED OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND

CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,

LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN

APPROVED THIRD PARTY TESTING AGENCY.

17. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE

BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS

DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.

18. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED. WHERE SUBJECT TO BEING IN A WET LOCATION - RAIN, ETC. COMPRESSION FITTINGS SHALL BE LISTED

'RAINTIGHT'.

USING OHM'S LAW AND THE KNOWN RESISTIVITY

CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM

PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE

REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED

THE RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH

CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP

CALCULATIONS

ELECTRICAL SYMBOL LEGEND

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND STAINLESS STEEL COVER PLATE SHALL BE RED

IN COLOR

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND STAINLESS STEEL COVER PLATE SHALL

BE RED IN COLOR

JUNCTION BOX, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

EQUIPMENT CONNECTION

AS

NOTED

E

120V DUPLEX RECEPTACLE OUTLET AND STAINLESS

STEEL COVER PLATE

18"

DEMOLITION GENERAL NOTES

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS

DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.

B. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE

CONTRACTOR SHALL COOPERATE WITH OTHER TRADES.

C. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY

CIRCUITING WHICH REQUIRES CONTINUATION THROUGH THE AREA.

D. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT

CONTINUITY IS MAINTAINED.

E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO

REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS

TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT

DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID

CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.

G. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR

NEW DEVICES.

H. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT

DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

I. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

a. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

b. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

c. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

d. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

e. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND

MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.

f. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER

OR OWNER'S REPRESENTATIVE.

J. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO

REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

FIRE ALARM PULL STATION

SYMBOL HEIGHT DESCRIPTION

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

F

F

FIRE ALARM SPEAKER

FIRE ALARM STROBE

FIRE ALARM SPEAKER AND STROBE

FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR

42"-48"

90"

90"

90"

FLOW SWITCH

TAMPER SWITCH

POST INDICATOR VALVEPIV

XX - CANDELA

XX - CANDELA

XX - WATTAGEF

S

F

S

SD CEILING

FIRE ALARM SYMBOL LEGEND

FIRE ALARM HORN AND STROBEF 90"

XX - CANDELA

XX - WATTAGE

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:3

:2

A M

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 4GDA

UPGRADE FIRE

SUPPRESSION SYSTEM AND

ANNUCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

GG

TYPE DESCRIPTION MOUNTING LAMP BALLAST/DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

A 4' LINEAR LED STRIPLIGHT WITH LENS SURFACE LED; 6000

LUMENS; 80

CRI; 4000K

ELECTRONIC LED

DRIVER

120.00 V 56 W LITHONIA ZL1F-L48-SMR-6000LM-MDD-M

VOLT-40K-90CRI-WH

B EXTERIOR LED WALL PACK WALL 44W QL

INDUCTION

INDUCTION DRIVER 277.00 V 44 W LITHONIA OLW-31

E1 CONTEMPORARY LED SINGLE FACED EXIT SIGN WITH BLACK

POWDER PAINT ALUMINUM HOUSING, BRUSHED ALUMINUM FACE,

RED LETTERS, AND CHEVRON ARROWS AS SHOWN ON PLANS.

UNIVERSAL LED --- 120.00 V 5 W LITHONIA LES 1 R 120/277

D. PROVIDE ALL HOLLOW POLES WITH VIBRATION DAMPERS BY THE FACTORY.

C. FOR APPROVAL OF FIXTURES FROM MANUFACTURERS OTHER THAN THOSE LISTED, PROPOSED FIXTURES SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER TEN BUSINESS DAYS PRIOR TO BID FOR REVIEW. FINAL DETERMINATION OF 'EQUAL' STATUS FOR BIDDING SHALL BE THE SOLE DETERMINATION OF THE ARCHITECT/ENGINEER.

B. REMOVE ALL FINGER PRINTS FROM LENSES, REFLECTORS, AND LOUVERS FOLLOWING LIGHT FIXTURE INSTALLATION.

NOTES: A. FOR CONTINUOUS FIXTURES, COORDINATE WITH SUPPLIER ON LENGTH AND REQUIRED FITTINGS, AND INSTALL WITH UNIFORM ILLUMINATION ALONG FIXTURE INCLUDING CORNERS.

LUMINAIRE SCHEDULE

DocuSign Envelope ID: 78E16923-5FFC-4703-B116-858E7B1A2C30

12/18/2020

G

FI

W P

GFI

WP

GFI

WP

E

A T

S

E

E

F F

SD

ELUA

EPDUA

A

A

A

B

A

A

E1

EPDUB

EPUA

LUA PUA

PDUA

B S W G R

(F P E

B501 4160

CHILLER SWGR

CCU-1, CCU-2,

CCU-3

PROPOSED 2-WAY DUCTBANK,

REFER TO DETAIL 2 ON SHEET

E-501

(E)'T1' 1500A 13.2kV-480V

(E) 2000A 13.2kVA-4160V

C

10 11

D

8 9

E

F

G

EXISTING DIESEL FIRE PUMP

EUH-1

EPDUA-1,3,5

ELUA-11

ELUA - 1

PROPOSED 3-WAY DUCTBANK,

REFER TO DETAIL 4 ON SHEET

E-501

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:3

:2

A M

E-101

ELECTRICAL NEW WORK PLAN

2 4GDA

UPGRADE FIRE

SUPPRESSION SYSTEM AND

ANNUCIATION SYSTEM

H.H. MCGUIRE VAMC

1201 BROAD ROCK BLVD.

RICHMOND, VA 23249 DECEMBER 18, 2020

CONSTRUCTION DOCUMENTS

652-18-10018-170

GG

0 4 8 16

N O

R T

H

TRUE

1. VERIFY WITH EQUIPMENT MANUFACTURER

EXACT CONNECTION REQUIREMENTS.

2. PROVIDE POWER AND SIGNAL CONDUCTORS

AND CONDUITS AS REQUIRED BY EQUIPMENT

MANUFACTURER.

3. VERIFY EXACT LOCATION OF FIRE PUMP

EQUIPMENT WITH FIRE PROTECTION

SHEETS.

4. UNLESS NOTED OTHERWISE, THE FIRE PUMP

ENCLOSURE IS A SINGLE-POINT CONNECTION,

SKID-MOUNTED UNIT WITH ALL EQUIPMENT

PROVIDED AND PRE-WIRED AT THE FACTORY.

5. SEE CIVIL DRAWING C-501 FOR LOCATION OF

BUILDING "BLACK BOX" AND BUILDING 501B

"GRAY BOX".

N

KEY PLAN

SCALE: NO SCALE

1 FIRE PUMP MAIN DISTRIBUTION PANEL,

ROUTE DUCTBANK AND CONDUITS TO TURN

UP UNDER PANEL. BRING ONE CONDUIT TO

PANEL. STUB THE OTHER CONDUIT 6-INCHES

ABOVE FINISHED FLOOR HEIGHT, PROVIDE

CAP, AND LABEL AS "SPARE".

2 THE FIRE PUMP MOTOR WILL BE PREWIRED

TO THE PANEL BY OTHERS.

3 THE JOCKEY PUMP WILL BE PREWIRED TO

THE PANEL BY OTHERS.

4 THE ELECTRICAL CONTRACTOR SHALL

PROVIDE THE FIRE ALARM NOTIFICATION

DEVICE, THE PULL STATION, AND SMOKE

DETECTOR. TAMPER SWITCHES ARE

PROVIDED BY OTHERS. THE ELECTRICAL

CONTRACTOR SHALL WIRE THE DEVICES TO

THE EXISTING FIRE ALARM CONTROL PANEL

IN BUILDING 501.

5 THE EMERGENCY LIGHT WILL BE PREWIRED

TO THE PANEL BY OTHERS.

6 THE UNIT HEATERS WILL BE PREWIRED TO

THE PANEL BY OTHERS.

7…