Drawings.pdf
PDF 27 MB Posted
- Attached to
- Z1DA--Upgrade Fire Suppression-Annunciation System Federal contract opportunity
- Solicitation number
- 36C24621B0006
About this file
This document provides details for a federal contract opportunity to upgrade the fire suppression and annunciation system at the Richmond VA Medical Center. The Department of Veterans Affairs is soliciting proposals to provide all labor, materials, and supervision necessary to reconfigure and update the current diesel fire pump and building systems. Work includes demolition, architectural, electrical, plumbing, mechanical, and structural improvements to comply with VA construction standards. The contract period is 275 calendar days with an estimated value between $500,000 and $1,000,000. The solicitation is designated as a service-disabled veteran owned small business set aside and will be available on May 4, 2021, with proposals due around 30 days later. A site visit is scheduled for May 17, 2021 and all questions must be emailed to the specified point of contact.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24621B0006 0003.docx | DOCX document | |
| 36C24621B0006 0002.docx | DOCX document | |
| 36C24621B0006_1.docx | DOCX document | |
| WAGE DETERMINATION.pdf | ||
| Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AREA OF WORK
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAPPROJECT LOCATION MAP
PROJECT IMAGE
/1 /2
:4
:5
A M
GI001
ENG. PROJECT COVER
1 1RK AKS
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
UPGRADE FIRE SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249
VA PROJECT #: 652-18-100 APOGEE PROJECT #: 18-170
DRAWING LIST
No. Description Dwg of Dwg
GI001 ENG. PROJECT COVER 1 1
STRUCTURAL
S-001 GENERAL NOTES & SCHEDULES 1 3
S-101 PLANS 2 3
S-201 SECTIONS & DETAILS 3 3
ARCHITECTURAL
A-101 FIRST FLOOR PLAN 1 2
A-301 SECTIONS AND DETAILS 2 2
CIVIL
C-501 DEMO, SITE, PAVING, AND UTILITY PLAN 1 2
C-502 CONSTRUCTION DETAILS 2 2
FIRE PROTECTION
F-001 FIRE PROTECTION GENERAL INFORMATION 1 3
F-101 FIRST FLOOR FIRE PROTECTION PLANS 2 3
F-501 FIRE PROTECTION DETAILS AND SCHEDULES 3 3
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 4
E-101 ELECTRICAL NEW WORK PLAN 2 4
E-501 ELECTRICAL DETAILS 3 4
E-601 ONE-LINE DIAGRAM 4 4
DocuSign Envelope ID: 79D23206-AF43-48F6-9A0A-D9DB532986A3
12/17/2020
F
SD
7 8 9 10 11 12
C
D
E
F
G
2 LAYERS OF FIRE RATED GYPSUM
WALL BOARD EACH SIDE OF 16 GA
STEEL STUD PARTITION @ 16"OC,
TYPICAL.
TOP OF WALLS UP TO
BOTTOM OF ROOF,
SEAL TO MAINTAIN
FIRE RATING.
6'-0" X 7'-0" HM 90
MIN RATED DOOR
AND FRAME
TOP OF WALLS UP TO
BOTTOM OF ROOF,
SEAL TO MAINTAIN
FIRE RATING.
NEW 2 HR RATED WALL TO
EXTEND FROM TOP OF
EXISTING CMU WALL TO
UNDERSIDE OF STRUCTURE.
A-301
A-301
7'-10" 6'-3"
VIF
17'-2"
4' -1
3'
-6
/2
2' -2
AL
IG
N
MIN.
4'-6"
3 3
A-301
SIM.
5 5
## KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
4/
0:
:3
AM
A-101
FIRST FLOOR PLAN
1 2DMM, LW GTS
UPGRADE FIRE
SUPPRESSION AND
ANNUNICATION SYSTEM
H.H MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
Scale: 1/4" = 1'-0"
1 FIRST FLOOR PLAN 0 4 8 16
N O
R
TH
TRUE
N
KEY PLAN
SCALE: NO SCALE
1 SAW CUT, REMOVE AND REPLACE CONCRETE SLAB
FOR NEW UG PIPE.
1 NEW FIRE PUMP PACKAGE UNIT, SEE SHEET
F-501 FOR CORRESPONDING DETAILS AND
INFORMATION.
2 EXISTING SIAMESE CONNECTIONS TO REMAIN.
3 EXISTING TRANSFORMER
4 12" PIPE, COORDINATE WITH ENGINEERS'
DRAWINGS.
5 EXISTING ELECTRICAL EQUIPMENT.
F
SE
E
SC
H
ED
U
LE
SCHEDULE
SEE
2" 2"
SCHEDULE
SEE
SE
E
SC
H
ED
U
LE
2"
DOOR AND
FRAME - SEE
DOOR SCHEDULE
CAULK BOTH
SIDES OF DOOR -
CONTINUOUS
(2) 2x METAL
STUDS TO FORM
HEADER
SEE DOOR
SCHEDULE
6" 2 LAYERS OF
FIRE RATED
GYPSUM WALL
BOARD BOTH
SIDES
DOOR AND
FRAME - SEE
DOOR
SCHEDULE
CAULK BOTH
SIDES OF DOOR -
CONTINUOUS
(2) 2x METAL
STUDS TO
FORM JAMB
6"
2 LAYERS FIRE
RATED GYPSUM
WALL BOARD
BOTH SIDES
T.O. SLAB
0"
T.O. RETAINING WALL
10' - 0"
T.O. JOIST ROOF LOW
POINT
27' - 0"
SEAL WALL AROUND
JOISTS TO MAINTAIN FIRE
RATING PER U.L. DETAIL
W-L-1065
SLIP TRACK, SEE
STRUCTURAL DRAWINGS
2 LAYERS OF 5/8" FIRE
RATED GYPSUM WALL
BOARD BOTH SIDES
6" METAL STUD FRAMING
EXISTING CMU
RETAINING WALL TO
REMAIN
'-0
SEAL BOTH SIDES
T.O. SLAB
0"
T.O. RETAINING WALL
10' - 0"
T.O. JOIST ROOF LOW
POINT
27' - 0"
SLIP TRACK, SEE
STRUCTURAL DRAWINGS
2 LAYERS OF 5/8" FIRE
RATED GYPSUM WALL
BOARD BOTH SIDES
6" METAL STUD FRAMING
SEAL BOTH SIDES
NOTE: SEAL ALL PENETRATIONS
THROUGH WALL TO MAINTAIN 2 HOUR
FIRE RATING PER U.L. DETAIL W-L-1065
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
4/
0:
:3
AM
A-301
SECTIONS AND DETAILS
2 2DMM, LW GTS
UPGRADE FIRE
SUPPRESSION AND
ANNUNICATION SYSTEM
H.H MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
DOOR SCHEDULE
Level
DOOR DOOR FRAME HEAD
DETAIL NO.
JAMB
DETAIL NO. LBL
HDWR
SET REMARKSNO. WIDTH HEIGHT THICK MAT'L FINISH ELEV MAT'L FINISH ELEV
T.O. SLAB 01 6' - 0" 7' - 0" 1 3/4" HM PT F HM PT 1 H1 J1 90MIN HW-12G PAINT DOOR AND FRAME TO MATCH EXISTING.
PROVIDE ADO.
Scale: 1/4" = 1'-0"
D1 DOOR ELEVATION
Scale: 1/4" = 1'-0"
F1 FRAME ELEVATION
Scale: 1 1/2" = 1'-0"
H1 HEAD DETAIL @ METAL STUD
Scale: 1 1/2" = 1'-0"
J1 JAMB DETAIL @ METAL STUD
Scale: 1/2" = 1'-0"
1 SECTION THRU EXISTING CMU WALL
Scale: 1/2" = 1'-0"
2 TYPICAL WALL SECTION
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
SIDEWALK
SIDEWALK
S
I
D
E
W
A
L
K
F
E
N
C
E
FENCE
CONC.
CONC.
C O
N C
CONC.
CONC.
DRAIN MH
TOP 178.66'
ELEC. BOX
POW
PO
W
INV. 173.12'
173.84'
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SS
SS
SS
SS
SS
170.09'
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
I N
V
171.27'
12"
C O
N C
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
ELEC.BOX WI RISER
CONNECTIONS
DRAIN
MH
TOP
178.40'
BUILDING
FF=179.04'
ELEC.
BOXES
H/C
RAMP
INV. 170.30'
SAN. MH
TOP 178.00'
INV. 170.36'
SAN. MH
TOP 177.85'
CURB &
GUTTER
EDGE OF
CONCRETE
SAN. MH
TOP 177.75'
SAN. MH
TOP 177.93' INV.
170.15'
STEPS
BUILDING
FF=179.39'
SIAMESE
HYDRANTS
SAN. MH
TOP 178.75'
ELEC.
BOXES
EDGE OF
CONCRETE
BUILDING
FF=178.99'
FILLER
CAPS
ELEC.
BOX
CURB &
GUTTER
PEDESTRIAN
CROSSING
CURB &
GUTTER
CALL
BOX
BUILDING
FF=178.21'
12"
PINE
PAVED
AREA
TRANSFORMER
ON CONC. PAD
BENCHMARK
'X' ON CORNER
OF CONC. PAD
ELEV.=178.15'
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
W W
W W
W W
W W
W W
W W
W W
W W
W W
UG/E UG/E UG/E UG/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
WW
WWWWWWWWWW
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/EUG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UG/E UG/E UG/E UG/E UG/E UG/E
UG
/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/T UG/T UG/T UG/T UG/T UG/T
UG
/T
UG
/T
UG
/T
UG/T
UG/T
UG/T
UG/T
UG/T
UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/EUG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
LOD
LOD
LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LOD
LODLODLODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LODLOD
LODLOD
EXISTING BOLLARD
(TO BE REMOVED, TYP.)
EXISTING FIRE HYDRANT
(TO REMAIN, TYP.)
EXISTING ASPHALT PAVEMENT
(TO BE SAWCUT, REMOVED, AND
REPLACED FOR PROPOSED WATER LINE)
EXISTING SEWER LINE
(TO REMAIN, TYP.)
EXISTING UNKNOWN UTILITY
(TO REMAIN)
EXISTING CONCRETE SIDEWALK
(TO BE SAWCUT, REMOVED, AND
REPLACED FOR PROPOSED WATER LINE)
EXISTING WATER LINE
(TO REMAIN, TYP.)
EXISTING UNDERGROUND ELECTRICAL LINE
(TO REMAIN, TYP.)
EXISTING SEWER MANHOLE
(TO REMAIN)
66.89'
29.35'
27.01'
3.01'
EXISTING CURB AND GUTTER
(TO BE SAWCUT, REMOVED, AND REPLACED)
EXISTING WATER SERVICE
(TO REMAIN)
EXISTING TRANSFORMER
(TO REMAIN)
EXISTING GAS LINE
(TO REMAIN)
4'
EXISTING MANHOLE AND SEWER LINE
(TO REMAIN)
EXISTING UNDERGROUND
PHONE LINE
(TO REMAIN)
EXISTING FENCE
(TO REMAIN)
EXISTING ELECTRICAL LINE
(TO REMAIN)
EXISTING WATER LINE
(TO REMAIN)
EXISTING FIRE
HYDRANT
(TO REMAIN)
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
SIDEWALK
SIDEWALK
S
I
D
E
W
A
L
K
F
E
N
C
E
FENCE
CONC.
CONC.
C O
N C
CONC.
CONC.
ELEC. BOX
POW
PO
W
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SS
SS
SS
SS
SS
170.09'
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
I N
V
171.27'
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
ELEC.BOX WI RISER
CONNECTIONS
BUILDING
FF=179.04'
ELEC.
BOXES
H/C
RAMP
INV. 170.30'
SAN. MH
TOP 178.00'
INV. 170.36'
SAN. MH
TOP 177.85'
CURB &
GUTTER
EDGE OF
CONCRETE
SAN. MH
TOP 177.75'
SAN. MH
TOP 177.93' INV.
170.15'
STEPS
BUILDING
FF=179.39'
SAN. MH
TOP 178.75'
ELEC.
BOXES
EDGE OF
CONCRETE
BUILDING
FF=178.99'
ELEC.
BOX
CURB &
GUTTER
PEDESTRIAN
CROSSING
CURB &
GUTTER
CALL
BOX
BUILDING
FF=178.21'
12"
PINE
PAVED
AREA
TRANSFORMER
ON CONC. PAD
BENCHMARK
'X' ON CORNER
OF CONC. PAD
ELEV.=178.15'
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
W W
W W
W W
W W
W W
W W
W W
W W
W W
UG/E UG/E UG/E UG/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
WW
WWWWWWWWWW
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W
W
W
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/EUG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UG/E UG/E UG/E UG/E UG/E UG/E
UG
/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/T UG/T UG/T UG/T UG/T UG/T
UG
/T
UG
/T
UG
/T
UG/T
UG/T
UG/T
UG/T
UG/T
UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/EUG/EUG/EUG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
66.89'
27.01'
3.01'
PROPOSED ELECTRICAL FIRE PUMP IN ENCLOSURE
(SEE FIRE PROTECTION PLANS FOR DETAILS)
PROPOSED 12' X 24' LEVEL CONCRETE PAD FOR
PROPOSED ELECTRIC FIRE PUMP
(REFERENCE STRUCTURAL PLANS PER PAD DETAILS)
C-502
REMOVABLE POST
BOLLARD (TYPE A)
(TYP.)
C-502
UTILITY TRENCH PATCH
(TYP.)
PROPOSED CURB
AND GUTTER
(TO MATCH EXISTING)
PROPOSED CONCRETE SIDEWALK
(TO MATCH EXISTING)
PROPOSED SOD
(TYP.)
PROPOSED 8" DIP FIRE WATER LINE
CONTRACTOR SHALL REFER TO FIRE PLANS
FOR DETAILS AT THE BUILDING
PROPOSED POST INDICATOR VALVE
(SEE FIRE PROTECTION PLANS FOR DETAILS)
CONTRACTOR SHALL REFER TO FIRE PLANS
FOR FIRE PUMP CONNECTIONS
PROPOSED 12" DIP FIRE WATER LINE
PROPOSED WATER SERVICE CONNECTION
WITH 12"X8"X12" TAPPING SLEEVE
29.35' 4'
PROPOSED ELECTRICAL DUCT BANK
(SEE ELECTRICAL PLANS FOR DETAILS)
24'
PROPOSED ELECTRICAL DUCT BANK
(SEE ELECTRICAL PLANS FOR DETAILS)
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
A
M
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-100
18-170
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
GRADING AND DRAINAGE PLAN LEGEND
EXISTING CONTOURS
PROPOSED CONTOURS
EXISTING SPOT ELEVATION
PROPOSED SPOT ELEVATION
PROPOSED TOP OF CURB / BOTTOM OF CURB
SPOT ELEVATION
TC
BC
XXXX.XX
XXXX.XX
XXXX.XX
XXXX.XX
XXXX
XXXX
SCALE: 1" = 20'
C-501
DEMOLITION PLAN
SCALE: 1" = 20'
C-501
SITE, PAVING, AND UTILITY PLAN
SITE AND PAVING PLAN LEGEND
PROPOSED HEAVY DUTY ASPHALT PAVING
PROPOSED CONCRETE SIDEWALK PAVING
PROPOSED CONCRETE PAVING
PROPOSED LANDSCAPING
PROPERTY LINE
DEMOLITION PLAN LEGEND
CONCRETE SIDEWALK AND/OR CURB & GUTTER TO BE
REMOVED
ASPHALT PAVING TO BE REMOVED
LANDSCAPING TO BE REMOVED
PROPERTY LINE
LIMITS OF DISTURBANCE
LOD LOD LOD
GENERAL NOTES:
1. CONTRACTOR TO PROVIDE TEMPORARY FENCING IN THE FORM
OF A 6' HIGH GALVANIZED CHAIN LINK FENCE AROUND THE
PROPOSED IMPROVEMENTS.
2. ALL NEW WORK SHOWN IN THESE SHEETS SHALL COMPLY WITH
APPLICABLE STATE, FEDERAL, AND LOCAL BUILDING AND UTILITY
INSTALLATION CODES.
3. ALL MATERIALS AND CONSTRUCTION METHODS SHALL BE IN
ACCORDANCE WITH DEPARTMENT OF VETERAN AFFAIRS
TECHNICAL INFORMATION LIBRARY STANDARD SPECIFICATIONS.
4. THERE MAY BE ADDITIONAL UTILITIES NOT SHOWN ON THESE
PLANS. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR
LOCATIONS SHOWN, AND IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO FIELD VERIFY THE LOCATIONS OF ALL UTILITIES
WITHIN THE LIMITS OF CONSTRUCTION AND TO NOTIFY THE OWNER
IN CASE OF DISCREPANCIES THAT AFFECT THE CONSTRUCTION
PROJECT.
5. THE CONTRACTOR IS RESPONSIBLE FOR NOTIFICATION OF AND
LIAISON WITH VETERAN AFFAIRS IN THE PROCESS OF LOCATION
AND RELOCATION OF AND TIE-IN TO VETERAN AFFAIRS' UTILITIES.
6. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE THAT MAY
OCCUR TO ANY ADJACENT STRUCTURES OR PROPERTY, OR ANY
EXISTING STRUCTURES WITHIN LIMITS OF CONSTRUCTION THAT
ARE DESIGNATED ON THE PLANS TO REMAIN, AND SHALL REPAIR
OR REPLACE SUCH DAMAGED PROPERTY TO THE VETERAN
AFFAIRS' SATISFACTION AT NO COST TO THE VETERAN AFFAIRS.
7. THE CONTRACTOR SHALL NOT DEVIATE FROM THESE PLANS
AND SPECIFICATIONS WITHOUT THE PRIOR WRITTEN CONSENT OF
THE ENGINEER.
8. CONTRACTOR IS RESPONSIBLE FOR CONTACTING
DEPARTMENT OF VETERAN AFFAIRS AND ALL EXISTING UTILITY
PROVIDERS BEFORE REMOVING ANY/ALL UTILITIES FROM THEIR
EXISTING LOCATION ON THE SITE. THE CONTRACTOR SHALL
PERFORM ALL UTILITY DEMOLITION OR RELOCATION ACTIVITIES IN
ACCORDANCE WITH THE EXISTING UTILITIES SPECIFICATIONS,
MATERIALS, AND REQUIREMENTS.
9. THE CONTRACTOR SHALL SEQUENCE THE WORK AND PROVIDE
TEMPORARY MEASURES AS NECESSARY TO MAINTAIN ACCESS TO
THE SITE THROUGH ALL ENTRANCES AT ALL TIMES DURING
CONSTRUCTION. TEMPORARY PROVISIONS MAY INCLUDE, BUT ARE
NOT LIMITED TO: BARRICADES, FLASHING LIGHTS, FLAGMAN,
TEMPORARY PAVEMENT, AND DIRECTIONAL SIGNAGE AS
NECESSARY TO ACCOMPLISH THE WORK.
10. CONTRACTOR SHALL CONSIDER COORDINATION ASPECTS OF
CRANES AND CONSTRUCTION EQUIPMENT OPERATIONS DURING
DEMOLITION ACTIVITY.
11. COORDINATE WITH DEPARTMENT OF VETERAN AFFAIRS CODES
ENFORCEMENT DIVISION AS REQUIRED DURING ALL DEMOLITION
AND NEW CONSTRUCTION ACTIVITIES.
12. ALL ITEMS DESIGNATED FOR REMOVAL SHALL BE LEGALLY
DISPOSED OF, OFF SITE.
13. CONTRACTOR TO POT HOLE EXISTING WATER LINE,
UNDERGROUND ELECTRICAL LINES, GAS LINE, UNDERGROUND
TELEPHONE, FIBER OPTIC, AND ANY OTHER UTILITY LINES DURING
DEMOLITION ACTIVITIES AND COORDINATE FIELD LOCATIONS AND
DEPTHS OF THESE UTILITIES WITH ENGINEER FOR PROPOSED
UTILITY CROSSINGS AND PROPOSED PAVEMENT OVER EXISTING
LINES. THESE LINES MAY REQUIRE RELOCATION.
14. THE CONTRACTOR SHALL PROVIDE DUST CONTROL AND SHALL
PROTECT ADJACENT PAVEMENTS FROM SOIL ACCUMULATION
DURING CONSTRUCTION.
15. ADDITIONAL EROSION CONTROL DEVICES MAY BE REQUIRED
BY THE ENGINEER OR OTHER INSPECTORS AS DETERMINED BY
FIELD CONDITIONS.
16. STORM DRAINAGE STRUCTURES AND CONDUITS SHALL BE
PROTECTED FROM SEDIMENTATION AS REQUIRED BY STATE OR
LOCAL CODES.
17. A SUBSURFACE UTILITY LOCATION LEVEL B INVESTIGATION
WAS PERFORMED FOR THE SITE, UTILIZING GROUND PENETRATING
RADAR AND AN ELECTROMAGNETIC PIPE LOCATOR (SEE SHEET
V-101). EVERY EFFORT WAS MADE TO LOCATE ANY AND ALL
UNDERGROUND UTILITIES ON SITE, BUT THERE MAY BE ADDITIONAL
UTILITIES NOT SHOWN ON THESE PLANS. THE ENGINEER ASSUMES
NO RESPONSIBILITY FOR THE LOCATIONS SHOWN. THE
CONTRACTOR IS REQUIRED TO PERFORM THERE OWN
SUBSURFACE UTILITY LOCATION PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL NOTIFY THE ENGINEER IN CASE OF
DISCREPANCIES THAT AFFECT THE CONSTRUCTION PROJECT.
CONTRACTOR IS REQUIRED TO POTHOLE ALL UTILITIES CROSSINGS
WITH THE PROPOSED IMPROVEMENTS. CONTRACTOR SHALL
NOTIFY THE ENGINEER IN CASE OF DISCREPANCIES THAT AFFECT
THE CONSTRUCTION PROJECT.
GENERAL NOTES:
1) ALL PROPOSED DIMENSIONS USED TO SHOW THE GEOMETRIC
LAYOUT OF THE PROPOSED PARKING LOT ARE SHOWN AT THE FACE
OF CURB. ALL PROPOSED DIMENSIONS USED TO SHOW THE
GEOMETRIC LAYOUT OF THE PROPOSED BUILDING LOCATION ARE
GIVEN AT THE OUTSIDE FACE OF THE BUILDING CORNERS. ALL
CURB RADII ARE GIVEN AT THE FACE OF CURB.
2) CONTRACTOR SHALL NOTIFY VETERANS AFFAIRS OF ANY
DISCREPANCIES BETWEEN THE EXISTING CONDITIONS IN THE FIELD
AND THE SURVEY SHOWN ON THE PLANS BEFORE PROCEEDING
WITH ANY NEW CONSTRUCTION.
3) CONTRACTOR IS RESPONSIBLE FOR CORRECT HORIZONTAL
AND VERTICAL ALIGNMENT OF ALL TIES BETWEEN PROPOSED AND
EXISTING PAVEMENTS, CURB AND GUTTER, SIDEWALKS, WALLS,
AND UTILITIES.
4) MAXIMUM CUT OR FILL SLOPE= 2H:1V.
5) THRUST BLOCKING TO BE PROVIDED AT ALL HORIZONTAL AND
VERTICAL BENDS ALONG THE PROPOSED FIRE WATER LINE.
GENERAL NOTES:
1) ALL SPOT ELEVATIONS SHOWN ARE AT THE EDGE OF
PAVEMENT UNLESS OTHERWISE NOTED.
SITE NOTES:
1) THE CONTRACTOR SHALL CLEAN OUT ACCUMULATED SILT IN
STORM WATER CONVEYANCE CHANNELS AND PIPES AT END OF
CONSTRUCTION WHEN DISTURBED AREAS HAVE BEEN STABILIZED.
2) IN ALL AREAS OF FILL OR OTHERWISE DISTURBANCE OF
EXISTING CONDITIONS, UNLESS OTHERWISE NOTED, THE
CONTRACTOR SHALL FULLY AND COMPLETELY REMOVE AND
LEGALLY DISPOSE OFF-SITE, ALL PLANT MATERIALS INCLUDING BUT
NOT LIMITED TO ROOT SYSTEMS, CONCRETE, REINFORCED
CONCRETE, ASPHALT DEBRIS, UNDERBRUSH, TOPSOIL, AND OTHER
DELETERIOUS MATERIAL. THE SUBGRADE TO REMAIN SHALL BE
COMPACTED TO 95% STANDARD PROCTOR MAXIMUM DRY DENSITY
FOLLOWING FULL REMOVAL OF THESE MATERIALS.
3) EXTREME CAUTION SHALL BE USED WHEN WORKING WITHIN
THE VICINITY OF THE EXISTING OVERHEAD POWER LINES.
CONTRACTORS SHALL NOTIFY/COORDINATE WITH VETERANS
AFFAIRS PRIOR TO CONSTRUCTION.
LEGEND
EXISTING FENCE LINE
PROPERTY LINE
EXISTING OVERHEAD POWER LINE
EXISTING UNDERGROUND POWER LINE
EXISTING UNDERGROUND TELEPHONE LINE
EXISTING GAS LINE
EXISTING SANITARY SEWER LINE
EXISTING WATER LINE
EXISTING STORM LINE
EXISTING UNKNOWN UTILITY LINE
PROPOSED FIRE WATER LINE
W W W
SS SS SS
GAS GAS GAS
UG/T UG/T
UG/E UG/E
OHP OHP OHP
N
TRUE NORTH
0 2010 40
N
TRUE NORTH
0 2010 40
N
KEY PLAN
SCALE: NO SCALE
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
A
M
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-100
18-170
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
TYPE 3 UTILITY TRENCH PATCH
NOT TO SCALE
C-502
REMOVABLE POST BARRICADE
NOT TO SCALE
C-502
REMOVABLE POST BARRICADE - STRAP DETAIL
NOT TO SCALE
C-502
UTILITY TRENCHING SCHEMATIC DETAIL
NOT TO SCALE
C-502
C-502
CONCRETE POST BARRICADES
NOT TO SCALE
THRUST BLOCKING FOR HIGH PRESSURE SYSTEM
NOT TO SCALE
C-502
THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA
13. IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE
PROTECTION WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS
DRAWING IS “FOR INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE
PROTECTION CONTRACTOR TO BASE THE DESIGN OF THE FIRE PROTECTION
SYSTEM ON. THE CONTRACTOR SHALL VERIFY THE EXACT CONDITIONS THAT THIS
DRAWING REPRESENTS, INCLUDING ANY PERCEIVED CONCEALED SPACES, AND THE
BUILDING TYPE AND CONSTRUCTION AS OUTLINED IN THE INTERNATIONAL BUILDING
CODE, PRIOR TO THE START OF WORK. REFER TO THE INTERNATIONAL BUILDING
CODE, ESPECIALLY CHAPTERS 6 (TYPES OF CONSTRUCTION) AND CHAPTER 9 (FIRE
PROTECTION SYSTEMS), NFPA 13 (CHAPTER 8), AND THE PROJECT SPECIFICATIONS
FOR OTHER FIRE PROTECTION REQUIREMENTS.
FIRE PROTECTION GENERAL NOTES
FIRE PROTECTION CONTRACTOR
SEMI-RECESSED SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
FIRE LINE
FPC
FL
TAMPER SWITCH
FLOW SWITCH
CONCEALED SPRINKLER HEAD
PENDANT SPRINKLER HEAD CHECK VALVE
GATE VALVE
EXTERIOR ALARM GONG (WATER ACTIVATED)
TEST AND DRAIN ASSEMBLY
ORDINARY HAZARD
GROUP 1 OCCUPANCY
SIDEWALL SPRINKLER HEAD
FIRE DEPARTMENT CONNECTION (FDC)
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT
FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
KEYNOTE
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER POINT OF NEW CONNECTION
LIMIT OF DEMOLITION
BACKFLOW PREVENTER
FIRE PROTECTION DEMOLITION GENERAL NOTES
A. LOCATIONS SHOWN FOR EXISTING FIRE PROTECTION PIPE AND EQUIPMENT ARE APPROXIMATE. THE CONTRACTOR IS
TO FIELD VERIFY THE EXACT LOCATIONS OF EXISTING FIRE PROTECTION LINES AND EQUIPMENT INCLUDING RISERS AND
VALVES PRIOR TO THE START OF WORK.
B. COORDINATE WITH VA FOR ANY SHUTDOWNS OR PLANNED INTERRUPTIONS OF THE FIRE PROTECTION SERVICE. THE CONTRACTOR SHALL GIVE THE OWNER THREE (3) DAYS NOTICE PRIOR TO THE PLANNED SHUTDOWN OR
INTERRUPTION.
C. COORDINATE DEMOLITION OF FIRE PROTECTION PIPING WITH OTHER PIPING WHICH IS NOT TO BE REMOVED. PROTECT
OTHER PIPING WHICH IS NOT TO BE REMOVED FROM DAMAGE, DIRT, AND DEBRIS.
D. ALL FIRE PROTECTION RELATED EQUIPMENT AND PIPING WHICH IS REMOVED FROM THE BUILDING IS TO BE TAKEN
OFFSITE AND DISPOSED OF.
BUILDING AND OCCUPANT SAFETY -
INTERRUPTION OF FIRE PROTECTION SERVICE
A. DURING THE TIME THAT THE FIRE PROTECTION RENOVATION WORK IS BEING PERFORMED, AND THE FIRE PROTECTION SYSTEM IS DOWN AND OUT OF COMMISSION, THE FIRE PROTECTION CONTRACTOR SHALL HAVE SUFFICIENT PERSONNEL ONSITE TO KEEP A “FIRE WATCH” ON THE FACILITY. COORDINATE THIS WITH VA COR.
B. A FIRE PROTECTION WATCH IS IMPLEMENTED TO ENSURE THE FIRE SAFETY OF A BUILDING IN THE EVENT OF ANY ACT, OR SITUATION INSTIGATING AN INCREASED RISK TO PERSONS OR PROPERTY. THE TERM “FIRE WATCH” IS USED TO DESCRIBE A DEDICATED PERSON OR PERSONS WHO’S SOLE RESPONSIBILITY IS TO LOOK FOR FIRES WITHIN AN
ESTABLISHED AREA.
C. FIRE WATCH PERSONNEL ARE TO KEEP WATCH FOR FIRES IN THE GENERAL AREA OF PERFORMANCE, THE PERSONS
PERFORMING THE FIRE WATCH ARE NOT PERMITTED TO PERFORM ANY OTHER DUTIES.
D. FIRE WATCH PERSONNEL ARE TO HAVE FIRE EXTINGUISHING EQUIPMENT READILY AVAILABLE AND TO BE TRAINED IN ITS
USE.
E. THE QUANTITY OF PERSONNEL INVOLVED IN THE FIRE WATCH IS TO BE ADEQUATE SUCH THAT EACH FLOOR, LEVEL, AND
ROOM OF THE FIRE AREA IS COVERED. COORDINATE THIS WITH VA COR.
T&D
TS
FS
ORDINARY HAZARD
GROUP 2 OCCUPANCY
A. THESE FIRE PROTECTION DRAWINGS ARE DIAGRAMMATIC IN NATURE. SPRINKLER HEAD TYPES AND APPROXIMATE LOCATIONS HAVE BEEN ESTABLISHED. THE FIRE PROTECTION LAYOUT INDICATED IS FOR REFERENCE ONLY. FINAL SYSTEM LAYOUT AND PIPE ROUTING SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR AND SHALL TAKE INTO CONSIDERATION THE BUILDING STRUCTURE, ARCHITECTURAL FEATURES AND SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES. THE FIRE PROTECTION CONTRACTORS SHALL PROVIDE WORKING DRAWINGS IN
ACCORDANCE WITH NFPA 13 FOR REVIEW AND APPROVAL BY COR.
B. ADJUST SPRINKLERS TO BE PLACED IN THE CENTER OF THE CEILING TILE IT IS SHOWN IN.
C. MODIFICATION TO EXISTING SPRINKLER SYSTEMS SHALL RESULT IN A COMPLETE AND WORKING WET PIPE SPRINKLER
SYSTEM THAT IS IN COMPLIANCE WITH CONTRACT DOCUMENTS AND NFPA 13.
D. ALL WORK SHALL BE CONDUCTED IN ACCORDANCE WITH NFPA 13, THE DEPARTMENT OF VETERANS AFFAIRS, FIRE PROTECTION DESIGN MANUAL 7TH EDITION AND ALL OTHER APPLICABLE CODES AND STANDARDS.
E. LIGHT HAZARD OCCUPANCIES: OFFICE AND CUSTOMARY ACCESS AREAS. LIGHT HAZARD SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM DENSITY OF 0.10 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST
REMOTE 1500 SQ.FT.
F. ORDINARY HAZARD GROUP 1 OCCUPANCIES: MECHANICAL ROOMS, TRANSFORMER ROOMS, ELECTRICAL SWITCHGEAR ROOMS AND ELECTRICAL CLOSETS. ORDINARY HAZARD GROUP 1 SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM DENSITY OF 0.15 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ.FT.
G. ORDINARY HAZARD GROUP 2 OCCUPANCIES: STORAGE ROOMS, TRASH ROOMS, CLEAN AND SOILED LINEN ROOMS AND KITCHENS. ORDINARY HAZARD GROUP 2 SPACES SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE A MINIMUM
DENSITY OF 0.20 GPM/SQ.FT. OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ.FT.
H. PRIOR TO THE OPERATION (OPENING OR CLOSING) OF ANY VALVES CONTROLLING WATER TO THE DOMESTIC OR FIRE SYSTEMS, NOTIFICATION SHALL BE GIVEN TO THE COR AND APPROVAL MUST BE OBTAINED BEFORE BEGINNING OF
WORK.
I. PROVIDE PIPING OFFSETS AS REQUIRED TO AVOID DUCTWORK, STRUCTURE, OTHER TRADES OR OTHER
OBSTRUCTIONS.
J. ALL PIPE SHALL BE INSTALLED ABOVE CEILINGS IN AREAS WITH FINISHED CEILINGS AND CORRESPONDING SPRINKLER HEADS SHALL BE RECESSED. IN AREAS WITH EXPOSED STRUCTURE, PIPING SHALL BE EXPOSED AND PAINTED TO MATCH ADJACENT SURFACES. IN NO CASE SHALL ANY EXPOSED SPRINKLER PIPING BE INSTALLED BELOW THE BOTTOM
HORIZONTAL PLANE OF LIGHTING FIXTURES.
K. NEW ZONE PIPING SHALL BE HYDRAULICALLY CALCULATED WITH THE AVAILABLE SUPPLY AND RESIDUAL PRESSURE AS SHOWN IN THE SPECIFICATIONS. PERFORM HYDRAULIC CALCULATIONS UTILIZING THE AREA/DENSITY METHOD. DESIGN AREA REDUCTIONS ARE PERMITTED WHEN USING QUICK RESPONSE SPRINKLERS. MINIMUM DESIGN AREA IS 1500 SQ.FT.
INCLUDE AN ALLOWANCE FOR A 250 GPM HOSE STREAM AT THE BASE OF THE RISER. SHOP DRAWINGS SHALL BE PREPARED AND SEALED STAMPED BY A REGISTERED PROFESSIONAL ENGINEER IN THE FIELD OF FIRE PROTECTION.
L. VERIFY ALL DISTANCES, HEIGHTS AND DIMENSIONS OF THE BUILDING AND ITS SYSTEMS PRIOR TO THE START OF WORK.
M. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS EXCEPT WHERE SPECIFICALLY PROHIBITED (E.G., HIGH TEMPERATURE AREAS AS DEFINED IN NFPA 13). ALL SPRINKLERS SHALL BE UL LISTED AND FM APPROVED.
N. ALL VALVES SHALL BE READILY ACCESSIBLE FOR OPERATION.
O. CONTRACTOR SHALL PROVIDE LOW POINT DRAINS AS REQUIRED BY NFPA 13. ALL LOW POINTS SHALL BE MARKED WITH
A SIGN INDICATING "AUXILIARY DRAIN".
P. TEST SPRINKLER SYSTEM, CONTROLS, PIPING AND MONITORING IN ACCORDANCE WITH NFPA 25.
Q. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR BURNED.
R. CONTRACTOR SHALL PRESSURE TEST RISERS AFTER NEW FIRE PUMP IS INSTALLED.
FP FIRE PUMP
AUTOMATIC AIR
RELEASE VALVE
M FLOWMETER JP JOCKEY PUMP
SANITARY SEWERSAN
A. CONTRACTOR SHALL COMPLY WITH THE OWNER'S WRITTEN DUST AND NOISE CONTROL REQUIREMENTS
B. EXISTING AIR QUALITY REQUIREMENTS AND OTHER UTILITY REQUIREMENTS FOR OCCUPIED AREAS SHALL BE
MAINTAINED.
C. RENOVATION AREAS SHALL BE ISOLATED FROM OCCUPIED AREAS DURING CONSTRUCTION USING AIRTIGHT BARRIERS.
PROVIDE EXHAUST AIRFLOW IN A MANNER THAT SHALL BE SUFFICIENT TO MAINTAIN NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZONE. COORDINATE TEMPORARY BARRIERS WITH INTERIM LIFE SAFETY MEASURES.
D. FIRE PROTECTION SYSTEM REVISIONS SHALL BE PROPERLY PERFORMED TO LIMIT WATERBOURNE OPPORTUNISTIC
PATHOGENS.
E. DOUBLE-BAGGING IS REQUIRED FOR CONSTRUCTION DEBRIS. COMPLY WITH OWNER'S DESIGNATED ROUTE FOR
REMOVAL.
DUST AND NOISE CONTROL MEASURES
CONSTRUCTION PHASING
PHASE - 1 ( REQUIRE EXISTING FIRE PUMP SHUTDOWN)
1. INSTALL NEW ELECTRICALLY DRIVEN FIRE PUMP WITH ENCLOSURE AS PER ARCHITECTURAL/CIVIL DRAWINGS.
2. INSTALL SUCTION AND DISCHARGE PIPING TO PUMP AS PER FIRE PROTECTION DRAWINGS.
3. INSTALL FIRE PUMP CONTROL PANEL AND ELECTRICAL POWER TO FIRE PUMP PER ELECTRICAL DRAWINGS.
4. TEST AND COMMISSION FIRE PUMP, AND PUT IN OPERATION.
PHASE - 2
1. RELOCATE DIESEL TANK SERVING EXISTING FIRE PUMP WITH IN BUILDING 501.
2. RE-ORIENT GATE VALVES TO ACCOMMODATE ARCHITECTURAL MODIFICATIONS.
3. PROVIDE ARCHITECTURAL MODIFICATIONS PER ARCHITECTURAL DRAWINGS.
4. TEST AND COMMISSION FIRE PUMP AND PUT IN OPERATION AS BACK UP TO PRIMARY ELECTRICALLY DRIVEN PUMP.
PHASE - 3
1. TEST BOTH FIRE PUMPS PER NFPA REQUIREMENTS TO BE WITNESSED BY VA AND LOCAL FIRE AUTHORITY.
2. TEST PUMP CONTROLS AND CHANGEOVER FROM PRIMARY TO SECONDARY PUMP.
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:4
A M
F-001
FIRE PROTECTION GENERAL
INFORMATION
1 3RK AKS
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA
13. IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE
PROTECTION WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS
DRAWING IS “FOR INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE
PROTECTION CONTRACTOR TO BASE THE DESIGN OF THE FIRE PROTECTION
SYSTEM ON. THE CONTRACTOR SHALL VERIFY THE EXACT CONDITIONS THAT THIS
DRAWING REPRESENTS, INCLUDING ANY PERCEIVED CONCEALED SPACES, AND THE
BUILDING TYPE AND CONSTRUCTION AS OUTLINED IN THE INTERNATIONAL BUILDING
CODE, PRIOR TO THE START OF WORK. REFER TO THE INTERNATIONAL BUILDING
CODE, ESPECIALLY CHAPTERS 6 (TYPES OF CONSTRUCTION) AND CHAPTER 9 (FIRE
PROTECTION SYSTEMS), NFPA 13 (CHAPTER 8), AND THE PROJECT SPECIFICATIONS
FOR OTHER FIRE PROTECTION REQUIREMENTS.
8 9
D
E
F L
F L
F L
F L
D C
W
FIRE SUPPRESSION SERVICE TO BULDING 500
6" x 2 1/2" x 2 1/2" SIDEWALK
FIRE DEPARTMENT SIAMESE
6" x 2 1/2" x 2 1/2" SIDEWALK
HOSE HEADER
S A
N
4" SAN
4" SAN
S A
N
S A
N
4" SAN
S A
N
6" SAN
EXISTING FIRE PUMP CONTROLLER
EX FP
7 8 9
D
E
FP-1
D C
W
F L
F L
FIRE SUPPRESSION SERVICE TO BULDING 500
F L
S A
N
4" SAN 6" SAN
S A
N
EUH-1
*JP-1 IS WITHIN PUMP
ENCLOSURE.
EX FP
F L
F L
12" FL UP
PIV
8" HOSE VALVE
TEST HEADER
PRV
## DEMOLITION KEY NOTES:
# NEW WORK KEYNOTES
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:4
A M
F-101
FIRST FLOOR FIRE PROTECTION
PLANS
2 3RK AKS
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
01 FP-1 IS WITHIN SKID-MOUNTED EXTERNAL FIRE
RATED ENLCOSURE.
02 DEISEL TANK TO BE RELOCATED AS SHOWN.
RECONNECT TO EXISTING FIRE PUMP (EX FP).
03 PROVIDE CHECK VALVE IN VERTICAL POSITION.
04 12" LINE FROM OUTDOOR FIRE PUMP DISCHARGE
ROUTED BELOW SLAB TO CONNECT TO EXISTING
FIRE MAIN SUPPLY TO BUILDING 500. SEE
STRUCTURAL AND CIVIL DRAWINGS FOR EXACT
LOCATIONS.
05 THIS DOOR SHALL REMAIN OPEN DURING FIRE
PUMP OPERATION TO PROVIDE VENTILATION.
PROVIDE ELECTRIC DOOR CLOSER AND
INTERLOCK WITH PUMP CONTROL PANEL TO OPEN
DOOR WHENEVER MAIN PUMP TURNS ON.
06 MODIFY EXISTING SPRINKLER PIPING TO PROVIDE
SPRINKLER COVERAGE IN NEW PUMP ROOM IN
ACCORDANCE WITH NFPA13 AS AN EXTRA
HAZARD GROUP 2 OCCUPANCY CLASSIFICATION.
07 PROVIDE INTERLOCK BETWEEN EX FP AND FP-1.
SEQUENCE OF OPERATIONS SHALL BE AS
FOLLOWS: 1. ON CALL FOR FIRE PUMP FP-1
STARTS. 2. IF FIRE PUMP FAILS TO START IN 10
SECONDS, EX FP SHALL START. 3. IN NO CASE
SHALL TWO PUMPS START SIMULTANEOUSLY.
08 FOR EXACT LOCATION OF FIRE PUMP ENCLOSURE
AND POST INDICATOR VALVE, SEE C-501.
N
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
FIRE PUMP AREA WITHIN BUILDING 501 DEMOLITION
01 GATE VALVES IN VERTICAL SECTION OF PIPING TO
BE RE-ORIENTED TO MAKE ROOM FOR NEW WALL.
02 EXISTING DIESEL TANK TO BE RELOCATED AS
SHOWN.
Scale: 1/4" = 1'-0"
FIRE PUMP AREA WITHIN BUILDING 501 AND NEW PUMP
PIPING PLAN
D. WHEN THE DIESEL PUMP INSIDE THE BUILDING IS IN
OPERATION, THE DOOR TO THE OUTSIDE SHALL BE
OPEN.
C. DIESEL REMOVED FROM TANK BY VA PRIOR TO TANK
RELOCATIOM.
B. PROVIDE SPRINKLER COVERAGE TO NEW FIRE PUMP
ROOM.
A. EXISTING PIPING BELOW SLAB IS SHOWN FOR
COORDINATION PURPOSES BASED ON RECORD
DRAWINGS. ANY DAMAGE TO EXISTING PIPING OR
CONDUIT SHALL BE REPAIRED AT NO COST TO VA.
0 2 4 8
N O
R T
H
TRUE
Scale: No Scale
PHOTO OF EXISING DIESEL ENGINE AND TANK
Scale: No Scale
PHOTO OF EXISTING FIRE PUMP AREA
Scale: No Scale
PHOTO OF EXISTING FIRE PUMP PIPING CONDITIONS
0 2 4 8
N O
R T
H
TRUE
T
NOTES:
1. SKID SHALL BE FILLED WITH CONCRETE AT INSTALLATION. THE
BASE PLATE OF PUMP AND DRIVER SHALL BE GROUTED PER
INSTALAITON INSTRUCTIONS.
2. PIPING TO THE PUMP ENCLOSURE SHOULD NOT BE ANCHORED
RIGIDLY UNTIL FINAL FIT-UP IS COMPLETE.
3. TAMPER SWITCHES SHALL BE PROVIDED ON ALL BUTTERFLY
VALVES, WIRING PROVIDED BY OTHERS.
4. LOCATION OF EQUIPMENT WITHIN ENCLOSURE IS APPROXIMATE.
5. ELECTRICAL SERVICE SHOWN ON ELECTRICAL DRAWINGS.
6. FINAL ORIENTATION AND LAYOUT OF INLET AND OUTLET
LOCATIONS, DOOR LOCATION, ELECTRICAL CONNECTION, PUMP
ROTATION, FDC, TEST DRAIN, AND LIGHTING SHALL BE PER SITE
CONDITIONS. SEE PLANS.
FP
M
TO SYSTEM
METER CONTROL VALVE
TO HOSE HEADER
JP
BYPASS (IF OF VALUE)
NOTES:
1. THE DISTANCE FROM THE FLOWMETER TO EITHER ISOLATION VALVE
SHALL BE AS RECOMMENDED BY THE METER MANUFACTURER.
2. THERE SHALL BE A DISTANCE OF NOT LESS THAN 5 DIAMETERS OF
SUCTION PIPE FOR TOP OR BOTTOM SUCTION CONNECTION TO THE
FIRE PUMP SUCTION FLANGE. THERE SHOULD BE A DISTANCE OF
NOT LESS THAN 10 DIAMETERS OF SUCTION PIPE FOR SIDE
CONNECTIONS (NOT RECOMMENDED) TO THE FIRE PUMP SUCTION
FLANGE.
3. AUTOMATIC AIR RELEASE SHALL BE PROVIDED IF PIPING FORMS AN
INVERTED "U", TRAPPING AIR.
4. OS&Y GATE VALVE OR INDICATING BUTTERFLY VALVE.
FROM SUPPLY
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:4
A M
F-501
FIRE PROTECTION DETAILS AND
SCHEDULES
3 3RK AKS
UPGRADE FIRE
SUPPRESSION AND
ANNUNCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
Scale: No Scale
FP-1, 1500 GPM ELECTRICALLY DRIVEN FIRE PUMP ENCLOSURE
Scale: No Scale
FIRE PUMP PIPING ARRANGEMENT (PER NFPA-20)
ELECTRIC UNIT HEATER SCHEDULE
TAG TYPE
MIN.
CAPACITY
POWER
REMARKS
AMP PHASE VOLT
EUH-1 ELECTRIC 5 kW 6 3 480 1, 2
HYDRONIC FIRE PUMP SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG
SERVED
SYSTEM TYPE
CIRCULATING FLUID
MIN % EFF
ELECTRICAL MOTOR
REMARKS
FLUID FLOW HEAD NPSH TEMPERATURE
NOMINAL
POWER
PHASE VOLT RPM
SPEED
CONTROL
FP-1 OUTSIDE BUILDING 501 BLDG 500 FIRE PROTECTION HORIZONTAL, SPLIT CASING WATER 1500 GPM 160 psig 60 61 % 200 hp 3 460 3570 VARIABLE 1, 2, 3, 4, 5, 6, 8, 9, 10, 12
JP-1 OUTSIDE BUILDING 501 BLDG 500 FIRE PROTECTION IN LINE JOCKEY WATER 60 GPM 170 psig 60 70 % 20 hp 3 460 1750 VARIABLE 5, 11
REMARKS:
1. PROVIDE PUMP WITH 2 HR ENCLOSURE RATED FOR OUTDOOR INSTALLATION.
2. PUMP SHALL BE ELECTRICALLY POWERED.
3. FIRE PUMP ENCLOSURE SHALL INCLUDE VENTILATION, HEAT, AND DRAIN.
4. PROVIDE REDUCED PRESSURE BACKFLOW PREVENTOR DETECTOR ASSEMBLY.
5. PROVIDE JOCKEY PUMP PIPED PER NFPA WITH ALL CONTROLS AND ACCESSORIES.
6. SUCTION PRESSURE AT PUMP INLET MIINIMUM 40 PSIG.
7. PROVIDE SOFT START FIRE PUMP CONTROLLER.
8. FIRE PUMP CONTROLLER SHALL HAVE MODBUS COMMUNICATION CAPABILITIES.
9. BASIS OF DESIGN IS PATTERSON FIRE PUMP (SERIES 8x6) WITH ENCLOSURE AND ACCESSORIES.
10. BASIS OF DESIGN IS PATTERSON HORIZONTAL SPLIT CASE PUMP (8X6).
11. BASIS OF DESIGN FOR FIRE PUMP CONTROLLER IS FIRETROL MODEL-FTT1930-AM200B.
REMARKS:
1. PROVIDE WALL MOUNTED THERMOSTAT.
2. BASIS OF DESIGN IS QMARK INDUSTRIAL UNIT HEATER ( IUH SERIES).
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
STD STANDARD
SWBD SWITCHBOARD
TYP TYPICAL
UTIL UTILITY
V VOLT
VA VOLT-AMPERES
W WATT
W/ WITH
W/O WITHOUT
XFMR TRANSFORMER
XFR TRANSFER
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PB PULL BOX OR PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PWR POWER
QTY QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
SEC SECONDARY
SF SQUARE FEET/FOOT
SPEC SPECIFICATION
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
AMP AMPERE
APPROX APPROXIMATELY
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BFF BELOW FINISHED FLOOR
BLDG BUILDING
C CONDUIT
CALC CALCULATED
CAP CAPACITY
CB CIRCUIT BREAKER
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CONN CONNECTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CU COPPER
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DISC DISCONNECT
DS SAFETY DISCONNECT SWITCH
DWG DRAWING
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EX EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GALV GALVANIZED
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
HP HORSEPOWER
IMC INTERMEDIATE METAL CONDUIT
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LF LINEAR FEET/FOOT
LRA LOCKED ROTOR AMPS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MSBD MAIN SWITCHBOARD
MT MOUNT
c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE. EQUIPMENT SHALL HAVE PERMANENT PHELONIC LABELS SECURE WITH SCREW TO THE EXTERIOR OF THE DISCONNECTS, PANELBOARDS, ETC. WITH APPROPRIATE IDENTIFICATION.
RED LETTERING ON WHITE FOR EMERGENCY ESSENTIAL/CRITICAL POWER; BLACK LETTERING ON
WHITE FOR NORMAL POWER.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT". THE OVERCURRENT
PROTECTIVE DEVICE SHALL COORDINATE WITH ALL UPSTREAM DEVICES TO ENSURE 100%
SELECTIVITY.
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND
CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,
LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
17. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
18. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED. WHERE SUBJECT TO BEING IN A WET LOCATION - RAIN, ETC. COMPRESSION FITTINGS SHALL BE LISTED
'RAINTIGHT'.
USING OHM'S LAW AND THE KNOWN RESISTIVITY
CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM
PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE
REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED
THE RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH
CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP
CALCULATIONS
ELECTRICAL SYMBOL LEGEND
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND STAINLESS STEEL COVER PLATE SHALL BE RED
IN COLOR
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND STAINLESS STEEL COVER PLATE SHALL
BE RED IN COLOR
JUNCTION BOX, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
EQUIPMENT CONNECTION
AS
NOTED
E
120V DUPLEX RECEPTACLE OUTLET AND STAINLESS
STEEL COVER PLATE
18"
DEMOLITION GENERAL NOTES
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS
DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.
B. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE
CONTRACTOR SHALL COOPERATE WITH OTHER TRADES.
C. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY
CIRCUITING WHICH REQUIRES CONTINUATION THROUGH THE AREA.
D. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT
CONTINUITY IS MAINTAINED.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO
REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS
TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT
DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID
CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.
G. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR
NEW DEVICES.
H. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT
DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
I. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
a. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
b. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
c. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
d. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
e. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND
MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
f. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER
OR OWNER'S REPRESENTATIVE.
J. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO
REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
F
F
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
42"-48"
90"
90"
90"
FLOW SWITCH
TAMPER SWITCH
POST INDICATOR VALVEPIV
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
F
S
SD CEILING
FIRE ALARM SYMBOL LEGEND
FIRE ALARM HORN AND STROBEF 90"
XX - CANDELA
XX - WATTAGE
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:2
A M
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 4GDA
UPGRADE FIRE
SUPPRESSION SYSTEM AND
ANNUCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
GG
TYPE DESCRIPTION MOUNTING LAMP BALLAST/DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
A 4' LINEAR LED STRIPLIGHT WITH LENS SURFACE LED; 6000
LUMENS; 80
CRI; 4000K
ELECTRONIC LED
DRIVER
120.00 V 56 W LITHONIA ZL1F-L48-SMR-6000LM-MDD-M
VOLT-40K-90CRI-WH
B EXTERIOR LED WALL PACK WALL 44W QL
INDUCTION
INDUCTION DRIVER 277.00 V 44 W LITHONIA OLW-31
E1 CONTEMPORARY LED SINGLE FACED EXIT SIGN WITH BLACK
POWDER PAINT ALUMINUM HOUSING, BRUSHED ALUMINUM FACE,
RED LETTERS, AND CHEVRON ARROWS AS SHOWN ON PLANS.
UNIVERSAL LED --- 120.00 V 5 W LITHONIA LES 1 R 120/277
D. PROVIDE ALL HOLLOW POLES WITH VIBRATION DAMPERS BY THE FACTORY.
C. FOR APPROVAL OF FIXTURES FROM MANUFACTURERS OTHER THAN THOSE LISTED, PROPOSED FIXTURES SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER TEN BUSINESS DAYS PRIOR TO BID FOR REVIEW. FINAL DETERMINATION OF 'EQUAL' STATUS FOR BIDDING SHALL BE THE SOLE DETERMINATION OF THE ARCHITECT/ENGINEER.
B. REMOVE ALL FINGER PRINTS FROM LENSES, REFLECTORS, AND LOUVERS FOLLOWING LIGHT FIXTURE INSTALLATION.
NOTES: A. FOR CONTINUOUS FIXTURES, COORDINATE WITH SUPPLIER ON LENGTH AND REQUIRED FITTINGS, AND INSTALL WITH UNIFORM ILLUMINATION ALONG FIXTURE INCLUDING CORNERS.
LUMINAIRE SCHEDULE
DocuSign Envelope ID: 78E16923-5FFC-4703-B116-858E7B1A2C30
12/18/2020
G
FI
W P
GFI
WP
GFI
WP
E
A T
S
E
E
F F
SD
ELUA
EPDUA
A
A
A
B
A
A
E1
EPDUB
EPUA
LUA PUA
PDUA
B S W G R
(F P E
B501 4160
CHILLER SWGR
CCU-1, CCU-2,
CCU-3
PROPOSED 2-WAY DUCTBANK,
REFER TO DETAIL 2 ON SHEET
E-501
(E)'T1' 1500A 13.2kV-480V
(E) 2000A 13.2kVA-4160V
C
10 11
D
8 9
E
F
G
EXISTING DIESEL FIRE PUMP
EUH-1
EPDUA-1,3,5
ELUA-11
ELUA - 1
PROPOSED 3-WAY DUCTBANK,
REFER TO DETAIL 4 ON SHEET
E-501
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:3
:2
A M
E-101
ELECTRICAL NEW WORK PLAN
2 4GDA
UPGRADE FIRE
SUPPRESSION SYSTEM AND
ANNUCIATION SYSTEM
H.H. MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 DECEMBER 18, 2020
CONSTRUCTION DOCUMENTS
652-18-10018-170
GG
0 4 8 16
N O
R T
H
TRUE
1. VERIFY WITH EQUIPMENT MANUFACTURER
EXACT CONNECTION REQUIREMENTS.
2. PROVIDE POWER AND SIGNAL CONDUCTORS
AND CONDUITS AS REQUIRED BY EQUIPMENT
MANUFACTURER.
3. VERIFY EXACT LOCATION OF FIRE PUMP
EQUIPMENT WITH FIRE PROTECTION
SHEETS.
4. UNLESS NOTED OTHERWISE, THE FIRE PUMP
ENCLOSURE IS A SINGLE-POINT CONNECTION,
SKID-MOUNTED UNIT WITH ALL EQUIPMENT
PROVIDED AND PRE-WIRED AT THE FACTORY.
5. SEE CIVIL DRAWING C-501 FOR LOCATION OF
BUILDING "BLACK BOX" AND BUILDING 501B
"GRAY BOX".
N
KEY PLAN
SCALE: NO SCALE
1 FIRE PUMP MAIN DISTRIBUTION PANEL,
ROUTE DUCTBANK AND CONDUITS TO TURN
UP UNDER PANEL. BRING ONE CONDUIT TO
PANEL. STUB THE OTHER CONDUIT 6-INCHES
ABOVE FINISHED FLOOR HEIGHT, PROVIDE
CAP, AND LABEL AS "SPARE".
2 THE FIRE PUMP MOTOR WILL BE PREWIRED
TO THE PANEL BY OTHERS.
3 THE JOCKEY PUMP WILL BE PREWIRED TO
THE PANEL BY OTHERS.
4 THE ELECTRICAL CONTRACTOR SHALL
PROVIDE THE FIRE ALARM NOTIFICATION
DEVICE, THE PULL STATION, AND SMOKE
DETECTOR. TAMPER SWITCHES ARE
PROVIDED BY OTHERS. THE ELECTRICAL
CONTRACTOR SHALL WIRE THE DEVICES TO
THE EXISTING FIRE ALARM CONTROL PANEL
IN BUILDING 501.
5 THE EMERGENCY LIGHT WILL BE PREWIRED
TO THE PANEL BY OTHERS.
6 THE UNIT HEATERS WILL BE PREWIRED TO
THE PANEL BY OTHERS.
7…