This document package includes drawings and specifications for the rehabilitation of a sanitary sewer system located on a USDA campus in Ames, Iowa. Major work includes replacing approximately 413 linear feet of 8-inch gravity sewer pipe and installing 134 linear feet of 6-inch gravity sewer pipe. Additional work involves rehabilitating 25 manholes to address infiltration issues by cleaning, replacing lids and frames, and grouting joints. The solicitation was issued by the USDA Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services for project number 12639521R0015. Drawings depict the site plan, manhole locations and rehabilitation needs.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and answers.pdf | ||
| Q and A from 5-5-21.pdf | ||
| Amendment 0002.pdf | ||
| Amendment 0001.pdf | ||
| 12639521R0015.pdf | ||
| DOL wage rates-IA20210074.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TITLE PAGE
T-1
SOUTH CAMPUS
SANITARY SEWER
REPAIRS
UNITED STATES DEPARTMENT OF AGRICULTURE
NATIONAL CENTERS FOR ANIMAL HEALTH
SOUTH CAMPUS SANITARY SEWER REPAIRS
I:\Projects\20098 - Site - South Campus Sanitary Sewer Repairs\DESIGN\Misc\20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS.dwg, 3/11/2021 10:44:29 AM, AutoCAD PDF (General Documentation).pc3
Attachment 2
SITE PLAN
SHEET 1
SOUTH CAMPUS
SANITARY SEWER
MAINTENANCE
I:\Projects\20098 - Site - South Campus Sanitary Sewer Repairs\DESIGN\Misc\20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS.dwg, 3/11/2021 10:44:30 AM, AutoCAD PDF (General Documentation).pc3
NOTES
AND
SCHEDULES
SHEET 2
SOUTH CAMPUS
SANITARY SEWER
MAINTENANCE
MANHOLE REHABILATION TABLE
MANHOLE # LOCATION STEPS DEPTH [FT] FRAME CLEAR
OPENING [IN]
LOCATION SURFACE CONDITION SUMMARY REQUIRED SCOPE FOR
REHABILITATION OF MANHOLE
1 NW OF BLDG Z2 6 10.200000 22 CONCRETE PAVEMENT INFILTRATION STAINS ON WALLS,
SEDIMENT ON BENCH
CLEAN MH, SEAL FRAME, GROUT
CHIMNEY AND WALL JOINTS TO SEAL
ALL GROUND WATER INFILTRATION
POINTS
2 SW OF BLDG Y2 NOT LOCATED LOCATE AND EXCAVATE MANHOLE
TO ACCESS FOR
INSPECTION, MAKE CORRECTIONS
AS REQUIRED TO TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
3 S OF BLDG Y2 IN GRASS
AREA
6 9.9 22 GRASS/DIRT INFILTRATION STAINS ON WALLS,
SEDIMENT ON BENCH
CLEAN MH, SEAL FRAME, GROUT
CHIMNEY AND WALL JOINTS TO SEAL
ALL GROUND WATER INFILTRATION
POINTS
4 N OF MB BLDG, ON NE OF
ROAD
INTERSECTION
5 10.2 24 GRASS/DIRT INFILTRATION STAINS ON WALLS,
SEDIMENT ON BENCH,
INFILTRATION AT JOINT BETWEEN
BENCH AND WALL
CLEAN MH, SEAL FRAME, GROUT
CHIMNEY, BENCH, AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
5 N OF MB BLDG, ON SE OF
DRIVE
INTERSECTION
5 10.5 24 GRASS/DIRT VENTED LID, INFILTRATION STAINS
ON WALLS, SEDIMENT ON
BENCH
CLEAN MH, REPLACE LID, GROUT
CHIMNEY AND WALL JOINTS TO SEAL
ALL GROUND WATER INFILTRATION
POINTS
6 SW OF BLDG C3 6 10.8 24 GRASS/DIRT VENTED LID, INFILTRATION STAINS
ON WALLS, SEDIMENT ON
BENCH
CLEAN MH, SEAL FRAME, REPLACE
LID, GROUT CHIMNEY AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
7 SE OF BLDG C4 5 10.3 24 GRASS/DIRT VENTED LID, INFILTRATION STAINS
ON WALLS, SEDIMENT ON
BENCH, BREAK-IN SERVICE
CONNECTION SHOWS EXPOSED
REINFORCEMENT
CLEAN MH, REPLACE LID, GROUT
CHIMNEY AND WALL JOINTS, REPAIR
PIPE CONNECTION TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
7a SE OF BLDG C5 5 9.0 24 GRAVEL INFILTRATION STAINS ON WALLS, SEDIMENT ON BENCH
CLEAN MH, GROUT CHIMNEY AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
7b E OF BLDG C5 6 8.5 24 GRASS/DIRT INFILTRATION STAINS ON WALLS, SEDIMENT ON BENCH
CLEAN MH, SEAL FRAME, GROUT
CHIMNEY AND WALL JOINTS TO SEAL
ALL GROUND WATER INFILTRATION
POINTS
7c SW OF BLDG C5 NOT LOCATED LOCATE AND EXCAVATE MANHOLE
TO ACCESS FOR
INSPECTION, MAKE CORRECTIONS
AS REQUIRED TO TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
8 W OF BLDG C8 GRAVEL CLEANOUT
9 W OF BLDG A1 6 10 24 GRAVEL VENTED LID, INFILTRATION
DEPOSITS AND SCALING ON WALLS
AND BENCH
CLEAN MH, REPLACE LID, SEAL
FRAME, GROUT CHIMNEY,
BENCH, AND WALL JOINTS TO SEAL
ALL GROUND WATER INFILTRATION
POINTS
10 S OF BLDG A2 2 8.0 24 GRAVEL VENTED LID, INFILTRATION STAINS
ON WALLS, INFILTRATION AT
PIPE CONNECTIONS AND LIFTING
HOLES
REPLACE LID, GROUT CHIMNEY AND
WALL JOINTS AND PIPE
CONNECTIONS TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
11 SW OF BLDG AT, ON NE
OF INTERSECTION
5 8.3 24 GRAVEL VENTED LID, INFILTRATION STAINS
ON WALLS AND DEPOSITS
AND SCALING ON WALLS AND BENCH
CLEAN MH, REPLACE LID, GROUT
CHIMNEY, BENCH, AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
12 SE OF BLDG AI 6 7.8 24 GRAVEL INFILTRATION STAINS ON WALLS
AND DEPOSITS AND SCALING
ON WALLS AND BENCH
CLEAN MH, GROUT CHIMNEY, BENCH,
AND WALL JOINTS TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
13 SW OF BLDG A2 5 7.3 24 GRAVEL INFILTRATION STAINS ON WALLS,
SEDIMENT ON BENCH
CLEAN MH, GROUT CHIMNEY AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
14 SW OF BLDG A3 3 7.2 30 GRAVEL FRAME BROKEN BELOW COVER
BEARING SURFACE,
INFILTRATION STAINS ON WALLS,
SEDIMENT ON BENCH
CLEAN MH, REPLACE FRAME, GROUT
CHIMNEY AND WALL
JOINTS
15 S OF BLDG A3 5 9.7 30 GRAVEL INFILTRATION STAINS ON WALLS GROUT CHIMNEY AND WALL JOINTS
TO SEAL ALL GROUND WATER
INFILTRATION POINTS
16 S OF BLDG A5 NOT LOCATED LOCATE AND EXCAVATE MANHOLE
TO ACCESS FOR
INSPECTION, MAKE CORRECTIONS
AS REQUIRED TO TO SEAL ALL
GROUND WATER INFILTRATION
POINTS
17 SEOTBLDGA6 4 8.3 30 GRAVEL INFILTRATION STAINS ON WALLS,
INFILTRATION AT WALL JOINT
AND PIPE CONNECTION
GROUT CHIMNEY AND WALL JOINTS
TO SEAL ALL GROUND WATER
INFILTRATION POINTS. SEAL PIPE
CONNECTIONS.
18 SW OF BLDG A8 NOT LOCATED NO SCOPE
19 SE OF BLDG A9 2 6.8 30 GRAVEL INFILTRATION STAINS ON WALLS NO SCOPE
20 IN ROAD N OF GATE BY
SUPPORT BLDG
5 8.6 22 CONCRETE PAVEMENT VENTED LID, INFILTRATION STAINS
ON WALLS AND DEPOSITS
AND SCALING ON WALLS AND BENCH
CLEAN MH, REPLACE LID, GROUT
CHIMNEY, BENCH, AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
21 IN SOUTH DRIVE W OF
SUPPON BLDG
4 7.5 22 CONCRETE PAVEMENT VENTED LID, INFILTRATION STAINS
ON WALLS AND DEPOSITS
AND SCALING ON WALLS AND BENCH
CLEAN MH, REPLACE LID, GROUT
CHIMNEY, BENCH, AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
22 NW OF BLDG H2 3 6.0 22 GRAVEL VENTED LID, INFILTRATION STAINS
ON WALLS, INFILTRATION AT
JOINT BETWEEN BENCH AND WALL
REPLACE LID, SEAL FRAME, GROUT
CHIMNEY, BENCH, AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
23 IN SOUTH DRIVE W OF
SUPPORT BLDG
4 7.1 22 CONCRETE PAVEMENT VENTED LID, INFILTRATION STAINS
ON WALLS
REPLACE LID, GROUT CHIMNEY AND
WALL JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
24 IN SOUTH DRIVE W OF
SUPPORT BLDG
4 8.3 22 CONCRETE PAVEMENT VENTED LID, CRACKED ADJUSTING
RING, DEBRIS IN MH
BOTTOM, INFILTRATION STAINS ON
WALLS, INFILTRATION AT JOINT
BETWEEN BENCH AND WALL
REPLACE LID, REMOVE DEBRIS,
GROUT CHIMNEY, BENCH, AND WALL
JOINTS TO SEAL ALL GROUND
WATER INFILTRATION POINTS
25 IN SOUTH DRIVE, SW OF
INTERSECTION
WITH MIDDLE DRIVE
6 9.0 24 CONCRETE PAVEMENT INFILTRATION STAINS ON WALLS GROUT CHIMNEY AND WALL JOINTS
TO SEAL ALL GROUND WATER
INFILTRATION POINTS
I:\Projects\20098 - Site - South Campus Sanitary Sewer Repairs\DESIGN\Misc\20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS.dwg, 3/11/2021 10:44:31 AM, AutoCAD PDF (General Documentation).pc3
Adam Bunnell Text Box 10.2
| Sheets and Views |
| 20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS-TITTLE |
| 20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS-SHEET1 |
| 20098 - SOUTH CAMPUS SANITARY SEWER REPAIRS-SHEET2 |
File details come from the government source that posted it. Updated .