Drawings.pdf

PDF 3 MB Posted

Attached to
Dept of Military, Huron-Replace HVAC System
Solicitation number
23IFB9077
Issued by
Bennett County, South Dakota

About this file

This document is a set of construction drawings and project details for a state-led HVAC replacement project at the South Dakota National Guard Armory in Huron, South Dakota. The project scope includes removing the existing air handling units serving the drill floor and replacing them with a new large roof-mounted HVAC unit. Additional work involves removing and replacing the condensing unit and coil for an existing multizone unit, as well as reworking steam piping, installing new ductwork, and completing associated electrical, plumbing, architectural, and insulation work. The solicitation number is CFMO 466789, and the project is being managed by the South Dakota Department of the Military.

The bid documents provide detailed drawings, specifications, and equipment schedules for the HVAC system components and related construction work. Pricing is not explicitly stated, but the project involves a concrete pad, fencing, and integration with existing infrastructure. Funding sources are not specified, but the project is being led by the state government. No set-asides or incumbent contractor details are provided. Bidders must comply with federal Build America Buy America requirements for products and materials.

View the file

Other files

File Type Posted
Invite to Bid.pdf PDF
Project Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROGER C.

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

TITLE/DISCIPLINE NAME/CONTACT COMPANY PHONE

PROJECT MANAGER ROGER NIKOLAS TSP, Inc. 605.336.1160

MECHANICAL ENGINEER ROGER NIKOLAS TSP, Inc. 605.336.1160

ELECTRICAL ENGINEER JAKE BUCKMILLER TSP, Inc. 605.336.1160

DESIGN TEAM

NikolasRC@teamtsp.com

E-MAIL

NikolasRC@teamtsp.com

BuckmillerJR@teamtsp.com

08/15/2023

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :21

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

COVER SHEET

G-001

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

RCN08/15/2023

RCN04232057

SDARNG HURON ARMORY

HVAC REPLACEMENT CFMO# 466789

CONSTRUCTION DOCUMENTS

08/15/2023

HURON, SOUTH DAKOTA

GENERAL SHEET INDEX

SHEET # SHEET NAME

G-001 COVER SHEET

DRAWING INDEX

ELECTRICAL SHEET INDEX

SHEET # SHEET NAME

E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

ED101 ELECTRICAL DEMOLITION PLAN

EP101 POWER PLAN

E-601 ELECTRICAL RISER AND SCHEDULES

MECHANICAL SHEET INDEX

SHEET # SHEET NAME

M-001 MECHANICAL TITLE SHEET

MD101 MECHANICAL DEMOLITION PLAN - FIRST FLOOR

MH101 MECHANICAL HVAC PLAN - FIRST FLOOR

MP101 MECHANICAL PIPING PLAN - FIRST FLOOR

M-501 MECHANICAL DETAILS

ME601 MECHANICAL SCHEDULES

ISSUE DATE DESCRIPTION

NIKOLAS

RE

G IS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

& AND

Ø ROUND

A AIR

AC AIR CONDITIONING

ACOUS ACOUSTICAL

AD AREA DRAIN

ADD ADDENDUM

ADDL ADDITIONAL

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION

EFFICIENCY

AG ABOVE GROUND

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AV ACID RESISTANT VENT

AW ACID RESISTANT WASTE

AUTO AUTOMATIC

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BLW BELOW

BM BEAM

BO BY OTHER

BOT BOTTOM

BSMT BASEMENT

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER

HOUR

BTWN BETWEEN

CAP CAPACITY

CB CATCH BASIN

CCW COUNTER CLOCKWISE

CFCV CONSTANT FLOW CONTROL

VALVE

CFM CUBIC FEET PER MINUTE

CHW CIRCULATING HOT WATER

CI CAST IRON

CLG CEILING

CLG COOLING

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

COND CONDENSATE

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE/CONTINUATION

CONTR CONTRACT/CONTRACTOR

COORD COORDINATE

CTR CENTER

CUFT CUBIC FEET

CV CHECK VALVE

CW COLD WATER

CW CLOCKWISE

D DEGREE

DB DRY BULB

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DIV DIVISION

DI DEIONIZED WATER

DMPR DAMPER

DN DOWN

DWG DRAWING

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR

TEMPERATURE

EL ELBOW

ELEC ELECTRICAL

ELEV ELEVATION

EP EXPLOSION PROOF

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER

TEMPERATURE

E/A EXHAUST AIR

EAH EXHAUST HOOD

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FHC FIRE HOSE CABINET

FL FLOOR

FLEX FLEXIBLE

FLG FLANGE

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED

PIPE

FS FULL SIZE

FS FLOOR SINK

FT FOOT/FEET

FTG FOOTING

FTR FIN TUBE RADIATION

GA GAGE/GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR/GENERAL

GPM GALLONS PER MINUTE

GR GRADE

GW GREASE WASTE

HB HOSE BIBB

HORZ HORIZONTAL

HP HORSE POWER

HP HIGH PRESSURE

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INL INLET

INSUL INSULATION

INT INTERIOR

INV INVERT

INWG INCHES WATER GAUGE

JT JOINT

LAB LABORATORY

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LF LINEAR FOOT

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LR LIQUID REFRIGERANT

LS LAWN SPRINKLER

LVR LOUVER

LWT LEAVING WATER

TEMPERATURE

M/A MIXED AIR

MAN MANUAL

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBD MOTORIZED BYPASS

DAMPER

MBH ONE THOUSAND BTU PER

HOUR

MCF ONE THOUSAND CUBIC FEET

MCW MAKE-UP COLD WATER

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

N NECK / NORTH

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER / NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

OC ON CENTER

OF OVERFLOW

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PR PAIR

PRESS PRESSURE

PRIM PRIMARY

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH

GAUGE

PW POTABLE WATER

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

REFR REFRIGERATION

RH RELATIVE HUMIDITY

REQD REQUIRED

REV REVERSE

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SCHED SCHEDULE

SECT SECTION

SD SMOKE DAMPER

SHT SHEET

SIM SIMILAR

SLV SLEEVE

SM SURFACE MOUNT

SP STANDPIPE / STATIC

PRESSURE

SPEC SPECIFICATION

SPS STATIC PRESSURE STATION

SQ SQUARE

SR SUCTION REFRIGERANT

SSD SOIL SUBDRAIN

SS STAINLESS STEEL

STD STANDARD

STM STEAM

STRUCT STRUCTURAL

SUCT SUCTION

SUSP SUSPENDED

T THERMOSTAT

TCP TEMPERATURE CONTROL

PANEL

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UFD UNDER FLOOR DUCT

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VENT VENTILATION

VERT VERTICAL

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONSGENERAL MECHANICAL SYMBOLS

HVAC SYMBOLS

LAB AND MEDICAL SYMBOLS

FIRE PROTECTION SYMBOLS

SA

RA

ELBOW WITH TURNING VANES

LAB AIRLA

LAB DEIONIZED WATERLDE

LAB DISTILLED WATERLDI

LAB GASLG

LAB VACUUMLV

MEDICAL AIRMA

MEDICAL CO2CO2

MEDICAL GASMGAS

MEDICAL HYDROGENH

MEDICAL NITROGENNI

MEDICAL NITROUS OXIDENO

MEDICAL OXYGENO

MEDICAL VACUUMMV

FIRE PROTECTION OTHERFP-O

DRY FIRE SPRINKLERDF

COUPLING

SOUND ATTENUATOR

M

F B

S C

MOTORIZED

DAMPER

SMOKE

DAMPER

COMBINATION

SMOKE & FIRE

DAMPER

VOLUME

DAMPER

FIRE

DAMPER

BACKDRAFT

DAMPER

TYPE

CFM

S-1 (3X)

16"x16"

R-1

VOLUME DAMPER

TOTAL

(IF EXCEEDS 1)

RETURN

DIFFUSER

VAV BOXES

POWER ROOF VENTILATOR

UNIT HEATERS

RADIANT

PANEL

x x-xxx

Room

POINT WHERE NEW CONNECTS TO EXISTING

NUMBER OF DETAIL ON SHEET

NUMBER OF SHEET WHERE DETAIL APPEARS

KEYNOTE

CONTINUATION SYMBOL

ROOM NAME AND NUMBER

SQUARE DUCT SIZE TAG (WIDTH X HEIGHT)16"x8"

16"/8"

16"Ø

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

ROUND DUCT SIZE TAG (DIAMETER)

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISEDROP

ROUND SUPPLY/OUTSIDE AIR DUCT RISEDROP

RECTANGULAR RETURN/TRANSFER AIR DUCT RISEDROP

ROUND RETURN/TRANSFER AIR DUCT RISEDROP

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISEDROP

ROUND EXHAUST/RELIEF AIR DUCT RISEDROP

SA

RA

EA

EA

FLEX DUCT

x-xxx EQUIPMENT TAG

LINEAR DIFFUSER

CO2 TH

CO TS

NO2 T

HS SVV

H S

TEMPERATURE & HUMIDITY SENSORCARBON DIOXIDE SENSOR

TEMPERATURE SENSORCARBON MONOXIDE SENSOR

THERMOSTATNITROGEN DIOXIDE SENSOR

MANUAL SWITCHHUMIDITY SENSOR

SENSORHUMIDISTAT

FIRE PROTECTION PRE-ACTIONFP-PA

FIRE PROTECTION WETFP

COMBINATION FIRE & DOMESTICFP-DOM-W

UPRIGHT SPRINKLER HEAD

PENDANT SPRINKER HEAD

RECESSED SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

'D' REPRESENTS DRY SPRINKLER HEAD

D

SIDEWALL SPRINKLER HEAD

EXTENDED COVERAGE

SIDEWALL SPRINKLER HEAD

OBSTRUCTION FROM

DUCTWORK 48" AND

GREATER

48"x18" S/A

PLUMBING AND PIPING SYMBOLS

CONDENSATE DRAINCD

DUAL TEMP WATER RETURNDTWR

DOMESTIC HOT WATER RECIRCULATINGRHW

DOMESTIC HOT WATERHW

DOMESTIC COLD WALTERCW

DOMESTIC COLD WATER SOFTSCW

SANITARY VENTV

SANITARY WASTE - BELOW GROUNDWB

SANITARY WASTEW

NATURAL GASG

NATURAL GAS - 2LBG-2LB

PROCESSPRO

STORM DRAINAGERD

STORM DRAINAGE - BELOW GRADERDB

STORM DRAINAGE OVERFLOWORD

STORM DRAINAGE OVERFLOW BELOW GRADEORDB

GLYCOL HOT WATER RETURNGHR

GLYCOL HOT WATER SUPPLYGHS

HEATING WATER RETURNHWR

HEATING WATER SUPPLYHWS

OIL WASTEOW

CHILLED WATER RETURNCWR

CHILLED WATER SUPPLYCWS

CONDENSER WATER RETURNCR

CONDENSER WATER SUPPLYCS

OIL VENTOV

REFRIGERANTREF

REFRIGERANT HOT GASRHG

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

ACID WASTE ABOVE GRADEAW

ACID VENT PIPINGAV

ACID WASTE BELOW GRADEAWB

GEOTHERMAL SUPPLYGTS

GEOTHERMAL RETURNGTR

LPS

STEAM - LP CONDENSATELPR

23. FLOW SWITCH

24. PRESSURE TEMPERATURE TAP

25. MANUAL CALIBRATED BALANCING VALVE

26. AUTOMATIC FLOW CONTROL VALVE

27. MEDICAL GAS OUTLET

28. HOSE BIBB OR WALL HYDRANT

29. INSERTION FLOW METER

30. FLOW METER

31. REDUCED PRESSURE BACKFLOW

PREVENTER

32. AQUASTAT

33. 3-WAY VALVE

1. SIDE CONNECTION

2. ELBOW DOWN

3, ELBOW UP

4. SHUT OFF VALVE

5. BALANCING VALVE

6. CONTROL VALVE

7. PRESSURE REDUCING VALVE

8. PRESSURE RELIEF VALVE

9. CHECK VALVE

10. AIR VENT

11. PRESSURE GAUGE

12. THERMOMETER

13. PIPE ANCHOR

14. PIPE GUIDE

15. CONCENTRIC REDUCER

16. ECCENTRIC REDUCER

17. STRAINER

18. UNION

19. DIRECTION OF FLOW

20. PITCH PIPE DOWN

21. 3-WAY CONTROL VALVE

22 PUMP

STEAM - LP

MPS

STEAM - MP CONDENSATEMPR

STEAM - MP

HPS

STEAM - HP CONDENSATEHPR

STEAM - HP

CONDENSATE RETURNCDR

COMBINATION WASTE AND VENTCWV

COMPRESSED AIRA

PUMP DISCHARGEPD

MITIGATION VENTMIT

GREASE VENTGV

GREASE WASTEGW

DEIONIZED WATERDI

REVERSE OSMOSIS WATERRO

DUAL TEMP WATER SUPPLYDTWS

PIPE BEING DEMOLISHED

EXISTING PIPE TAG

DOMESTIC COLD WATER HARDHCW

DOMESTIC HOT WATER - 140 DEGRESSHW 140

FM AFS

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

333231302928272625242322212019

PLUG

REDUCING 45 DEGREE TEE

45 DEGREE TEE

2"4"

4"

ROOF DRAIN FIXTURE

4" RD-1

4" ORD-1

DRAIN SIZE

DRAIN TAG

TYPE (SEE SCHEDULE)

FCO WCO W

WH-1

PLUMBING FIXTURE

PLUMBING FIXTURE TAG

TYPE (SEE SCHEDULE)

DOWNSPOUT NOZZLE

FLOOR

CLEAN

OUT

WALL

CLEAN

OUT

FLOOR

DRAIN

DOMESTIC

WATER HEATER GAS METER END CAP PIPE BREAK

DOMESTIC HOT WATER RECIRCULATING 140 DEGREESRHW 140

DOMESTIC COLD WALTER - FILTEREDF-CW

(E)

1/8" / 12" SLOPE

2"

PIPE SLOPE TAG

PIPE SIZE TAG (DIAMETER)

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AFMS AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CF CABINET FAN

CF CHEMICAL FEEDER

CFP CHEMICAL FEEDER PUMP

CH CHILLER

CRU CONDENSATE RETURN UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

H HUMIDIFIER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

ILC INLINE CENTRIFUGAL

PF PROPELLER FAN

PRV POWER ROOF VENTILATOR

PWF POWER WALL FAN

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SA SHOCK ABSORBER

SAT SOUND ATTENUATOR

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

US UTILITY SET

UV UNIT VENTILATOR

WFMS WATER FLOW MEASURING STATION

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL

OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN

ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.

08/15/2023

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :25

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL TITLE

SHEET

M-001

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

RCN08/15/2023

RCN04232057

PROJECT GENERAL NOTES

* DEMO 1 WHERE EQUIPMENT AND/OR FIXTURES ARE INDICATED TO BE REMOVED, THE EXISTING

SERVICES SHALL BE CAPPED AND CONCEALED BEHIND FINISHED SURFACES. ABANDONED

BRANCH SERVICES SHALL BE REMOVED BACK TO THE MAINS AND CAPPED, UNLESS OTHERWISE

INDICATED.

* DEMO 2 CAP ANY ABANDONED OR UNUSED PIPE AND/OR DUCT OPENINGS.

* DEMO 3 THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING TO MATCH EXISTING

WALLS, FLOORS, AND CEILINGS.

* DEMO 4 HYDRONIC AND DOMESTIC PIPING SHALL BE THOROUGHLY CLEANED BEFORE PUTTING INTO

PERMANENT SERVICE.

* DEMO 5 WHERE MATERIAL IS INDICATED TO BE REMOVED, IT SHALL REMAIN THE PROPERTY OF THE

OWNER. THIS CONTRACTOR SHALL DISPOSE OF MATERIAL AS DIRECTED BY THE OWNER.

* EXST 1 REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.

* EXST 2 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING, PRIOR TO FINAL

BID, ALL EXISTING CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS.

* EXST 3 WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT

CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO

START OF WORK.

* NEW 1 COORDINATE AND COOPERATE WITH THE OTHER TRADES ON THE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY, STRUCTURE, AND EQUIPMENT TO PREVENT

CONFLICTS.

* NEW 2 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH EXISTING AND THOSE

ILLUSTRATED BY THESE DOCUMENTS AS WELL AS THOSE WHICH CAN BE REASONABLY

ANTICIPATED INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS INVOLVED ON THIS PROJECT.

* NEW 3 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO ALL REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT

LIMITED TO THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE.

* NEW 4 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.

* NEW 5 ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0" FROM EDGE OF ROOF.

* NEW 6 LOCATE DUCTWORK, PIPING, AND MECHANICAL EQUIPMENT AWAY FROM THE SPACE ABOVE

ELECTRICAL PANELS, TRANSFORMERS, AND OTHER ELECTRICAL EQUIPMENT.

* NEW 7 ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO MECHANICAL EQUIPMENT.

* NEW 8 REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C. CONDENSATE DRAIN PIPING.

* NEW 9 PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL ANOTHER SIZE IS

SHOWN.

* NEW 10 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE SEGMENTS, REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.

* NEW 11 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN

INSTALLATION INSTRUCTIONS.

* NEW 12 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE DRAWING, ARE

APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL BE

COORDINATED WITH ALL OTHER TRADES TO AVOID INTERFERENCE IN THE FIELD.

* NEW 13 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT

CEILINGS.

* NEW 14 MATERIALS AND EQUIPMENT SHOWN ON PLANS SHALL BE NEW AND FURNISHED BY THIS

CONTRACTOR UNLESS OTHERWISE INDICATED.

* NEW 15 THIS CONTRACTOR IS RESPONSIBLE FOR ALL SLEEVES AND/OR OPENINGS WHERE REQUIRED TO

RUN PIPES AND DUCTS THROUGH FOUNDATIONS, FLOOR SLABS, WALLS, BRIDGING AND BEAMS

EXCEPT WHERE OTHERWISE INDICATED.

* NEW 16 CEILING ACCESS IS REQUIRED AT ALL REHEAT COILS, VALVES, FIRE DAMPERS, MANUAL AND

MOTORIZED DAMPERS LOCATED ABOVE CEILING. CEILING ACCESS PANELS WILL BE PROVIDED

UNDER THE GENERAL SECTION OF CONSTRUCTION AND SHALL BE MINIMUM OF 24" X 24" UNLESS

OTHERWISE INDICATED. COORDINATE WITH GENERAL CONTRACTOR.

* NEW 17 THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS AND

DIMENSIONS. NOTIFY THE A/E IMMEDIATELY OF ANY DISCREPANCIES.

* NEW 18 WHERE NEW SERVICES ARE SHOWN CONNECTING TO EXISTING, VERIFY EXACT LOCATION AND

SIZE OF EXISTING.

* NEW 19 EXISTING SERVICES SHALL BE MAINTAINED UNLESS OTHERWISE INDICATED.

* NEW 20 ALL DUCTS, PIPING, FIXTURES, ETC., WHICH ARE DASHED AND/OR INDICATED BY NOTE ON

DEMOLITION PLANS SHALL BE REMOVED.

* NEW 21 ALL PLUMBING SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH NATIONAL, STATE, AND LOCAL CODES.

* NEW 22 SEAL ALL SHEET METAL DUCTWORK JOINTS.

* NEW 23 BALANCING OF AIR AND HYDRONIC SYSTEMS SHALL BE PERFORMED BY AN NEBB OR AABC

CERTIFIED TEST AND BALANCE AGENCY.

* NEW 24 PIPE PENETRATIONS OF RATED WALLS AND FLOORS SHALL BE SLEEVED AND PROPERLY FIRE

SEALED.

* NEW 25 ALL PIPE AND DUCT PENETRATIONS OF SMOKE PARTITION WALLS SHALL BE PROPERLY SEALED

TO RESIST THE PASSAGE OF SMOKE AS REQUIRED BY THE LOCAL AUTHORITY.

HVAC GENERAL NOTES

* NEW 1 SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.

* NEW 2 CONTRACTOR SHALL LOCATE THERMOSTATS, CO2, AND TEMPERATURE SENSORS AT 4'-0" AFF, A MINIMUM OF 8" FROM LIGHT SWITCH.

* NEW 3 REFER TO PIPING DRAWINGS FOR THERMOSTAT, CO2, AND TEMPERATURE SENSOR LOCATIONS.

* NEW 4 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR SHALL

ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE, AND LOCAL

CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER.

* NEW 5 PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT. COORDINATE

SIZES WITH MECHANICAL EQUIPMENT SELECTED.

* NEW 6 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMENT AFTER ALL

DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.

SHEET INDEX - MECHANICAL

SHEET # SHEET NAME

M-001 MECHANICAL TITLE SHEET

MD101 MECHANICAL DEMOLITION PLAN - FIRST FLOOR

MH101 MECHANICAL HVAC PLAN - FIRST FLOOR

MP101 MECHANICAL PIPING PLAN - FIRST FLOOR

M-501 MECHANICAL DETAILS

ME601 MECHANICAL SCHEDULES

T

T

ROGER C.

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

(E) 3/4" LPR

(E) 1" LPS

6 7

08/15/2023

KEYNOTES

1 REMOVE AIR HANDLING UNIT, ALL DUCTWORK AND PIPING. REMOVE LPS AND LPR PIPING BACK TO

MAINS AND CAP.

2 SPACE TEMPERATURE SENSOR TO REMAIN.

3 GRAVITY RELIEF DUCT AND ROOF HOOD TO REMAIN.

4 STEAM FIN-TUBE RADIATION TO REMAIN.

5 MULTI-ZONE AIR HANDLER TO REMAIN. REMOVE EXISTING COOLING COIL AND REFRIGERANT PIPING.

6 UNDER ALTERNATE NO. 1, REMOVE SUPPLY FAN MOTOR AND REPLACE WITH NEW MOTOR.

7 UNDER ALTERNATE NO. 1, REMOVE ALL EXISTING DDC ACTUATORS SERVING AHU AND REPLACE

WITH NEW. INCLUDE ALL ZONE DAMPER, RETURN DAMPER, OUTSIDE AIR DAMPER, AND STEAM COIL

CONTROL VALVE ACTUATORS.

8 LOW PRESSURE STEAM BOILER TO REMAIN.

9 REMOVE AIR COOLED CONDENSING UNIT AND ALL PIPING.

10 REMOVE OUTDOOR AIR LOUVER.

11 OUTDOOR AIR LOUVER TO REMAIN. CAP LOUVER WITH 3" RIGID INSULATION AND 16 GA. METAL

PANEL.

12 REMOVE SIDEWALK AT CONDENSING UNIT.

13 LPS AND LPR PIPING TO REMAIN.

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :28

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL

DEMOLITION PLAN -

FIRST FLOOR

MD101

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

JHL08/15/2023

RCN04232057

SHEET GENERAL NOTES

A EQUIPMENT, DUCTWORK, PIPING, ETC. TO BE REMOVED OR RELOCATED IS SHOWN IN HEAVY DAHSED

LINES, UNLESS NOTED OTHERWISE.

B EQUIPMENT, DUCTWORK, PIPING, ETC. TO REMAIN IS SHOWN IN LIGHT LINES, UNLESS NOTED

OTHERWISE.

C CONTRACTOR SHALL CONFIRM LOCATION AND SIZE OF EXISITNG EQUIPMENT, DUCTWORK, PIPING ETC.

D COORDINATE WORK WITH ALL OTHER TRADES. UNCOORDINATED WORK WILL BE REPLACED AT THE

CONTRACTOR'S EXPENSE.

E COORDINATE ALL SYSTEM SHUTDOWNS WITH OWNER'S REPRESENTATIVE.

F COORDINATE WORK IN ALL OCCUPIED PROJECT AREAS WITH OWNER'S REPRESENTATIVE PRIOR TO

COMMENCEMENT OF WORK.

SCALE: 1/8" = 1'-0"A1 MECHANICAL DEMOLITION PLAN - FIRST LEVEL

PLAN NORTH

M

M

T

T H CO2

ROGER C.

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINE ER

REG. NO.

SOUTH DAKOTA

DATE:

ACCU-1

111B

STORAGE

109A

STORAGE

TELECOM

BN

CONFERENCE

ROOM

HHC OFFICE

SHOWERS

118A

MEN'S LOCKER

JANITOR

BN TRAINING

AIDS SUPPLY

133A

OFFICE

BN S-3

TRAINING TECH

HQ BN OFFICE

132A

A-O OFFICE

132B

BN ADMIN

OFFICE

WOMEN'S

LOCKER

125A

HVAC

109B-2

S-4 OFFICE-2

107B

HVAC

UNIT SUPPLY /

STORAGE

107A

SUPPLY

OFFICE

VAULT/ORDINANCE

MEDICAL

CDR

NCO ROOM

120A

RECRUITER

PT

120B

COMO

MEN'S

RESTROOM

WOMEN'S

RESTROOM

11A

SCULLERY

110A

BN S-4 SUPPLY

/ STORAGE

110B

CLASSROOM 2

KITCHEN

STAIR

BOILER ROOM

BN S-4 OFFICE

CLASSROOM 1

VESTIBULE

DRILL FLOOR

CORRIDOR

CORRIDOR

CORRIDOR

CC-1

(E ) 3

6" x1

2"

(E ) 2

6" x1

2"

(E ) 2

4" x1

2"

(E ) 1

8" x1

2"

(E ) 1

8" x1

2"

7'- 6"

RTU-1

VFD-SF

40"Ø

"Ø

"Ø

• SAWCUT AND REMOVE ASHPALT PAVING BELOW NEW RTU

• PROVIDE 6” GRANULAR BASE COURSE COMPACTED TO 93% PROCTOR

• PROVIDE 6” THICK CONCRETE EQUIPMENT PAD PER THE FOLLOWING

SPECIFICATIONS:

• COMPRESSIVE STRENGTH - 4500 PSI @ 28 DAYS

• AGGREGATE: ASTM C33, CLASS 3S OR BETTER, 3/4" MAX

COURSE AGGREGATE SIZE

• CEMENTITIOUS MATERIALS: PORTLAND CEMENT, ASTM C150,

TYPE I/II OR IL

• FLY ASH (25% MAX BY WEIGHT) - ASTM C618, CLASS F OR C

• WATER/CEMENT RATIO: 0.45 (MAX)

• AIR CONTENT 6" +/- 1.5%

• REINFORCE SLAB W/ ASTM A615 GRADE 60 #5 BARS AT 12” OC EACH WAY

AT BOTTOM

5'- 6"

4'- 0"

RS

RL

A3 M-501

42"x32" R/A36"x36" S/A

32'-0"

2'- 0"

S-1 1500 (8X)

36"x42"12

GENERAL NOTES:

1. ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH

FEDERAL BUILD AMERICA BUY AMERICA REQUIREMENTS.

2. THE DIMENSIONS OF THE FENCING AROUND RTU-1 HAS

BEEN COORDINATED WITH THE BASIS OF DESIGN

EQUIPMENT MANUFACTURER AND CONFIRMED TO BE

ACCEPTABLE FOR THE SERVICE CLEARANCE

REQUIREMENTS FOR THE SPECIFIED UNIT. ALTERNATE

MANUFACTURERS MUST SUBMIT WRITTEN

DOCUMENTATION THAT THE FENCING DIMENSIONS SHOWN

IS ADEQUATE FOR SERVICIBILITY OF THEIR EQUIPMENT.

(E) 60"x12" R/A

AFMS

2'-0" MIN.

08/15/2023

KEYNOTES

1 INSTALL NEW COOLING COIL IN EXISTING AHU. FIELD VERIFY COIL DIMENSIONS PRIOR TO ORDERING.

2 UNDER ALTERNATE NO. 1, PROVIDE NEW SUPPLY FAN MOTOR. MOTOR TO BE 5 HP, NEMA PREMIUM

EFFICIENCY, INVERTER DUTY WITH SHAFT GROUNDING RING.

3 REMOVE MANUFACTURER'S OUTDOOR AIR HOOD. CONNECT OUTDOOR AIR DUCT TO FULL SIZE OF

RTU CONNECTION. EXTEND 36"x36" O/A DUCT ABOVE UNIT AND TRANSITION TO 36"x42" WHERE DUCT

GOES HORIZONTAL.

4 INSTALL RTU ON 30" ROOF CURB PROVIDED BY RTU MANUFACTURER.

5 6' HIGH CHAIN LINK FENCE WITH 48" GATE. GATE TO INCLUDE LOCKABLE LATCH.

6 INSTALL NEW MOTORIZED DAMPER IN EXISTING RELIEF AIR DUCT. FIELD VERIFY SIZE OF EXISTING

DUCT. BMS CONTRACTOR TO PROVIDE SPACE ΔP SENSOR. MODULATE DAMPERS TO MAINTAIN

SPACE PRESSURE.

7 ROUTE R/A DUCT THRU EXISTING LOUVER OPENING IN EXTERIOR WALL. SEAL UNUSED PORTION OF OPENING WITH 3" RIGID INSULATION AND 16 GA. METAL PANEL INSIDE AND OUTSIDE. PAINT EXTERIOR SIDE OF METAL TO MATCH ORIGINAL LOUVER COLOR. SEAL PERIMETER WATER TIGHT.

8 SIZE REFRIGERANT PIPING PER CONDENSING UNIT MANUFACTURER'S REQUIREMENTS.

9 INSULATE OUTDOOR SUPPLY AND RETURN DUCTS WITH 2" RIGID INSULATION AND FLEXCLAD 400

WEATHERPROOF JACKET.

10 6" DIA. X 48" HIGH CONCRETE PIPE BOLLARDS. REFER TO DETAIL SHEET M-501.

11 PROVIDE MESH SCREEN OVER OPEN ENDED DUCT.

12 42"x40" WEATHERHOOD WITH MESH SCREEN AT INLET. BOTTOM OF INLET SHALL BE MINIMUM 10'-0"

ABOVE GRADE.

13 EXISTING SPACE TEMPERATURE SENSOR. AVERAGE THE TWO SENSORS IN DRILL FLOOR 100 FOR

CONTROL OF RTU-1.

14 NEW HUMIDITY SENSOR.

15 EXTEND EXISTING 4" HIGH CONCRETE PAD BELOW NEW UNIT.

16 INSTALL NEW 4" THICK CONCRETE SIDEWALK AROUND NEW UNIT.

17 EXISTING CONCRETE SIDEWALK.

18 NEW CO2 SENSOR.

19 PROVIDE VFD UNDER ALTERNATE NO. 1.

20 PROVIDE AIRFLOW MEASURING STATION MOUNTED IN OUTDOOR AIR DUCT. ACCUTROL MODEL

IAQ-TEK WITH QUANTITY OF PROBES AS RECOMMENDED BY MANUFACTURER. ALL WIRING BY BMS

CONTRACTOR.

21 UNDER ALTERNATE NO. 1, REMOVE ALL EXISTING DAMPER ACTUATORS ON MULTIZONE AIR

HANDLING UNIT AND REPLACE WITH NEW DDC ACTUATORS. FIELD VERIFY QUANTITY.

22 PROVIDE STEEL LINTEL AT NEW DUCT PENETRATION THRU EXTERIOR WALL. SEE DETAIL SHEET M-501.

23 SPIRAL LOCKSEAM DUCT.

24 ALL EXPOSED DUCTWORK SERVING DRILL FLOOR SHALL BE CONSTRUCTED WITH PAINT GRIP METAL.

PAINT DUCTS WITH WATER BASED DRY-FALL SYSTEM MPI INT. 5.1C-G1. PROTECT ALL EXISTING CONSTRUCTION AND SYSTEMS TO REMAIN IN PLACE INCLUDING STRUCTURE, LIGHTING, FLOORING, ETC. PROVIDE PRODUCT DATA SUBMITTAL FOR REVIEW. COLOR TO BE SHERWIN WILLIAMS DOVER

WHITE.

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :33

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL HVAC

PLAN - FIRST FLOOR

MH101

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

JHL08/15/2023

RCN04232057

SCALE: 1/8" = 1'-0"A1 MECHANICAL HVAC PLAN - FIRST LEVEL PLAN NORTH

NIKOLAS

RE

GIS

TE

REDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

UNIT SUPPLY /

STORAGE

111B

STORAGE

109A

STORAGE

TELECOM

BN

CONFERENCE

ROOM

HHC OFFICE

SHOWERS

118A

MEN'S LOCKER

JANITOR

BN TRAINING

AIDS SUPPLY

133A

OFFICE

BN S-3

TRAINING TECH

HQ BN OFFICE

132A

A-O OFFICE

132B

BN ADMIN

OFFICE

WOMEN'S

LOCKER

125A

HVAC

109B-2

S-4 OFFICE-2

107B

HVAC

107A

SUPPLY

OFFICE

VAULT/ORDINANCE

MEDICAL

CDR

NCO ROOM

120A

RECRUITER

PT

120B

COMO

MEN'S

RESTROOM

WOMEN'S

RESTROOM

11A

SCULLERY

110A

BN S-4 SUPPLY

/ STORAGE

110B

CLASSROOM 2

KITCHEN

STAIR

BOILER ROOM

BN S-4 OFFICE

CLASSROOM 1

VESTIBULE

DRILL FLOOR

CORRIDOR 122

CORRIDOR

CORRIDOR

ACCU-1

RTU-1

2" G

2" G

GENERAL NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL

BUILD AMERICA BUY AMERICA REQUIREMENTS.

3 4

(E) 2 1/2" LPS

5 08/15/2023

KEYNOTES

1 EXISTING GAS SERVICE AND METER. EXISTING CONNECTED LOAD = 3,700 CFH (ESTIMATED). NEW

CONNECTED LOAD = 4,500 CFH. COORDINATE REPLACEMENT OF GAS METER AND/OR SERVICE WITH

UTILITY CO. CONTACT INFO: KIRBY WICKS, NORTHWESTERN ENERGY 605-353-7609.

2 NEW GAS PIPING ON ROOF. COORDINATE ROUTING WITH EXISTING PV PANELS AND OTHER

EQUIPMENT ON ROOF. INSTALL PIPING ON ROOFTOP BLOX RTB-01 OR EQUAL POLYPROPYLENE

ADJUSTABLE PIPE SUPPORTS.

3 EXISTING AIR HANDLING UNIT.

4 EXISTING LOW PRESSURE STEAM BOILER.

5 UNDER ALTERNATE NO. 1, REMOVE EXISTING ACTUATOR ON STEAM CONTROL VALVE AND REPLACE

WITH NEW.

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :37

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL PIPING

PLAN - FIRST FLOOR

MP101

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

JHL08/15/2023

RCN04232057

SCALE: 1/8" = 1'-0"A1 MECHANICAL PIPING PLAN - FIRST LEVEL

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE:

40"Ø S/A

36"x36" S/A 42"x32" R/A

40"Ø S/A

'-1

0" A

PP

RO

X.

ALL SUPPLY GRILLES TO BE

MOUNTED PARALLEL TO

ROOF SLOPE.

S-1

S-1

ROUTE S/A DUCT

PARALLEL TO ROOF

SLOPE

8"

(2) L7X4X3/8 (LLV)

GROUT FILL ENDS OF CMU

JAMB (3000 PSI MIX)

EXIST CMU

SECTION A-A

A

A

(2) #5 BARS

1/4" PLATE CONT

(PL WIDTH = 1"

MINUS WIDTH)

3/16"

V.I.F.

WIDTH

GENERAL STRUCTURAL NOTES

MATERIALS GRADES AND STRENGTHS

1. REINFORCING STEEL

BARS - ASTM A615 (GRADE 60)

2. STRUCTURAL STEEL

PLATES AND OTHER SHAPES - ASTM A36 (Fy=36 KSI)

STEEL FRAMING

1. LATEST AISC STEEL CONSTRUCTION MANUAL, AISC 303 CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND

BRIDGES, AND AISC 360 SPECIFICATIONS APPLY.

2. WELDING ELECTRODES SHALL BE 70XX, UNO.

3. ALL WELDING SHALL BE BY WELDERS HOLDING VALID CERTIFICATES IN THE TYPE OF WELD REQUIRED.

4. TO AVOID UNDESIRABLE STRESSES IN PLATES OR THEIR ANCHORS, ALL WELDS SHALL BE MADE IN SINGLE PASSES IF APPLICABLE, SYMMETRICALLY AROUND THE PLATE. WHEN MULTIPLE PASSES ARE REQUIRED, SUFFICIENT TIME SHALL BE

ALLOWED BETWEEN PASSES FOR THE HEAT TO DISSIPATE.

5. ALL WELDING AND TESTING OF WELDS SHALL BE IN ACCORDANCE WITH AMERICAN WELDING SOCIETY CODES AND

RECOMMENDATIONS.

6. ALL FULL PENETRATION WELDS SHALL BE ULTRASONICALLY TESTED BY AN INDEPENDENT TESTING LABORATORY.

7. NOT ALL CONNECTIONS ARE DETAILED; SIMILAR DETAILS APPLY TO SIMILAR CONDITIONS UNLESS OTHERWISE INDICATED.

CONTACT THE ENGINEER OR ARCHITECT PROMPTLY TO VERIFY THE DETAILS OF MEMBERS OR CONNECTIONS IN ANY SITUATION WHERE REQUIREMENTS ARE UNCLEAR. CONTRACTOR SHALL PROVIDE THE NECESSARY BRACING DURING

ERECTION AND UNTIL ALL STEEL IS PLUMB AND SECURED.

8. FIELD CUTTING OR OTHER FIELD MODIFICATIONS TO STRUCTURAL STEEL SHALL NOT BE MADE WITHOUT SPECIFIC PRIOR

WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.

9. ALL BEAM COPES MUST BE MADE TO A RADIUS (3/4" MINIMUM).

10. STRUCTURAL STEEL FRAMING SHALL BE TRUE AND PLUMB BEFORE CONNECTIONS ARE FINAL BOLTED OR WELDED.

SLOPED CONCRETE STEEL

TROWEL FINISH

6"Ø STEEL PIPE FILLED

WITH CONCRETE

PIPE TO BE PAINTED

COLOR: TO BE SPECIFIED

SLOPE TO DRAIN

LIGHT BROOM FINISH

FINISHED GRADE SURFACE MAY

VARY - SEE LAYOUT PLANS

CENTERLINE

16"Ø SONOTUBE POURED

CONCRETE FOOTING

UNDISTURBED SUBGRADE

REMOVE AND CLEAN ALL

CONCRETE OR DEBRIS

FROM FACE OF STEEL PIPE

GENERAL NOTES:

3/4

8" 8"

1'-4"

6" M

IN

4'

- 6

" M

IN

08/15/2023

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :39

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL DETAILS

M-501

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

RCN08/15/2023

RCN04232057

SCALE: 1/4" = 1'-0"A3 RTU-1 DUCTWORK - SECTION VIEW

SCALE: 3/4" = 1'-0"A2 STEEL LINTEL @ NEW OPENING

SCALE: NOT TO SCALEC4 6" GUARD POST

NIKOLAS

RE

GIS

TER

EDPROFESSIONALENGINEER

REG. NO.

SOUTH DAKOTA

DATE: 08/15/2023

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

RA

W

IN

GS

S

CA

LE

(S

) U

NL

ES

S

RE

DU

CE

D

FR

OM

O

RI

GI

NA

L x

F

OR

MA

T

8/1 5/2

3 1

:34 :43

A M

S D

De pt of Mi lita ry

HV

AC

R ep lac e_

M2 3_ de tac he d.r vt

MECHANICAL

SCHEDULES

ME601

CO

NS

TR

UC

TI

ON

D

OC

UM

EN

TS

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

RCN08/15/2023

RCN04232057

GRILLES, REGISTERS AND DIFFUSERS SCHEDULE

TYPE SYSTEM MANUFACTURER MODEL NO. FACE SIZE NECK SIZE MOUNTING TYPE SPECIFICATION MAX NC (dB) MAX PD ("WG) INTEGRAL DAMPER FINISH COLOR MATERIAL REMARKS S-1 SUPPLY KRUEGER 880H 34"x20" 32"x18" SURFACE DOUBLE DEFLECTION REGISTER WITH FRONT BLADES PARALLEL TO LONG DIMENSION. 3/4" SPACING. 20 0.05 OBD WHITE ENAMEL STEEL

ROOFTOP UNIT SCHEDULE

EQUIPMENT REQUIREMENTS

UNIT NO. MFG MODEL NO.

MIN.

OUTDOOR

AIRFLOW

FILTER SUPPLY FAN CONDENSER FAN GAS FIRED HEAT EXCHANGER EVAPORATOR COOLING COIL COMPRESSOR

LENGTH WIDTH HEIGHT

UNIT

WEIGHT

EQUIPMENT

NOTESTYPE

DESIGN APD FOR

FAN SIZING AIRFLOW TSP ESP RPM BHP

MOTOR

POWER

MOTOR

RPM QTY

BURNER AIRSIDE NOM.

TONS

CAPACITY

MBH EAT DB EAT WB LAT DB LAT WB NO. REFRIG. AMBIENT EER IEERINPUT MBH OUTPUT MBH TURNDOWN RATIO FUEL TYPE EAT LAT

RTU-1 JOHNSON CONTROLS JH35T 1800 CFM 4" MERV-13 0.50 in-wg 12000 CFM 2.00 in-wg 1.00 in-wg 1140 11.80 hp 15.0 hp 1800 4 800 648 5.7 TO 1 NG 45.0 °F 95.0 °F 35 394 79.0 °F 65.0 °F 56.2 °F 54.1 °F 2 R-410A 95.0 °F 10.5 14.6 18'-2" 7'-6" 7'-4" 4781 lb ALL

ROOFTOP UNIT SCHEDULE - ELECTRICAL

UNIT NO.

EQUIPMENT REQUIREMENTS ELECTRICAL REQUIREMENTS

VOLT/PH MIN AIC MIN CKT AMP MOCP WIRE SIZE / CONDUIT

CONTROLLER

CONTROL BY

DISCONNECT

ELECTRICAL NOTESTYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

RTU-1 208/3 6,331 166.2 200 SEE CIRCUIT SCHEDULE INTEGRAL - IN UNIT - - DIV 23 DIV 23 E1 DIV 23 E2

REMARKS:

1. HORIZONTAL SUPPLY AND RETURN DUCT CONNECTIONS.

2. TWO INDEPENDENT REFRIGERATION CIRCUITS WITH VFD COMRPESSOR ON LEAD CIRCUIT.

3. FACTORY CONTROLS WITH BACNET INTERFACE TO BMS. WALL MOUNTED SPACE TEMP AND HUMIDITY SENSOR TO BE PROVIDED BY BMS CONTRACTOR.

4.. MODULATING GAS HEAT WITH STAINLESS STEEL HX.

5. SINGLE ZONE VAV CONTROLS.

6. 100% ECONOMIZER WITH BAROMETRIC RELIEF AIR DAMPER.

7. MODULATING HOT GAS REHEAT. PROVIDE UNIT WITH DEHUMIDIFICATION CYCLE CONTROLS.

8. DISCONNECT SWITCH.

9. PROVIDE HINGED ACCESS PANELS AND LOUVERED HAIL GUARDS.

10. 5-YEAR COMPRESSOR WARRANTY. 15 YEAR HEAT EXCHANGER WARRANTY.

11. PROVIDE 30" HIGH CURB.

AIR COOLED CONDENSING UNIT SCHEDULE

EQUIPMENT REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT NO. MANUFACTURER MODEL NO.

CONDENSER FAN

TOTAL CLG. CAP.

COMPRESSOR OUTDOOR

AIR TEMP.

SUCT. TEMP

(DEG F)

COOLING

EFFICIENCY (EER)

EQUIPMENT

NOTES VOLT/PH MIN AIC

MIN CKT

AMP MOCP WIRE SIZE / CONDUIT

CONTROLLER

CONTROL BY

DISCONNECT

ELECTRICAL NOTESQUANTITY QUANTITY TYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

ACCU-1 JOHNSON CONTROLS J25YC 4 267 Btu/h 2 95.0 °F 45.0 °F 11.6 ALL 208/3 8,120 99.9 150 SEE CIRCUIT SCHEDULE INTEGRAL - IN UNIT - - DIV 23 DIV 23 E1 DIV 23 E2

DX COOLING COIL SCHEDULE

UNIT NO. SERVES MANUFACTURER TOTAL CAPACITY MBH SENSIBLE CAPACITY MBH AIRFLOW EAT DB EAT WB LAT DB LAT WB AREA FIN LENGTH FIN HEIGHT FACE VELOCITY AIR PD NO. OF DISTR. ROWS FINS PER FEET REFRIGERANT TYPE SUCTION TEMP EQUIPMENT NOTES

CC-1 AHU- JOHNSON CONTROL 265.4 201.8 7335 CFM 79 °F 65 °F 54.1 °F 52.8 °F 13.5 SF 60.0" 32.5" 542 FPM 0.80 in-wg 2 6 10 R-410A 45 °F ALL

REMARKS:

1. REPLACEMENT COIL. DIMENSIONS LISTED ARE ESTIMATED. CONTRACTOR TO VERIFY EXISTING COIL DIMENSIONS PRIOR TO ORDERING.

REMARKS:

1. R-410A REFRIGERANT.

2. TWO COMPRESSORS. VARIABLE SPEED COMPRESSOR ON LEAD CIRCUIT.

3. PROVIDE WITH LIQUID LINE DRIERS, SUCTION AND LIQUID SERVICE VALVES.

4. PROVIDE WITH DISCONNECT SWITCH AND PHASE MONITORS.

5. FACTORY CONTROLS WITH BACNET GATEWAY.

6. PROVIDE 5-YEAR COMPRESSOR WARRANTY.

ELECTRICAL REMARKS:

E1. DISCONNECT SWITCH FURNISHED WITH UNIT.

E2. UNIT SHALL HAVE SHORT CIRCUIT CURRENT RATING (SCCR) EQUAL TO OR GREATER THAN THE VALVE OF "MIN AIC" IN THE SCHEDULE ABOVE.

ELECTRICAL REMARKS:

E1. DISCONNECT SWITCH FURNISHED WITH UNIT.

E2. UNIT SHALL HAVE SHORT CIRCUIT CURRENT RATING (SCCR) EQUAL TO OR GREATER THAN THE VALVE OF "MIN AIC" IN THE SCHEDULE ABOVE.

NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL BUILD AMERICA BUY AMERICA

REQUIREMENTS

14596

JAKE R.

BUCKMILLER

R

EG

IS

TE

RED PROFESSIONAL ENG

IN

EER

REG . NO.

S

O

U TH D A KO

T

A

DATE:

E - 5 0 1

A N N NA

SHEET SEQUENCE

NUMBER 01-99

SHEET TYPE

DESIGNATOR

DISCIPLINE

CHARACTER

MODIFIER

CHARACTER

SHEET TYPE DESIGNATORS

0 GENERAL (SYMBOLS LEGEND)

1 PLANS (HORIZONTAL VIEWS)

2 ELEVATIONS (VERTICAL VIEWS)

3 SECTIONS (SECTIONAL VIEWS)

4 LARGE SCALE VIEWS

5 DETAILS

6 SCHEDULES AND DIAGRAMS

7 USER DEFINED

8 USER DEFINED

9 3D REPRESENTATIONS

1 2 3 4 5 6

E2 E3 E4

C5

A4A1

A

B

C

D

E

TSP

A

B

C

D

E

1 2 3 4 5 6

MODIFIER CHARACTERS

S SITE

D DEMOLITION

L LIGHTING

P POWER

T TECHNOLOGY

SHEET IDENTIFICATIONELECTRICAL ABBREVIATIONS LIST

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC AIR CONDITIONER

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AIC AVAILABLE INTERRUPTING FAULT

CURRENT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CB-XX RECESSED CEILING BOX (SEE SCHEDULE)

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CM CORNER MOUNT

CMPR COMPRESSOR

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR

CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER

CIRCULATING PUMP

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DT DOUBLE THROW

DTS DUAL TECHNOLOGY SENSOR

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FB-XX FLOOR BOX (SEE SCHEDULE)

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FVNR FULL VOLTAGE NON-REVERSING

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI/GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

HB HIGH BAY

HOA HANDS-OFF-AUTOMATIC

SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSB MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

OS OCCUPANCY SENSOR

PA PUBLIC ADDRESS

PB PULL BOX

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

(CONDUIT)

PWR POWER

QUAN QUANTITY

REC RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VS VACANCY SENSOR

W WATT

W/ WITH

WB-XX RECESSED WALL BOX (SEE SCHEDULE)

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

Y WYE-CONNECTED

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

SPACE TAG

REVISION TAG

KEYNOTE TAG

SECTION TAG

DETAIL TAG

ELEVATION TAG

EXISTING WORK

NEW WORK

EXISTING ITEMS TO BE REMOVED

NAME

A1

A-301

A1

A-501

A-201A1

NORTH ARROW

SHEET XXXXX

SHEET XXXXX

A1

PLAN OR DETAIL

SCALE: 1'-0" = 1'-0"

GRID COLUMN/FND GRID INDICATOR

MATCH LINE INDICATOR

DETAIL/SECTION/PLAN

INDICATOR

CONVENTIONS LEGEND

PLAN NORTH

A2

E c

1,3,5

SF-1

2,4,6

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER.

THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.

THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE 1: LIGHTING FIXTURE TYPE "A2" IS CONNECTED TO CIRCUIT 12 AND

CONTROLLED BY SWITCH "b".

EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE CIRCUIT DESIGNATION IS

INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "E" WITH

SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 14.

DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH

DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX

RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH "c".

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".

SPECIAL /RECEPT CONNECTIONS. THE CIRCUIT DESIGNATION IS INDICATED BY A

NUMBER(S) ADJACENT TO THE SYMBOL. SEE KEYNOTE FOR CONFIGURATION.

EXAMPLE: 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5.

MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR

CHARACTERS ADJACENT TO THE MOTOR SYMBOL. THE CIRCUIT DESIGNATION IS

INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: MOTOR SF-1; 3

PHASE CONNECTION TO CIRCUITS 2, 4, 6.

TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER "T". SEE THE SINGLE LINE DIAGRAM OR

RISER FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS.

EXAMPLE: TRANSFORMER TYPE "T1".

PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE

OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

CONDUIT RUN CONCEALED IN CEILING OR WALL CONSTRUCTION.

HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS

SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT

DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES

(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE

CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN

TO PANELBOARD LN12; CIRCUITS 1, 3, 5.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT

TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

LN12

1,3,5

T1 d b

LIGHT FIXTURE ON EM / LIFE SAFETY BRANCH

LIGHT FIXTURE ON CRITICAL BRANCH

SYMBOL

LV

UE

EX

UHVE

OHE

OHT

c. DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT

72"

AS NOTED

CIRCUIT BREAKER PANEL

2 POLE SINGLE THROW SWITCH

SINGLE POLE SWITCH

LIGHT ON CORD REEL (TYPE DENOTED)

DIMMER SWITCH

MOMENTARY CONTACT SWITCH

OCCUPANCY SENSOR SWITCH

PUSH BUTTON

SINGLE RECEPT (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

FAN SPEED CONTROL

TIME DELAY SWITCH

DUPLEX SPLIT RECEPT

FOURPLEX RECEPT. (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

DUPLEX RECEPT (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

DUPLEX RECEPT ON EMERGENCY CIRCUIT

DUPLEX ISOLATED GROUND RECEPT

EQUIPMENT CONNECTION

RECEPT ON DROP CORD (DUPLEX SHOWN)

RECEPT ON CORD REEL (DUPLEX SHOWN)

FLOOR RECEPT. (DUPLEX SHOWN)

ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED.

AS NOTED

a. DISTANCE ABOVE TOP OF DOOR FRAME

TIMER SWITCH

AS NOTED

46"

46"

KEYED SWITCH

PILOT SWITCH

3-WAY SWITCH

4-WAY SWITCH

b. DISTANCE TO TOP OF EQUIPMENT OR DEVICE

HAND OR HAIR DRYER (SEE ARCH SPEC)

SOLENOID VALVE

AS NOTED46"

AS NOTED

AS NOTED

72"

72"

72"

72"

72"

72"

72"

72"

72"

SF-1

BUS DUCT WITH PLUG-IN DISCONNECT

(FUSED)

THERMOSTAT

PHOTOCELL/PHOTOSENSOR

ENCLOSED CIRCUIT BREAKER

RELAY

84"

COMB. MOTOR STARTER (NON-FUSED)

MAG. MOTOR STARTER

SAFETY DISC. SW. (FUSED)

SAFETY DISC. SW. (NON-FUSED)

COMB. MOTOR STARTER (FUSED)

POWER OR DISTRIBUTION PANEL

MOTOR

TRANSFORMER (TYPE DENOTED)

MOTOR HORSEPOWER RATED SWITCH

SPECIAL CABINET (TYPE DENOTED)

46"

18"

46"

18"

DESCRIPTION

FLOODLIGHT (TYPE DENOTED)

SURFACE MOUNTED LIGHT (TYPE DENOTED)

POLE MOUNTED LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

EXIT SIGN (TYPE DENOTED)

PENDANT OR HUNG LIGHT (TYPE DENOTED)

TRACK LIGHT/FLOOD LIGHT (TYPES DENOTED)

SURFACE LIGHT (TYPE DENOTED)

STRIP LIGHT (TYPE DENOTED)

EMERGENCY BATTERY LIGHT (TYPE DENOTED)

RECESSED LIGHT (TYPE DENOTED)

PER SCHED

AS NOTED

12"

96"

P2 P1

E

A1 L1

A1

AA

D1

AS NOTED

HT AFF SYMBOL

S1 S1

18"

HT AFF

AS NOTED

SYMBOL

JUNCTION BOX (WALL/FLOOR/CEILING)

PULL BOX

POWER POLE (OPEN OFFICE STYLE)

MULTIOUTLET ASSEMBLY

DESCRIPTION HT AFF

12"

d. DISTANCE BELOW CEILING

ANTENNA

CCTV CAMERA

NURSE CALL MASTER STATION

NURSE CALL DOME LIGHT

NURSE CALL EQUIPMENT CABINET

AS NOTED

EQUIPOTENTIAL GROUND OUTLET

SPEAKER

HORN TYPE SPEAKER

VOLUME CONTROL

BELL / CHIME / BUZZER

CABLE TRAY (TYPE DENOTED)

COMBINATION VOICE / DATA OUTLET,

(SLASH INDICATES MOUNTING 8" ABOVE

FINISHED COUNTER)

WALL TELEPHONE OUTLET

INTERCOM OUTLET LOCATION

TELEPHONE OUTLET (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

TELEVISION OUTLET

DOOR CONTACTS / DOOR SWITCH

CARD READER

ELECTRIC STRIKE

MOTION DETECTOR

NURSE CALL DUTY STATION

NURSE CALL STAFF STATION

NURSE CALL CODE BLUE STATION

NURSE CALL SINGLE PATIENT STATION

NURSE CALL DUAL PATIENT STATION

F.A. PULLSTATION

F.A. DOOR HOLDER

FIRE ALARM SHUT DOWN RELAY

SPRINKLER VALVE TAMPER SWITCH

SPRINKLER FLOW SWITCH

HEAT DETECTOR

HT AFF

CONDUIT TRANSITION DOWN

CONDUIT TRANSITION UP

BRANCH CIRCUIT HOME RUN

UNDERGROUND HIGH VOLTAGE ELECTRICAL

UNDERGROUND ELECTRICAL

LOW VOLTAGE POWER WIRING

EXISTING CONDUIT

OVERHEAD TELEPHONE

OVERHEAD ELECTRIC

CONDUIT EXPOSED

CONDUIT STUBBED OUT

CONDUIT CONCEALED BELOW FLOOR

CONDUIT CONCEALED IN WALL OR

OVERHEAD

DESCRIPTION

FIRE ALARM CHIME

SMOKE DETECTOR

FIRE ALARM STROBE

FIRE ALARM SPEAKER / STROBE

DUCT SMOKE DETECTOR

REMOTE TEST/STATUS STATION

FIRE ALARM CHIME / STROBE

DESCRIPTION

FIRE ALARM HORN

FIRE ALARM HORN / STROBE

SYMBOL

GENERATOR (KVA DENOTED)25 KVA

UNDERGROUND TELEPHONEUT

UCOM UNDERGROUND COMMUNICATIONS

UTV UNDERGROUND CABLE (CATV OR CCTV)

UFIBR UNDERGROUND FIBER OPTIC

ELECTRICAL SYMBOL LEGEND

AS NOTED

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"18"

18"

18"

18"

18"

18"

FOURPLEX RECEPT ON EMERGENCY CIRCUIT18"

VARIABLE FREQUENCY DRIVE

OCCUPANCY SENSOR

18"

18"

84"

84"

OUTLET IN FLOOR (MICROPHONE SHOWN)

MULTI-SERVICE OUTLET

46"

46"

46"

46"

46"

46"

46"

46"

AS NOTED

8"

90"

90"

90"

90"

90"

90"

90"

FIRE ALARM REMOTE ANNUNCIATOR

MAGNETIC LOCK

REQUEST TO EXIT

46"

CONDUIT SLEEVE (SIZE DENOTED)

C C

F F

F S

S F

FIRE ALARM SPEAKER

DATA OUTLET, (SLASH INDICATES MOUNTING

8" ABOVE FINISHED COUNTER)

18"

AS NOTED AP WIRELESS ACCESS POINT

C84" SINGLE FACE CLOCK WALL MOUNTED

84" DOUBLE FACE CLOCK WALL MOUNTED

C

F

S

F

FIRE ALARM CONTROL PANEL

72" LIFE SAFETY CIRCUIT BREAKER PANEL

72" CRITICAL CIRCUIT BREAKER PANEL

72" EQUIPMENT CIRCUIT BREAKER PANEL

GFI DUPLEX RECEPT. (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

18"

GFI FOURPLEX RECEPT. (SLASH INDICATES 8"

MOUNTING ABOVE FINISHED COUNTER)

18" a a b b b b b b b b b b b b b c b b b b b b b d c c c c c c

DATA OUTLET, FLOOR

AUDIO VISUAL OUTLET18"

D H

F

T1

EM

E

E

P

J J

PB

T1

R

P

C PC

W T

V

M

S S

S

FA ANNUN

D

ES

ML

R E

DC

C R

B

D

S

P

P

D D

NCM

NCC

L

J

T

V

K

P D

O S

M C

T

TD

F M

VFD

OS

H

IC

A

V G

S

FACP

FR

FS

TS

M D

AV

D1

72" b CONTACTOR

46"

DEAD FRONT GFI (SLASH INDICATES

MOUNTING 8" ABOVE FINISHED COUNTER)

D D18"

KEYPAD46"c K

LOW-VOLTAGE SWITCH46" L

LOW-VOLTAGE DIMMING SWITCH46"

LV

D

MANUAL MTR. STR. (W/OVERLOADS)46"

M M

S

J

AS NOTED SPECIAL RECEPTACLE

USB RECEPTACLEU

S

B

3-WAY DIMMER SWITCH46" 3D

SWITCHBOARD

46" POWER-OPERATED DOOR ACTUATOR

46" EMERGENCY POWER OFF PUSH BUTTONE

P

O

TELECOM. EQUIPMENT RACK

GROUNDING BUS BAR

C

S

MD

C D

Z12"a Z NURSE CALL ZONE LIGHT 18"

AS NOTED PROJECTOR

NURSE CALL WORKFLOW STATION46" W

NURSE CALL BATH CALL CORD STATION46" C

NURSE CALL COMBINATION STAFF/

CODE BLUE STATION

46" SB

NURSE CALL 37-PIN PATIENT BED JACK18" J

ADDITIONAL NURSE CALL PATIENT STATION SYMBOL SUPERSCRIPTS

S = PATIENT STATION WITH PILLOW SPEAKER

C = PATIENT STATION WITH CALL CORD

2S = DUAL PATIENT STATION WITH PILLOW SPEAKERS

2C = DUAL PATIENT STATION WITH CALL CORD

VS VACANCY SENSOR

VACANCY SENSOR SWITCH46" V

S

8/15/2023

SHEET INDEX - ELECTRICAL

SHEET # SHEET NAME

E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

ED101 ELECTRICAL DEMOLITION PLAN

EP101 POWER PLAN

E-601 ELECTRICAL RISER AND SCHEDULES

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

T E

D D

R A

W

IN

G S

S C

A

LE

(S

U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

8/

/2

:4 0:

A

M

L:

T S

P R ev it

Lo ca l\0

S

D D ep t o f M ili ta ry

H V

A C

R ep la ce

_E

_k lo ib er ka te am ts p.

co m

.rv t

ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND

GENERAL NOTES

E-001

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

KAK08/15/2023

JRB04232057

E

D

D

W P

WP

14596

JAKE R.

BUCKMILLER

R

EG

IS

TE

RED PROFESSIONAL ENG

IN

E

ER

REG . NO.

S

O

U TH D A K O

T

A

DATE:

PC

FAA PD PA

A

BMDP

PB

FACP

MDS PV PNL

8/15/2023

KEYNOTES

1 DISCONNECT AND REMOVE EXISTING EXTERIOR DISCONNECT SWITCH SERVING CONDENSING UNIT.

DISCONNECT AND REMOVE EXISTING CIRCUIT FROM DISCONNECT SWITCH TO UNIT. REMOVE

EXISTING CONDUCTORS BACK TO DISCONNECT SWITCH IN MAIN ELECTRICAL ROOM, MAINTAIN

EXISTING RACEWAY FOR NEW CONDUCTORS TO SERVE NEW UNIT AT THIS LOCATION AS SHOWN ON

SHEET EP101.

2 DISCONNECT AND REMOVE EXISTING POWER CONNECTION AND ASSOCIATED DISCONNECT AND

STARTER FOR MECHANICAL UNIT. REMOVE EXISTING CONDUIT AND WIRING BACK TO SOURCE.

REMOVE EXISTING DUCT SMOKE DETECTOR AND ASSOCIATED WIRING.

3 UNDER ALTERNATE #1, DISCONNECT EXISTING 208V, 3 PH POWER CONNECTION TO EXISTING AIR HANDLING UNIT. REMOVE EXISTING STARTER/DISCONNECT SWITCH IN ITS ENTIRETY. MAINTAIN POWER FOR RECONNECTION TO DIV 23 FURISHED VFD AND MOTOR. SEE SHEET EP101, KEYNOTE 11

FOR MORE INFORMATION.

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

A

TSP, Inc.

Architecture Engineering

Planning

PROJECT TITLE

1112 N. West Ave, Sioux Falls, SD 57104

(605) 336-1160 www.teamtsp.com

B B

C

C

D D

© TSP, Inc. 2022

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

T E

D D

R A

W

IN

G S

S C

A

LE

(S

U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

8/

/2

:4 0:

A

M

L:

T S

P R ev it

Lo ca l\0

S

D D ep t o f M ili ta ry

H V

A C

R ep la ce

_E

_k lo ib er ka te am ts p.

co m

.rv t

ELECTRICAL

DEMOLITION PLAN

ED101

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

HURON, SOUTH DAKOTA

HVAC REPLACEMENT

CFMO# 466789

SDARNG HURON

ARMORY

KAK08/15/2023

JRB04232057

SCALE: 1/8" = 1'-0"

A1

FIRST LEVEL ELECTRICAL DEMOLITION PLAN

D D

W P

WP

14596

JAKE R.

BUCKMILLER

R E

G

IS

TE

RED PROFESSIONAL ENG

IN

E ER

REG. NO.

S

O

U TH D A KO

T

A

DATE:

PD PA

PC

PB

MDP B

A

FAA

RTU-1

ACCU-1

4 8

FACP

MDS

EXIST

AHU

NOTE:

ALL PRODUCTS AND MATERIALS SHALL COMPLY WITH FEDERAL

BUILD AMERICA BUY AMERICA REQUIREMENTS

8/15/2023

KEYNOTES

1 PROVIDE "LB" CONNECTOR TO TRANSITION FROM WALL PENETRATION TO VERTICAL DESCENT AND

ROUTE CONDUIT SURFACE ON EXTERIOR WALL. TRANSITION TO FLEXIBLE WP CONDUIT FOR

CONNECTION TO NEW RTU DISCONNECT SWITCH. SEAL ALL WALL PENETRATIONS AS REQUIRED.

2 PROVIDE SURFACE MOUNTED CONDUIT TIGHT TO WALL NEAR THE CEILING. PAINT CONDUIT AND

BOXES TO MATCH WALL SURFACE.

3 PROVIDE NEW 200A/3P, 208V 3 PHASE ENCLOSED CIRCUIT BREAKER. SEE SHEET E-601, KEYNOTE 3

FOR MORE INFORMATION.

4 PROVIDE A FEEDER TAP ON THE EXISTING FEEDER TO SERVE NEW ENCLOSED CIRCUIT BREAKER OF

KEYNOTE 3 ABOVE. PROVIDE TAP WITHIN EXISTING J-BOX.

5 PROVIDE NEW SURFACE MOUNTED JUNCTION BOX IN PLACE WHERE DEMOLISHED DISCONNECT

SWITCH WAS LOCATED. PROVIDE NEW CONDUCTORS FROM DISCONNECT TO MAIN ELECTRICAL

ROOM TO J-BOX AND EXTEND EXISTING CONDUIT AS NEEDED. EXTEND CIRCUIT FROM J-BOX TO NEW

ACCU-1. SIZE J-BOX PER NEC.

6 PROVIDE SURFACE MOUNTED CONDUIT FROM NEW J-BOX AND MOUNT TO EXTERIOR WALL AS

REQUIRED. TRANSITION TO FLEXIBLE CONDUIT FOR EQUIPMENT CONNECTION.

7 ROUTE CONDUIT OUT OF ENCLOSED BREAKER UP TO HEIGHT ABOVE CORRIDOR LAY-IN CEILING IN ELECTRICAL ROOM AND PENETRATE WALL INTO CORRIDOR. ROUTE ABOVE CEILING AND PENETRATE

WALL INTO SPACE ADJACENT TO DRILL FLOOR AND CONNECT TO J-BOX OF KEYNOTE 13.

8 PROVIDE NEW 150A FUSES IN EXISTING 200A FUSED DISCONNECT SWITCH THAT SERVES NEW

ACCU-1.

9 EXISTING SIEMENS MXL-IQ FIRE ALARM CONTROL PANEL.

10 EXISTING POLE MOUNTED UTILITY TRANSFORMERS.

11 UNDER ALTERNATE #1, EXTEND EXISTING 208V, 3 PHASE POWER AS REQUIRED AND CONNECT TO NEW VFD AND MOTOR. NEW VFD AND MOTOR FURNISHED AND INSTALLED BY DIV 23, WIRED BY DIV

26. COORDINATE EXACT REQUIREMENTS WITH DIV 23 CONTRACTOR.

12 PROVIDE DUCT SMOKE DETECTION ON BOTH THE SUPPLY AND RETURN DUCT FOR RTU-1.

COORDINATE EXACT LOCATION OF DEVICES WITH DIV 23. CONNECT INTO EXISTING FIRE ALARM

SYSTEM. PROVIDE FAN RELAY TO SHUT UNIT DOWN UPON GENERAL ALARM AND RESTART AFTER

ALARM HAS BEEN CLEARED.

13 PROVIDE SURFACE MOUNTED PULL BOX FOR TRANSITION FOR CONDUIT FROM CORRIDOR TO OPEN

SPACE. SIZE BOX PER NEC.

14 PROVIDE PULL BOX FOR TRANSITION OF SURFACE CONDUIT TO CONDUIT CONCEAED ABOVE LAY-IN

CEILING. SIZE BOX PER NEC.

15 PROVIDE CONDUIT…