This is a pre-solicitation notice for a planned invitation for bid to renovate seven restrooms at the John D. Dingell VA Medical Center in Detroit, Michigan. The project scope includes furnishing all labor, materials, equipment and supervision to complete the renovations. The period of performance is 80 calendar days. The estimated cost is between $500,000 and $1 million. The NAICS code is 236220 for commercial and institutional building construction. The acquisition is a 100% set-aside for qualified SDVOSBs. The IFB is expected to be issued on May 5, 2021 via SAM.gov. Responses are due by the date specified in the solicitation. The government intends to award a firm fixed price contract within 120 days of bid opening. Prospective contractors must be registered in SAM.gov and VIP and have a current VETS-4212 report on file, if applicable. Questions should be directed to the contracting officer via email only.

View the file

Other files

File Type Posted
36C25021B0041.docx DOCX document
Wage Determination.pdf PDF
553-21-203 Renovate First Floor Restrooms SOW.pdf PDF
Specifications.pdf PDF
RFI Form Solicitation.doc DOC document
Contractor EMR Certification Form 2021.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JOHN D.

DINGELL

VAMC

JOHN R. STREET

E. H

ANCOCK STREET

W

OODW

ARD AVENUE

BRUSH STREET

E. C

ANFIEL

D STREET

WARREN AVENUE

INTER

STATE-

INTERSTATE-75

W

OODW

ARD AVENUE

INTER

STATE-7

GRAND RIVER AVENUE

LOCATION OF JOHN

D. DINGELL VAMC

LIST OF BID ALTERNATES

DEDUCT ALTERNATE #1: PROVIDE DEDUCT PRICING TO LEAVE EXISTING HOLLOW METAL FRAMES IN PLACE, TO BE RE-USED FOR NEW DOOR SLABS.

EXISTING FRAMES SHALL BE PREPARED FOR NEW HARDWARE, PRIMED AND PAINTED.

DEDUCT ALTERNATE #2: PROVIDE DEDUCT PRICING TO OMIT FLOOR DRAINS AND ASSOCIATED SANITARY PIPING SHOWN ON PL301, PLAN NOTE 2.

DEDUCT ALTERNATE #3: PROVIDE DEDUCT PRICING TO OMIT SPRINKLER PIPING AND HEAD REPLACEMENT, SHOWN ON AD301 AND AS301.

DEDUCT ALTERNATE #4: PROVIDE DEDUCT PRICING TO OMIT THE 3RD TOILET LOCATED IN THE SOUTH ALCOVE OF WOMEN'S TOILET B1232. THIS ALTERNATE SHALL ALSO CONTAIN ITEMS RELATED TO THE ADDITION OF THE THRID TOILET, INCLUDING:

1.) OMISSION OF SANITARY PIPING, TOILET PARTITIONS AND TOILET ACCESSORIES ASSOCIATED WITH THIS TOILET.

2.) OMISSION OF THE SOUTHERNMOST LAVATORY IN THIS RESTROOM.

3.) EXISTING WING WALL ADJACENT TO LAVATORIES SHALL REMAIN.

DEDUCT ALTERNATE #5: PROVIDE DEDUCT PRICING TO OMIT ACCENT WALL TILE GWT-1. ACCENT BAND SHALL BE CREATED USING PFT-1. SEE

SAMPLE ELEVATION ON AS1001.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural Design, Inc. and shall not be used for any purpose without prior expressed written consent.

The Owner shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

NORTH

REFERENCE

PROJECT # SIGNATURE DATE

Director

Associate Director

Chief, FMS

Chief, Engineering Section

Infectious Control Officer

Safety Specialist

Contracting Officer Representative

JOHN D. DINGELL VETERANS AFFAIRS MEDICAL CENTER

JOHN D. DINGELL

VA MEDICAL CENTER

4646 John R. Street Detroit, Michigan 48201

VA PROJECT NO.:

FINAL BID

DOCUMENTS

01 17OF

Z:

\V iri di an \P ro je ct s\

\0

D R

AW

IN

G S\

R

EV

IT

\L

O C

AL

F

IL

ES

\0

7_ D et ro it_

VA

_F irs t_ Fl oo r_

R es tro om s_ R

_C

EN

TR

AL

_d ro an

.rv t

/4

/2

2:

:0

PM

GI001

COVER SHEET RENOVATE FIRST FLOOR

RESTROOMS

553-21-203

12/15/2020 TWT DSR

RENOVATE FIRST FLOOR RESTROOMS

553-21-203

553-21-203

DETROIT, MICHIGAN

INDEX OF DRAWINGS

SHEET NO DRAWING TITLE DRAWING N0

GENERAL

GI001 COVER SHEET 01

GI002 ARCHITECTURAL - ABBREVATIONS AND SYMBOLS 02

GI003 INFECTION CONTROL AND PHASING PLAN 03

GI004 INFECTION CONTROL AND ENLARGED PHASING PLANS 04

GI005 INFECTION CONTROL DETAILS 05

DEMOLITION

AD101 DEMOLITION - KEY PLAN 06

AD301 DEMOLITION - ENLARGED PLANS 07

ARCHITECTURAL

AS101 ARCHITECTURAL - KEY PLAN 08

AS301 ARCHITECTURAL - ENLARGED PLANS 09

AS701 ARCHITECTURAL - DOOR AND SIGNAGE SCHEDULE AND DETAILS 10

AS1001 ARCHITECTURAL - CASEWORK, INTERIOR ELEVATIONS, AND MILLWORK 11

AS1101 ARCHITECTURAL - FIRST FLOOR FINISH PLANS 12

PLUMBING

PL301 ENLARGED PLUMBING PLANS 13

ELECTRICAL

ED101 ELECTRICAL - DEMOLITION PLAN 14

ED301 ELECTRICAL - ENLARGED DEMOLITION PLANS 15

ES101 ELECTRICAL - NEW ELECTRICAL PLANS 16

ES301 ELECTRICAL - ENLARGED PLANS 17

LOCATION MAP VICINITY MAP

Revisions: Date:

vhadetsteiskf Cross-Out

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAMA AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION

AB ANCHOR BOLT

ABC AGGREGATE BASE COURSE

AC ASBESTOS CEMENT OR ASPHALTIC CONCRETE

ACI AMERICAN CONCRETE INSTITUTE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT, ADJOINING, OR ADJUSTABLE

ADMIN ADMINISTRATION

ADB AUTOMATIC DOOR BOTTOM

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGA AMERICAN GAS ASSOCIATION

AGC ASSOCIATED GENERAL CONTRACTORS

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURISDICTION

AHR ANCHOR

AHU AIR HANDLING UNIT

AIA AMERICAN INSTITUTE OF ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINUM

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ANT ANTENNA

APA AMERICAN PLYWOOD ASSOCIATION

APPD APPROVED

APPROX APPROXIMATE

APT APARTMENT

AR AS REQUIRED

ARCH ARCHITECT

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION

ASKLR AUTOMATIC SPRINKLER

ASPH ASPHALT

ASSN ASSOCIATION

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

ATCH ATTACHMENT

ATM AUTOMATIC TELLER MACHINE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AVE AVENUE

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL WOODWORKING INSTITUTE

AWPA AMERICAN WOOD PRESERVERS' ASSOCIATION

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B LABEL CLASS B DOOR

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD BOARD

BD FT BOARD FEET (FOOT)

BEV BEVEL

BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION

BI FLD DR BIFOLDING DOORS

BITUM BITUMINOUS

BKG BACKING

BLD BUILD

BLDG BUILDING

BLKT BLANKET

BLVD BOULEVARD

BM BEAM OR BENCHMARK

BOT BOTTOM

BR BEDROOM

BRCG BRACING

BRDG BRIDGING

BRDG JST BRIDGING JOIST

BRG BEARING

BRG PL BEARING PLATE

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BTWN BETWEEN

BU BUSHEL

BUR BUILT-UP ROOFING

C CELSIUS CHANNEL

C CHANNEL CELSIUS

C CONC CAST CONCRETE

C LABEL CLASS C DOOR

C TO C CENTER TO CENTER

CAB CABINET

CAC CEILING ATTENUATION CLASS

CB CATCH BASIN OR CORNER BEAD

CBB CEMENTITIOUS (BACKER) BOARD

CC CUBIC CENTIMETER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CD CONSTRUCTION DOCUMENTS OR CONTRACT DOCUMENTS

CEM CEMENT

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CENTER OF GRAVITY OR CORNER GUARD

CGSFU CERAMIC GLAZED STRUCTURAL FACING UNITS

CH BD CHALKBOARD

CHEM CHEMICAL

CHFR CHAMFER

CHK CHECK

CI CAST IRON

CIP CAST-IN-PLACE

CIR CIRCLE

CIRC CIRCULAR

CJ CONSTRUCTION JOINT OR CONTROL JOINT

CL CENTER LINE

CLDG CLADDING

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

cm² SQUARE CENTIMETER cm³ CUBIC CENTIMETER

CM CONSTRUCTION MANAGEMENT

CMU CONCRETE MASONRY UNIT

CNR CORNER

CNTR COUNTER

CO CARBON MONOXIDE, CERTIFICATE OF OCCUPANCY,

CLEANOUT, OR COMPANY

CO₂ CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC CONCRETE

CONC FLR CONCRETE FLOOR

COND CONDENSER OR CONDITION

CONF CONFERENCE

CONN CONNECT

CONSTR CONSTRUCTION

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CPM CRITICAL PATH METHOD

CPRS COMPRESSIBLE

CPT CARPET

CRS COLD ROLLED STEEL

CRSI CONCRETE REINFORCING STEEL INSTITUTE

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSI CONSTRUCTION SPECIFICATIONS INSTITUTE

CSK COUNTER SUNK

CSMT CASEMENT

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTG COATING

CTR CENTER CONTOUR

CTRL CONTROL

CTV CABLE TELEVISION

CU COPPER C

CU FT CUBIC FEET

CU IN CUBIC INCH

CU YD CUBIC YARD

CURT CURTAIN

CYL CYLINDER

CYL L CYLINDER LOCK

D DEPTH OR PENNY (NAIL)

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL DOUBLE

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL DIAGRAM

DIAG DIAGRAM DIAGONAL

DIFF DIFFERENCE OR DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE OR DIVISION

DL DEAD LOAD

DOC DOCUMENT

DOUG FIR DOUGLAS FIR

DOZ DOZEN

DR DOOR, DRAIN, DRESSING ROOM,

OR DRIVE

DR CL DOOR CLOSER

DR FR DOOR FRAME

DR OPNG DOOR OPENING

DS DOWNSPOUT

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

DWTR DUMBWAITER

E EAST

E LABEL CLASS E DOOR

EA EACH

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

EIFS EXTERIOR INSULATION AND FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELAST ELASTOMERIC

ELEC ELECTRIC

ELEC DR OP ELECTRIC DOOR OPENER

ELEV ELEVATOR

EMER EMERGENCY

EMER SHR EMERGENCY SHOWER

ENCL ENCLOSURE

ENGR ENGINEER

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION AGENCY

EPDM ETHYLENE PROPYLENE DIENE MONOMER

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE BOARD (INSULATION)

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ERD EXISTING ROOF DRAIN

ESC ESCAPE OR ESCUTCHEON

ESCAL ESCALATOR

ESMT EASEMENT

ESP ESPECIALLY

EST ESTIMATE

ETC AND SO FORTH OR ET CETERA

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION OR EXPOSED

EXP BT EXPANSION BOLT

EXST GR EXISTING GRADE

EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER

EXT GR EXTERIOR GRADE

F FAHRENHEIT OR FEMALE

FA FIRE ALARM

FAB FABRIC

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FAS BD FASCIA BOARD

FCO FLOOR CLEANOUT

FCTY FACTORY

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FH FLAT HEAD OR FLAT HEAD SCREWS

FHC FIRE HOSE CABINET

FHMS FLAT HEAD MACHINE SCREW

FHP FULL HEIGHT PARTITION

FHWS FLAT HEAD WOOD SCREW

FIG FIGURE

FIL FILLET

FIN FINISH

FIN FINISH

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIN WD FINISH WOOD

FIXT FIXTURE

FL FLOORLINE

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR FLOOR

FLR FIN FLOOR FINISH

FLR FLOOR

FLR FIN FLOOR FINISH

FLR SK FLOOR SINK

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FM FACTORY MUTUAL

FM-G FACTORY MUTUAL GLOBAL

FO FINISHED OPENING

FOC FACE OF CONCRETE OR FACE OF CURB

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF SLAB OR FACE OF STUD

FOUNT FOUNTAIN

FOW FACE OF WALL

FP FIRE PROTECTION OR FIREPROOF

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FIRE RATING, FIRE RESISTANT, OR FRAME

FR SNK FLUSHING RIM SINK

FREQ FREQUENCY

FRMG FRAMING

FRP FIBER REINFORCED POLYESTER OR

FIBERGLASS REINFORCED PLASTIC

FRZ FREEZER

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET OR FOOT

FTG FOOTING

FURG FURRING

FURN FURNISH OR FURNITURE

FUT FUTURE

FV FIELD VERIFY

FWC FABRIC WALLCOVERING

GA GAGE OR GYPSUM ASSOCIATION

GAL GALLON

GALV GALVANIC OR GALVANIZED

GALV STL GALVANIZED STEEL

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GUARD

GDR GUARD RAIL

GEN GENERAL OR GENERATOR

GFRC GLASS-FIBER-REINFORCED CONCRETE

GFRG GLASS-FIBER-REINFORCED GYPSUM

GFRP GLASS-FIBER-REINFORCED PLASTIC

GI GALVANIZED IRON

GL GLASS

GL BLK GLASS BLOCK

GLU LAM GLUED LAMINATED WOOD

GR FL GROUND FLOOR

GRAN GRANITE

GRTG GRATING

GSB GYPSUM SHEATHING BOARD

GSM GALVANIZED SHEET METAL

GSU GLAZED STRUCTURAL UNIT

GT GROUT

GUAR GUARANTEE

GUT GUTTER

GYP GYPSUM

GYP BD GYPSUM BOARD

GYP PLAS GYPSUM PLASTER

H HIGH

H PLAM HIGH PRESSURE PLASTIC LAMINATE

HAZ MAT HAZARDOUS MATERIALS

HB HOSE BIBB

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD DOOR

HDBD HARDBOARD

HDNR HARDENER

HDO HIGH DENSITY OVERLAY

HDR HEADER

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)

HEX HEXAGON

HF HIGH FREQUENCY

HGR HANGER

HM HECTOMETER

HM HOLLOW METAL

HMD HOLLOW METAL DOOR

HMDF HOLLOW METAL DOOR AND FRAME

HMF HOLLOW METAL FRAME

HNDRL HANDRAIL

HO HOLD OPEN

HORIZ HORIZONTAL

HOSP HOSPITAL

HP HIGH PRESSURE OR HORSEPOWER

HQ HEADQUARTERS

HS HEAT-STRENGTHENED (GLASS) OR HIGH STRENGTH

HSE HOUSE

HSKPG HOUSEKEEPING

HST HOIST

HT HEIGHT

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HVY HEAVY

HW HOT WATER

HYD HYDRANT

HYDR HYDRAULIC

I INTERSTATE (HIGHWAY) OR MOMENT OF INERTIA

IAQ INDOOR AIR QUALITY

IBC INTERNATIONAL BUILDING CODE

ID IDENTIFICATION, INSIDE DIAMETER, OR INTERIOR DESIGN

ID NO IDENTIFICATION NUMBER

ILLUM ILLUMINATION

INCL INCLUDED

IND INDEPENDENT OR INDUSTRIAL

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

INTERCOM INTERCOMMUNICATION

INTL INTERNATIONAL

IRMA INVERTED ROOF MEMBRANE ASSEMBLY

IWH INSTANTANEOUS WATER HEATER

JAN JANITOR

J-BOX JUNCTION BOX

KD KILN DRIED OR KNOCKED DOWN

KIT KITCHEN

KO KNOCKOUT

KPL KICKPLATE

L ANGLE

LAB LABORATORY

LAD LADDER

LAM LAMINATE

LAM GL LAMINATED GLASS

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

LBS POUND

LD BRG LOAD-BEARING

LDR LEADER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LH LEFT HAND

LHR LEFT HAND REVERSE

LHR LEFT HAND REVERSE LATENT HEAT RATIO

LIB LIBRARY

LIN LINEAR

LINO LINOLEUM

LIQ LIQUID

LKR LOCKER

LKR RM LOCKER ROOM

LL LEAD LINED

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMST LIMESTONE

LNDSCP LANDSCAPE

LR LIVING ROOM

LRG LARGE

LRV LOUVERED ROOF VENT

LS LUMP SUM

LT LIGHT

LT GA LIGHT GAGE

LT WT LIGHTWEIGHT

LTG LIGHTING

LTNG LIGHTNING

LVD LOUVERED

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

LWIC LIGHTWEIGHT INSULATING CONCRETE

LYR LAYER

MACH MACHINE

MACH RM MACHINE ROOM

MAINT MAINTENANCE

MAN MANUAL

MATL MATERIAL

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MB MACHINE BOLT

MCB METAL CORNER BEAD

MD DECK

ME MECHANICAL ENGINEER

MEAS MEASURE

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MED MEDICAL MEDIUM

MED MEDIUM MEDICAL

MEK METHYL ETHYL KETONE

MEL MELAMINE

MEMB MEMBRANE

MEMO MEMORANDUM

MEZZ MEZZANINE

MF MILL FINISH

MFD MANUFACTURED

MFG MANUFACTURING

MFR MANUFACTURER

MFR REC MANUFACTURER'S RECOMMENDATION

MGT MANAGEMENT

MH MANHOLE

MIC MICROPHONE

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM MINUTE

MIN MINUTE MINIMUM

MIRR MIRROR

MISC MISCELLANEOUS

MIT MITER

MKR MARKER

ML METAL LATH

MLDG MOLDING (MOULDING)

MLWK MILLWORK

mm MILLIMETER

MO MASONRY OPENING OR MOTOR OPERATED

MOD MODEL, MODIFY OR MODULE

MOD BIT MODIFIED BITUMEN

MON MONITOR

MOPR MOP RACK

MR MOISTURE RESISTANT

MS MACHINE SCREW OR MOP SINK

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

N NORTH

NA NOT APPLICABLE

NAAMM NATIONAL ASSOCIATION OF ARCHITECTURAL METAL

MANUFACTURERS

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEC NATIONAL ELECTRICAL CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NRC NOISE REDUCTION COEFFICIENT

NRCA NATIONAL ROOFING CONTRACTORS ASSOCIATION

NRP NONREMOVABLE

NS NARROW STILE

NUM NUMERAL

O/O OUT TO OUT

O OXYGEN

OA OUTSIDE AIR OR OVERALL

OC ON CENTER

OCC OCCUPY

OCT OCTAGON

OD OUTSIDE DIAMETER OUTSIDE DIMENSION

OD OUTSIDE DIMENSION OUTSIDE DIAMETER

OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED

OFD OVERFLOW DRAIN

OFF OFFICE

OF/OI OWNER FURNISHED/OWNER INSTALLED

OH OVERHANG

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM OR OUTSIDE RADIUS

ORD ORDNANCE OR OVERFLOW ROOF DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINSTRATION

OUT OUTLET

OZ OUNCE

PAR PARALLEL OR PARAPET

PARA PARAGRAPH

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PC PIECE, POLYCARBONATE OR PORTLAND CEMENT

PCA PORTLAND CEMENT ASSOCIATION

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PED PEDESTAL

PEN PENETRATE

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PGBD PEGBOARD

PHAR PHARMACY

PHOTO PHOTOGRAPH

PHS PHILLIPS HEAD SCREW

PKG PACKAGE

PL PROPERTY LINE

PL GL PLATE GLASS

PLAM PLASTIC LAMINATE

PLAS PLASTER OR PLASTIC

PLBG PLUMBING

PLYWD PLYWOOD

PMTL PAINTED METAL

PNEU PNEUMATIC

PNL PANEL

PO POST OFFICE PURCHASE ORDER

PO PURCHASE ORDER POST OFFICE

POLY POLYETHYLENE (PLASTIC)

PR PAIR

PRCST PRECAST

PREFAB PREFABRICATE

PREFIN PREFINISH

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

PRMLD PREMOLDED

PROJ PROJECT

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT, PNEUMATIC TUBE, OR PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PVC POLYVINYL CHLORIDE (PLASTIC)

PVG PAVING

PWR POWER

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE

QTB QUARRY TILE BASE

QTF QUARRY TILE FLOOR

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RADIUS OR RISER

RA RETURN AIR

RAD RADIATOR

RB RESILIENT BASE OR RUBBER BASE

RB HK ROBE HOOK

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RC REMOTE CONTROL

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECD RECEIVED

RECPT RECEPTACLE

RECT RECTANGLE

REF REFERENCE OR REFRIGERATOR

REFR REFRACTORY REFRIGERATION

REFR REFRIGERATION REFRACTORY

REG REGISTER

REINF REINFORCE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

RET RETURN

REV REVISION

RF RADIO FREQUENCY

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RHMS ROUND HEAD MACHINE SCREW

RHR RIGHT HAND REVERSE

RHWS ROUND HEAD WOOD SCREW

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

SA SUPPLY AIR

SALV SALVAGE

SAMP SAMPLE

SAN SANITARY

SAT SUSPENDED ACOUSTICAL TILE

SATC SUSPENDED ACOUSTICAL TILE CEILING

SB SPLASH BLOCK

SBS STYRENE BUTADIEN STYRENE

SBSTR SUBSTRATE

SC SHADING COEFFICIENT OR SOLID CORE

SCH SCHOOL

SCHED SCHEDULE

SCHEM SCHEMATIC

SCP SCUPPER

SCRN SCREEN

SCT STRUCTURAL CLAY TILE

SCWD SOLID CORE WOOD DOOR

SD SHOP DRAWINGS, SMOKE DETECTOR, OR SOAP DISPENSER

SDG SIDING

SECT SECTION

SEG SEGMENT

SEL SELECT

SEP SEPARATE

SF SQUARE FOOT (FEET)

SFTWD SOFTWOOD

SGD SLIDING GLASS DOOR

SGL SINGLE

SHR SHOWER

SHR HD SHOWER HEAD

SHRD SHOWER DRAIN

SHT SHEET

SHT MTL FLASH SHEET METAL (FLASHING)

SHTHG SHEATHING

SHV SHELVING

SIM SIMILAR

SJ SCORED JOINT

SJI STEEL JOIST INSTITUTE

SK SKETCH

SKLT SKYLIGHT

SLD WDW HORIZONTAL SLIDING WINDOW

SLDG SLIDING

SLNT SEALANT

SM SHEET METAL

SMK SMOKE

SND SANITARY NAPKIN DISPENSER

SND INS SOUND INSULATION

SNDU SANITARY NAPKIN DISPOSAL UNIT

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SPLY SUPPLY

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SANITARY SEWER OR SERVICE SINK

SST STAINLESS STEEL

ST STAIRS OR STREET

STC SOUND TRANSMISSION CLASS

STD STANDARD

STIF STIFFENER

STL JST STEEL JOIST

STL LNTL STEEL LINTEL

STL PL STEEL PLATE

STL RF DK STEEL ROOF DECK

STL TB STEEL TUBE

STL TR STEEL TRUSS

STNLS STAINLESS

STOR STORAGE

STR STRINGERS

STRUCT STRUCTURAL

STRUCT STL STRUCTURAL STEEL

SUB SUBSTITUTE

SURF SURFACE

SUSP SUSPEND

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SW SWITCH

SWDR SWING DOOR

SYM SYMBOL

SYNTH SYNTHETIC

SYS SYSTEM

T TREAD

T&G TONGUE AND GROOVE

T&M TIME AND MATERIALS

TB THROUGH BOLT OR TOWEL BAR

TCA TILE COUNCIL OF AMERICA

TCP TELEPHONE CONTROL PANEL TEMPERATURE CONTROL PANEL;

TRAFFIC CONTROL PLAN

TD TOWEL DISPENSER

TECH TECHNICAL

TEL TELEPHONE

TEMP TEMPERATURE OR TEMPORARY

TER TERRAZZO

THD THREAD

THERM THERMAL

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

THRUOUT THROUGHOUT

TK BD TACKBOARD

TMPD TEMPERED

TMPD GL TEMPERED GLASS

TN TRUE NORTH

TO TOP OF ___

TO FDN TOP OF FOUNDATION

TOB TOP OF BEAM

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOS TOP OF STEEL

TOW TOP OF WALL

TPD TOILET PAPER DISPENSER

TPH TOILET PAPER HOLDER

TR TOWEL RACK

TRANS TRANSOM

TRANS WD FIN TRANSPARENT WOOD FINISH

TRTD TREATED

TS TENSILE STRENGTH OR TUBE STEEL

TSTAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

U HEAT TRANSFER COEFFICIENT

UC UNDERCUT

UCD UNDERCUT DOOR

UGND UNDERGROUND

UL UNDERWRITERS LABORATORIES

ULT ULTIMATE

UNFIN UNFINISH

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UR URINAL

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VAC VACUUM

VAR VARIES

VCT VINYL COMPOSITION TILE OR VITRIFIED CLAY TILE

VEH VEHICLE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VFAT VINYL FACED ACOUSTICAL TILE

VIC VICINITY

VID VIDEO

VNR VENEER

VOC VOLATILE ORGANIC COMPOUND

VOL VOLUME

VOLT VOLTAGE

VP VENEER PLASTER

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

VWF VINYL WALL FABRIC

W WIDE OR WEST

W/ WITH

W/O WITHOUT

WARR WARRANTY

WBL WOOD BLOCKING

WC WALL COVERING OR WATER CLOSET

WC WL HNG WATER CLOSET, WALL HUNG

WCHR WATER CHILLER

WCL WL MTD WATER COOLER, WALL HUNG

WD WOOD

WDW WINDOW

WF WIDE FLANGE

WFAB WALL FABRIC

WFR WOOD FRAME

WFS WOOD FURRING STRIPS

WH WATER HEATER

WHSE WAREHOUSE

WLD WELDED

WM WIRE MESH

WP WATERPROOFING

WPD WATER PRESSURE DROP

WPM WATERPROOF MEMBRANE

WR WEATHER RESISTANT

WS WEATHERSTRIP

WSCT WAINSCOT

WT WEIGHT

WWF WELDED WIRE FABRIC

X BRACE CROSS BRACE

XPS EXTRUDED POLYSTYRENE BOARD (INSULATION)

YD YARD

YR YEAR

ARCHITECTURAL ABBREVIATIONS GENERAL NOTES

1. THE CONTRACTOR SHALL REVIEW THE DRAWINGS AND UNDERSTAND THE SCOPE OF THE

DRAWINGS TO BE THE FOLLOWING: THE DOCUMENTS (DRAWINGS, SPECIFICATIONS,

ADDENDUM, ETC.) INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF

ARCHITECTURAL DESIGN CONCEPTS, THE DIMENSION OF THE BUILDING, THE MAJOR

ARCHITECTURAL ELEMENTS, THE MAJOR STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS.

THE DOCUMENTS DO NOT AND ARE NOT INTENDED TO INDICATE OR DESCRIBE ALL THE WORK

REQUIRED FOR FULL PERFORMANCE OF, AND COMPLETION OF THE REQUIREMENTS OF THE

CONTRACT. ON THE BASIS OF THE GENERAL SCOPE INDICATED IN THESE DOCUMENTS, THE

TRADE CONTRACTOR SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER EXECUTION AND

COMPLETION OF THE WORK.

2. GENERAL CONTRACTOR IS TO FOLLOW AND OBEY THE LATEST VERSION OF ALL FEDERAL, STATE

AND LOCAL CODES, LAWS, SAFETY REGULATIONS AND HAZARDOUS WASTE LAWS, ETC.

INCLUDING OSHA, NFPA 101 LIFE SAFETY CODE AND NEC.

3. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.

4. ALL DIMENSIONS ARE TO FACE OF CONCRETE, FACE OF MASONRY, FACE OF METAL STUDS, OR

COLUMN CENTERLINE, UNLESS NOTED OTHERWISE.

5. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN EACH BUILDING COMPONENT

LOCATION. BRING ANY DISCREPANCIES TO THE CONTRACTING OFFICER REPRESENTATIVE'S

(COR) ATTENTION IN WRITING IMMEDIATELY.

REFERENCE SYMBOLOGY

Room Name

A101

DETAIL IDENTIFICATION NUMBER

AREA OF DETAIL

NUMBER OF SHEET ON WHICH

SECITON IS DRAWN

SYMBOL WHERE SECTION IS TAKEN

1 VIEW NAME

SCALE: 1/8" = 1'-0"

SCALE AT WHICH SECTION

IS DRAWN

SECTION IDENTIFICATION

NUMBER

SUBTITLE FOR SECTION DRAWNG

SYMBOL WHERE DETAIL IS TAKEN

A101

SIM

SUBTITLE FOR DETAIL DRAWNG

A001

SHEET REFERENCE NUMBER

SHEET SEQUENCE NUMBER

DISCIPLINE CODE NORTH

NORTH ARROW

P5-3

PARTITION TYPE DOOR NUMBER

DOOR REFERENCE NUMBER

ROOM NAME & NUMBER

PARTITION TYPE

NUMBER

ROOM NUMBER

SHEET NOTE

NOTE REFERENCE NUMBER

SYMBOL WHERE ELEVATION IS TAKEN ELEVATION TAG

A101 Name

Elevation

ELEVATION IDENTIFICATION

ELEVATION HEIGHT

A101

1 Ref

R ef

1 Ref

R ef

NUMBER OF SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION IDENTIFICATION

NUMBER

1 VIEW NAME

SCALE: 1/8" = 1'-0"

SCALE AT WHICH DETAIL IS

DRAWN

DETAIL IDENTIFICATION NUMBER

NUMBER OF SHEET ON WHICH DETAIL IS DRAWN

WOOD (ROUGH)

PLYWOOD

STEEL OR METAL

ALUMINUM

FIRE SAFING INSULATION

BLANKET, BATT OR LOOSE FILL INSULATION

GRANULAR/GRAVEL FILL

BRICK

CMU

EARTH

CONCRETE

GROUT/GYPSUM BOARD

RIGID/FOAM INSULATION

MATERIAL LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural

Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

FINAL BID

DOCUMENTS

OF02 17

Z:

\V iri di an \P ro je ct s\

\0

D R

AW

IN

G S\

R

EV

IT

\L

O C

AL

F

IL

ES

\0

7_ D et ro it_

VA

_F irs t_ Fl oo r_

R es tro om s_ R

_C

EN

TR

AL

_d ro an

.rv t

/4

/2

2:

:2

PM

GI002

ARCHITECTURAL - ABBREVATIONS AND

SYMBOLS

RENOVATE FIRST FLOOR

RESTROOMS

DETROIT, MICHIGAN

553-21-203

12/15/2020 TWT DSR

Revisions: Date:

WOMEN'S

STAFF

TOILET

B1232

MEN'S

TOILET

B1301

WOMEN'S

TOILET

B1300

MEN'S

TOILET

C1589

WOMEN'S

TOILET

C1581

MEN'S

TOILET

C1824

WOMEN'S

TOILET

C1823

ELECTRICAL

B1230

ELECTRICAL

C1671

ELECTRICAL

C1772

GI004

PHASE IPHASE II

PHASE III

GI004

GI004

GI004

TO LOWER LEVEL

LOADING DOCK.

COORDINATE EXACT

PATH WITH COR.

PATH OF DEMOLITION / TRASH REMOVAL. TYP.

SEE GI004 FOR ADDITIONAL INFORMATION.

PHASE III

GENERAL CONSTRUCTION AND PHASING NOTES

APPLICABILITY OF GENERAL CONSTRUCTION NOTES:

1. EXISTING BUILDING UTILITIES: PRIOR TO THE COMMENCEMENT OF ANY / ALL WORK, VERIFY THE LOCATION AND ENSURE THE OBVIOUS MARKING OF ALL EXISTING UTILITIES AND RELATED EQUIPMENT ON, ABOVE OR BENEATH THE ADJACENT WORK AREA, WHETHER INDICATED TO REMAIN TO BE MODIFIED, OR TO BE REMOVED. COORDINATE

ALL VERIFICATION AND MARKING WORK WITH COR.

2. BUILDING DUST AND INFECTION CONTROL: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING ALL PHASES OF THE WORK. THEREFORE, PROVIDE, INSTALL AND MAINTAIN ALL CONSTRUCTION DUST, DEBRIS AND INFECTION CONTROL MEASURES OUTLINED. SEE INFECTION CONTROL PLAN AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION. COORDINATE SPECIFIC INFORMATION WITH THE COR.

3. BUILDING ACCESS AND SECURITY: THE BUILDING WILL REMIAN FULLY OCCUPIED DURING ALL PHASES OF THE WORK. THEREFORE, PROVIDE, INSTALL AND MAINTAIN ALL TEMPORARY MEASURES REQUIRED TO MAINTAIN ACCESS AND SECURITY OF THE EXISTING BUILDING AND THE WORK AREA FOR THE DURATION OF THE

CONSTRUCTION PROJECT. COORDINATE SPECIFIC INFORMATION WITH THE COR.

4. EXISTING WORK AREA AND BUILDING CONDITION: PROVIDE, INSTALL AND MAINTAIN PROTECTIVE MEASURES TO KEEP THE EXISTING BUILDING ADJACENT TO THE WORK AREA AND PATH OF DEMOLITION TRAVEL FROM CONSTRUCTION DAMAGE DURING WORK. RESTORE ANY PORTION OF THE EXISTING BUILDING OR ADJACENT SITE INADVERTENTLY DAMAGED BY, OR AS A RESULT OF THIS WORK AT NO ADDITIONAL COST TO THE VA. SEE

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

5. EXITS TO BE MAINTAINTED: MAINTAIN ONE (1) EXIT FROM ALL AREAS OF THE WORK AT ALL TIMES FOR THE

DURATION OF CONSTRUCTION.

6. GENERAL DEMOLITION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS FOR GENERAL DEMOLITION NOTES AND INFORMATION INCLUDING DISPOSAL AND / OR SALVAGE OF DEMOLISHED MATERIALS.

COORDINATE SPECIFIC INFORMATION WITH THE COR.

7. GENERAL CONSTRUCTION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS FOR GENERAL CONSTRUCTION NOTES AND INFORMATION INCLUDING STORAGE AND STAGING OF CONSTRUCTION

MATERIALS. COORDINATE SPECIFIC INFORMATION WITH THE COR.

8. EXISTING ELECTRICAL POWER SUPPLIES AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL TEMPORARY AND PERMANENT DISCONNECTING AND RECONNECTING OF EXISTING POWER SUPPLIES AND EQUIPMENT WITH COR. SEE DEMOLITION, ARCHITECTURAL

AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

9. PROJECT PHASING: ALL WORK FOR THIS PROJECT SHALL BE PHASED TO LIMIT DISRUPTIONS TO DAILY

OPERATIONS, CONTRACTOR SHALL COORDINATE FINAL SCHEDULE WITH COR.

ORDER OF CONSTRUCTION:

THE FOLLOWING ORDER OF PHASING SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. ALL WORK ASSOCIATED WITH ONE AREA SHALL BE COMPLETED AND FULLY FUNCTIONAL PRIOR TO MOVING TO THE NEXT

PHASE. APPROVAL WILL BE GIVEN BY THE COR.

AT THE COMPLETION OF EACH PHASE, NOTICE SHALL BE GIVEN TO THE CONTRACTOR BY THE COR TO PROCEED TO

THE NEXT PHASE.

PHASING SHALL BE COMPLETED IN THE ORDER LISTED BELOW AND COORDINATED WITH THE COR:

PHASE I: RESTROOMS C1823 AND C1824.

PHASE II: RESTROOMS C1581 AND C1589.

PHASE III: RESTROOMS B1232, B1300 AND B1301.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural

Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

FINAL BID

DOCUMENTS

OF03 17

Z:

\V iri di an \P ro je ct s\

\0

D R

AW

IN

G S\

R

EV

IT

\L

O C

AL

F

IL

ES

\0

7_ D et ro it_

VA

_F irs t_ Fl oo r_

R es tro om s_ R

_C

EN

TR

AL

_d ro an

.rv t

/4

/2

2:

:3

PM

GI003

INFECTION CONTROL AND PHASING

PLAN

RENOVATE FIRST FLOOR

RESTROOMS

DETROIT, MICHIGAN

553-21-203

12/15/2020 TWT DSR

SCALE: 3/64" = 1'-0"

GI003

INFECTION CONTROL AND PHASING PLAN

NORTH

COORDINATE WITH VAMC CONTRACTING OFFICER'S REPRESENTATIVE (COR) TO COMPLETE AN

INFECTION CONTROL RISK ASSESSMENT MATRIX AND OBTAIN AN INFECTION CONTROL CONSTRUCTION

PERMIT FOR EACH PHASE OF WORK OUTLINED IN THESE DOCUMENTS PRIOR TO THE START OF

DEMOLITION AND CONSTRUCTION. COMPLY WITH ALL INFECTION CONTROL REQUIREMENTS FOR THE DURATION OF THE CONSTRUCTION PROJECT. SEE ITEMS LISTED BELOW AND SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

1. REFER TO SPECIFICATIONS FOR MEDICAL CENTER "INFECTION CONTROL RISK

ASSESSMENT MATRIX OF PRECAUTIONS FOR CONSTRUCTION & RENOVATION" FOR INFECTION

CONTROL INFORMATION AND REQUIREMENTS.

2. USING THE "INFECTION CONTROL RISK ASSESSMENT MATRIX OF PRECAUTIONS FOR

CONSTRUCTION & RENOVATION" COORDINATE WITH COR TO DETERMINE THE FOLLOWING

PROJECT CONDITIONS:

· PATIENT RISK GROUPS (LOW, MEDIUM, HIGH, HIGHEST)

· TYPE OF CONSTRUCTION PROJECT ACTIVITY (A, B, C, OR D)

· CLASS OF PRECAUTION/ LEVEL OF INFECTION CONTROL ACTIVITIES REQUIRED (CLASS II

REQUIRED)

3. ONCE THE "CLASS OF PRECAUTION" HAS BEEN DETERMINED IN COORDINATION WITH THE COR, COMPLETE THE "INFECTION CONTROL CONSTRUCTION PERMIT." PROCEED WITH DEMOLITION

AND CONSTRUCTION WORK ONLY AFTER THE PERMIT HAS BEEN AUTHORIZED BY THE COR.

ONCE THE PERMIT IS AUTHORIZED, POST THE PERMIT AS DIRECTED BY THE COR.

4. USING THE "DESCRIPTION OF REQUIRED INFECTION CONTROL PRECAUTIONS BY CLASS" AS

OUTLINED BELOW, COORDINATE WITH THE COR TO DETERMINE THE SPECIFIC EXTENT AND

APPLICATION METHODS OF THE REQUIRED INFECTION CONTROL PRECAUTIONS. PRECAUTIONS

LISTED BELOW ARE TO BE CONFIRMED WITH THE COR:

1.1. DURING CONSTRUCTION PROJECT PHASE:

1.1.1. ISOLATE THE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

1.1.2. COMPLETE ALL CRITICAL BARRIERS TO SEAL WORK AREA FROM NON-WORK AREA BEFORE DEMOLITION OR

CONSTRUCTION BEGINS.

1.1.3. MAINTAIN NEGATIVE AIR PRESSURE OF -0.01" W.C. WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.

CONTRACTOR SHALL PROVIDE MAGNOMETER TO MEASURE AIR PRESSURE.

1.1.4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

1.1.5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED

USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT

ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

1.1.6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE EXCHANGED

EACH TIME WORKER EXITS THE WORK AREA.

INFECTION CONTROL PLAN GENERAL NOTES

INFECTION CONTROL PLAN GENERAL NOTES (CONT.) INFECTION CONTROL PLAN GENERAL NOTES (CONT.)

1.1.7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE SAFETY OFFICE AND

INFECTION CONTROL AND THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICE.

1.2. UPON COMPLETION OF PROJECT PHASE:

1.2.1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

1.2.2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS

1.2.3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

1.2.4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

1.2.5. WET MOP AREA WITH DISINFECTANT.

1.2.6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK HAS BEEN PERFORMED.

2. DURING THE CONSTRUCTION PROJECT PHASE, PROVIDE, INSTALL, & MAINTAIN THE SPECIFIC INFECTION CONTROL PRECAUTIONS

AS DETERMINED BY COORDINATION WITH COR.

NOTE:

CONTRACTOR SHALL MOP AS NECESSARY TO

PREVENT TRACKS LEAVING CONSTRUCTION AREA

AND PROVIDE NECESSARY SIGNAGE FOR WET AREAS.

NOTE:

CONTRACTOR SHALL PROTECT CEILING, FLOOR AND

WALLS FROM DAMAGE DURING CONSTRUCTION AND

IMPLEMENTATION OF INFECTION AND DUST CONTROL

BARRIERS. TOUCH UP PAINT ON CEILINGS AND

WALLS AS NEEDED AS A RESULT OF CONSTRUCTION

TO SHOW NO EVIDENCE OF CONSTRUCTION.

NOTE:APPLICABLE PROJECT ACRONYMS & ABBREVIATIONS:

1. ICRA = INFECTION CONTROL RISK ASSESSMENT

2. ILSM = INTERIM LIFE SAFETY MEASURES

NOTE:

AFTER COMPLETION OF WORK, CONTRACTOR SHALL

CLEAN THOROUGHLY AND REQUIRE INSPECTION BY

COR.

MEN'S

TOILET

C1824

WOMEN'S

TOILET

C1823

3 3

MEN'S

TOILET

C1589

WOMEN'S

TOILET

C1581

3 3

WOMEN'S

TOILET

B1300

MEN'S

TOILET

B1301

WOMEN'S

STAFF

TOILET

B1232

GENERAL CONSTRUCTION AND PHASING NOTES

APPLICABILITY OF GENERAL CONSTRUCTION NOTES:

1. EXISTING BUILDING UTILITIES: PRIOR TO THE COMMENCEMENT OF ANY / ALL WORK, VERIFY THE LOCATION AND ENSURE THE OBVIOUS MARKING OF ALL EXISTING UTILITIES AND RELATED EQUIPMENT ON, ABOVE OR BENEATH THE ADJACENT WORK AREA, WHETHER INDICATED TO REMAIN TO BE MODIFIED, OR TO BE REMOVED. COORDINATE

ALL VERIFICATION AND MARKING WORK WITH COR.

2. BUILDING DUST AND INFECTION CONTROL: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING ALL PHASES OF THE WORK. THEREFORE, PROVIDE, INSTALL AND MAINTAIN ALL CONSTRUCTION DUST, DEBRIS AND INFECTION CONTROL MEASURES OUTLINED. SEE INFECTION CONTROL PLAN AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION. COORDINATE SPECIFIC INFORMATION WITH THE COR.

3. BUILDING ACCESS AND SECURITY: THE BUILDING WILL REMIAN FULLY OCCUPIED DURING ALL PHASES OF THE WORK. THEREFORE, PROVIDE, INSTALL AND MAINTAIN ALL TEMPORARY MEASURES REQUIRED TO MAINTAIN ACCESS AND SECURITY OF THE EXISTING BUILDING AND THE WORK AREA FOR THE DURATION OF THE

CONSTRUCTION PROJECT. COORDINATE SPECIFIC INFORMATION WITH THE COR.

4. EXISTING WORK AREA AND BUILDING CONDITION: PROVIDE, INSTALL AND MAINTAIN PROTECTIVE MEASURES TO KEEP THE EXISTING BUILDING ADJACENT TO THE WORK AREA AND PATH OF DEMOLITION TRAVEL FROM CONSTRUCTION DAMAGE DURING WORK. RESTORE ANY PORTION OF THE EXISTING BUILDING OR ADJACENT SITE INADVERTENTLY DAMAGED BY, OR AS A RESULT OF THIS WORK AT NO ADDITIONAL COST TO THE VA. SEE

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

5. EXITS TO BE MAINTAINTED: MAINTAIN ONE (1) EXIT FROM ALL AREAS OF THE WORK AT ALL TIMES FOR THE

DURATION OF CONSTRUCTION.

6. GENERAL DEMOLITION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS FOR GENERAL DEMOLITION NOTES AND INFORMATION INCLUDING DISPOSAL AND / OR SALVAGE OF DEMOLISHED MATERIALS.

COORDINATE SPECIFIC INFORMATION WITH THE COR.

7. GENERAL CONSTRUCTION NOTES AND INFORMATION: SEE DISCIPLINE DRAWINGS AND SPECIFICATIONS FOR GENERAL CONSTRUCTION NOTES AND INFORMATION INCLUDING STORAGE AND STAGING OF CONSTRUCTION

MATERIALS. COORDINATE SPECIFIC INFORMATION WITH THE COR.

8. EXISTING ELECTRICAL POWER SUPPLIES AND EQUIPMENT: THE BUILDING WILL REMAIN FULLY OCCUPIED DURING CONSTRUCTION. THEREFORE, COORDINATE ALL TEMPORARY AND PERMANENT DISCONNECTING AND RECONNECTING OF EXISTING POWER SUPPLIES AND EQUIPMENT WITH COR. SEE DEMOLITION, ARCHITECTURAL

AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

9. PROJECT PHASING: ALL WORK FOR THIS PROJECT SHALL BE PHASED TO LIMIT DISRUPTIONS TO DAILY

OPERATIONS, CONTRACTOR SHALL COORDINATE FINAL SCHEDULE WITH COR.

ORDER OF CONSTRUCTION:

THE FOLLOWING ORDER OF PHASING SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. ALL WORK ASSOCIATED WITH ONE AREA SHALL BE COMPLETED AND FULLY FUNCTIONAL PRIOR TO MOVING TO THE NEXT

PHASE. APPROVAL WILL BE GIVEN BY THE COR.

AT THE COMPLETION OF EACH PHASE, NOTICE SHALL BE GIVEN TO THE CONTRACTOR BY THE COR TO PROCEED TO

THE NEXT PHASE.

PHASING SHALL BE COMPLETED IN THE ORDER LISTED BELOW AND COORDINATED WITH THE COR:

PHASE I: RESTROOMS C1823 AND C1824.

PHASE II: RESTROOMS C1581 AND C1589.

PHASE III: RESTROOMS B1232, B1300 AND B1301.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural

Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

FINAL BID

DOCUMENTS

OF04 17

Z:

\V iri di an \P ro je ct s\

\0

D R

AW

IN

G S\

R

EV

IT

\L

O C

AL

F

IL

ES

\0

7_ D et ro it_

VA

_F irs t_ Fl oo r_

R es tro om s_ R

_C

EN

TR

AL

_d ro an

.rv t

/4

/2

2:

:5

PM

GI004

INFECTION CONTROL AND ENLARGED

PHASING PLANS

RENOVATE FIRST FLOOR

RESTROOMS

DETROIT, MICHIGAN

553-21-203

12/15/2020 TWT DSR

SCALE: 3/16" = 1'-0"

GI004

INFECTION CONTROL & PHASING PLAN - PHASE I

SCALE: 3/16" = 1'-0"

GI004

INFECTION CONTROL & PHASING PLAN - PHASE II

SCALE: 3/16" = 1'-0"

GI004

INFECTION CONTROL & PHASING PLAN - PHASE III

SCALE: 3/16" = 1'-0"

GI004

INFECTION CONTROL & PHASING PLAN - PHASE III

INFECTION CONTROL PLAN NOTES

1 PROVIDE AND INSTALL INFECTION / DUST CONTROL "ZIP WALL" PARTITION WITH 2-PLY

FIRE-RETARDANT PLASTIC AND ZIPPERED EGRESS DOOR. EGRESS DOOR SHALL BE

SECURED, SEALED AND PROTECTED FOR DURATION OF CONSTRUCTION.

COORDINATE INFECTION CONTROL RISK ASSESSMENT (ICRA) AND SPECIFIC

REQUIREMENTS WITH COR. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2 PROVIDE AND INSTALL "STICKY" MAT FLOOR PADS IMMEDIATELY OUTSIDE ALL

INFECTION / DUST CONTROL PARTITIONS TO ENSURE FLOOR CLEANLINESS IS

MAINTAINED THROUGHOUT THE DURATION OF CONSTRUCTION.

3 PATH OF DEMOLITION / TRASH REMOVAL TRAVEL FROM RENOVATED AREA. ALL

CONSTRUCTION DEBRIS REMOVED AS PART OF DEMOLITION SHALL BE REMOVED IN

ENCLOSED / SEALED CONTAINERS AND FOLLOW THE INFECTION CONTROL RISK

ASSESSMENT (ICRA) REQUIREMENTS AS COORDINATED WITH THE COR. SEE GI003

FOR FULL PATH.

COORDINATE WITH VAMC CONTRACTING OFFICER'S REPRESENTATIVE (COR) TO COMPLETE AN

INFECTION CONTROL RISK ASSESSMENT MATRIX AND OBTAIN AN INFECTION CONTROL CONSTRUCTION

PERMIT FOR EACH PHASE OF WORK OUTLINED IN THESE DOCUMENTS PRIOR TO THE START OF

DEMOLITION AND CONSTRUCTION. COMPLY WITH ALL INFECTION CONTROL REQUIREMENTS FOR THE DURATION OF THE CONSTRUCTION PROJECT. SEE ITEMS LISTED BELOW AND SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

1. REFER TO SPECIFICATIONS FOR MEDICAL CENTER "INFECTION CONTROL RISK

ASSESSMENT MATRIX OF PRECAUTIONS FOR CONSTRUCTION & RENOVATION" FOR INFECTION

CONTROL INFORMATION AND REQUIREMENTS.

2. USING THE "INFECTION CONTROL RISK ASSESSMENT MATRIX OF PRECAUTIONS FOR

CONSTRUCTION & RENOVATION" COORDINATE WITH COR TO DETERMINE THE FOLLOWING

PROJECT CONDITIONS:

· PATIENT RISK GROUPS (LOW, MEDIUM, HIGH, HIGHEST)

· TYPE OF CONSTRUCTION PROJECT ACTIVITY (A, B, C, OR D)

· CLASS OF PRECAUTION/ LEVEL OF INFECTION CONTROL ACTIVITIES REQUIRED (CLASS II

REQUIRED)

3. ONCE THE "CLASS OF PRECAUTION" HAS BEEN DETERMINED IN COORDINATION WITH THE COR, COMPLETE THE "INFECTION CONTROL CONSTRUCTION PERMIT." PROCEED WITH DEMOLITION

AND CONSTRUCTION WORK ONLY AFTER THE PERMIT HAS BEEN AUTHORIZED BY THE COR.

ONCE THE PERMIT IS AUTHORIZED, POST THE PERMIT AS DIRECTED BY THE COR.

4. USING THE "DESCRIPTION OF REQUIRED INFECTION CONTROL PRECAUTIONS BY CLASS" AS

OUTLINED BELOW, COORDINATE WITH THE COR TO DETERMINE THE SPECIFIC EXTENT AND

APPLICATION METHODS OF THE REQUIRED INFECTION CONTROL PRECAUTIONS. PRECAUTIONS

LISTED BELOW ARE TO BE CONFIRMED WITH THE COR:

1.1. DURING CONSTRUCTION PROJECT PHASE:

1.1.1. ISOLATE THE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

1.1.2. COMPLETE ALL CRITICAL BARRIERS TO SEAL WORK AREA FROM NON-WORK AREA

BEFORE DEMOLITION OR CONSTRUCTION BEGINS.

1.1.3. MAINTAIN NEGATIVE AIR PRESSURE OF -0.01" W.C. WITHIN WORK SITE UTILIZING HEPA

EQUIPPED AIR FILTRATION UNITS. CONTRACTOR SHALL PROVIDE MAGNOMETER TO

MEASURE AIR PRESSURE.

1.1.4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

1.1.5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM

SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK

SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME

THEY LEAVE THE WORK SITE.

1.1.6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE

COVERS MUST BE EXCHANGED EACH TIME WORKER EXITS THE WORK AREA.

1.1.7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS

INSPECTED BY THE SAFETY OFFICE AND INFECTION CONTROL AND THOROUGHLY

CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICE.

1.2. UPON COMPLETION OF PROJECT PHASE:

1.2.1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH CONSTRUCTION.

1.2.2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED

CONTAINERS

1.2.3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

1.2.4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

1.2.5. WET MOP AREA WITH DISINFECTANT.

1.2.6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK HAS BEEN PERFORMED.

2. DURING THE CONSTRUCTION PROJECT PHASE, PROVIDE, INSTALL, & MAINTAIN THE SPECIFIC

INFECTION CONTROL PRECAUTIONS AS DETERMINED BY COORDINATION WITH COR.

INFECTION CONTROL PLAN GENERAL NOTES

NOTE:

CONTRACTOR SHALL MOP AS NECESSARY TO

PREVENT TRACKS LEAVING CONSTRUCTION AREA

AND PROVIDE NECESSARY SIGNAGE FOR WET AREAS.

NOTE:

CONTRACTOR SHALL PROTECT CEILING, FLOOR AND

WALLS FROM DAMAGE DURING CONSTRUCTION AND

IMPLEMENTATION OF INFECTION AND DUST CONTROL

BARRIERS. TOUCH UP PAINT ON CEILINGS AND

WALLS AS NEEDED AS A RESULT OF CONSTRUCTION

TO SHOW NO EVIDENCE OF CONSTRUCTION.

NOTE:APPLICABLE PROJECT ACRONYMS & ABBREVIATIONS:

1. ICRA = INFECTION CONTROL RISK ASSESSMENT

2. ILSM = INTERIM LIFE SAFETY MEASURES

NOTE:

AFTER COMPLETION OF WORK, CONTRACTOR SHALL

CLEAN THOROUGHLY AND REQUIRE INSPECTION BY

COR.

TEMP. ANTE ROOM

A

O

V

MONTHLY CHANGED HEPA

FILTER

FL

EX

D

UC

T

E

OUTSIDE OF BUILDING

PROVIDE STICKY

MATS (CHANGED

END OF SHIFT OR

MORE IF NECESSARY

TO MAINTAIN

CLEANLINESS)

POST ICRA, ILSM,

FIRE INSPECTION

SHEETS VISIBLE TO

PUBLIC

INDICATOR MUST BE AT -0.01 OR MORE

NEGATIVE DAILY, IF NOT VERIFY ALL OPENING

SUCH AS DOORS ARE CLOSED AND/OR

CHANGE OUT NEGATIVE AIR PRE-FILTER.

ABC TYPE FIRE EXTINGUISHER ON

PORTABLE FLOOR BRACKET (ISLM MAY

REQ. MORE THAN ONE OR WALL MOUNTED)

NEED INSPECTION TAG AND MONTHLY

INSPECTION; INITIALS AND DATED.

TAPE ALL SERVICES

TO PROTECT

AGAINST

CONTAMINATION

OPTIONAL EXHAUST DUCTS

(COVER THE GRATES AND THE

DIFFUSERS).

COVER ALL RETURNS AT

THE GRATE / DIFFUSERS

WITH FIRE RATED PLASTIC

SHEETING AND SECURE

WITH DUCT TAPE.

SUPPLY DUCTS EITHER KEEP

RUNNING OR COVER WITH

FIRE RATED PLASTIC

SHEETING AND SECURE

WITH DUCT TAPE TO KEEP

DUST OUT.

HEPA NEGATIVE AIR UNIT

WEEKLY CHANGED (OR

MORE AS NEEDED PRE-

FILTER)

EXHAUST DUCT

AA

WORK AREA

2-PLY FIRE-RETARDANT

PLASTIC AND ZIPPERED

EGRESS DOOR.

2-PLY FIRE-RETARDANT

PLASTIC "ZIP" WALL

ASSEMBLY.

EXISTING CONCRETE SLAB FLOORING

FIRE / U.L. RATED PLASTIC

TO PREVENT DUST (INSTALL

PRIOR TO CONSTRUCTION).

FIRE / U.L. RATED PLASTIC

TO PREVENT DUST (INSTALL

PRIOR TO CONSTRUCTION).

EXISTING WALL

FINISHED FLOORING TO BE KEPT

CLEAN. FLOORS NOT BEING

REPLACED SHALL BE PROTECTED

OR COVERED WITH ROSEN PAPER /

FIRE TREATED PLYWOOD.

HEPA NEGATIVE AIR UNIT.

EXISTING WALL

EXISTING FIRE

SPRINKLER SYSTEM

EXHAUST DUCT

AREA UNDER

CONSTRUCTION

RESTRICTED AREA

THIS IS A

ICRA, ILSM

FIRE WATCH

MISC. FORMS

PAPER

CADDY

COMING SOON!!!

PERSONNEL ENTERING MUST HAVE: HARD HAT,

SAFETY GLASSES AND PROPER I.D.

-DESCRIPTION OF NEWLY PROPOSED OCCUPANCY-

XXXXX

XXXXX

XXXXX

XXXXX

POST ICRA, ILSM,

FIRE INSPECTION

SHEETS VISIBLE

TO PUBLIC

SUSPENDED

PLASTIC ZIPPER

WALL CURTAIN

BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

All Concepts, ideas, design elements, plans, and details as shown on this document are the sole property of Viridian Architectural

Design, Inc. and shall not be used for any purpose without prior expressed written consent. The Owner shall be permitted to retain copies for information and reference.

2020 E. Washington Boulevard Suite 200 Fort Wayne, Indiana 46803

PH: 260.424.4830

www.viridian-design.net

FINAL BID

DOCUMENTS

OF05 17

Z:

\V iri di an \P ro je ct s\

\0

D R

AW

IN

G S\

R

EV

IT

\L

O C

AL

F

IL

ES

\0

7_ D et ro it_

VA

_F irs t_ Fl oo r_

R es tro om s_ R

_C

EN

TR

AL

_d ro an

.rv t

/4

/2

2:

:0

PM

GI005

INFECTION CONTROL DETAILS RENOVATE FIRST FLOOR

RESTROOMS

DETROIT, MICHIGAN

553-21-203

12/15/2020 TWT DSR

LOW RISK MEDIUM RISK HIGH RISK HIGHEST RISK

• OFFICE AREAS • CARDIOLOGY

• ECHOCARDIOGRAPHY

• ENDOSCROPY

• NUCLEAR MEDICINE

• PHYSICAL THERAPY

• RADIOLOGY / MRI

• RESPIRATORY THERAPY

• CCU

• EMERGENCY ROOM

• LABOR AND DELIVERY

• LABORATORY (SPECIMEN)

• NEWBORN NURSEY

• OUTPATIENT SURGERY

• PEDIATRICS

• PHARMACY

• POST ANESTHESIA CARE UNIT

• SURGICAL UNITS

• ANY AREA CARING FOR

IMMUNOCOMPROMISED PATIENTS

• BURN UNIT

• CARDIAC CATH LAB

• CENTRAL STERILE SUPPLY

• INTENSIVE CARE UNITS

• MEDICAL UNIT

• NEGATIVE PRESSURE ISOLATION ROOMS

• ONCOLOGY

• OPERATING ROOMS INCLUDING

C-SECTION ROOMS

PATIENT RISK GROUPS

TYPE A

INCLUDES, BUT IS NOT LIMITED TO:

• REMOVABLE OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET.

• PAINTING (BUT NOT SANDING).

• WALL COVERING, ELECTRICAL TRIM, MINOR PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE DUST OR

REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.

INFECTION CONTROL RISK ASSESSMENT (ICRA)

MATRIX OF PRECAUTIONS FOR

CONSTRUCTION & RENOVATION

INSPECTION AND NON-INVASIVE ACTIVITIES

TYPE B

INCLUDES, BUT IS NOT LIMITED TO:

• INSTALLATION OF TELEPHONE AND COMPUTER CABLING.

• ACCESS TO CHASE SPACES.

• CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.

SMALL SCALE, SHORT DURATION ACTIVITIES

WHICH CREATES MINIMAL DUST

TYPE C INCLUDES, BUT IS NOT LIMITED TO:

• SANDING OF WALLS FOR PAINTING OR WALL COVERING.

• REMOVAL OF FLOOR COVERINGS, CEILING TILES OR CASEWORK.

• NEW WALL CONSTRUCTION.

• MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS.

• MAJOR CABLING ACTIVITIES.

• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORK SHIFT.

WORK THAT GENERATES A MODERATE TO HIGH LEVEL

OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF

ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES

TYPE D INCLUDES, BUT IS NOT LIMITED TO:

• ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.

• REQUIRE HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CABLING SYSTEM.

• NEW CONSTRUCTION.

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS

RISK RELATED GROUP

LOW RISK GROUP

MEDIUM RISK GROUP

HIGH RISK GROUP

HIGHEST RISK GROUP

TYPE A

I

I

I

II

TYPE B

II

II

II

III / IV

TYPE C

II

III

III / IV

III / IV

TYPE D

III / IV

IV

IV

IV

CONTRUCTION PROJECT TYPE

NOTE:

INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACITIVITY AND RISK LEVEL

INDICATE THAT CLASS OR CLASS CONTROL PROCEDURES ARE NECESSARY.

IC MATRIX - CLASS OF PRECAUTIONS:

CONSTRUCTION PROJECT BY PATIENT RISK

III IV

CL

AS

S

IV

CLASS IV WORK ITEMS NOTES:

1. ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT

CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR

VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS INDICATED.

4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

5. CONSTRUCT ANTE ROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING HEPA

VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER OVERALLS THAT ARE REMOVED EACH TIME

THEY LEAVE THE WORK SITE.

6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA SITE OR THEY CAN WEAR CLOTH OR PAPER OVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE

THE WORK SITE.

7. DO NOT REMOVE BARRIERS FROM WORK UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER’S SAFETY DEPARTMENT AND

INFECTION CONTROL.

PRIOR TO ANY CONSTRUCTION:

1. OBTAIN APPROVAL BY MCOT TEAM TO REMOVE BARRIERS.

2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.

3. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

4. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

5. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.

6. WET MOP AREA WITH DISINFECTANT.

7. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

8. ROOM AND / OR SHALL BE THOROUGHLY CLEANED BY THE OWNER’S ENVIRONMENTAL SERVICES DEPARTMENT.

POST CONSTRUCTION:

SCALE: 3/8" = 1'-0"

GI005

TYPICAL CONSTRUCTION LAYOUT

SCALE: 3/8" = 1'-0"

GI005

TYPICAL CONSTRUCTION CROSS SECTION "A-A"

INFECTION CONTROL GENERAL NOTES

1. ALL PERSONNELL ENTERING THE CONSTRUCTION SITE AREA MUST WEAR A HARD HAT AND

SAFETY GLASSES ALONG WITH ANY OTHER PPE REQUIRED IN THAT AREA.

2. ALL APPLICABLE FORMS TO BE COMPLETED AND APPROVED PRIOR TO STARTING WORK.

3. PERMITS TO INCLUDE:

ICRA, ILSM, ABOVE CEILING, FIRE SPRINKLER SYSTEM, MEDICAL GASES, UTILITY

SHUTDOWN, FIRE / SMOKE WALL, FIRE ALARM SYSTEM.

4. THE CONSTRUCTION AREA MUST MAINTAIN A NEGATIVE PRESSURE VENTILATION. NEGATIVE

PRESSURE MACHINES MUST BE ON AND OPERATIONAL 24 / 7. NEGATIVE AIR UNIT TO BE

MAINTAINED WITH FILTER(S) REPLACED PER SPECIFICATIONS. (WEEKLY REPLACEMENT OF PRE-

FILTER OR MORE AS NECESSARY. HEPA FILTER REPLACED MONTHLY. CLEAN ALL EXTERIOR

SURFACES OF CARTS AND TOOLS AT THE END OF EACH SHIFT. MONITOR NEGATIVE PRESSURE

AND POST LOG AT THE END OF EACH SHIFT.

5. CONSTRUCTION CLASS WILL BE DETERMINED BY THE CONSTRUCTION SAFETY COMMITTEE.

6. DURING CONSTRUCTION BE CERTAIN THAT:

BARRIERS ARE INTACT AND MAINTAINED.

PARTICLE COUNT METER IS AVAILABLE.

NEGATIVE INDICATOR IS AVAILABLE.

ICRA REQUIREMENTS ARE INTACT AND

VERIFY ARE BEING MAINTAINED.

CL

AS

S

II

CLASS II WORK ITEMS NOTES:

1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.

3. SEAL UNUSED DOORS WITH DUCT TAPE.

4. BLOCK OFF AND SEAL AIR VENTS.

5. PLACE DUST MAT AT ENTRANCE AND EXIT WORK AREAS.

6. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

PRIOR TO ANY CONSTRUCTION:

1. WIPE WORK SURFACES TO CONTROL DUST WHILE CUTTING.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

3. WET MOP AND / OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREA.

4. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

POST CONSTRUCTION:

CL

AS

S

III

CLASS III WORK ITEMS NOTES:

1. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS, SUCH AS SHEET ROCK, PLYWOOD, PLASTIC, TO SEAL AREAS FROM NON-WORK AREA OR

IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM

FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS IF INDICATED.

4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN…