Drawings_C26863016.pdf

PDF 8 MB Posted

Attached to
C26863016 HEARST SAN SIMEON SHM - Reservoir #3 Water Treatment Plant Upgrade
Solicitation number
0000040461
Issued by
San Luis Obispo County, San Luis Obispo City, California

About this file

Reservoir #3 Water Treatment Plant Upgrade at Hearst San Simeon State Historic Monument

This document is a set of architectural and engineering drawings prepared for the California Department of Parks and Recreation, Facilities and Development Division, for the Reservoir #3 Water Treatment Plant Upgrade project located at Hearst San Simeon State Historic Monument in San Simeon, California. The project involves upgrading water treatment infrastructure including mechanical, electrical, and structural improvements to the existing water treatment plant. The scope includes installation of new filtration panels, filter control systems, a variable frequency drive (VFD) for a booster pump, electrical panel modifications, and integration of new water quality analyzers and turbidity controllers. The project is in the Bid Set phase of design, with fire and panic approval dated August 14, 2026. The drawings indicate that contractors must conduct site visits to verify existing conditions and coordinate with the State Representative throughout construction. The site is accessed through and surrounded by a working ranch, requiring contractors to maintain gate security at all times.

The contract documents specify compliance with current California codes including Title 19 CCR for fire safety, the 2025 California Building Code, Electrical Code, Mechanical Code, Plumbing Code, Energy Code, and Green Building Standards, as well as The Secretary of the Interior's Standards for the Treatment of Historic Properties. No new, additional, or relocated quantities of hazardous materials are stored or used on site, eliminating the need for a Hazardous Materials Management Program. All contractors must prepare and submit fire prevention programs and emergency fire action plans prior to work commencement and maintain temporary fire protection measures throughout the project. Construction activities and equipment must be confined to designated staging and construction areas, with all disturbed surfaces restored to original conditions and positive drainage maintained. The contractor is responsible for obtaining deferred submittals, programming of the programmable logic controller (PLC), and coordinating with a system integrator for complete configuration of the operational water treatment system.

View the file

Other files

File Type Posted
Bid_Forms_C26863016.pdf PDF
Project_Manual_C26863016.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

20 20

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T

Fi le

\w oo dr od ge rs .lo c\ Pr od uc tio nD at a\

Jo bs

\J ob s\

.0

_s ta te

_p ar ks _h ea rs t_ ca st le

_w tp

\G en

\D w g\ G

-0

TI

TL

E

SH

EE

T_

.d w g La yo ut

: L O

C

AT

IO

N

V

IC

IN

IT

Y

M

AP

S A

N D

S H

EE

T

IN

D

EX

D at e:

J ul y

- 2

:4 pm U se r:

lg ut ie rre z

CALIFORNIA DEPARTMENT OF PARKS AND RECREATION

FACILITIES AND DEVELOPMENT DIVISION

SITE ADDRESS

SHEET INDEX

LOCATION MAP

N

S

W E

DEFERRED SUBMITTALS

SCOPE OF WORK

PREPARED BY

WOOD RODGERS, INC.

3301 C STREET, BUILDING 100B

SACRAMENTO, CA 95816

VICINITY MAP

N

S

W E

1- ALL MATERIALS SHOWN OR NOTED ON THE PLANS ARE NEW UNLESS CALLED OUT OTHERWISE.

2- THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS SHOWN OR

DIMENSIONED HERE. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE STATE

REPRESENTATIVE FOR RESOLUTION BEFORE PROCEEDING WITH THAT PORTION OF THE WORK.

3- ALL WORK SHALL COMPLY WITH THE CURRENT EDITION OF THE FOLLOWING LISTED CODES, AND ALL

OTHERS HAVING JURISDICTION OVER THE WORK.

TITLE 19, CCR, PUBLIC SAFETY, SFM REGULATIONS.

2025 CA ADMINISTRATIVE CODE TITLE 24, PT 1.

2025 CA BUILDLING CODE (CBC) TITLE 24, PT 2.

2025 CA ELECTRICAL CODE (CEC) TITLE 24, PT 3.

2025 CA MECHANICAL CODE (CMC) TITLE 24, PT 4

2025 CA PLUMBING CODE (CPC) TITLE 24, PT 5.

2025 CA ENERGY CODE CCR TITLE 24, PT 6.

2025 CA GREEN BUILDING STANDARDS TITLE 24, PT 11.

2025 CA REFERENCED STANDARDS TITLE 24, PT 12.

THE SECRETARY OF THE INTERIOR'S STANDARDS FOR THE TREATMENT OF HISTORIC PROPERTIES.

4- CONDUCT ALL WORK IN ACCORDANCE WITH THE LATEST SAFETY RULES AND REGULATIONS OF ALL

AUTHORITIES AND AGENCIES HAVING JURISDICTION OVER THE WORK.

5- ALL WORK SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. WHERE DETAILED INFORMATION OR CLARIFICATION IS REQUIRED, THE MATTER SHALL BE REFERRED TO THE STATE

REPRESENTATIVE FOR WRITTEN RESOLUTION.

6- THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS, BUT SHALL RELY ONLY ON THE WRITTEN DIMENSIONS GIVEN. IF A DISCREPANCY OCCURS OR NO DIMENSION IS GIVEN, THE CONTRACTOR SHALL NOTIFY THE STATE REPRESENTATIVE FOR WRITTEN CLARIFICATION BEFORE PROCEEDING WITH THAT

PORTION OF THE WORK.

7. THE OFFICIAL CONTRACT DRAWINGS ARE 36" x 24" PRINTED IN GRAYSCALE TO SHOW THE LINE WORK OF EXISTING AND/OR FUTURE IMPROVEMENTS DRAWN IN GRAY. SCALES LISTED ON THE DRAWINGS ARE APPLICABLE TO 36" x 24" AND MUST BE ADJUSTED ACCORDINGLY WHERE REDUCED SIZE DRAWINGS ARE REFERENCED. USE OF DRAWINGS PRINTED TO NON-STANDARD SCALES OR IN PURE BLACK & WHITE IS

DONE AT-RISK.

8. UNLESS NOTED OTHERWISE, STANDARD DETAILS ARE TO BE USED WHERE THEY APPLY REGARDLESS AS

TO WHETHER THEY ARE SPECIFICALLY CALLED OUT.

9. ALL WORK TO CONSTRUCT THE IMPROVEMENTS SHOWN IN THE CONTRACT DOCUMENTS AND THAT

WHICH IS NOT SHOWN BUT NECESSARY TO CONSTRUCT THE IMPROVEMENTS SHOWN IS TO BE

PERFORMED BY THE CONTRACTOR UNLESS OTHERWISE NOTED.

10. ABSENCE OF A SPECIFICATION SECTION FOR A MATERIAL, EQUIPMENT, PRODUCT, ETC. SHOWN ON THE DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO PREPARE A SUBMITTAL AND PROVIDE SUCH ITEM AND DOES NOT CONSTITUTE A CHANGE ORDER. CONTACT THE STATE'S REPRESENTATIVE FOR CLARIFICATION BEFORE PREPARING THE SUBMITTAL, ORDERING THE ITEM, AND

PROCEEDING WITH THE AFFECTED WORK.

11.THE IMPROVEMENTS SHOWN ON THE DRAWINGS ILLUSTRATE THE GENERAL PLACEMENT OF THE WORK.

NOT ALL APPURTENANT PARTS OR ACCESSORIES REQUIRED BY THE MANUFACTURERS, THE

SPECIFICATIONS, OR BY APPLICABLE CODES ARE SHOWN. FURNISH AND INSTALL ALL SUCH ITEMS FOR A

PROPER, COMPLETE, AND FULLY FUNCTIONAL INSTALLATION IN ACCORDANCE WITH THE

MANUFACTURER'S INSTRUCTIONS, THE APPLICABLE SPECIFICATION SECTIONS, AND THAT ARE REQUIRED

FOR CODE COMPLIANCE.

12. WORK PERFORMED MUST COMPLY WITH NFPA 241 AND CFC CHAPTER 33. PREPARE AND SUBMIT FIRE PREVENTION PROGRAM AND EMERGENCY FIRE ACTION PLANS AND PLACE TEMPORARY FIRE CONTROL MEASURES PRIOR TO THE START OF WORK AND MAINTAIN THEM FOR THE DURATION OF THE PROJECT.

SEE SECTION 015116 - TEMPORARY FIRE PROTECTION FOR ADDITIONAL INFORMATION AND

REQUIREMENTS.

13.CONFINE EQUIPMENT AND CONSTRUCTION ACTIVITIES TO THE STAGING AND CONSTRUCTION AREA

SHOWN ON THE DRAWINGS. PROMPTLY REPAIR DAMAGE TO EXISTING FACILITIES CAUSED BY

CONSTRUCTION ACTIVITY INCLUDING UNDERGROUND UTILITIES, AND CLEAN UP SPILLS AND STAINS

FROM EQUIPMENT LEAKS.

14.UNLESS OTHERWISE SHOWN, RESTORE ALL SURFACE AREAS DISTURBED BY CONSTRUCTION ACTIVITY IN KIND TO ORIGINAL LINE AND GRADE. ADJUST AS REQUIRED TO PROVIDE POSITIVE DRAINAGE AWAY FOR

NEW AND EXISTING IMPROVEMENTS. RESTORE PAVED AND CONCRETE SURFACES TO EXISTING

THICKNESS AND GRADE.

15.MAINTAIN THE JOB SITE AND AREAS ACCESSIBLE OR VISIBLE TO THE PUBLIC IN A CLEAN, SAFE, AND USABLE CONDITION. COLLECT AND CONTAIN ALL CONSTRUCTION DEBRIS, TRASH, AND WASTE MATERIAL DAILY. PROMPTLY REMOVE SPILLS OF FLUIDS, SOIL, AND ROCK. CONTAIN CONSTRUCTION DEBRIS, TRASH, AND WASTE MATERIAL WITHIN THE CONSTRUCTION AREA UNTIL DISPOSED OFF-SITE.

16.MAINTAIN SECURITY OF THE PROJECT SITE AND STAGING AREA AT ALL TIMES. PROVIDE TEMPORARY FENCING, GATE(S), BARRICADES, ETC., AS REQUIRED TO SECURE THE PERIMETERS AND TO PREVENT UNAUTHORIZED ENTRY. SECURE ALL GATES AT THE END OF EACH WORKDAY. SEE SPECIFICATION

SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS FOR ADDITIONAL INFORMATION.

17.THE SITE IS ACCESSED THROUGH AND IS SURROUND BY A WORKING RANCH. KEEP GATES CLOSED AT

ALL TIMES.

RESERVOIR #3 WATER TREATMENT PLANT UPGRADE

HEARST SAN SIMEON STATE HISTORIC MONUMENT

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T

HEARST CASTLE

SUMMIT RD.

CABRILLO HWY

PROJECT

LOCATION

PROJECT LOCATION

RESERVOIR #3

HEARST CASTLE VISITOR CENTER

L. GUTIERREZ

K. GUSTORF

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T

E. GOSSE

G-01

LO

C

AT

IO

N

V

IC

IN

IT

Y M

AP

S, AN

D

S H

EE

T

IN

D

EX

7/28/2026

MECHANICAL EQUIPMENT ANCHORAGE TO CONCRETE

ELECTRICAL EQUIPMENT ANCHORAGE TO CONCRETE

HEARST SAN SIMEON STATE HISTORICAL MONUMENT

750 HEARST CASTLE ROAD

SAN SIMEON, CA 93452

NO NEW, ADDITIONAL, OR RELOCATED QUANTITIES OF HAZARDOUS

MATERIALS ARE STORED OR USED ON ANY SITE FOR THIS PROJECT.

THEREFORE, AND HAZARDOUS MATERIALS MANAGEMENT PROGRAM

(HMMP) OR UPDATES TO THE STATE'S EXISTING HMMP ARE NOT

REQUIRED FOR THIS PROJECT.

HAZARDOUS MATERIALS

IN STORAGE AND IN USE

CSFM #26-S-2887-C-AC

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

26-2887 mpatrick Text Box

EXEMPT

mpatrick Text Box mpatrick Text Box 8.10.26

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T

Fi le

\w oo dr od ge rs .lo c\ Pr od uc tio nD at a\

Jo bs

\J ob s\

.0

_s ta te

_p ar ks _h ea rs t_ ca st le

_w tp

\G en

\D w g\ G

-0

G

EN

ER

AL

N O

TE

S.

dw g

La yo ut : G

EN

ER

AL

N

O

TE

S D at e:

J ul y

- 2

:5 pm U se r:

lg ut ie rre z

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T

G-02

G

EN

ER

AL

N O

TE

S

7/28/2026

L. GUTIERREZ

K. GUSTORF

E. GOSSE

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

26-2887

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

: J :\J ob s\

.0

_S ta te _P ar ks

_H ea rs t_

C as tle _W

TP

\G en \D w g\

G -0

G

EN

ER

AL

S

YM

BO

LS

A

N D

A

BB

R

EV

IA

TI

O N

S.

dw g La yo ut

: G

EN

ER

AL

S

YM

BO

LS

A N

D A

BB

R

EV

IA

TI

O

N S

D at e:

J ul y

- 4 :3 pm

U se r:

eg os se

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

G-03

G

EN

ER

AL

S

YM

BO

LS

A N

D

AB

BR

EV

IA

TI

O N

S

6/25/2026

L. GUTIERREZ

K. GUSTORF

E. GOSSE

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

: J :\J ob s\

.0

_S ta te _P ar ks

_H ea rs t_

C as tle _W

TP

\C iv il\

D w g\ C

-0

Ex is tin g

Si te

.d w g La yo ut

: S

IT

E

PL

AN

D at e:

J ul y

- 4

:5 pm U se r:

eg os se

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

MAINTENANCE ACCESS ROAD

(E) OPEN RESERVOIR

5/15/2026

L. GUTIERREZ

K. GUSTORF

E. GOSSE

(E) RESERVOIR #3

G-04

SI

TE

P

LA

N

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

----8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

3' -0

" M

IN

4" 4"

3' -0

" M

IN

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

\w oo dr od ge rs .lo c\ Pr od uc tio nD at a\

Jo bs

\J ob s\

.0

_s ta te

_p ar ks _h ea rs t_ ca st le

_w tp

\M ec h\ D w g\

G M

-0

M

EC

H

AN

IC

AL

D

ET

AI

LS

.d w g La yo ut

: M

EC

H

AN

IC

AL

D

ET

AI

LS

D at e:

J ul y

- 5 :5 pm

U se r:

eg os se

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

7/9/2026

L. GUTIERREZ

E. GOSSE

E. GOSSE

M

EC

H

AN

IC

AL

D

ET

AI

LS

GM-01

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

2" 41

2"

8"

1'-3"

13'-6"3'-3"

MODELNUMBERTRADENAMEPRODUCTMATERIAL

MATERIALPRODUCTTRADENAMEMODELNUMBER

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

: J :\J ob s\

.0

_S ta te _P ar ks

_H ea rs t_

C as tle _W

TP

\M ec h\

D w g\ M

-0

T R

EA

TM

EN

T

BU

IL

D

IN

G .d w g

La yo ut : T

R

EA

TM

EN

T

BU

IL

D

IN

G

IM

PR

O

VE

M

EN

TS

D at e:

J ul y

- 6

:0 pm U se r:

eg os se

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

M-01

TR

EA

TM

EN

T

BU

IL

D

IN

G

IM

PR

O

VE

M

EN

TS

7/9/2026

L. GUTIERREZ

E. GOSSE

E. GOSSE

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

: J :\J ob s\

.0

_S ta te _P ar ks

_H ea rs t_

C as tle _W

TP

\M ec h\

D w g\ M

-0

AN

AL

YZ

ER

P

AN

EL

.d w g

La yo ut : F

IL

TE

R S

YS

TE

M D

ET

AI

LS

D at e:

J ul y

- 6

:4 pm U se r:

eg os se

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: BID SET

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

M-02

FI

LT

ER

S

YS

TE

M D

ET

AI

LS

7/10/2026

L. GUTIERREZ

E. GOSSE

E. GOSSE

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

SCALE:

POST BASE PLATE

1 1/2" = 1'-0"

S-01

SCALE:

FILTRATION PANEL FRAMING ELEVATION

1" = 1'-0"

B

S-01

SCALE:

FILTRATION PANEL ELEVATION

1" = 1'-0"

A

S-01

SOUTH ELEVATION SHOWN.

NORTH ELEVATION SIMILAR.

REFER TO MECH DWGS FOR LAYOUTS.

SCALE:

STRUT CONNECTIONS

AT BOTTOM OF POST

3" = 1'-0"

S-01

SCALE:

STRUT CONNECTIONS AT TOP OF POST

3" = 1'-0"

S-01

STRUCTURAL SHEET NOTES:

SCALE:

FRP PANEL CONNECTION

AT CHANNEL STRUT

3" = 1'-0"

S-01

FRONT VIEW SIDE VIEW

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE: 90% DESIGN

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

Fi le

\w oo dr od ge rs .lo c\ Pr od uc tio nD at a\

Jo bs

\J ob s\

.0

_S ta te

_P ar ks _H ea rs t_ C as tle

_W

TP

\S tru ct ur al \0

4_ D ra w in gs

\C ur re nt

S tru ct ur al D

W G s\ S-

.d w g

La yo ut : S tru ct ur al

D at e:

J un e

- 4 :5 pm

U se r:

ffr as ie r

8691.011

S-01 X15

FI

LT

ER

S

YS

TE

M

F. FRASIER

A. JOHNSON

D. SLAVIN

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

ST

R

U C

TU

R

AL

N

O

TE

S

AN

D D

ET

AI

LS

6/30/26

100%

7/9/2026

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

LE

TCE

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : G

E-

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

(D)

(RS)

(E)

EXISTING TO BE DEMOLISHED.

EXISTING TO BE REMOVED AND SALVAGED.

EXISTING TO REMAIN

GROUND FAULT RELAYGFR

CONTACT ACTION RETARDED ON DE-ENERGIZATION

TIME CONTACT

CONTACT ACTION RETARDED ON ENERGIZATION

TIME CONTACT

OR CONTROL PANEL

ELECTRICAL SYMBOLS - SCHEMATIC DIAGRAMS

NORMALLY

OPEN

NORMALLY

CLOSED DEVICE

CONTACT

PUSH BUTTON SINGLE CIRCUIT

LOCK-OUT

PUSH BUTTON SINGLE CIRCUIT

MOMENTARY CONTACT

LIQUID FLOAT LEVEL SWITCH

PRESSURE OR VACUUM SWITCH

FLOW SWITCH

TEMPERATURE SWITCH

SELECTOR SWITCH (H-O-A)

MOTOR OVERLOAD RELAY CONTACT

MOTOR OVERLOAD HEATER

PILOT LIGHT R=RED, W=WHITE

G=GREEN, A=AMBER

PILOT LIGHT-PUSH TO TEST

RELAY

TIME DELAY RELAY

STARTER COIL

SOLENOID OPERATED VALVE

MOTOR

BELL OR BUZZER

FUSE

CONTROL POWER TRANSFORMER

GROUND

WIRING IN MOTOR STARTER

OR CONTROL PANEL

FIELD WIRING

WIRE TERMINAL IN MOTOR STARTER

WIRE TERMINAL IN PLC

PHASE/POWER FAILURE RELAY

SPACE HEATER

RESISTOR

O.L.

A

R

R

TD

M

S

CIRCUIT BREAKER

F

MCP

100A

M

GW

GW

J

G

G

J

GROUND

MOTOR, 15 HORSEPOWER

"F" INDICATES FUSED, SEE PLANS FOR RATING

DISCONNECT SWITCH

FUSE

SWITCH

2S, 2W = 2 SPEED, 2 WINDING

FVNR=FULL-VOLTAGE NON-REVERSING

MAGNETIC MOTOR STARTER, NEMA SIZE INDICATED

3 POLE UNLESS NOTED

CIRCUIT BREAKER,

POWER TRANSFORMER

CURRENT TRANSFORMER, QUANTITY INDICATED

UTILITY METERING

WITH GROUND WELL. SEE DETAIL,

GW NEXT TO SYMBOL INDICATES GROUND ROD

GROUND ROD, 3/4" x 10'-0"

MOTOR CONNECTION

CONDUIT SEAL (HAZARDOUS LOCATION)

FLEXIBLE CONDUIT CONNECTION

CONDUIT STUB-OUT AND CAPPED

CONDUIT BENDS AWAY FROM OBSERVER

CONDUIT BENDS TOWARD OBSERVER

EXOTHERMIC WELD CONNECTION

GROUNDING CONDUCTOR 30" BELOW GRADE, #4/0 U.O.N.

CONDUIT EXPOSED

CAP, THREE CONDUITS OR LESS

CONDUIT IN SLAB OR UNDER CONCRETE

OR ONE LINE DIAGRAM FOR SIZE

FEEDER DESIGNATION SEE SCHEDULE

ELECTRICAL SYMBOLS - SINGLE LINE DIAGRAM

JUNCTION BOX

DUPLEX RECEPTACLE

AREA FLOOD LIGHT AND POLE

SYMBOLS DESCRIPTIONFLR.WALLCLG.

ELECTRICAL SYMBOLS - PLANS

POWER FAILURE RELAY

FLUORESCENT LIGHT FIXTURE

DISC DISCONNECT

AWG AMERICAN WIRE GAUGE

UNLESS OTHERWISE NOTEDUON

XFMR TRANSFORMER

CB CIRCUIT BREAKER

OVERLOADSO/L'S

MOUNTEDMT'D

GROUND FAULT CURRENT INTERUPTINGGFCI

PRESSURE TRANSDUCERPT

ELECTRICAL ABBREVIATIONS

VOLTV

TYPICALTYP

SACRAMENTO MUNICIPAL UTILITY DISTRICTSMUD

POLYVINYL CHLORIDEPVC

L

KILOVOLT AMPERESKVA

HAND OFF AUTOMATICHOA

DIRECT CURRENTDC

CONDUIT ONLYCO

CONDUITC

A AMPERES

G, GND GROUND

RVSS REDUCED VOLTAGE SOLID STATE

P POLE

UTILITY SERVICE

GRS GALVANIZED RIGID STEEL

HH HANDHOLE

PFR

PFR

X

E-Y Y- SHEET WHERE DETAIL IS DRAWN

DETAIL CALLOUT- X, DETAIL IDENTIFIER.

JUNCTION BOX OR PULLBOX

ALTERNATING CURRENTAC

AMPERES INTERRUPTING CAPACITY, SYMMETRICALAICS

BC BARE COPPER

CKT CIRCUIT

CURRENT TRANSFORMERCT

CPT CONTROL POWER TRANSFORMER

DWG DRAWING

EXISTINGE

ELEV ELEVATION

LIGHTING ARRESTORLA

LIGHTINGLTG

KILOWATTKW

MOTOR CONTROL CENTERMCC

MAIN CIRCUIT BREAKERMCB

MILLIAMPEREMA

MIN MINIMUM

N NEUTRAL

NO NORMAL OPEN

NC NORMAL CLOSED

PB PULL BOX, PUSH BUTTON

PH, Ø PHASE

RECP RECEPTACLE

SW SWITCH

TERMINAL BOARDTB

TSP TWISTED SHIELDED PAIR

W/ WITH

WEATHERPROOFWP

PS PRESSURE SWITCH

PROGRAMMABLE LOGIC CONTROLLERPLC

HP HORSEPOWER

HR HOUR

HERTZHz

RIGID STEEL CONDUITRGS

POWER QUALITY METERSHARK

FOUR CONDUITS OR MORE

CONCRETE ENCASED DUCT BANK

SS STAINLESS STEEL

HDG HOT DIPPED GALVANIZED

CAT CATEGORY 6 CABLE

FCP FILTER CONTROL PANEL

LONG

MOTOR CIRCUIT PROTECTORMCP

MS MOISTURE SENSOR

NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

SURGE PROTECTIVE DEVICESPD

PFR POWER FAIL RELAY

TEMPERATURE SWITCHTS

VOLTS ACVAC

YELLOWFOREIGN VOLTAGE

TERMINAL BLOCK COLOR CODE TABLE

DESCRIPTION TERMINAL BLOCK COLOR

WIRE COLOR CODE TABLE

PHASE/CODE LETTER

A480V, 3P

240V OR 208V, 3P

240/120V, 1P

AC CONTROL

DC CONTROL

NEUTRAL

GROUND

SHIELDED PAIR

N G

L1 L2

B C

C A

B

DESCRIPTION

BROWN

BLUE

RED

CLEAR (WHITE)

BLACK

GREEN

WHITE

RED

BLACK

BLUE

RED

BLACK

YELLOW

ORANGE

WIRE OR TAPE COLOR

AC WIRING

DC WIRING

BEIGE

PVC COATED GALVANIZED STEELPVC-GRS

GE-01

MODIFYM

SY

M

BO

LS

A N

D

AB

BR

EV

IA

TI

O N

S

AIR COMPRESSORA/C

FLA FULL LOAD AMPS

FT FLOW TRANSDUCER

LIGHTING PANELBOARDLP

PCP PLANT CONTROL PANEL

SV SOLENOID VALVE

VARIABLE FREQUENCY DRIVEVFD

X159

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : G

E-

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

A (E)PANELBOARD LP MODEL

GE-02

EX

IS

TI

N

G E

Q U

IP

M

EN

T

B SPACE FOR SUB PANEL LP-2 C (E)BUILDING CEILING

F (E)PCP BACK PANELD (E)PLANT CONTROL PANEL (PCP)

KEY NOTES:

EX PANELBOARD “LP”, WESTINGHOUSE B10 1224RT.

EX PLANT CONTROL PANEL (PCP).

COORDINATE LOCATION OF SUBPANEL “LP-2” WITH STATE

REPRESENTATIVE.

CONTRACTOR TO PROGRAM PLC AND CONFIGURE OIT FOR

ADDITIONAL PUMP AND FILTERS AND ANALYZERS FOR COMPLETE AND

OPERABLE WATER TREATMENT PLANT; WORK TO BE DONE BY SYSTEM

INTEGRATOR.

CONTRACTOR TO REPLACE ETHERNET SWITCH IN PCP WITH NEW ONE;

PROVIDE NEW RS-485 COMMUNICATION NETWORK FROM PLC TO NEW

WATER QUALITY CONTROLLERS, AND TIE IN EXISTING RS-485

NETWORKS. ADD 24V DC POWER SUPPLY FOR NEW FILTER CONTROL

PANELS, ADD TERMINAL BLOCKS AS REQUIRED. WORK TO BE DONE BY

SYSTEM INTEGRATOR.

LOCATION OF NEW CHEMICAL METERING PUMP.

ROUTE CONDUITS FROM "LP-2" AND FROM FCP ABOVE EXISTING

LIGHTING, SECURE TO BUILDING TRUSSES ON UNISTRUT SYSTEM.

LP-2

4 4

E (E)PCP SWING PANEL

X1510

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

GE-03

EX

IS

TI

N

G E

Q U

IP

M

EN

T

LE

TCE

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : G

E-

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

A (E)VFD AND (E)INFLUENT PUMP B TYPICAL (E)FILTERS C TYPICAL (E)FILTER CONTROL PANEL (FCP)

D TYPICAL (E)FCP BACK PANEL

KEY NOTES:

REMOVE EXISTING VFD AND REPLACE WITH NEW VFD. PROVIDE

EXISTING VFD TO STATE REPRESENTATIVE RECONNECT CABLES TO

PCP AND PRESSURE TRANSDUCER. CONNECT NEW LINE SIDE

CONDUIT AND CABLE FROM SUBPANEL LP-2. PROVIDE NEW CONDUIT

AND CABLE TO NEW BP-1 MOTOR TERMINATION BOX. CONFIGURE VFD

FOR PRESSURE SETPOINT AND CONTROL. ADJUST CONDUITS TO FIT

NEW VFD.

PICTURES OF EXISTING EQUIPMENT FOR INFORMATION ONLY.

CONTRACTOR RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT

FOR NEW FILTER EQUIPMENT, AND PROVIDE NEW FILTER CONTROL

PANELS (FCP) AND EQUIPMENT BASED ON APPROVED SUBMITTALS.

PICTURES OF EXISTING EQUIPMENT FOR INFORMATION ONLY.

PROVIDE ALL REQUIRED ELECTRICAL CONDUITS AND CABLES AND

EQUIPMENT AND ANALYZERS FOR COMPLETE AND OPERABLE FILTER

SYSTEM, TYPICAL OF NEW EQUIPMENT.

PICTURES OF EXISTING EQUIPMENT FOR INFORMATION ONLY.

CONTRACTOR TO PROVIDE AND INSTALL FILTER CONTROL PANELS,

COMPLETE WITH PROGRAMMING AND COMMUNICATIONS BACK TO

PCP. FILTER CONTROL PANELS, PROGRAMMING, AND COMMUNICATION

CONFIGURATION WORK, ALL TO BE DONE BY SYSTEM INTEGRATOR VIA

CONTRACTOR. CONDUITS AND CABLES BY CONTRACTOR.

REMOVE (E)20A/2P BREAKER AND INSTALL 60A/2P EATON #BRX260.

PROVIDE BLANK PLATES WHERE EXISTING TAPE IS LOCATED.

PROVIDE NEW NAMEPLATE WHERE "VFD" IS, INSCRIBED "SUBPANEL

LP-2".

E TYPICAL (E)FILTER COMPRESSOR

3 4

3 4

F (E)PANELBOARD "LP"

X1511

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : E

-0

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

E-01

NOTES:

1. EXISTING PANELBOARD "LP" SCHEDULE FOR INFORMATION

ONLY.

2. MAKE MODIFICATIONS TO "LP" AS SHOWN IN MODIFIED

SCHEDULE. COORDINATE SHUTDOWN OF VFD WITH STATE

REPRESENTATIVE.

3. VFD SIZED FOR SINGLE PHASE TO THREE PHASE CONVERSION.

PROVIDE AMPACITY SHOWN. VFD TO BE WIRED AND

CONFIGURED FOR CONSTANT PRESSURE CONTROL. PROVIDE

CAPACITORS AT VFD AS REQUIRED. SI

N G

LE

L

IN

E

AN

D

PA

N

EL

BO

AR

D

S C

H

ED

U

LE

S

SINGLE LINE DIAGRAM

50A 2P

VFD

18A

BP-1

240V, 3 PH

11 FLA

3/4"(3#12, #12G)

3/4"(2#6, #8G)

60A 2P

SPD

SEE MODIFIED SUB-PANEL LP

SCHEDULE TO LEFT

SUB -PANEL "LP-2"

(E)PANELBOARD "LP"

100A, 120/240VAC, 1PH, 3W

100A, 120/240VAC, 1PH, 3W

100A 2P

(E)15KVA TRANSFORMER

480-120/240VAC, 1PH, 3W

(E)100A DISC SWITCH

(E)480VAC, 1PH

NOTE 1

NOTE 2

(E)120/240VAC, 1PH, 3W

SEE SUB-PANEL LP-2 SCHEDULE BELOW

60A 2P

NOTE 3

1" (2#4, #4N, #8G)

PT

(E)PRESSURE

TRANSDUCER

X1512

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : E

-0

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

E-02

TREATMENT BUILDING

TR

EA

TM

EN

T

BU

IL

D

IN

G

PO

W

ER

A

N D

C O

N

TR

O L

PL

AN

SCALE: 3/4" = 1'-0"

GENERAL NOTES:

1. LOCATIONS OF EQUIPMENT AND CONDUIT ROUTINGS ARE APPROXIMATE. FINAL

LOCATIONS AND ROUTINGS SHALL BE APPROVED IN FIELD WITH STATE

REPRESENTATIVE.

2. ALL EXPOSED CONDUITS AND FITTINGS TO BE PVC SCH 40, UNLESS SHOWN

OTHERWISE, OR WHERE FLEXIBLE METAL SEALTIGHT CONDUIT REQUIRED.

3. ALL HARDWARE, STRUT, STRAPS, AND ANCHORS SHALL BE 316 STAINLESS STEEL.

4. ALL CONDUITS AND CABLES SHALL BE LABELED AT BOTH ENDS. PROVIDE

NAMEPLATES ON ALL EQUIPMENT AND INSTRUMENTS. PROVIDE LABELS ON ALL

WIRES.

5. ALL DETAILS APPLY EVEN IF NOT CALLED OUT.

6. MAXIMUM LENGTH OF FLEXIBLE METAL SEALTIGHT CONDUIT IS 18” UNLESS NOTED

OTHERWISE.

7. CONTRACTOR MAY COMBINE CABLES IN SINGLE CONDUIT; SIZED PER NEC.

KEY NOTES:

PROVIDE NEW BREAKER IN EX PANELBOARD LP. REFER TO SINGLE LINE DIAGRAM, DWG

E-01. COORDINATE SHUTDOWN WITH STATE REPRESENTATIVE.

INSTALL SUBPANEL “LP-2” SO TOP OF PANEL IS 72” AFF, WITH FINAL LOCATION PER

STATE REPRESENTATIVE.

FIELD ROUTE CONDUITS OVERHEAD AND ATTACH TO EXISTING TRUSSES WITH

UNISTRUT SYSTEM.

PROVIDE AND INSTALL NEW VFD FOR BOOSTER PUMP BP-1. CONFIGURE VFD BASED ON

MOTOR NAMEPLATE DATA, AND FOR PRESSURE SETPOINT AND CONTROL. VFD SHALL

CONVERT SINGLE PHASE TO THREE PHASE.

ADJUST EXISTING CONDUITS TO ALLOW FOR WALL MOUNT VFD. CONDUITS TO ENTER

BOTTOM OF VFD ENCLOSURE.

REFER TO EXISTING EQUIPMENT DWG GE-02 FOR ADDITIONAL WORK.

REFER TO EXISTING EQUIPMENT DWG GE-03 FOR ADDITIONAL WORK.

DEMOLISH EXISTING VFD AND INFLUENT PUMP AND MOTOR, PROVIDE TO STATE

REPRESENTATIVE. INSTALL NEW VFD AND PUMP.

REFER TO DWG E-03 FOR TYPICAL FILTER INTERCONNECTIONS.

COORDINATE CONFIGURATION OF TURBIDITY CONTROLLER AND CHLORINE ANALYZER

WITH STATE REPRESENTATIVE AND SYSTEM INTEGRATOR.

PROVIDE “T” CONDULET AND CONTINUE 3/4" (#12, #12N, #12G) TO TURBIDITY

CONTROLLER AND TO CHLORINE ANALYZER.

USE EXISTING CONDUIT AND CABLE BETWEEN PCP AND VFD FOR BP-1. MODIFY ENDS

OF CONDUITS AS REQUIRED TO CONNECT TO VFD.

RECONNECT PRESSURE TRANSDUCER TO NEW VFD FOR BP-1.

PROVIDE “T” CONDULET AND CONTINUE 3/4" (2-RS-485, #14G) TO TURBIDITY

CONTROLLER AND 3/4" (2-RS-485, #14G) TO CHLORINE ANALYZER FROM PCP.

PROVIDE CONDUIT AND CABLE SHOWN TO (E)J-BOX BELOW PLANT CONTROL PANEL.

MAY USE (E)CONDUITS IF CAPACITY PER CEC. REFER TO NAOCL INJECTION PUMP

INTERCONNECIONS ON DWG E-04. CONTINUE SPEED COMMAND SIGNAL TO NAOCL

PUMP #2 LOCATED NEXT TO (E)NAOCL PUMP BELOW PCP.

A E-

B E-

M

J

J

3/4"(2#12, 2#12N, #12G)

1"(2#4, #4N, #8G)

3/4"(2#6, #8G)

(TYP)

3/4"(#12, #12N, #12G)

(TYP)

TO PCP

BP-1 VFD,

WALL MOUNT

74 8

BP-1

3/4"(3#12, #12G)

FCP

#9 & #10

FCP

#5 & #6

FCP

#7 & #8

7 9

7 9

TO BP-1 VFD

TYPICAL FILTER

CONTROL PANEL

(FCP)

3/4"(CAT6, 4#14, #14G)3/4"(CAT6, 4#14, #14G)

3/4"(CAT6, 4 #14, #14G)

3/4"(2-RS-485, #14G)

(E)PANELBOARD "LP"

SEE DWG E-01 FOR

SCHEDULE

(E)PLANT

CONTROL

PANEL (PCP) 6

SUBPANEL "LP-2"

SEE DWG E-01

FOR SCHEDULE 2 6

CHLORINE

ANALYZER

TURBIDITY

CONTROLLER

(E)PRESSURE

TRANSDUCER

3/4"(EXIST MANU

CABLE)

3/4"(2#16 TWSP, 2#12, #14G) 15

M

CHEMICAL

METERING PUMP

(BELOW PCP)

X1513

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : E

-0

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

E-03

TYPICAL FILTER "FCP" INTERCONNECTION DIAGRAM

TR

EA

TM

EN

T

BU

IL

D

IN

G

SE

C

TI

O

N A

N D

D

ET

AI

LS

SV

SV

SV

SV

SV

SV

SV

PT

PT

FT

SV

SV

SV

SV

SV

SV

SV

PT

PT

FT

A/C

#12, #12N, #12G, 6#14

TYP FILTER EQUIPMENT,

REFER TO DWG M-02 FOR

ACTUAL FILTER LAYOUT

FCP

FILTER

J-BOX

FILTER

J-BOX

2#14, #14G

(TYP)

MANU CABLE

MANU CABLE

MANU CABLE

FILTER TOP

FILTER BOTTOM

BACKWASH

2#14, #14G

(TYP)

AIR

COMPRESSOR,

1 A/C PER

FILTER PAIR

#12, #12N, #12G

TYP FILTER EQUIPMENT,

REFER TO DWG M-02 FOR

ACTUAL FILTER LAYOUT

#12, #12N, #12G, 6#14

2#14, #14G

(TYP)

MANU CABLE

MANU CABLE

MANU CABLE

FILTER TOP

FILTER BOTTOM

BACKWASH

2#14, #14G

(TYP)

120VAC

FROM LP-2

COMMS

TO PCP

PANEL BY SYSTEM

INTEGRATOR, PART

OF WORK

CAT6, 4#14, #14G#12, #12N, #12G

NOTES:

1. PROVIDE CONDUITS AND CONDULETS AS REQUIRED, NOT SHOWN

FOR CLARITY. SIZE CONDUITS PER CEC.

2. FINAL WIRE SIZES AND QUANTITIES SHALL BE BASED ON

APPROVED SUBMITTALS.

3. SOLENOID VALVES SHALL BE SIMILAR MAKE AND MODELS AS

EXISTING FILTERS 1-4.

SCALE: 1" = 1'-0"

FILTRATION PANEL NORTH ELEVATION VIEW - FILTERS 8, 9, & 10A

SCALE: 1" = 1'-0"

FILTRATION PANEL SOUTH ELEVATION VIEW - FILTERS 5, 6, & 7B

FCP

#9 & #10

FCP

#7 & #8

FCP

#5 & #6

A/CA/C

J

J

"T" CONDULET

(TYP)

FILTER

J-BOX

FILTER

J-BOX

A/C

F #9

F #10

F #8

F #7

F #6

F #5

CHLORINE

ANALYZER

TURBIDIMETER

CONTROLLER

FILTER

J-BOX

(TYP)

TYPICAL WELLSPRING

UNITS, SEE DWG

M-02 FOR DETAIL

FILTER

J-BOX

FILTER

J-BOX

FILTER

J-BOX

FILTER

J-BOX

PRESSURE

TRANSDUCER

(TYP)

FLOW

TRANSMITTER

(TYP)

X1514

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

JO

HN C. CALTON

LACIR

Fi le

: C :\U se rs

\k cn am \D oc um en ts

\C al to n

Pr oj ec ts

\H ea rs t C as tle

W

TP

\G E-

1_

E- 1_

.d w g

La yo ut : E

-0

D at e:

J un e

- 5 :1 pm

U se r:

kc na m

SHEET NO.

OF

DRAWN:

REVISIONS

CHECKED:

DATE

DESIGNED:

DATE:

FACILITIES AND

DEVELOPMENT DIVISION

PROJECT MILESTONE:

DPR ACCESSIBILITY COMPLIANCE REVIEW

ACCESSIBILITY COMPLIANCE AND SFM SIGNED

ORIGINALS ARE ON FILE AT THE DEPARTMENT OF

PARKS & RECREATION, NORTHERN SERVICE CENTER

Certification #

Reviewed by

DateCASp#

BID SET

6/12/2026

K. CHUNG

J. CALTON

J. CALTON

W

AT

ER

S

YS

TE

M

IM

PR

O

VE

M

EN

TS

H

EA

R

ST

C

AS

TL

E

ST

AT

E

PA

R K

E-04

IN

TE

R C

O N

N

EC

TI

O

N D

IA

G

R

AM

S

DIGITAL

INPUTS

(N)ETHERNET

SWITCH

G

DI

DI

DI

DO

COM

DIGITAL

OUTPUTS

RS-485

SIGNALS

ON PLC

(E)PLC I/O

24VDC

POWER

SUPPLY

PT

1327 18

U

G

Y

R

G

L2

L1

G

G

N

L

G

N

L

S1+

S1-

S2+

S2-

PLC

G

N

L

N

G

15A/1P

FILTER CONTROL

PANEL (TYP OF 3)

CAT6

#14 24VDC

#14 COM

#14 GND

50A/2P

N

G

15A/1P

N

G

15A/1P

#14 2 SPARES

24VDC

INPUT

#12 L

#12 N

#12 GND

CKTS 3, 5 , 7 (TYP)

REFER TO SCHEDULE

ON DWG E-001

CKTS 10

REFER TO SCHEDULE

ON DWG E-001

CKT 1

REFER TO SCHEDULE

ON DWG E-001

CKT 2/4

REFER TO SCHEDULE

ON DWG E-001

#12 L

#12 N

#12 GND

#12 L

#12 N

#12 GND

#6 L1

#6 L2

#8 GND

FIELD LP-2PLANT CONTROL PANEL

(N)FUSE BLOCKS AND

TERMINAL BLOCKS

TO (E)TURBIDITY

CONTROLLER

AND ANALYZER

COIL END

+24VDC

(E)PRESSURE

TRANSDUCER

JUMPERS

(TYP)

HAND

AUTO

RUN

VFD

CHLORINE

ANALYZER

TURBIDITY

CONTROLLER

RS-485

RS-485

RS-485

RS-485

RS-485

"T" CONDULET

AT FILTRATION

PANEL

"T" CONDULET

AT FILTRATION

PANEL

CALL TO

START #12 T1

#12 T2

#12 T3

#12 GND

M

5HP

BOOSTER

PUMP "BP-1"

120VAC

INPUT

120VAC

INPUT

120VAC

INPUT

120VAC

INPUT

(E)CABLES

(E)MANU

CABLE

USE (E)I/O OR NEW,

PER STATE

REPRESENTATIVE

KEY NOTES:

PROVIDE NEW DUPLEX RECEPTACLE NEAR EXISTING. LABEL EACH

RECEPTACLE SAME AS EXISTING. PROVIDE WHILE IN USE COVER.

CURRENT SWITCH VERTIS H300 OR EQUAL.

REFER TO MECHANICAL DRAWINGS FOR LOCATION.

CAPACITORS, AS REQUIRED, NOT SHOWN. COORDINATE WITH VFD

SUPPLIER.

ANALOG

OUTPUT

SH

TS3

DIGITAL

INPUT

TS4

DIGITAL

OUTPUT

RELAY

TS4

NAOCL

PUMP 2

SPEED

NAOCL

PUMP 2

RUNNING

NAOCL

PUMP 2

CALL

#16 TWSP

#16 TWSP

#12 AWG

#12 AWG

NAOCL

PUMP 2

(SPEED

COMMAND)

(E)120V IN J-BOX

(AUTO) H

(HAND) H

N

HAND

AUTO

SPLICE

SPLICE

H N

ON SHELF NEXT

TO (E)NAOCL PUMP

(E)J-BOX

BELOW PCP,

MODIFY AS

SHOWN

CORD GRIP

FITTING

X1515

R

ES

ER

VO

IR

W

AT

ER

T R

EA

TM

EN

T

PL

AN

T U

PG

R

AD

E

H

EA

R

ST

S

AN

S

IM

EO

N

S

TA

TE

H

IS

TO

R

IC

M O

N U

M

EN

T R

ES

ER

VO

IR

W

AT

ER

T

R

EA

TM

EN

T

PL

AN

T

U

PG

R

AD

E H

EA

R

ST

S

AN

S

IM

EO

N S

TA

TE

H

IS

TO

R

IC

M

O N

U M

EN

T

8691.011

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

8/14/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

02-0001-G-01-TITLE SHEET
02-0002-G-02-GENERAL NOTES
02-0003-G-03-GENERAL SYMBOLS
02-0004-G-04-SITE PLAN
02-0005-GM01-MECHANICAL DETAILS
02-0006-M-01-TREATMENT BUILDING IMPROVEMENTS
02-0007-M-02-FILTER SYTEM DETAILS
02-0008-S-01-STRUCTURAL NOTES AND DETAILS
02-0009-GE-01-SYMBOLS AND ABBREVIATIONS
02-0010-GE-02-EXISTING EQUIPMENT 1
02-0011-GE-03-EXISTING EQUIPMENT 2
02-0012-E-01-SINGLE LINE AND PANELBOARD SCHEDULES
02-0013-E-02-TREATMENT BUILDING POWER AND CONTROL PLAN
02-0014-E-03-TREATMENT BUILDING SECTION AND DETAILS
02-0015-E-04-INTERCONNECTION DIAGRAMS

File details come from the government source that posted it. Updated .