Drawings Attachment Y.pdf
PDF 3 MB Posted
- Attached to
- MDOT MVA Easton Replacement of Fire Alarm System
- Solicitation number
- BPM035579
- Issued by
- Talbot County, Elkridge CDP, Maryland
About this file
This document contains drawings and specifications for the replacement of the fire alarm system at the Maryland Department of Transportation Motor Vehicle Administration (MDOT MVA) Easton Branch Office in Easton, Maryland. The project involves the complete removal of the existing fire alarm system and installation of a new system including a new fire alarm control panel, notification appliance circuit panel, communicator, graphic annunciator panel, and related components. The drawings provide details on the system layout, equipment locations, demolition work, and new installation. The project is solicited through Solicitation No. VEAS23045C, with a 100% bid set dated October 21, 2022.
The new fire alarm system must comply with the latest NFPA 72 requirements and any additional requirements from the local fire marshal. Pricing, funding sources, and any set-asides are not provided in the drawings. The contract term and any renewal options are also not specified.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MDOT MVA V-EAS-23046-C_Amendment No.2.pdf | ||
| Prevailing Wage Attachment P.pdf | ||
| Technical Specification - Attachment X.pdf | ||
| MDOT MVA V-EAS-23046-C_Amendment No.1.pdf | ||
| Attachment B-1 BID FORM.xlsx | XLSX spreadsheet | |
| MVA Easton Fire Alarm Replacement IFB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
B
A
MVA
9148 CENTREVILLE ROAD
EASTON, MD 21601
QUEEN ANNE'S COUNTY
SOLICITATION NO.: VES23046C
COST CLASSIFICATION: D
VICINITY MAP LOCATION MAP
@) __,.SITE/ ' Paner Bread
Lowe's Home A Improvement Y ch:ck-fil-A 8 Amish Country T Farmer's Marke ft labor Licensing �& Re§ulat1on
Talbot Clerk of ft Circuit Court T ft United St tes
Easton Pub T Postal S rvice
- ��@George's Green� Thumb Garden Y
Eastern Shore Nurseries f
Glem
I
ER H,
Metal Wo
�orks Departme _
Wawa "
I @I
Saints Peter andO Paul Eleme tary and Y q Easton Auto Care, LLC l)(loer Rd
Q Ma�olia Manor � -...,,,.. - Q ���t.Pn -���matology I
PROJECT LOCATION --
E-Kole Photographyft Tem�oranlyclosed T N
EB
SITE
:astern Shore :essing and ...
APG Media of ft Chesapeake T
Grand Rental station Easton, MD
9 @) Harper and Sons � General Contractors ��
:ubu,ba, P,opa,e
Du,all Bmthe, "9 � ��•ge St Parkway Storage, N c_
PROJECT LOCATION --
I
N
EB
100% BID SET
CODES:
IEBC 2018 - LEVEL 1
NO CHANGE IN FLOOR PLAN AND EGRESS,
SECTION 707 ENERGY CONSERVATION - NOT
APPLICABLE "
SYMBOLS
NORTH DIRECTION
DRAWING LIST
CS100 COVER SHEET
ARCHITECTURAL
A101 FIRST FLOOR PLAN
FIRE ALARM
F001 FIRE ALARM LEGEND AND ABBREVIATIONS
F002 FIRE ALARM GENERAL NOTES
F101 FIRE ALARM PLAN - DEMOLITION
F102 ELECTRICAL FIRE ALARM PLAN - NEW WORK
F501 FIRE ALARM ANNUNCIATOR AND DETAILS
F601 FIRE ALARM RISER AND SCHEDULES
PRIME
BRUDIS-ATI JT. VENTURE
AE I DESIGN I MANAGEMENT
BAI ''"''''-=,..,..,,.,,.
'""""'"E•-•
11000 Broken Land Parkway
Suite 450
Columbia, Maryland 21044
Telephone: 410 B84 3607 www.brudis.com
COL I MO R E
ARCHITECTS
1501 S Clinton Street, 13Th Floor
Baltimore, Maryland 21224.
Telephone: 41 O 752 3720 coli more.com
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 16057
EXPIRATION DATE: FEBRUARY 23, 2□24
SEAL
\ '· 1 I ' II I/ I/
, ..,_'l'.-.:.,os·1 s··:'1'�_,.;,., I ��,)�_-_ ...
/· .. ..,., __ •"J:r-: -� r. �<c,, -:. "�"'.;,, -�-.t-..,-'�_,-�,.... � t't�-. J�l ·;, :\'� . ;_
';'.Ii"� l"--,:,,_1. "I , :;;
" \ q "'Ml'""'/j : C
;� ,ft!!"t>·/0
. -.i_�jl-�1 .. -:...., , tr Cfil ,,-£ C(,'' ",,,. I I 11 c"c" JOHNSON & MALHOTRA, P"C"
400 East Pratt St., Suite 604
Baltimore, Maryland 21202"
Telephone: 410 461 9920
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE Of MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: JUNE 18, 2023
SEAL
\,,,,011111,,,,� ':.-.❖' of MA" t,,t: '
·wr �..., •· e1-11 ��. g ,_"t;.-�� . . � � ,: "': �
�l: = -:::.o• , '%l&·•.'!!�/ o��-.:.
.,..t,,1/1ONA\. �,,� 'lt1111111 n\\\\, These drawings are the property of BAI-ATI JT. VENTIJRE.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Viole.tore will be subject to proae(:uijon by tlla fullast extent of1he IBW.
DESIGN PHASE SUBMISSION ANO DATE:
100% BID SET
OCTOBER 21, 2022
MOTOR VEHICLE ADMINISTRATION
APP ROVAL
TITLE DATE
TITLE DATE
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADM INISTRATION
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON, M ARYLAND
SOLICITATION NO" VEAS23045C
REVISIONS
MARK CATE OESCRIPTION
DRAWN BY: BP/CM
CH ECKEO BY: AB
Sheet Title
COVER SHEET
DRAWING NO.
CS100
SHEET 1 OF 8
CCJM
F-001
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
110110
ABBREVIATIONS
ABBREV ABBREV DESCRIPTIONDESCRIPTION
DRAWINGS.
NOT ALL SYMBOLS INDICATED ARE USED ON THESE CONTRACT
LEGEND AND ABBREVIATIONS
FIRE ALARM & MASS NOTIFICATION
HORN - WALL MTD (OR "C"-CEILING)
STROBE - WALL MTD (OR "C"-CEILING)
COMBINATION HORN WITH STROBE - WALL MTD (OR "C"-CEILING)
MANUAL PULL STATION - DUAL ACTION TYPE
STROBE, MARKED "ALERT", AMBER LENS - MASS NOTIFICATION
SIGNALING ONLY - WALL MTD (OR "C"-CEILING)
THE NUMBER ADJACENT TO THE SYMBOL INDICATES PREFERRED
CANDELA VALUE. STROBE SYMBOL WITHOUT IDENTIFICATION SHALL
BE AS FOLLOWS:
CORRIDORS/HALLWAYS - 30 CANDELA
ROOMS <= 2,000 SQFT - 75 CANDELA
ROOMS > 2,000 SQFT - 110 CANDELA
USB UNIVERSAL SERIAL BUS
PH, ɸ
DVR DIGITAL VIDEO RECORDER
AS/AF AMPERES SWITCH & FUSE RATING
WW
VARIABLE FREQUENCY DRIVEVFD
GROUND FAULT CURRENT INTERRUPTER
HIGH INTENSIFY DISCHARGE
ENCLOSED CIRCUIT BREAKER
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM AND DETECTION SYSTEM
FULL VOLTAGE NON REVERSING
ELECTRICAL METALLIC TUBING
ELECTRIC BASEBOARD HEATER
CLOSED CIRCUIT TELEVISION
CONTROL POWER TRANSFORMER
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TEMPERATURE CONTROL
AUTOMATIC TRANSFER SWITCH
HC HANDICAP
NATIONAL ELECTRICAL CODE
NOT-IN-CONTRACT
MAIN DISTRIBUTION PANEL
MOUNTING
MAIN LUGS ONLY
NEUTRAL
MOUNTED
NIC
NEC
MLO
MTG
N
MDP
MTD
HAND-OFF-AUTOMATIC
HIGH PRESSURE SODIUM
HORSE POWER
HIGH VOLTAGE
HEATER
HEAVY DUTY
HTR
HV
HOA
HPS
HP
HID
HD
CL CURRENT LIMITING
GALVANIZED RIGID STEEL
GROUND WIRE
GROUND
FLUORESCENT
FUSED SAFETY SWITCH
FOOT OR FEET
FEEDER
GFCI
GRS
GW
GND
FSS
FVNR
FT
FLUOR
FDR
EXHAUST
FURNISHED BY OTHERS
FUSED OR FUSIBLE
FRAME AMPERE
EXISTING-TO-REMAIN
EXISTING
FADS
FBO
FACP
FAAP
FA
EXH
EX
F
ETR
DWG DRAWING
ELECTRIC GENERATOR SET
EQUIPMENT
EXISTING RELOCATED
EXHAUST FAN
ELECTRIC HEATER
ELECTRICAL
ENCLOSURE
EMERGENCY
EMPTY CONDUIT
EQUIP
ER
ENCL
EH
ELECT
EMT
EC
ECB
EGS
EF
EBH
E
CURRENT TRANSFORMER
DIESEL GENERATOR SET
DISTRIBUTION
DISTRIBUTION PANEL
CABINET UNIT HEATER
COOL WHITE
DIAMETER
DISCONNECT
CEILING
DGS
DIST
DN
DP
DIA
DISC
DOWN
CT
CUH
CW
CPT
CLG
A, AMP
AUX AUXILIARY
BLDG ELECTRICAL SYSTEM
CIRCUIT BREAKER
CARD READER
CIRCUIT
BASIC IMPLUSE LEVEL
BACKBOARD
BREAKER
CONDUIT
BUILDING
AMERICAN WIRE GAUGE
BRKR
CCTV
CKT
CR
CB
C
BIL
BKBD
BLDG
BES
AWG
ALTERNATING CURRENT, ARMORED CABLE
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE FRAME
AMPERES
AIC
ATC
ATS
AFG
AHU
AFF
ACU
AF
AC
SOLID NEUTRALS/N
VOLT (S) OR VOLTAGE
WEATHER PROOF, WORK PHONE
TRANSFORMER
VOLT AMPERE
WIREWAY
@ AT
XFMR
W/
WP
W WIRE
WITH
V
VA
UON
UOI
TERMINAL BOX
UNDER COUNTER
UNDERGROUND
TIME CLOCK
TIME DELAY
TYPICAL
TELEVISION
SWITCHBOARD
SWITCHGEAR
SYMMETRICAL
TRIP AMPERE
SHUNT TRIP
SUB STATION
STARTER
SMOKE DETECTOR
SECONDARY
SYSTEMSYS
UG
UC
TV
TTB
TTC
TYP
TA
TB
TC
TD
SOPN
SYM
ST
SW
SWBD
SWGR
SS
STR
SWITCH
SFA
SMR
SEC
SD
POLYVINYL CHLORIDE
RETURN AIR FAN
ROOT MEAN SQUARE
REDUCED VOLTAGE AUTOTRANSFORMER
RAPID START
REMOVE
RECEPTACLE
REQUIRED
POLE OR POLES
POWER FACTOR
NORMALLY OPEN
OVERLOAD
PANELBOARD
NIGHT LIGHT
NOT TO SCALE
ON CENTER
RECEPT
REQD
RS
RVAT
RMS
RGS
R
RAF
PVC
PNL
PF
VT
OL
P
PHASE
NFSS
OC
NTS
NL
NO
UNLESS OTHERWISE INDICATED
UNLESS OTHERWISE NOTED
TELEPHONE TERMINAL BOARD/BLOCK
TELEPHONE TERMINAL CLOSET
SPRINKLER FLOW ALARM
SURFACE METAL RACEWAY
SPACE OR POLE NUMBER
RIGID GALVANIZED STEEL
NON FUSED SAFETY SWITCH
POTENTIAL TRANSFORMER
CEC CHICAGO ELECTRICAL CODE
MOUNTING HEIGHTS
NOTE: UNLESS OTHERWISE INDICATED, STANDARD MOUNTING HEIGHTS FOR OUTLET BOXES FOR
THE FOLLOWING EQUIPMENT/DEVICE SHALL BE ABOVE FINISHED FLOOR AND SHALL BE TO THE
CENTER LINE OF EQUIPMENT & FIELD COORDINATED.
EQUIPMENT/DEVICE MOUNTING HEIGHT
SWITCHES
RECEPTACLE-GENERAL
RECEPTACLE-SPECIAL
RECEPTACLE-SINGLE
RECEPTACLE-REST ROOM
RECEPTACLE-COUNTER
RECEPTACLE- MONITOR (DISPLAY)
RECEPTACLE-EXTERIOR
CABLE TV OUTLET
TELEPHONE/DATA-GENERAL
TELEPHONE-WALL TYPE
FIRE ALARM PULL STATION
FIRE ALARM AUDIO/VISUAL DEVICE
CARD READER
EXIT LIGHT WALL MOUNTED
SAFETY SWITCH
PANELBOARD
MANUAL MOTOR STARTER
PUSH BUTTON
AUTOMATIC DOOR OPENER
48 INCH
18 INCH
18 INCH
18 INCH
9 INCH ABOVE BASIN
8 INCH ABOVE COUNTER
78 INCH OR DIRECTED BY OWNER
30 INCH
78 INCH, 18 INCH FOR APARTMENTS, UON
18 INCH
54 INCH, (48 INCH ADA ACCESSIBLE)
48 INCH
80 INCH
40 INCH
MAX. 90 INCH
72 INCH TO HANDLE
72 INCH TO TOP CB
48 INCH
48 INCH
36 INCH
APARTMENT UNITS
TELEPHONE/DATA, KITCHEN ONLY
REFRIGERATOR RECEPTACLE
WASHER/DRYER RECEPTACLE
48 INCH
48 INCH
36 INCH
FIRE ALARM SYSTEM HEAT DETECTOR
FIRE ALARM SYSTEM SMOKE DETECTOR
SPEAKER
ADDRESSABLE FIRE ALARM CONTROL PANEL, WITH BATTERY
FIRE ALARM GRAPHIC ANNICIATOR PANEL WITH LED TROUBLE LIGHT
NOTIFICATIONS
FIRE ALARM COMMUNICATOR PANEL
NOTIFICATION APPLIANCE CIRCUIT BOOSTER/EXTENDER PANEL
SECURITY CONTROL PANEL
FIRE ALARM REMOTE TEST SWITCH
PANELBOARD - SURFACE MTD
PANELBOARD - RECESSED
JUNCTION BOX FOR SYSTEM FURNITURE DATA - 18" AFF
POWER DISTRIBUTION
D
JUNCTION BOX
CIRCUIT BREAKER
MOTOR CONNECTION
SAFETY SWITCH NONFUSED, SIZE AS INDICATED
ELECTRICAL DEVICE AS INDICATED
COMBINATION TYPE MOTOR STARTER, SIZE AS INDICATED
SAFETY SWITCH FUSED, SIZE AS INDICATED
480 VOLT PANELBOARD
208 VOLT PANELBOARD
CONDUIT, CONCEALED IN CEILING OR WALL OR CHASE
SYSTEM GROUND OR EQUIPMENT GROUND
CONDUIT CONCEALED IN FLOOR OR UNDERFLOOR OR
UNDERGROUND
D
ANNOTATIONS
MEDIA CENTER
F
FIXTURE SCHEDULE
a
3 INDICATES CIRCUIT NUMBER
A INDICATES TYPE OF LIGHTING FIXTURE REFER TO
A a 3 , R-2,4
HOME RUN TO PANELBOARD
UNLESS OTHERWISE NOTED.
R INDICATES THE PANEL
DISTRIBUTION EQUIPMENT AS INDICATED.
2,4 NUMBERS INDICATE SOPN NUMBER FOR PANEL
ELECTRICAL GENERAL NOTE APPLY TO ALL DRAWINGS,EGN-x
CROSS HATCH LINES INDICATE THE NUMBER OF CURRENT
CARRYING CONDUCTORS CROSS HATCH LINES WITH DOT AT END
INDICATES THE EQUIPMENT GROUNDING CONDUCTOR (GREEN
WIRE) AND SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE 250.
GREEN GROUNDING WIRE SHALL BE PROVIDED WITH EACH CIRCUIT,
AND/OR FEEDER. WHERE NO WIRES ARE INDICATED, PROVIDE 2
(TWO) CURRENT CARRYING # 12 AWG CONDUCTORS AND 1 (ONE) #
12 GROUND FOR BRANCH CIRCUIT WIRING IN MINIMUM 3/4"
RACEWAY UNLESS OTHERWISE INDICATED IN THE SCHEDULES.
a a INDICATES SWITCH LEG OR CONTROL ZONE a INDICATES SWITCH LEG OR CONTROL ZONE
3 INDICATES CIRCUIT NUMBER
INDICATES SPECIAL / KEYED NOTE. UNLESS
OTHERWISE NOTED, SPECIAL / KEYED NOTE APPLIES
ONLY TO THE DRAWING ON WHICH IT APPEARS.
EXISTING (INDICATED WITH SLANTED TEXT)
XXXX XX
JJ
JJ
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM DUCT HEAT DETECTOR
CODES AND STANDARDS
2018 INTERNATIONAL BUILDING CODE WITH MARYLAND
2018 INTERNATIONAL EXISTING BUILDING CODE WITH MARYLAND AMENDMENTS
2018 INTERNATIONAL FIRE CODE WITH MARYLAND AMENDMENTS
2018 NFPA 1
2017 NFPA 70 (NEC)
2016 NFPA 101
AS PER LOCAL AUTHORITIES HAVING JURISDICTION (AHJ)
FIRE ALARM LEGEND AND
ABBREVIATIONS
AutoCAD SHX Text P
AutoCAD SHX Text
SP
AutoCAD SHX Text
FCP
AutoCAD SHX Text
NAC
AutoCAD SHX Text
BAT
AutoCAD SHX Text
COM
AutoCAD SHX Text
RTS
AutoCAD SHX Text
CTR
AutoCAD SHX Text C
AutoCAD SHX Text
FSA
AutoCAD SHX Text
EXISTING
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
CCJM
CCJM
F-002
FIRE ALARM GENERAL NOTES
FIRE ALARM SYSTEM GENERAL NOTES
GENERAL CONSTRUCTION NOTES GENERAL DEMOLITION NOTES
1. EXISTING ELECTRICAL SYSTEM IS DESCRIBED BASED ON SITE
CONDITIONS VISIBLE AT THE TIME OF THE SURVEY. THE CONTRACTOR
SHALL VISIT THE JOB SITE TO FAMILIARIZE HIM/HERSELF WITH THE
EXTENT OF EXISTING WORK TO BE DEMOLISHED
2. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT
AFFECTED BY THE DEMOLITION. COORDINATE EXACT SCOPE OF WORK
WITH ALL OTHER DISCIPLINE DRAWINGS
3. ALL EXPOSED CONDUITS, HANGERS, SUPPORTS, ETC. THAT ARE
ABANDONED SHALL BE REMOVED. CONDUIT WHICH IS BURIED IN
CONCRETE OR OTHERWISE INACCESSIBLY POSITIONED MAY BE
ABANDONED. IN SUCH CASES, WIRE SHALL BE PULLED OUT OF THE
CONDUIT AND THE CONDUIT ITSELF PLUGGED AT EACH END
4. WHERE EXISTING DEVICES, CONDUIT WIRE, SUPPORTS, HANGERS AND
OTHER ELECTRICAL EQUIPMENT MUST BE REMOVED AS A RESULT OF
THE ALTERATIONS, THEY SHALL BE COMPLETELY REMOVED, BACK TO
THE FIRST OUTLET WHICH IS LEFT UNAFFECTED. IF REMOVED BACK TO
THE PANEL, LABEL THAT CIRCUIT AS SPACE
5. PATCH ALL HOLES IN SLABS, WALLS AND CEILING WHERE ELECTRICAL
DEVICES AND/OR CONDUIT ARE REMOVED. IF THE REMOVAL OF
CONDUIT, BOXES, EQUIPMENT, ETC. COMPROMISES THE FIRE RATING OF
THESE ITEMS, THE CONTRACTOR SHALL SEAL OPENINGS WITH CODE
APPROVED FIRE STOPPING MATERIAL
6. WHERE EXISTING ELECTRICAL WORK PREVENTS PROPER
CONSTRUCTION OF NEW WORK, REMOVE, REROUTE, RELOCATE, OR IN
OTHER WAYS ALTER EXISTING WORK TO ACCOMMODATE
7. SOME EXCEPTIONS MAY ARISE WHEREIN EQUIPMENT, EITHER IN
ALTERED AREAS OR OTHER AREAS, MUST BE KEPT IN SERVICE,
REQUIRING THAT FEEDERS, SIGNAL CONDUCTORS, CONDUITS, BOXES
ETC. SERVING THE SAME ALSO BE KEPT IN SERVICE. IN SUCH CASES,
THE ELECTRICAL FEEDERS, SIGNAL CONDUCTORS, CONDUITS, ETC.
SHALL BE REROUTED AND RECONNECTED BEFORE PRESENT WORK IS
REMOVED. IF THIS IS NOT POSSIBLE, TEMPORARY WIRING SHALL BE
PROVIDED TO ALLOW FOR INSTALLATION OF NEW WORK, AFTER WHICH
TEMPORARY WIRING SHALL BE REMOVED
8. ALL PROPOSED DEMOLITION WORK SHALL BE THOROUGHLY
COORDINATED WITH ALL OTHER TRADES
9. CONTRACTOR IS TO PERFORM DEMOLITION WORK IN A NEAT, SKILLFUL,
AND CAREFUL MANNER SO AS NOT TO DAMAGE OR DEFACE EXISTING
CONSTRUCTION THAT IS TO REMAIN
10. CONFIRM WITH THE MANUFACTURERS OF EXISTING EQUIPMENT THAT IS
TO BE REVISED OR EXTENDED. ENSURE THAT EXISTING EQUIPMENT
COMPLIES WITH NEW WORK REQUIREMENTS
11. ELECTRICAL CONTRACTOR TO REROUTE, AND REFEED ALL EXISTING
EQUIPMENT/DEVICES TO REMAIN BUT MAY BE AFFECTED BY EQUIPMENT
BEING DEMOLISHED
12. EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN SERVICE UNTIL NEW
SYSTEM IS FULLY OPERATIONAL AND TESTED. PROVIDE PROPOSED
DEMOLITION AND INSTALLATION PLAN AS PART OF SUBMITTAL PACKAGE.
NEW FIRE ALARM SYSTEM SHALL BE INSTALLED IN PARALLEL WITH
EXISTING. EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED ONLY
WHEN NEW SYSTEM INSTALLED THROUGHOUT, OPERATIONAL, TESTED
AND APPROVED BY THE AHJ.
13. WHEN THE EXISTING FIRE ALARM SYSTEM IS OUT OF SERVICE FOR MORE
THAN 4 HOURS OR LESS AS APPROVED BY AHJ IN A 24-HOUR PERIOD,
THE AHJ SHALL BE NOTIFIED AND BUILDING SHALL BE EVACUATED OR AN
APPROVED FIRE WATCH SHALL BE PROVIDED BY THE CONTRACTOR
UNTIL THE EXISTING SYSTEM HAS BEEN RETURNED TO SERVICE, AND
DETERMINED ACCEPTABLE BY THE AHJ.
14. DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES, CONDUITS, AND
CIRCUITS SHALL PROCEED WITH CAUTION. CONTRACTOR SHALL BE
RESPONSIBLE FOR MAINTAINING ALL EXISTING-TO-REMAIN FIRE
PROTECTION CONDUIT, CIRCUITS, AND DEVICES IN OPERATIONAL
CONDITION. IN THE DAMAGE TO THE EXISTING FIRE ALARM SYSTEM OR
CIRCUITS, REPAIRS TO THE EXISTING FIRE ALARM SYSTEM SHALL BE
COMPLETED ON THE SAME DAY AS THE DAMAGE. REMOVE EXISTING FIRE
ALARM DEVICES SHOWN IN PROJECT AREA.
15. WHERE EXISTING WALL MOUNTED FIRE ALARM DEVICES ARE REMOVED,
PROVIDE AN OVER-SIZED METAL COVER PLATE TO COVER EXISTING
OPENING. COVER PLATE SHALL HAVE ROUNDED EDGES AND CORNERS
AND FINISH TO MATCH ADJACENT FINISHES/COLOR AS APPROVED BY
OWNER.
16. REPLACE ANY DAMAGED, DISCOLORED, OR DETERIORATING EXISTING
CEILING TILES TO MATCH EXISTING CEILING WHERE OLD FIRE ALARM
DEVICES ARE REMOVED OR WHERE NEW DEVICES ARE BEING
INSTALLED, TYPICAL OF ALL FIRE ALARM DEVICE LOCATIONs.
1. ALL DOCUMENTS AND PUBLICATIONS (SUCH AS, BUT NOT LIMITED TO,
MANUALS, HANDBOOKS, CODES, STANDARDS AND SPECIFICATIONS)
WHICH ARE CITED IN THIS CONTRACT OR THE SPECIFICATIONS
INCORPORATED HEREIN, FOR THE PURPOSE OF ESTABLISHING
REQUIREMENTS APPLICABLE TO EQUIPMENT, MATERIALS OR
WORKMANSHIP UNDER THIS CONTRACT SHALL BE DEEMED TO BE
INCORPORATED HEREIN AS FULLY AS IF PRINTED AND BOUND WITH THIS
CONTRACT. WHEREVER REFERENCE IS MADE TO ANY SUCH DOCUMENT,
THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS SET OUT IN
THE EDITION SPECIFIED IN THIS CONTRACT, OR IF NOT SPECIFIED, THE
LATEST EDITION OR REVISION THEREOF, AS WELL AS THE LATEST
AMENDMENT OR SUPPLEMENT OR SUPPLEMENT THERETO, EXCEPT AS
MODIFIED BY, OR OTHERWISE PROVIDED IN THE SPECIFICATIONS OR THIS
CONTRACT.
2. CONTRACTOR SHALL COORDINATE THE WORK WITH EXISTING FIELD
CONDITIONS & THE WORK OF OTHER TRADES. UNRESOLVABLE CONFLICTS
OR INTERFERENCES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION
OF THE ARCHITECT/ENGINEER AND OWNER.
3. ALL AUXILIARY ELECTRICAL COMPONENTS, OR CONTROL & POWER
WIRING, REQUIRED TO ENSURE THE FUNCTIONALITY OF THE ITEMS
SHOWN ON THE DRAWINGS SHALL BE PROVIDED, EVEN IF NOT
SPECIFICALLY SHOWN ON THE DRAWINGS. THIS INCLUDES SUCH ITEMS AS
LOW VOLTAGE CONTROL POWER AND WIRING TO REMOTE MOUNTED
INTERLOCK DEVICES. CONTRACTOR SHALL CONSULT ALL TRADES
FURNISHING EQUIPMENT & OBTAIN FROM THEM ALL DATA AND
INSTALLATION INSTRUCTIONS TO ENSURE THAT ALL ELECTRICAL
REQUIREMENTS ARE INCLUDED.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OF THE RACEWAY,
BOXES, PENETRATIONS, SUPPORTS AND OTHER COMPONENTS THAT ARE
REQUIRED TO COMPLETE THE WORK. ONLY MAJOR ITEMS ARE SHOWN ON
THE DRAWINGS. PROVIDE ALL WORK AS REQUIRED FOR A COMPLETE AND
FULLY FUNCTIONAL ELECTRICAL SYSTEM.
5. EQUIPMENT MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS
AND ALL LABELS AND WARNINGS AFFIXED TO THE INSTALLED EQUIPMENT
SHALL BE STRICTLY ADHERED TO.
6. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST
REQUIREMENTS OF ALL APPLICABLE CODES & REGULATIONS.
7. CONDUCTOR SIZING, BREAKER TRIP RATINGS AND FUSE SIZES FOR
MECHANICAL EQUIPMENT FEEDERS AS SHOWN ON THE DRAWINGS ARE
BASED ON PRELIMINARY DESIGN INFORMATION. CONTRACTOR SHALL
VERIFY THE PROPER SIZING AND RATINGS FROM THE FURNISHED
EQUIPMENT WRITTEN DATA OR EQUIPMENT NAMEPLATES PRIOR TO
ROUGH IN. IMMEDIATELY ADVISE THE ARCHITECT/ENGINEER AND OWNER
OF ANY DISCREPANCIES.
8. PROVIDE EQUIPMENT DISCONNECT SWITCHES IN STRICT COMPLIANCE
WITH CODE REQUIREMENTS. (NOT ALL LOCAL DISCONNECT SWITCHES
ARE SHOWN)
9. ALL OUTLET BOXES SHALL BE PROVIDED WITH PROPER COVER PLATES.
10. IN AREAS WHERE COUNTERS ARE PROVIDED, COORDINATE EXACT
LOCATION OF OUTLETS AND WIRING WITH CASEWORK.
11. CONDUITS SHALL BE CONCEALED IN WALLS AND CEILINGS TO THE
GREATEST EXTENT POSSIBLE. INTERIOR SURFACE METAL RACEWAY
(WIREMOLD OR EQUAL) MAY BE USED FOR LIGHTING FIXTURES OR WIRING
DEVICES LOCATED ON INACCESSIBLE BUILDING ELEMENTS, SUCH AS
CONCRETE CEILINGS OR MASONRY WALLS. SURFACE METAL RACEWAY
SHALL BE MOUNTED TIGHT TO WALLS OR CEILINGS. LOCATION AND
ROUTING SHALL BE APPROVED BY ARCHITECT AND OWNER. SEE
TECHNICAL SPECIFICATION FOR FURTHER INFORMATION.
12. ALL OUTDOOR RECEPTACLES SHALL BE W.P. AND THE GFI TYPE.
13. ALL OUTDOOR ENCLOSURES SHALL BE NEMA 3R. THE PADLOCKED TYPE
WITH TAMPER PROOF SCREWS.
14. THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS
NECESSARY FOR A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM.
15. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED,
CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED
IN SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS
AND RECOMMENDATIONS.
16. CONDUIT RUNS OR PULL BOXES SHALL NOT BLOCK OR PREVENT FULL
COMPLETE ACCESS AND/OR OPERATION OF HVAC EQUIPMENT, ACCESS
DOORS, PIPING VAULTS, JUNCTION BOXES MAIN RETURN AIR DUCTS, PULL
BOXES, CLEANOUTS, ETC.
17. VERIFY CLEARANCES FOR ALL NEW ELECTRICAL WORK BEFORE
PROCEEDING WITH CONSTRUCTION. COORDINATE USAGE OF AVAILABLE
SPACE WITH ALL TRADES. IN THE EVENT OF CONFLICTS, NOTIFY THE
ARCHITECT/ENGINEER AND OWNER BEFORE PROCEEDING WITH THE
WORK.
18. SEAL ALL NEW WALL AND FLOOR CONDUIT PENETRATIONS.
19. CIRCUITS ARE SIZED ASSUMING THAT NO MORE THAN THREE CURRENT
CARRYING CONDUCTORS ARE IN A SINGLE CONDUIT. FOR CONDUITS
CONTAINING MORE THAN THREE, PROVIDE APPROPRIATE DERATING OF
CONDUCTORS PER CODE.
20. NUMBERED CIRCUITS ARE CREATED FOR THE CONVENIENCE OF DESIGN
ONLY. DESIGN INTENT MUST BE FOLLOWED THROUGHOUT, INDICATE THE
CIRCUIT NUMBERS AND CORRESPONDING ROOM NUMBERS USED ON THE
"AS-BUILT" DRAWINGS. EMERGENCY PANEL CIRCUIT NUMBERS MAY VARY,
ACTUAL FIELD CONDITIONS SHALL BE VERIFIED.
21. NO WIRING SHALL BE INSTALLED PRIOR TO THE CONTRACTOR'S REVIEW
OF THE PROJECT EQUIPMENT SHOP DRAWINGS AND COORDINATION WITH
THE DESIGN DOCUMENTS. ANY DISCREPANCIES SHALL BE BROUGHT TO
THE ARCHITECT/ENGINEER AND OWNER ATTENTION FOR FINAL
RESOLUTION. WORK THAT HAS TO BE REPLACED DUE TO LACK OF
PROPER SHOP DRAWINGS COORDINATION SHALL BE DONE AT
CONTRACTORS EXPENSE.
22. ALL INCOMING POWER & LOW VOLTAGE CONDUCTORS SHALL RUN IN
CONCEALED CONDUIT. UTILIZE EXISTING CONDUIT WHERE POSSIBLE.
23. ALL EQUIPMENT INSTALLED IN MECHANICAL AIR PLENUM SPACE SHALL BE
RATED FOR THAT USE PER LOCAL REQUIREMENT.
26. FOR 15A OR 20A BRANCH CIRCUITS, PROVIDE WIRE SIZE AS SHOWN
BELOW BASED ON LENGTH OF CIRCUIT:
UP TO 50 FT USE #12
OVER 50 FT TO 135 FT USE #10
OVER 135 FT USE #8
27. NOTIFY ARCHITECT AND OWNER NO FEWER THAN SEVEN (7) DAYS IN
ADVANCE OF PROPOSED INTERRUPTION OF ELECTRICAL SERVICE. DO
NOT PROCEED WITH INTERRUPTION OF ELECTRICAL SERVICE WITHOUT
ARCHITECT'S AND OWNER WRITTEN PERMISSION.
28. SURFACE MOUNTED METAL RACEWAYS ONLY PERMISSIBLE ON EXISTING
WALLS, WHERE CONDUIT CANNOT BE CONCEALED, IN OCCUPIED, OR
NON-OCCUPIED SPACES, AND SHALL BE APPROVED BY THE ARCHITECT
AND OWNER.
29. ALL WORK TO BE COMPLETED DURING HOURS WHEN FACILITY IS CLOSED.
ALL WORK AREAS TO BE CLEARED OF ALL CONSTRUCTION EQUIPMENT
AND CLEANED AT THE END OF EACH WORK SESSION. COORDINATE
WORKING HOURS AND CLEANLINESS PROTOCOLS WITH OWNER AND
ARCHITECT.
A. ALL NEW WIRING AND RACEWAY SIZES AND THEIR QUANTITIES SHALL BE STRICTLY IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND AHJ FIRE MARSHAL
REQUIREMENTS. ALL WIRING SHALL BE INSTALLED IN RACEWAYS APPROVED BY AHJ WITH
MAXIMUM 40% FILL CAPACITY. PLENUM RATED FIRE ALARM WIRING OR MC CABLE IS NOT
PERMITTED.
B. FAS RISER DIAGRAM IS DIAGRAMMATIC. RUNS OF WIRING AND THE MANNER OF
CONNECTIONS SHALL BE DETERMINED BY THE CONTRACTOR IN THE FIELD. INSTALLATION
OF FAS SHALL MEET SYSTEM'S MANUFACTURER'S AND FIRE MARSHAL'S REQUIREMENTS.
C. CONTRACTOR SHALL BE RESPONSIBLE TO SUBMIT THE SHOP DRAWINGS TO AHJ AND
OBTAINING FIRE MARSHAL'S APPROVAL PRIOR TO ANY SUBMISSION TO ENGINEER OF
RECORD AND ANY INSTALLATION OF WORK.
D. FAS DEVICES AND EQUIPMENT SHOWN ON PLANS ARE FOR MINIMUM REQUIREMENTS.
ADDITIONAL DEVICES AND/OR EQUIPMENT SHALL BE PROVIDED WITHOUT ANY ADDITIONAL
COST TO THE OWNER TO MEET THE LATEST NFPA 72 REQUIREMENTS AND ANY OTHER FIRE
MARSHAL'S REQUIREMENTS.
E. ALL MANUAL PULL STATION SHALL BE LOCATED WITHIN 5 FEET OF THE EXIT DOORS. ALL
NEW MANUAL PULL STATIONS SHALL HAVE TWO PAIRS OF DRY CONTACTS.
F. ALL FAS VISUAL DEVICES SHALL BE MOUNTED AT A HEIGHT WHICH IS IN THE LINE OF SIGHT
AND MEET ADA REQUIREMENTS.
G. PROVIDE ALL WIRING AND RACEWAYS TO FIRE PROTECTION SYSTEM (SPRINKLER SYSTEM)
DEVICES SUCH AS FLOW SWITCHES, TAMPER SWITCHES ETC. AS PER NFPA AND AHJ
REQUIREMENTS. FIRE ALARM SYSTEM ZONES SHALL BE COORDINATED WITH FIRE
PROTECTION SYSTEM WHILE PREPARING THE SHOP DRAWINGS.
H. ALL NEW FIRE ALARM DEVICES FLUSH AND/OR SURFACE MOUNTED SHALL BE MOUNTED ON
A FIRE ALARM SYSTEM'S MANUFACTURER FURNISHED BACK BOXES. STANDARD BOX OR 4"
SQUARE BOX WILL NOT BE PERMITTED.
I. PROVIDE SHUT OFF SWITCHES FOR HVAC UNITS IN ACCORDANCE WITH NFPA 72
REQUIREMENTS BOTH AT ANNUNCIATOR PANEL AND CONTROL PANEL.
J. FOR ADDRESSABLE SYSTEM, WHICH INCLUDE SEPARATE SIGNALING LINE CIRCUITS (SLC)
AND NOTIFICATION APPLIANCE CIRCUITS (NAC) EACH CIRCUIT MUST BE LOCATED IN
SEPARATE CONDUITS TO AVOID CROSS TALK BETWEEN THE CIRCUITS. CABLE FOR NAC
MUST BE PROPERLY SHIELDED AND PROPERLY GROUNDED AND WIRING TERMINATIONS
MUST BE PROPERLY TAPED TO PREVENT SHIELDS FROM CONTACTING CIRCUITS AND OTHER
WIRING. PROVIDE AMPLIFIERS AND NAC ZONES AS NEEDED FOR THE AREAS.
FIRE ALARM SYSTEM (FAS) NOTES
A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING THE FAS SHOP DRAWINGS TO
THE FIRE MARSHALL AND OBTAINING PERMIT AND APPROVAL PRIOR TO FAS SYSTEM
SUBMISSION OF SHOP DRAWINGS TO THE ENGINEER. THE CONTRACTOR SHALL NOT
INSTALL ANY EQUIPMENT AND/OR DEVICE PRIOR TO WRITTEN APPROVAL FROM THE
ENGINEER AND AHJ.
B. SHOP DRAWINGS SHALL INCLUDE ALL BUILDING FLOOR PLANS INDICATING THE ZONES AND
THE LOCATIONS OF ALL FAS EQUIPMENT, DEVICES AND OTHER COMPONENTS SUCH AS
JUNCTION BOXES. SHOP DRAWINGS SHALL CLEARLY INDICATE THE CANDELA POWER AND
SOUND LEVEL WITH EACH DEVICE AND THEIR MOUNTING HEIGHT ON THE FLOOR PLANS.
CLEARLY INDICATE ALL LOCATIONS OF BOOSTER PANELS.
C. SUBMIT WIRING RISER DIAGRAM, PANEL WIRING DIAGRAM AND EACH DEVICE WIRING
DETAILS CLEARLY INDICATING THE NUMBER OF CONDUCTORS AND THE SIZE OF CONDUITS.
D. SHOP DRAWINGS SHALL CLEARLY INDICATE THE PHYSICAL DIMENSIONS OF EACH
EQUIPMENT AND/OR DEVICES.
E. SHOP DRAWINGS SHALL INCLUDE THE DETAILS OF GRAPHIC PANEL AND FIRE ALARM
ANNUNCIATION PANEL INDICATING THE FLOOR PLANS, EXITS, AND ALL INDICATING LIGHTS
AND CONTROLS ETC. IN ACCORDANCE WITH NFPA 72 AND AHU FIRE MARSHALL.
ANNUNCIATOR PANEL SHALL INCLUDE THE KEY SWITCH FOR GLOBALLY SHUTTING DOWN
ALL AHU'S IN THE FACILITY. COORDINATE WITH CONTROL CONTRACTOR. PROVIDE ALL
WIRING AS REQUIRED FOR COMPLETE WORKING SYSTEM.
F. SHOP DRAWING SHALL INCLUDE BATTERY CALCULATIONS IN ACCORDANCE WITH
SPECIFICATIONS. BATTERY CALCULATIONS SHALL INDICATE NUMBER OF EACH TYPE
DEVICES, CURRENT REQUIREMENTS AND THEIR LOCATIONS. PROVIDE CALCULATIONS FOR
48 HOURS OPERATION AT FULL LOAD.
G. SHOP DRAWINGS SHALL INCLUDE THE LIST OF SPARE PARTS. THE CONTRACTOR SHALL BE
RESPONSIBLE TO SUPPLY THESE SPARE PARTS TO THE OWNER AT THE COMPLETION OF
THE PROJECT.
H. SHOP DRAWINGS SHALL INCLUDE INSTALLATION, PROGRAMMING INSTRUCTIONS, AND
SEQUENCE OF OPERATION.
I. INCLUDE ROOM NUMBERS IN THE DEVICE ADDRESS PROGRAMMING.
J. PROVIDE CUSTOM LABELS FOR DUCT DETECTORS WHICH SHALL INCLUDE THE EQUIPMENT
TAG NUMBER, ROOM WHERE IT IS LOCATED, AND SUPPLY AND RETURN DUCT DESIGNATIONS.
PROVIDE REMOTE LED INDICATING LIGHT AND TEST SWITCH FOR ALL DUCT DETECTORS.
WHETHER SHOWN ON THE DRAWINGS OR NOT, THE CONTRACTOR SHALL BE RESPONSIBLE
TO PROVIDE REMOTE LED INDICATING LIGHTS, CUSTOM LABELS AND TEST STATIONS AT
ACCESSIBLE LOCATIONS FOR ALL DUCT SMOKE DETECTORS.
K. SUBMIT COMPLETED ABC INFORMATION DATA REQUEST FORMS TO OWNER FOR
IMPLEMENTATION ON WITH THE MONITORING COMPANY.
FIRE ALARM SYSTEM SUBMITTAL NOTES
GENERAL DRAWING NOTES (WHERE SHOWN ON PLANS)
NOTE # KEYED NOTE DESCRIPTION
G1
INFORMATION SHOWN ON DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROM AVAILABLE BUILDING DRAWING OR GENERAL FIELD OBSERVATION AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR THE INSTALLATION OF NEW FIRE ALARM EQUIPMENT, SHOULD CONDITION BE DISCOVERED THE PREVENTS WORK INDICATED FROM BEING DONE, THE CONTRACTOR IMMEDIATELY NOTIFY ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH NEW WORK.
G2 EXISTING FIRE ALARM SYSTEM SHALL BE ENTIRELY REMOVED INCLUDING ALL DEVICES, PANELS, PULL- BOXES, CONDUITS, AND
ASSOCIATED WIRING UNLESS OTHERWISE NOTED.
G3 EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN SERVICE UNTIL NEW SYSTEM IS FULLY OPERATIONAL AND TESTED. PROVIDE PROPOSED DEMOLITION AND INSTALLATION PLAN AS PART OF SUBMITTAL PACKAGE. THE NEW SYSTEM MAY BE SWITCHED OVER IN A
PHASED MANNER, OR COMPLETELY INSTALLED.
G4 COORDINATE WORK AND OUTAGES REQUIRED WITH THE OWNER PRIOR TO THE INSTALLATION OF NEW FIRE ALARM SYSTEM.
FIRE ALARM KEYED DEMOLITION NOTES (WHERE SHOWN ON PLANS)
NOTE # KEYED NOTE DESCRIPTION
D1 REMOVE ALL: EXISTING FIRE ALARM PANEL, PANEL WITH INTEGRAL BATTERIES, FIRE ALARM DIALER, BOOSTER POWER SUPPLY FOR FIRE ALARM DEVICES, FIRE ALARM PULL BOX, AND COMMUNICATION LINE TO PUNCH-DOWN BLOCK, FIRE ALARM AND PANEL AND BOOSTER FED EXISTING PANEL; REMOVE ASSOCIATED EXISTING POWER WIRING AND CONDUIT, AND EXISTING 20A BREAKER.
D2 REMOVE EXISTING EXTERIOR MOUNTED KNOX BOX; FIELD VERIFY AND REMOVE TAMPER NOTIFICATION CONNECTION TO FIRE ALARM
CONTROL PANEL.
D3 FIELD VERIFY EXISTING CONNECTIONS FROM FIRE ALARM TO SECURITY AND COMMUNICATION SYSTEM. REMOVE UN-USED FIRE
ALARM CONNECTIONS.
XX
ELEC.
GROUNDS
HEARING / MAB
TAGS
GENERAL OFFICE
STORAGE
MEN WOMEN
STORAGE
WOMEN
MEN
VEST.
INFORMATION CHIEF INVEST.
VEST.
ASST. MANAGER
MANAGERDEALER TITLE
SAFE
CHECK OUT
EX. SERVER
JAN
LUNCH
CORRIDOR
ENTRY
JAN.
CLASSROOM
SERVER
LOBBY
NEW LAW TEST ROOM
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
EX. PANEL AC2
EX. PANEL AC1
EX. PANEL R2
EX. PANEL R
EX. PANEL L
F-101
PROPOSED GROUND LEVEL FLOOR PLAN - FIRE ALARM - DEMOLITION
SCALE: 1/16"=1'-0"
1 00 8' 16'4'
SCALE: 1/8"=1'-0"
IF DRAWING IS REDUCED, USE
GRAPHIC SCALE
CCJM
CCJM
F-101
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
FIRE ALARM PLAN -
DEMOLITION
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
FSA
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
FCP
F1 F2
F3 F4
F6
F9
ELEC.
GROUNDS
HEARING / MAB
TAGS
GENERAL OFFICE
STORAGE
MEN WOMEN
STORAGE
WOMEN
MEN
VEST.
INFORMATION CHIEF INVEST.
VEST.
ASST. MANAGER
MANAGERDEALER TITLE
SAFE
CHECK OUT
EX. SERVER JAN
LUNCH
CORRIDOR
ENTRY
JAN.
CLASSROOM
SERVER
LOBBY
NEW LAW TEST ROOM
EX. PANEL AC2
EX. PANEL AC1
EX. PANEL R2
EX. PANEL R
EX. PANEL L
F14
F7
FIRE ALARM KEYED NEW WORK NOTES (WHERE SHOWN ON PLANS)
NOTE # KEYED NOTE DESCRIPTION
F1
PROVIDE NEW FIRE ALARM CONTROL PANEL WITH INTEGRAL BATTERIES, 2#16 TWISTED SHIELD PAIR OUT TO DEVICES FOR SLC LOOP. PROVIDE 2#14 AWG TWISTED PAIR TO FIRE ALARM COMMUNICATOR AS REQUIRED. PROVIDE 2#16 TWISTED/SHIELDED PAIR FOR DATA AND 2#14 24 V DC POWER CIRCUIT TO ANNUNCIATOR PANEL AS REQUIRED. CONFIRM AND PROVIDE ALL CONNECTION
QUANTITIES, TYPES, AND SI8ZES AS REQUIRED FOR THE PROVIDED FIRE ALARM SYSTEM.
F2 PROVIDE NEW FIRE ALARM COMMUNICATOR, AND CONNECTION TO NEW PUNCH DOWN BLOCK FOR POTS PHONE COMMUNICATIONS.
COMMUNICATIONS AND CONNECTIONS TO MVA HEADQUARTERS NETWORK BY OWNER IT GROUP.
F3 PROVIDE NEW FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT PANEL WITH SYNCHRONIZATION, PROVIDE SLC 2#16
TWISTED/SHIELDED PAIR OUT TO DEVICES.
F4 PROVIDE FIRE ALARM CONTROL AND RELAY MODULES IN QUANTITIES FOR INSTALLED DEVICES.
F5 REPLACE ANY DAMAGED, DISCOLORED, OR DETERIORATING EXISTING CEILING TILES TO MATCH EXISTING CEILING WHERE OLD FIRE ALARM DEVICES ARE REMOVED. OR WHERE NEW DEVICES ARE BEING INSTALLED, TYPICAL OF ALL FIRE ALARM DEVICE LOCATION.
F6 PROVIDE NEW GRAPHIC ANNUNCIATOR PANEL WITH LAMP DRIVER MODULE. ANNUNCIATOR PANEL SHALL DETAIL FLOOR PLAN WITH ALERTS FOR LED MATRIX FOR TROUBLE AND OTHER NOTIFICATION. SEE SHEET F- FOR MORE INFORMATION.
F7 PROVIDE NEW EXTERIOR KNOX BOX WITH TAMPER NOTIFICATION BACK TO FIRE ALARM SYSTEM. PROVIDE KEY TO TO NEW
ANNUCIATOR PANEL.
XX
F8 PROVIDE COMMUNICATION WIRING FROM FACP AS REQUIRED TO SECURITY/FIRE ALARM PANEL IN STOR/EQUIPMENT ROOM.
F9 PROVIDE NEW 1P-20A CIRCUIT BREAKER FOR FIRE ALARM SYSTEMS IN EXISTING PANEL R2, BREAKER SHALL BE RED, LOCKABLE IN "ON" POSITION, AND CLEARLY LABELED AS SERVING FIRE ALARM DEVICES. PROVIDE 2#12 + 1#12G IN 3/4" C FROM BREAKER FOR ALL
FIRE ALARM PANELS AT 120V.
F10 PROVIDE TWISTED/SHIELD PAIR FOR SLC LOOP OUT TO ALL NOTIFICATION DEVICES ON EACH LOOP. PROVIDE TWISTED PAIR LOOP OUT TO ALL HORN/STROBE DEVICES. SIZE WIRE AS PER DEVICE LOAD ON LOOP AND DISTANCES FOR LOOP AS ROUTED IN THE FIELD;
PROVIDE VOLTAGE DROP CALCULATION AS PART OF SUBMITTAL PACKAGE. TYPICAL OF ALL DEVICES.
F11 PROVIDE KEY-OPERATED REMOTE SHUT-DOWN FOR ALL ROOF-TOP UNITS AS PART OF ANNUNCIATOR PANEL BOARD. PROVIDE
CONNECTION FROM SHUT DOWN SWITCH TO EXISTING HVAC SHUT-OFF.
F12 PROVIDE REMOTE ALARM INDICATOR AND ROUTE THROUGH CEILING AND UP TO EXISTING ROOF-TOP UNIT, TYPICAL OF 2.
COORDINATED ROOFTOP FINAL MOUNTED LOCATION WITH MVA ARCHITECT PRIOR TO INSTALLATION. COORDINATE ROOFTOP
PENETRATIONS, LABEL "RIA" DEVICES WITH SERVING EQUIPMENT NAME AND LOCATION.
F13 PROVIDE REMOTE TEST SWITCHES WITH PILOT LIGHT AND KEYED CONTROL FOR DUCT SMOKE DETECTORS, TYPICAL OF 7. COMBINE
TEST SWITCHES AS RECOMMENDED BY MANUFACTURER.
F14 EXPLOSION PROOF SMOKE DETECTOR
F-102
PROPOSED GROUND LEVEL FLOOR PLAN - FIRE ALARM - NEW WORK
SCALE: 1/6"=1'-0"
1 00 8' 16'4'
SCALE: 1/8"=1'-0"
IF DRAWING IS REDUCED, USE
GRAPHIC SCALE
CCJM
CCJM
ELECTRICAL FRIE ALARM PLAN - NEW WORK
F-102
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
AutoCAD SHX Text
AutoCAD SHX Text
FCP
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FSA
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
NAC
AutoCAD SHX Text
BAT
AutoCAD SHX Text
COM
AutoCAD SHX Text
RTS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KB
AutoCAD SHX Text
SP
YOU ARE HERE
FACP
ANNUNCIATOR LEGEND ALARM SIGNALS
SUPERVISORY SIGNALSANNUNCIATOR LEGEND
FIRE ALARM GRAPHIC ANNUNCIATOR
SCALE: 1/8" = 1'-0"
4'0
MVA EASTON
9148 Centreville Rd, Easton, MD 21601
CCJM
CCJM
F-501
F-501
FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
NO SCALE
NOTE:
THE GRAPHIC ANNUNCIATOR PANEL SHALL NOT DISPLAY THE NAME OR CONTACT INFORMATION OF THE
MANUFACTURER/INSTALLER.
FIRE ALARM ANNUNCIATOR
AND DETAILS
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
F-501
ELECTRICAL ROOM - NEW FACP LOCATION
NO SCALE
EX. FIRE ALARM
CONTROL PANEL
PROPOSED
LOCATION FOR
NEW FIRE ALARM
CONTROL PANEL
AND AUXILIARY
DEVICES
AutoCAD SHX Text R
AutoCAD SHX Text
RED LED (ALARM)
AutoCAD SHX Text Y
AutoCAD SHX Text
YELLOW LED (SUPERVISORY)
AutoCAD SHX Text G
AutoCAD SHX Text
GREEN LED (NORMAL)
AutoCAD SHX Text
PUSH BUTTON
AutoCAD SHX Text
KEY SWITCH
AutoCAD SHX Text R
AutoCAD SHX Text
MANUAL PULL STATION
AutoCAD SHX Text R
AutoCAD SHX Text
SMOKE/HEAT DETECTOR
AutoCAD SHX Text R
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text R
AutoCAD SHX Text
FACP ROOM SMOKE DETECTOR
AutoCAD SHX Text G
AutoCAD SHX Text
BUILDING ON NORMAL UTILITY POWER
AutoCAD SHX Text Y
AutoCAD SHX Text
FIRE ALARM ON BATTERY POWER
AutoCAD SHX Text Y
AutoCAD SHX Text
SYSTEM TROUBLE
AutoCAD SHX Text
OFF
AutoCAD SHX Text
LAMP TEST
AutoCAD SHX Text
ACKNOWLEDGE
AutoCAD SHX Text
TROUBLE SILENCE
RESET
F-601
PRIME
MOTOR VEHICLE ADMINISTRATION
APPROVAL
MARK DATE DESCRIPTION
DRAWN BY:
CHECKED BY:
SHEET OF
A
B
C
TITLE DATE
DESIGN PHASE SUBMISSION AND DATE:
REVISIONS
TITLE DATE
MDOT MVA REPLACEMENT OF FIRE
ALARM SYSTEM
EASTON BRANCH
SOLICITATION NO. VEAS23045C
DRAWING NO.
MARYLAND DEPARTMENT OF TRANSPORTATION
MOTOR VEHICLE ADMINISTRATION
Sheet Title
100% BID SET
OCTOBER 21, 2022
SEAL
C.C. JOHNSON & MALHOTRA, P.C.
PROFESSIONAL CERTIFICATION:
I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM DULY LICENSED ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NUMBER: 44664
EXPIRATION DATE: 06-18-2023
COPYRIGHT 2022, C.C. JOHNSON & MALHOTRA, P.C.
These drawings are the property of C.C Johnson & Malhotra, P.C.
Unauthorized reproduction for any purpose is an infringement upon copyright laws. Violators will be subject to prosecution by the fullest extent of the law.
F-601
FIRE ALARM RISER DIAGRAM
NOT TO SCALE
FIRE ALARM
CONTROL PANEL
BATTERY
NAC/BOOSTER
PANEL
COMMUNICATOR
INTEGRATED
SECURITY FIRE ALARM
CONTROL PANEL
MM
FIRE ALARM
ANNUNCIATOR PANEL
MM
KNOX
BOX
MM
VESTIBULE
PROVIDE (2) TWO
PHONE LINES
ROOF
FIRST FLOOR
FIRE ALARM RISER DIAGRAM GENERAL NOTES
1. THIS DIAGRAM SHOWS SCHEMATIC DESIGN FOR FIRE ALARM SYSTEM ONLY: ADDITIONAL DEVICES
AND/OR EQUIPMENT SHALL BE PROVIDED WITHOUT ANY ADDITIONAL COST TO THE OWNER TO MEET THE LATEST NFPA 72 REQUIREMENTS AND ANY OTHER FIRE MARSHAL'S REQUIREMENTS. PROVIDE ALL ADDITIONAL DEVICES, EQUIPMENT, MODULES, AND ACCESSORIES, FOR A COMPLETE AND FULLY FUNCTIONING FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM, WHETHER SHOWN OR NOT.
2. ALL 120V WIRING FOR FIRE ALARM DEVICES SHALL BE RUN IN RED RACEWAY AND JUNCTION BOXES AND
IDENTIFIED AS FOR FIRE ALARM DEVICES.
3. FOR ALL AREAS, THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE PROPER SIZE FAS DEVICES AND TO DETERMINE THEIR LOCATIONS IN THE FIELD TO MEET THE NFPA 72 CANDELA POWER AND
SOUND LEVEL REQUIREMENTS.
4. FAS SHALL SEND AN OPEN SIGNAL (OVER DRY PAIR CONTACT) TO SECURITY SYSTEM (TO RELEASE ALL LOCKS ON THE EXTERIOR WALLS) UPON THE ACTIVATION OF ANY PULL STATION, SPRINKLER AND/OR
SMOKE DETECTOR.
5. SEE FIRE ALARM SYSTEM GENERAL NOTES AND FIRE ALARM SYSTEM SUBMITTAL NOTES FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
FIRE ALARM RISER AND
SCHEDULES
ELECTRICAL ROOM
AutoCAD SHX Text P
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
C
| 1912013.004 MVA Easton FAS Repl_BID SET Signed Drawings CCJM.pdf |
| 1912013.004_F-001_FIRE ALARM LEGEND AND ABBREVIATION-F-001 |
| Sheets and Views |
| F-001 |
| 1912013.004_F-002_FIRE ALARM GENERAL NOTES-F-002 |
| Sheets and Views |
| F-002 |
| 1912013.004_F-101__FIRE ALARM_DEMOLITON-F-101 |
| Sheets and Views |
| F-101 |
| 1912013.004_F-102__FIRE ALARM_NEW WORK-F-102 |
| Sheets and Views |
| F-102 |
| 1912013.004_F-501__ANNUNCIATOR-F-501 |
| Sheets and Views |
| F-501 |
| 1912013.004_F-601__FIRE ALARM_RISER AND DIAGRAMS-F-601 |
| Sheets and Views |
| F-601 |