This is a Drawings file supporting a roof replacement project at Hargett, College of Coastal Georgia in Georgia. The project involves comprehensive roofing system replacement for an existing building with approximately 15,255 square feet of roof area. The existing roofing system consists of a built-up roofing system over rigid insulation and lightweight concrete sloping. The building features one main roof with a smaller lower roof on the front facade and a rear addition matching the height of the main roof. The main roof and lower roof areas are ballasted, while the addition features a granulated top sheet without ballast.
The scope of work includes selective demolition, miscellaneous rough carpentry, installation of flashings and roof accessories such as curbs, roof drains, metal copings and caps, TPO roof systems, roof insulation, and sealants. The contractor is responsible for verifying all existing conditions and dimensions, as the information provided regarding the existing roofing system and building configuration is for courtesy reference only. The drawings file serves as a technical reference document to support bidders in preparing accurate proposals and understanding the project requirements for the roof replacement work.
Text of this file
A1.1
EXISTING ROOF PLAN
1/8" = 1'-0"
MAXIMUM
FRONT FACE
HEIGHT
(in.)
PERIMETER PRESSURE
(psf)
HORIZONTAL
METAL TYPE
CORNER PRESSURE
(psf)
VERTICAL HORIZONTAL VERTICAL
0.050" ALUMINUM
0.050" ALUMINUM
24 GA. STEEL
24 GA. STEEL
24 GA. STEEL
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.050" ALUMINUM 12 116 N/A N/A109
CLEAT
(ga.)
1. PRODUCT TO BE INSTALLED IN STRICT ACCORDANCE WITH
MANUFACTURER'S PRINTED INSTRUCTIONS.
2. PRE-DRILL WITH 3/16-IN. DRILL BIT FOR MASONRY CONDITIONS.
3. CONTACT/COORDINATE WITH MANUFACTURER FOR INSTALLATION
NEEDED TO MEET/EXCEED ANSI/SPRI/FM4435/ES-1 DESIGN CRITERIA.
REINFORCED TPO ROOFING
MEMBRANE
1-1/2-IN. SS RING SHANK NAILS,
PROVIDED @ 12-IN. O.C. FOR ALL
FACE SIZES
#14 x 1-1/2-IN. UNIVERSAL FASTENER, PROVIDED @ 12-IN. O.C. FOR FACE
SIZES > 9-IN
1-1/2-IN. SS RING SHANK NAILS,
PROVIDED @ 12-IN. O.C. FOR
FACES > 6-IN.
SPRING CLEAT FORMED IN 10-ft. LENGTHS CONCEALED SPLICE, 4-in. WIDE FASCIA CAP FORMED IN 10-ft. LENGTHS
BOTTOM OF NEW FASCIA SHALL
MATCH BOTTOM OF ORIGINAL FASCIA.
A1.1
FASCIA DETAIL
1/8" = 1'-0"
REVISIONS:
RA
M
SA
Y
SH
ER
RI
LL
A
RC
HI
TE
CT
S
Sa va nn ah
, G eo rg ia
9- A
Ea st
C ha rlt on
S tre et
2-
8-
CO
LL
EG
E
OF
C
OA
ST
AL
G
EO
RG
IA
BR
UN
SW
IC
K, G
EO
RG
IA
HA
RG
ET
T
BU
IL
DI
NG
R
OO
F
RE
PL
AC
EM
EN
T
ROOF PLAN
& DETAILS
A1.1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
1. VERIFY ALL EXISTING CONDITIONS PRIOR TO VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF CONSTRUCTION. 2. SEE SPECIFICATIONS FOR ADDITIONAL SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. 3. NOT ALL ROOF PENETRATIONS AND EQUIPMENT IS NOT ALL ROOF PENETRATIONS AND EQUIPMENT IS SHOWN.
AutoCAD SHX Text
GENERAL ROOFING NOTES
AutoCAD SHX Text
1. PERFORM A COMPLETE TEAR OFF. SEE PERFORM A COMPLETE TEAR OFF. SEE SPECIFICATIONS FOR ADDITIONAL INFORMAITON. 2. VERIFY CONDITION OF ROOF DECK AFTER ROOF VERIFY CONDITION OF ROOF DECK AFTER ROOF TEAR OFF AND PRIOR TO START OF ROOF SYSTEM INSTALLATION. DECK/SUBSTRATE SHALL BE DRY, SOUND, CLEAN, SMOOTH AND FREE OF DEPRESSIONS, WAVES AND PROJECTIONS. DO NOT BEGIN INSTALLATION OF ROOF SYSTEM UNTIL ROOF DECK/SUBSTRATE IS ACCEPTABLE.
AutoCAD SHX Text
ROOF PLAN NOTES
AutoCAD SHX Text
1. EXISTING ROOF DRAIN: REMOVE AND REPLACE. EXISTING ROOF DRAIN: REMOVE AND REPLACE. 2. EXISTING SKYLIGHT: REMOVE AND INFILL. EXISTING SKYLIGHT: REMOVE AND INFILL. 3. EXISTING SKYLIGHT CURB (CURB ONLY): REMOVE EXISTING SKYLIGHT CURB (CURB ONLY): REMOVE AND INFILL. 4. EXISTING HVAC ITEM: TO BE REMOVED. VERIFY EXISTING HVAC ITEM: TO BE REMOVED. VERIFY WITH OWNER PRIOR TO REMOVAL. 5. EXISTING SKYLIGHT: TO REMAIN. NEW FLASHING. EXISTING SKYLIGHT: TO REMAIN. NEW FLASHING. 6. EXISTING DOWNSPOUT FROM UPPER ROOF TO EXISTING DOWNSPOUT FROM UPPER ROOF TO LOWER ROOF. SEE SPECIFICATIONS FOR WORK. 7. IT ANTENNA. COORDINATE WITH CAMPUS IT FOR IT ANTENNA. COORDINATE WITH CAMPUS IT FOR TEMPORARY RELOCATION AND REINSTALLATION (BY CAMPUS IT).
AutoCAD SHX Text
ANSI/SPRI/FM4435/ES-1 TEST PRESSURES UP TO 117 PSF (HORIZONTAL)
AutoCAD SHX Text
COPYRIGHT AND REPRODUCTION NOTICE
AutoCAD SHX Text This drawing is the property of
AutoCAD SHX Text and must be returned upon request.
AutoCAD SHX Text or copied in whole or in part without written permission.
AutoCAD SHX Text It is not to be used on any other project
AutoCAD SHX Text Ramsay Sherrill Architects and may not be reproduced
AutoCAD SHX Text consult the Architect for further clarification.
AutoCAD SHX Text Do not scale drawings. Use dimensions given or
AutoCAD SHX Text
DRWN/CHKD:
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
PLOTTED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/2022
AutoCAD SHX Text 11/30/2021
AutoCAD SHX Text
SLS
AutoCAD SHX Text th
E N
N A
V I
A S
R Y
R
P WR
E
E NI G N
E
I R
GN
NI .C
A
AS
A V
N N
A G
H
9 4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXTENT OF LOW ROOF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AREA (SQ FT.)
AutoCAD SHX Text
ZONE 1 (PSF)
AutoCAD SHX Text
ROOF WIND UPLIFT SCHEDULE FOR STEPPED ROOFS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text WIND PRESSURE UPLIFT NOTES: 1. DESIGN WIND PRESSURES WERE CALCULATED IN ACCORDANCE WITH ASCE 7-16 DESIGN WIND PRESSURES WERE CALCULATED IN ACCORDANCE WITH ASCE 7-16 BASED ON AN EFFECTIVE WIND AREA AND WITH KD=0.85. 2. MULTIPLY DESIGN WIND PRESSURES BY A FACTOR OF 0.6 TO CONVERT TO MULTIPLY DESIGN WIND PRESSURES BY A FACTOR OF 0.6 TO CONVERT TO SERVICE LEVEL LOADS (ASD). 3. ROOF UPLIFT WIND PRESSURES IN ZONES 1, 2, AND 3 ARE GROSS UPLIFT ROOF UPLIFT WIND PRESSURES IN ZONES 1, 2, AND 3 ARE GROSS UPLIFT VALUES. NET UPLIFT PRESSURES SHALL BE CONSIDERED EQUAL TO GROSS PRESSURES. 4. IF A PARAPET EQUAL TO OR HIGHER THAN 3FT IS PROVIDED AROUND THE IF A PARAPET EQUAL TO OR HIGHER THAN 3FT IS PROVIDED AROUND THE PERIMETER OF THE ROOF, THE UPLIFT VALUES FOR ZONE 3 SHALL BE EQUAL TO THOSE FOR ZONE 2. 5. TABULATED WIND PRESSURES SHALL BE USED IN THE DESIGN OF EXTERIOR TABULATED WIND PRESSURES SHALL BE USED IN THE DESIGN OF EXTERIOR COMPONENT AND CLADDING MATERIALS. INTERPRETATION AND APPLICATION OF THESE PRESSURES TO SPECIFIC PORTIONS OF THE BUILDING AREAS SHALL BE THE RESPONSIBILITY OF THE EXTERIOR COMPONENT AND CLADDING MATERIAL SUPPLIER.
AutoCAD SHX Text
48.4 psf
AutoCAD SHX Text
45.2 psf
AutoCAD SHX Text
41.0 psf
AutoCAD SHX Text
37.8 psf
AutoCAD SHX Text
ZONE 2 (PSF)
AutoCAD SHX Text
63.9 psf
AutoCAD SHX Text
59.8 psf
AutoCAD SHX Text
54.4 psf
AutoCAD SHX Text
50.2 psf
AutoCAD SHX Text
ZONE 3 (PSF)
AutoCAD SHX Text
87.1 psf
AutoCAD SHX Text
78.9 psf
AutoCAD SHX Text
68.0 psf
AutoCAD SHX Text
60.0 psf
AutoCAD SHX Text
SCALE
AutoCAD SHX Text RWP JOB No.
AutoCAD SHX Text DRAWING No.
AutoCAD SHX Text
ISSUE
AutoCAD SHX Text
SEAL & SIGNATURE
AutoCAD SHX Text
THIS IS A REPRODUCTION OF A
AutoCAD SHX Text
RWP DRAWING AND IS SUPPLIED
AutoCAD SHX Text
FOR USE ONLY FOR WORK AUTHORIZED
AutoCAD SHX Text
THIS REPRODUCTION SHALL NOT
AutoCAD SHX Text
BE DISCLOSED, USED OR REPRODUCED
AutoCAD SHX Text
EITHER WHOLLY OR IN PART EXCEPT
AutoCAD SHX Text
IN CONNECTION WITH SUCH USE, OR
AutoCAD SHX Text
WITH THE PRIOR WRITTEN CONSENT
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
THIS DRAWING MUST NOT BE USED
AutoCAD SHX Text
FOR CONSTRUCTION OR FABRICATION
AutoCAD SHX Text
UNTIL SIGNED AS CHECKED AND
AutoCAD SHX Text
ISSUED FOR CONSTRUCTION BY RWP.
AutoCAD SHX Text
OF RWP.
AutoCAD SHX Text
BY RWP.
AutoCAD SHX Text
INITIAL DRAWING DATE:
AutoCAD SHX Text
LAST DATE REV. :
AutoCAD SHX Text
RWP PROJECT ENGR:
AutoCAD SHX Text
CADD FILE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CLIENT PROJECT MANAGER:
AutoCAD SHX Text
RWP PROJECT MANAGER:
AutoCAD SHX Text
LAST REV. BY:
AutoCAD SHX Text
REFERENCE
AutoCAD SHX Text
DRAWINGS
AutoCAD SHX Text
ISSUE FOR:
AutoCAD SHX Text ISSUE No.
AutoCAD SHX Text ISSUE No.
AutoCAD SHX Text
ISSUE FOR:
AutoCAD SHX Text ISSUE No.
AutoCAD SHX Text
ISSUE FOR:
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text RWP Engineering, Inc.
AutoCAD SHX Text Industrial / Commercial / Utilities
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text 9100 White Bluff Rd., Suite 605 Savannah, GA 31406
AutoCAD SHX Text Phone: (912) 231-9212
AutoCAD SHX Text
ROOF WIND UPLIFT SCHEDULE AND CONSTRUCTION NOTES
AutoCAD SHX Text
RAMSAY SHERRILL ARCHITECTS
AutoCAD SHX Text
COLLEGE OF COASTAL GEORGIA - HARGETT ADMINISTRATION BUILDING
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
21RM02
AutoCAD SHX Text
AutoCAD SHX Text 10/25/21
AutoCAD SHX Text 10/25/21
AutoCAD SHX Text
FAM
AutoCAD SHX Text 21RM02-S01.dwg
AutoCAD SHX Text
JGP
AutoCAD SHX Text
21-RM02-S1.0
AutoCAD SHX Text
FAM
AutoCAD SHX Text
JGP
AutoCAD SHX Text
AutoCAD SHX Text
ISSUE FOR CONSTRUCTION
AutoCAD SHX Text 10/25/21
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
ISSUE FOR CONSTRUCTION
AutoCAD SHX Text 10/25/21
AutoCAD SHX Text 10/25/21
AutoCAD SHX Text CONSTRUCTION SPECIFICATIONS DESIGN CRITERIA DESIGN IS IN ACCORDANCE WITH 2018 INTERNATIONAL BUILDING CODE WITH 2020 GEORGIA STATE AMENDMENTS. WIND LOADS: ULTIMATE WIND SPEED = 130 MPH (3 SECOND GUST) NOMINAL WIND SPEED = 101 MPH (3 SECOND GUST) RISK CATEGORY: II EXPOSURE CATEGORY: B INTERNAL PRESSURE COEFFICIENT = +0.18/-0.18 COMPONENTS AND CLADDING PRESSURE = (SEE DIAGRAM)
AutoCAD SHX Text
JOB NORTH
AutoCAD SHX Text No. 024568 024568 024568 PROFESSIONAL
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text
EXISTING ROOF PLAN
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DRAWING SIZE =
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text 0'-0"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 16'-0"
AutoCAD SHX Text 24x36
| Sheets and Views |
| A1-1 |
Other files
| File | Type | Posted |
|---|---|---|
| Award Information | — | |
| Bid Results | — | |
| NIO | — | |
| Project Manual | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .