Drawings 18387.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ 171 190000000252 3
- Issued by
- Barry County, Michigan
About this file
This file contains construction drawings for a boiler replacement and HVAC system upgrade project for the State of Michigan at the Coldwater State Police Post located at 186 East Street, Coldwater, Michigan 49036. The project involves demolition of an existing heating steam system and its associated equipment, piping, and controls, to be replaced with a gas-fired heating boiler system. Additional work includes removal of a steam air handling unit and replacement with a grade-mounted gas-fired air handling unit with web-based controls, along with the addition of modulating air-side zone dampers for enhanced airflow and comfort control. The project requires upgrades to both the building's electrical service and natural gas service. The building has a gross area of 13,400 square feet and is governed by the 2015 Michigan Building Code and 2015 Michigan Electric Code standards. The construction documents are dated February 20, 2019, and are marked as 100% construction documents.
The project scope includes structural work involving new 4-inch concrete slabs with fiber reinforcement, new concrete bollards and guard rails, and slab edge details. Mechanical systems include installation of a natural gas-fired boiler (Model CM300, 300 MBH input), expansion tanks, circulation pumps with variable frequency drives, a water heater, unit heaters, a new air handling unit (AHU-1) with 8,000 CFM supply capacity, fan coils, damper controls, and complete hydronic piping systems. Electrical work encompasses new disconnect switches rated at 175 amperes for the air handling unit, circuit breaker modifications, new 20-ampere circuits for the boiler and water heater, wiring for damper controls, and duct smoke detectors. The natural gas service upgrade includes a new buried 2-inch main gas line with branch connections sized at various diameters (3/4 inch to 2 inches) for the boiler, water heater, and air handling unit. The work is detailed across multiple drawing sheets including structural plans, mechanical demolition and installation plans, piping schematics, electrical plans, and enlarged detail sections prepared by Byce & Associates, Inc., Engineers and Architects of Kalamazoo, Michigan.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Advertisement 18387.pdf | ||
| PreBid Sign In 18387.pdf | ||
| Specifications 18387.pdf | ||
| Addendum 1 18387.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S U
N U M
E P
L U
R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
R
A
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:3 :4
P
M
G
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
KEWEENAW
ONTONAGON
GOGEBIC
DICKINSON
MENOMINEE
ALGER
DELTA
HOUGHTON
IRON
BARAGA
MARQUETTE
SCHOOLCRAFT
MACKINAC
CHIPPEWA
LUCE
EMMET
PRESQUE ISLE
CHEBOYGAN
LEELANAU
ARENACGLADWINCLAREOSCEOLALAKEMASON
BENZIE
ANTRIM
CHARLEVOIX
ALPENAMONTMORENCY
MANISTEE
GRAND
WEXFORD
TRAVERSE
IOSCO
ALCONA
OGEMAW
OSCODA
MISSAUKEE
KALKASKA
OTSEGO
CRAWFORD
ROSCOMMON
LAPEER
BARRY
MECOSTANEWAYGO
KENT
OCEANA
MUSKEGON
OTTAWA
ALLEGAN
HURON
TUSCOLA
ST. CLAIR
MACOMB
SANILAC
GENESEE
OAKLAND
BAY
SAGINAW
SHIAWASSEE
LIVINGSTON
MIDLAND
GRATIOT
CLINTON
INGHAM
ISABELLA
MONTCALM
IONIA
EATON
BERRIEN
VAN BUREN
CASS
KALAMAZOO
ST. JOSEPH
WAYNE
MONROE
WASHTENAW
LENAWEE
CALHOUN
BRANCH HILLSDALE
JACKSON
MENOMINEE
EAGLE RIVER
HOUGHTON
ONTONAGON
IRONWOOD
L'ANSE
CRYSTAL FALLS
IRON RIVER
IRON MOUNTAIN
MARQUETTE
ESCANABA
MANISIQUE
MUNISING NEWBERRY SAULT STE. MARIE
ST. IGNACE
ALPENA
ROGERS CITY
CHEBOYGAN
BEULAH
LELAND
ATLANTA
GAYLORD
PETOSKEY
CHARLEVOIX
MANCELONA
KALKASKATRAVERSE CITY
LAKE CITY
MANISTEE
HARRISVILLE
MIO
GRAYLING
ROSCOMMON
WEST BRANCH TAWAS CITY
STANDISH
MOUNT CLEMENS
PORT HURON
BAY CITY
BAD AXE
SANDUSKY
CASS CITY
CARO
LAPEER
FLINT
SAGINAW
MIDLAND
MOUNT PLEASANT
CADILLAC
GLADWIN
HARRISON
CLARE
BALDWIN REED CITY
LUDINGTON
HART
NEWAYGO
WHITE CLOUD
BIG RAPIDS
OWOSSO
ITHACA
STANTON
HOWARD CITY
ALMA
ST. JOHNSIONIA
GRAND RAPIDS
MUSKEGON
GRAND HAVEN
DEARBORN
DETROIT
LIVONIA
WARREN
PONTIAC
HOWELL
LANSING
ANN ARBOR
MONROEADRIAN
JACKSON
HILLSDALE
ALBION
COLDWATERTHREE RIVERS
CHARLOTTE
HASTINGS
ALLEGAN
SOUTH HAVEN
PAW PAW
STURGIS
CASSOPOLIS
DOWAGIAC
HOLLAND
BATTLE CREEK
KALAMAZOO
NILES
ST. JOSEPH
DESCRIPTIONLOCATION MAP
MICHIGAN LOCATION MAP
OWNER:
BUILDING SITE ADDRESS:
BUILDING CODE:
GROSS BUILDING AREA:
PROJECT INFORMATION
2015 Michigan Electric Code
2014 NFPA
DRAWING LIST
Boiler Replacement for:
COLDWATER STATE POLICE POST
186 EAST STATE STREET - COLDWATER, MICHIGAN 49036
STATE OF MICHIGAN
186 EAST STATE STREET - COLDWATER, MICHIGAN 49036
13,400 SF
2015 Michigan Building Code
02/20/2019 - 100% CONSTRUCTION DOCUMENTS
Structural
S310 Slab Plan & Details
Mechanical
DM510 Mechanical Demoltion Plans
M001 Mechanical Schedules
M110 Natural Gas Site Plan
M410 First Floor Hydronic Plan
M510 First Floor Mechanical Plan
M700 Mechanical Enlarged Plans
M800 Mechanical Details
Electrical
DE110 Electrical Demolition Plan
E110 Electrical Plan
E500 Enlarged Electrical Plans
PROJECT LOCATION
HVAC REPLACEMENT AND UPGRADE FOR THE STATE OF MICHIGAN'S COLWATER MICHIGAN STATE POLICE STATION. PROJECT TO INCLUDE DEMOLITION OF EXISTING HEATING STEAM SYSTEM, ASSOCIATED EQUIPMENT, PIPING, AND CONTROLS, TO BE REPLACED WITH A GAS-FIRED HEATING BOILER SYSTEM. DEMOLITION OF STEAM AIR HANDLING UNIT, ASSOCIATED EQUIPMENT, PIPING, AND
CONTROLS, TO BE REPLACED WITH A GRADE MOUNTED GAS-FIRED AIR HANDLING UNIT AND WEB BASED CONTROLS. ADDITION OF MODULATING AIR-SIDE ZONE DAMPERS, FOR ENHANCED AIRFLOW AND COMFORT CONTROL. THIS PROJECT WILL REQUIRE
UPGRADES TO BOTH THE BUILDING'S ELECTRICAL SERVICE AND NATURAL GAS SERVICE.
S310
S310
NEW 4" CONC. SLAB WITH 3 LBS/CY
TUFF STRAND FIBERS &
THICKENED EDGE
REMOVE EXIST. CONC. BOLLARDS,
TYP. OF 6
EXIST. CONC. SLAB TO
REMAIN
NEW CONCRETE
BOLLARD, TYP.
EXIST. CONC. BOLLARD
TO REMAIN, PROVIDE
NEW PLASTIC SLEEVE
EXIST. CONC. FOUNDATION WALL
BELOW
CONCRETE STEP
S310
DUCTWORK, SEE MECH.
NEW GRADE MOUNTED
RTU, SEE MECH.
7'-5" V.I.F. 3'-11" V.I.F.
4' -7
V
.I.
F
'-2
V .I.
F
1'-0"
1'
-0
3'-9"
6' -8
6'
-8
1' -1
/4
±1'-0"
NEW GUARD RAIL
NEW GUARD RAIL
S310
'-0
'-6
V .I.
F
'-0
EXISTING WALL, TYP.
S310
EXIST. BOLLARD TO
REMAIN, PROVIDE NEW
PLASTIC SLEEVE
3'-6 3/4" V.I.F.
L2X2X1/4
'-0
NEW 4" CONC. SLAB WITH 3 LBS/CY
TUFF STRAND FIBERS &
THICKENED EDGE
GALV.
REMOVE EXIST. CONC. TOPPING AND EMBED. ANGLE 23'-11 1/2" V.I.F.
6"
EQ EQ EQ
PROVIDE
HANDRAIL @ STEP
'-0
/4
± 19'-11"
2' -6
CONCRETE FILLED
6" DIAMETER PIPE
20" DIAMETER CONCRETE
EXISTING PAVEMENT
'-6
'-0
PLASTIC SLEEVE
EXISTING PAVEMENT
3/4" CHAMFER, TYPICAL
1' -8
8"
(2) #4 CONTINUOUS
CONCRETE SLAB,
SEE SLAB PLAN
COMPACTED SUB-BASE, SUB-BASE
IS TO BE MDOT CLASS II SAND
'-0
RTU ON CURB, SEE MECH.
± 1'-0"
#4@24" O.C., EPOXY SET INTO EXIST.
CONC. WALL, COAT FREE END W/
BOND BREAKER
BROOM FINISH STEP
CONC. SLAB, SEE PLAN
4" 1'-0"
#3@16" O.C., EPOXY SET INTO
EXIST. CONC. SLAB & WALL
4"
4" 1'-0" 11"
7" M
A X
E Q
7" M
A X
E Q
EXIST. CONC. WALL
GALV. L2x2x1/4 CONT. W/ 3/8" DIA.
HEADED STUDS @ 16" O.C.
(2) #3 CONT.
EXIST. 5" STRUCTURAL SLAB
1' -0
V
.I.
F
.V .I.
F
5"
EXIST. CONC. TOPPING,
V.I.F. THICKNESS
(2) #3 CONT.
#3@16" O.C., EPOXY SET INTO
EXIST. WALL
1' -0
COMPACTED SUB-BASE, SUB-BASE
IS TO BE MDOT CLASS II SAND
#4 CONT.
8"
EXIST. PAVEMENT
1. VERIFY EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING
WORK.
2. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN
AN APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
3. COORDINATE DETAILS AND DIMENSIONS ON THE STRUCTURAL
DRAWINGS WITH RELATED REQUIREMENTS ON THE MECHANICAL AND
ELECTRICAL DRAWINGS.
4. VERIFY SIZE AND LOCATION OF MECHANICAL UNIT AND DUCTWORK
BEFORE LOCATING BOLLARDS AND GUARD RAIL.
5. PROVIDE PLASTIC SLEEVES FOR ALL NEW AND EXIST. TO REMAIN
BOLLARDS.
6. GUARD RAIL TO BE POWDER COATED HIGH VISIBLITY YELLOW.
7. NEW L2x2x1/4 EDGE ANGLE TO BE GALVANIZED.
8. FILL ALL HOLES THAT RESULT FROM BOLLARD DEMOLITION.
GENERAL:
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE
SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS, ACI 318 &
301.
2. CONCRETE PLACEMENT AND QUALITY: SPECIFIED IN PROJECT
SPECIFICATIONS.
3. REMOVE ALL DEBRIS FROM FORMS BEFORE POURING.
4. ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS,
BOLTS, ANCHORS, PIPES, SLEEVES, ETC., SHALL BE SECURELY
POSITIONED IN THE FORMS BEFORE PLACING.
5. ALL REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO
A.S.T.M. A-615 GRADE 60, U.N.O.
6. MINIMUM REBAR COVER FOR CONCRETE SHALL BE AS FOLLOWS:
• CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
• EXPOSED TO EARTH OR WEATHER: 2"
• NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: 2"
7. ALL CONCRETE SHALL BE OF NORMAL WEIGHT UNLESS NOTED
OTHERWISE.
8. ALL CONCRETE SHALL BE ROCK CONCRETE CONFORMING TO A.S.T.M.
C-33.
9. AGGREGATE: SIZE OF AGGREGATE SHALL CONFORM TO ASTM C33-03.
• 3/4" ASTM SIZE C67
• 1"ASTM SIZE C57
10. CEMENT SHALL BE TYPE I PORTLAND.
11. REINFORCEMENT MAY NOT BE WET SET IN CONCRETE POURS.
12. NO ADMIXTURES SHALL BE ADDED TO THE CONCRETE MIX WITHOUT
THE APPROVAL OF THE ENGINEER, UNLESS NOTED OTHERWISE.
13. PROVIDE A 3/4" INCH CHAMFER ON ALL EXPOSED CORNERS OF
CONCRETE, UNLESS NOTED OTHERWISE.
14. CONCRETE FINISHES:
• EXTERIOR SLABS - LIGHT BROOM FINISH
15. REINFORCING AND ANCHOR SETTING EPOXY SHALL BE HILTI HIT/HY-200
OR EQUIVALENT.
16. CONCRETE SHALL DEVELOP THE FOLLOWING COMPRESSIVE
STRENGTHS AT 28 DAYS:
• 3,5000 PSI
CONCRETE & REINFORCEMENT:
3'
-6
V .I.
F
'-9
'-9
EXIST. STRUCTURAL
SLAB, DO NOT DRILL
EXIST. CONC. TOPPING
P1-1/4STD PIPE GUARD
RAIL W. VERTS. @ 4'-0" O.C.
1/2"x6"x6" BASE PL. W/ (4)
STAINLESS STEEL 3/8" DIA. HILTI
KWIK-HUS, EMBED 2"
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/1
/2
:2 :5
P
M
S
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/4" = 1'-0"
SLAB PLAN
SCALE: 3/4" = 1'-0"S310
1 EXTERIOR BOLLARD DETAIL
SCALE: 3/4" = 1'-0"S310
3 SLAB EDGE DETAIL
SCALE: 1" = 1'-0"S310
4 CONCRETE STEP DETAIL
SCALE: 3/4" = 1'-0"S310
2 GUARD RAIL DETAIL
DM1
DM1
DM1
DM1
M700
DM3
DM3
DM3
DM1
HS2" HR1"
HS1"
HR1"
DM4
DM6
DM3
DM8
DM9
DM8 DM8
DM1. REMOVE ALL STEAM AND CONDENSATE PIPING WHEREVER
ACCESSIBLE. CAP AND ABANDON WHERE INACCESSIBLE.
DM2. REMOVE ALL STEAM AND CONDENSATE PIPING,
EQUIPMENT, AND ASSOCIATED ACCESSORIES.
DM3. EXISTING HYDRONIC LOOP AND COMPONENTS TO REMAIN.
DM4. REMOVE GRADE MOUNTED CHILLER, ASSOCIATED PIPING,
CONTORLS, AND ACCESSORIES. PATCH ALL HOLES AND
DAMAGE FROM DEMOLITION.
DM5. ALTERNATE BID: REMOVE EXISTING WATER HEATER,
ASSOCIATED PIPING, AND ACCESSORIES. DEMO CW TO
CONNECTION POINT. PATCH ALL HOLES AND DAMAGE
FROM DEMOLITION.
MECHANICAL DEMO KEYNOTES
DM6. REMOVE EXISITING STEAM FAN COIL ALONG WITH ALL
ASSOCIATED PIPING AND ACCESSORIES. PREPARE FOR
INSTALLATION OF NEW HYDRONIC HEATING / DX COOLING
FAN COIL. REMOVE EXISTING CONDENSING UNIT FROM
ROOF ALONG WITH ALL ASSOCIATED PIPING AND
ACCESSORIES. PATCH ALL HOLES AND DAMAGE FROM
DEMOLITION.
DM7. REMOVE AHU, ALL ASSOCIATED PIPING, CONTROLS, AND
ACCESSORIES. REMOVE EXISTING AHU HOUSEKEEPING
PAD. PATCH ALL HOLES AND DAMAGE FROM DEMOLITION.
DM8. CONTRACTOR TO FIELD VERIFY EXISTING DUCT SIZES.
REMOVE SUPPLY AND RETURN DUCTWORK UP TO NEW
CONNECTION POINTS. PATCH ALL HOLES AND DAMAGE
FROM DEMOLITION. PREPARE AREA FOR NEW DUCTWORK.
DM9. REMOVE EXISTING ROOFTOP CONDENSING UNIT ALONG
WITH ALL ASSOCIATED PIPING AND ACCESSORIES.
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
D M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/8" = 1'-0"
FIRST FLOOR MCHANICAL DEMOLITION PLAN
PLUMBING SYSTEM VENT
P/T
LEGEND:
DOMESTIC COLD WATER
SOFT COLD WATER
TEPID WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
SANITARY SEWER
STORM
COMPRESSED AIR
GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DIRECTION OF FLOW
CAP
DROP
DROP TEE IN-LINE
RISE
REDUCER
UNION
GATE VALVE
GLOBE VALVE
BALL VALVE
CHECK VALVE
CALIBRATED BALANCING VALVE
BUTTERFLY VALVE
PLUG VALVE, GAS COCK
PRESSURE REDUCING VALVE
RELIEF VALVE
STRAINER WITH FULL SIZE BLOWDOWN VALVE WITH
HOSE END AND CAP
COMBINATION PRESSURE AND TEMPERATURE TEST
PLUG WITH EXTENDED NECK AND CAP
MANUAL AIR VENT
PRESSURE GAUGE
THERMOMETER
THROUGH WALL SLEEVE
POINT OF NEW CONNECTION TO EXISTING
VOLUME CONTROL DAMPER IN DUCT
FIRE DAMPER IN HORIZONTAL DUCT
FIRE DAMPER IN VERTICAL DUCT
THERMOSTAT
SUPPLY AIR (SECTION)
RETURN / EXHAUST AIR(SECTION)
AIR FLOW DIRECTION
T
V
SAN
G
ST
SCW
TW
CA
RL
RS
MOTORIZED DAMPERM
SENSORS
V
DUCT TRANSITION
DRY COMPRESSED AIRDCA
ABBREVIATIONS:
AFF ABOVE FINISH FLOOR
ATR AIR TEMPERATURE RISE
BF BELOW FLOOR
BOD BOTTOM OF DUCT
BOS BOTTOM OF STEEL
BTUH BRITISH THERAM UNIT PER HOUR
BV BALANCE VALVE
CEF CEILING EXHAUST FAN
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CABINET HEATER
CO CLEAN OUT
CONC CONCRETE
CW DOMESTIC COLD WATER
DB DECIBELS, SOUND PRESSURE LEVEL
DN DOWN
EA EXHAUST AIR/ EACH
EAL EXHAUST/RELIEF AIR LOUVER
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
EXIST EXISITING
FD FLOOR DRAIN
FS FLOW SWITCH
GPM GALLONS PER MINUTE
HB HOSE BIB
HO HUB OUTLET
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR DOMEXTIC HOT WATER RETURN
LAV,L LAVATORY
LAT LEAVING AIR TEMPEATURE/LATENT HEAT
LDB LEAVING DRY BULB
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
MAT MIXED AIR TEMPERATURE
MBH 1000 BRITHISH THERMAL UNITS PER HOUR
MIN MINIMUM
MFG MANUFACTURER
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTSIDE AIR
OAL OUTISDE AIR LOUVER
OD OVERFLOW DRAIN
OF OVERFLOW
OFCI OWNER FURNISHED - CONTRACTOR INSTALLED
PD PRESSURE DROP
PT PRESSURE/TEMPERATURE PLUG
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
RH RELATIVE HUMIDITY/REHEAT
RPM REVOLUTIONS PER MINUTE
BFP BACKFLOW PREVENTER
S SINK
SA SUPPLY AIR
SAN SANITARY
SP STATIC PRESSURE
S.S. STAINLESS STEEL
ST STORM
TEMP TEMPERATURE
TOD TOP OF DUCT
TOS TOP OF STEEL
TSP TOTAL STATIC PRESSURE
V VENT
VTR VENT THROUGH ROOF
WC WATER CLOSET
WH WATER HEATER
WPD WATER PRESSURE DROP
WTW WALL TO WALL
2. ARRANGE AND PAY FOR ALL PERMITS AND
INSPECTIONS AS REQUIRED.
3. ALL WORK SHALL BE PERFORMED TO FACILITATE
EXPEDITIOUS PROGRESS ON THE WHOLE PROJECT.
COORDINATE WORK WITH OTHER TRADES TO MINIMIZE
AND RESOLVE POTENTIAL CONFLICTS.
4. COMPLETED SYSTEM SHALL BE TESTED, BALANCED,
AND GUARANTEED.
5. PROVIDE A GAS SHUTOFF VALVE AND DIRT LEG AT
EACH PIECE OF GAS FIRED EQUIPMENT.
6.THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE
CONTRACTOR SHALL PROVIDE FITTINGS, OFFSETS,
ETC.., AS NECESSARY TO PROPERLY COMPLETE THE
INSTALLATION OF THE SYSTEMS.
1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE
WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL
CODES, ORDINANCES, AND LAWS.
7. ALL PIPES PASSING THRU FINISHED WALLS,
PARTITIONS AND FLOORS SHALL BE FITTED WITH
ADJUSTABLE ESCUTCHEONS, AND APPROPRIATE
FIRE TOPPING WHERE REQUIRED.
9. IT IS NOT THE INTENT OF THESE PLANS TO
SHOW EVERY DETAIL OF CONSTRUCTION.
CONTRACTOR SHALL FURNISH AND INSTALL ALL
ITEMS NECESSARY FOR A COMPLETE CODE
COMPLYING MECHANICAL SYSTEM TO BE IN
PROPER WOKRING ORDER.
10. PROVIDE APPROPRIATE FIRE STOPPING
MATERIALS WHERE FIRE RATED ASSEMBLIES
ARE PENETRATED.
8.FURNISH AND INSTALL ALL VALVING FOR THE PROPER
SECTIONALIZING AND OPERATION OF THE PIPING
SYSTEM.
11. MATERIALS EXPOSED WITHIN A PLENUM SHALL
BE NONCOMUSTIBLE OR SHALL HAVE A FLAME
SPREAD INDEX OF NOT MORE THAN 25 AND A
SMOKE-DEVELOPED INDEX OF NOT MORE THAN
50 WHEN TESTED IN ACCORDANCE WITH ASTEM
E84. EXISTING AND NEW PVC PIPING WILL
REQUIRE 1/2 INCH MINERAL FIBER INSULATION
WITH VAPOR RETARDER FACING THAT MEETS
ASTM E84.
GENERAL NOTES:
TEMPERATURE WELL
CW
HW
HWR
EQUIPMENT LIST
AS-1 AIR SEPARATOR
MANUFACTURER: BELL & GOSSETT
MODEL: CRSN-2F
SYSTEM FLOW: 62 GPM
WORKING PRESSURE: 150 PSIG
CONNECTION SIZE: 2"Ø
ET-1 EXPANSION TANK
MANUFACTURER: BELL & GOSSETT
MODEL: D-40
VOLUME: 21.7 GALLONS
ACCEPTANCE: 11.3 GALLON
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
UNIT HEATERS
MARK MODEL OUTPUT (MBh) CFM GPM PD (IN W.G.)
MAX MOUNTING
HEIGHT (FT) HP RPM V/P REMARKS
UH-1 HSB/HC 47L 21.1 855 2.2 0.2 15 1/12 1,550 120/1 1
UH-2 HSB/HC 63L 37.9 1,170 4.0 0.4 17 1/12 1,550 120/1 1
UH-3 HSB/HC 86L 44.6 1,510 4.6 0.6 18 1/8 1,625 120/1 1
PUMPS
MARK MODEL GPM HEAD (FT) RPM IMPELLER DIA V/P REMARKS
P-1 e1510 1.25 AD-es 31 34 1,800 5.75 120/1 1, 2
P-2 NBF-18S 2.5 12 3,300 NBF-18S 120/1 1, 3
WATER HEATER
MARK MODEL SERVICE INPUT (MBH) CAPACITY (GAL) GPH RECOVERY REMARKS
WH-1 GCVT-40 NATURAL GAS 50 40 75 1, 2
BOILER SCHEDULE
MARK MODEL SERVICE INPUT (MBH) OUTPUT (MBH) FLOWRATE (GPM) VENT ("Ø) V/P REMARKS
B-1 CM300 NATURAL GAS 300 279 28 4 120/1 1
1. BASED ON "PATTERSON-KELLEY"
1. BASED ON "A.O. SMITH"
2. ALTERNATE BID
1. BASED ON "AAON"
2. PROVIDE CO SENSOR ON INTAKE
3. PROVIDE FAN VFD
4. PROVIDE DEHUMIDIFICATION
5. PROVIDE INSULATED HORIZONTAL ROOF CURB ADAPTOR FOR SUPPLY AND RETURN DUCTWORK. BASED ON 'THYCURB' MODEL TC-3.
1. BASED ON "BELL AND GOSSETT."
2. PROVIDE VFD
3. ALTERNATE BID
1. BASED ON "MODINE"
DAMPER SCHEDULE
MARK MODEL MAX CFM MIN CFM MAX PD (IN. W.G.) WIDTH x HEIGHT ACTUATOR MFR/MODEL REMARKS
D-1 VCD-23 5,500 1,100 0.1 20 x 20 BELIMO / TFB24-SR 1
D-2 VCD-23 1,000 200 0.1 10 x 10 BELIMO / TFB24-SR 1
D-3 VCD-23 1,500 300 0.1 12 x 12 BELIMO / TFB24-SR 1
1. BASED ON "GREENHECK"
EXHAUST FANS
MARK MODEL CFM ESP HP BHP RPM V/P REMARKS
EF-1 SQ-80-D 200 0.5 1/12 0.05 1550 120/1 1
1. BASED ON "GREENHECK"
AIR INLETS AND OUTLETS SCHEDULE
MARK MODEL DESCRIPTION REMARKS
E-1 S300FL SPIRAL, SURFACE MOUNTED, DOUBLE DEFLECTED, ALUMINUM, BAKED ON ENAMEL 1
E-2 350RL SINGLE DEFLECTION, SURFACE MOUNTED, STEEL, BAKED ON ENAMEL 1
S-1 PAS 24x48 4-WAY DIFFUSER, PERFORATED FACE, LAY-IN, STEEL, BAKED ON ENAMEL 1
1. BASED ON "TITUS"
FAN COIL SCHEDULE
MARK MODEL AIRFLOW CFM
HEATING COIL CONDENSING UNIT
V/P REMARKSCOIL MODEL SYSTEM TYPE MBH GPM EAT EWT LAT LWT SIZE L/W/H (IN) APD (IN WG) MARK MODEL SYSTEM TYPE MBH
FC-1 TAM9A0C42V41D 1,400 HC-1 BAYWACC11SC1AA HOT WATER 61 3 70 180 112 145 21 13/16 x 23 1/2 x 7 1/4 0.19 CU-1 4TTR4042L1 REFRIGERANT 42 208/1 1
1. BASED ON " TRANE"
AIR HANDLING UNIT SCHEDULE
MARK MODEL OA CFM
SUPPLY FAN NATURAL GAS HEATING DX COOLING COIL REHEAT
V/P REMARKSCFM RPM ESP HP BHP INPUT (MBH) OUTPUT MBh EAT (DB/WB) LAT (DB/WB) EER MBh SEN EAT (DB/WB) LAT (DB/WB) MBh LAT (DB/WB)
AHU-1 RN-25 2,000 8,000 1,760 1.2 10 5.46 540 432 46.3 / 46.2 96.2 / 65.8 11.6 307.2 233 80 / 65.6 52.5 / 52.2 151 70 / 59 208/3 1, 2, 3, 4, 5
NEW 1,600 CFH GAS METER
BURIED 2" NATURAL GAS LINE
NEW BURIED NATURAL GAS LINE TO ROAD
ROUTE MAIN AS HIGH AS POSSIBLE
1" G DN TO GENERATOR
3/4" G BRANCH FOR FUTURE USE
3/4" G BRANCH FOR FUTURE USE
DN TO WH-1
DN TO B-1
DN TO AHU-1
G1 1/2"
G3/4"
G1"
G1 1/2"
G2"
G1 1/2"
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/16" = 1'-0"
NATURAL GAS SITE PLAN
UH-1
EXISTING FIN TUBE (TYP.)
AHU-1
M700
HS2"
HR2"
EXISTING
CABINET HEATER
EXISITNG CABINET HEATER
HR3/4"
HS3/4"
HS3/4" HR3/4"
HC-1
FC-1
CU-1
M700
COND3/4"
REFRIGERANT SUPPLY/RETURN BUNDEL,
SIZE PER MANUFACTURER'S INSTRUCTIONS.
ROUTE ABOVE CEILING.
1. FIELD ARCHITECT TO VERIFY EXACT LOCATION OF AHU AND
BOLLARDS.
2. CONNECT NEW DIFFUSER TO EXISTING DUCTWORK REFER TO
DETAIL 6/M800.
3. DUCTWORK DIMENSIONS ARE APPROXIMATE. FIELD VERIFY
EXACT DIMENSIONS AND PROVIDE TRANSITIONS AS REQUIRED.
4. PROVIDE PVC PIPE ENCLOSURE FOR REFRIGERANT PIPING
DOWN EXTERIOR OF THE BUILDING. PAINT TO MATCH EXTERIOR
WALL.
5. REPAIR OR REPLACE ANY CEILING TILE DAMAGED DURING
CONSTRUCTION.
6. CAP AND ABANDON EXISTING STEAM AND CONDENSATE
ENTRANCE TO BUILDING.
MECHANICAL KEYNOTES
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
FIRST FLOOR HYDRONIC PIPING PLAN
M700
AHU-1
ROUTE THROUGH
EXISTING UPPER
WINDOW.
GAS METER
G2"
G3/4"
G3/4"
G1 1/2"
UH-1
EXISTING CABINET HEATER
EXISTING FIN TUBE (TYP.)
40"x22" RA 40"x22" SA
G1"
NG DN TO EMERGENCY GENERATOR
x 20"26" x 14"16"
G1 1/2"
EXISTING
TRANSFER GRILLE
EXISTING TRANSFER GRILLE
EXISITNG CABINET HEATER
S(5)
S
S(2)
S(3)
S(4)
S(2)
S(2)
S(2)
S
S
S(2)
S
S
M700
S-1 24x48
S
S-1 24x48
S
T
D-1
T
D-3
BOTTOM OF PIPE 10'-4" AFF
EXISTING THERMOSTAT
FC-1
T
EXISTING RELIEF HOOD ON ROOF
T
MD-2
M
D-1 T
3 3
CU-1
REFRIGERANT SUPPLY / RETURN BUNDEL,
SIZE PER MANUFACTURER'S INSTRUCTIONS.
ROUTE ABOVE CEILING.
HC-1
5 35 x 20"34" x 12"12"
COND3/4"
M800
M800
CAP EXISTING LOUVER
1.FIELD VERIFY EXACT LOCATION OF AHU AND BOLLARDS.
2. CONNECT NEW DIFFUSER TO EXISTING DUCTWORK. REFER TO
DETAIL 7/M800.
3. EXISTING DUCTWORK DIMENSIONS ARE APPROXIMATE. FIELD
VERIFY EXACT DIMENSIONS AND PROVIDE TRANSITIONS AS
REQUIRED.
4. PROVIDE PVC PIPE ENCLOSURE FOR REFRIGERANT PIPING
DOWN EXTERIOR OF THE BUILDING. PAINT TO MATCH EXTERIOR
WALL.
5. REPAIR OR REPLACE ANY CEILING TILE DAMAGED DURING
CONSTRUCTION.
6. CAP AND ABANDON EXISTING STEAM AND CONDENSATE
ENTRANCE TO BUILDING.
MECHANICAL KEYNOTES
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
FIRST FLOOR MECHANICAL PLAN
1 1/4" DCW UP TO
MECHANICAL ROOM
CW1 1/4"
E-1 10x4
UH-3
UH-2
1" HS&R UP TO
MECHANICAL ROOM
HR3/4"
HS3/4"
E-2 6x6
HR3/4"
HS3/4"
6"Ø EA UP THROUGH ROOF.
REFER TO 5/M800 AND 6/M800.
4"Ø
6"Ø
COND1 1/4"
ST1 1/4"
T
UH-3
T
UH-2
CW1 1/4"
COND FROM UH TO BE REMOVED
STEAM TO UH TO BE REMOVED
COND FROM AHU
HS UP TO MECHANICAL ROOM
HEAT EXCHANGER TO BE REMOVED
CW MAKEUP
HR FROM FIRST FLOOR
STEAM DN TO HX
STEAM TO FIRST FLOOR
1" COND 1 1/4" CW
2" STEAM
CW UP
HW UP
DM2
DM5
DM2
DM2
CONDENSATE PUMPS
TO BE REMOVED
CONTROLS AIR COMPRESSOR
TO BE REMOVED ALONG WITH
ALL ASSOCIATED
ACCESSORIES.
STEAM UH TO BE REMOVED
REMOVE EXISTING SYSTEM PUMPS,
ASSOCIATED HYDRONIC PIPING, AND
ACCESSORIES UP TO CONNECTION POINT.
DM7DM8
DM8
M700
G1"
G3/4"
G1 1/2"
ET-1
P-1
B-1
AS-1
1 1/4" CW DN TO BASEMENT
POT FEEDER
16"x14"34"x20"
40"x22"40"x22"
3/4" HS&R DN TO UH-3
WH-1
EXISTING 1" HR FROM
BUILDING LOOP
EXISTING 2" HS TO
BUILDING LOOP.
6"Ø EA UP
THROUGH ROOF.
REFER TO 4/M800.
EXISTING 1 1/2" HW TO
BUILDING LOOP
M800
M D-3
EF-1 WALL MOUNTED
IN VERTICAL.
M800
BOTTOM OF
DUCT 8'-3" AFF
34"x20" M800
B-1
AS-1
P-1
ET-1
WH-1
POT FEEDER
CW3/4"
HS2"
HR2"
HS3/4"
CW1 1/4"
HW1 1/2"
CW1 1/4"
P-2
HWR1 1/4"
ALTERNATE BID
HS1"HR1"
M800
HS&R DN TO UH-1, UH-2
M800
M800
M800
1 1/4" CW
1. FIELD ARCHITECT TO VERIFY EXACT LOCATION OF AHU AND
BOLLARDS.
2. CONNECT NEW DIFFUSER TO EXISTING DUCTWORK REFER TO
DETAIL 6/M800.
3. DUCTWORK DIMENSIONS ARE APPROXIMATE. FIELD VERIFY
EXACT DIMENSIONS AND PROVIDE TRANSITIONS AS REQUIRED.
4. PROVIDE PVC PIPE ENCLOSURE FOR REFRIGERANT PIPING
DOWN EXTERIOR OF THE BUILDING. PAINT TO MATCH EXTERIOR
WALL.
5. REPAIR OR REPLACE ANY CEILING TILE DAMAGED DURING
CONSTRUCTION.
6. CAP AND ABANDON EXISTING STEAM AND CONDENSATE
ENTRANCE TO BUILDING.
MECHANICAL KEYNOTES
DM1. REMOVE ALL STEAM AND CONDENSATE PIPING WHEREVER
ACCESSIBLE. CAP AND ABANDON WHERE INACCESSIBLE.
DM2. REMOVE ALL STEAM AND CONDENSATE PIPING,
EQUIPMENT, AND ASSOCIATED ACCESSORIES.
DM3. EXISTING HYDRONIC LOOP AND COMPONENTS TO REMAIN.
DM4. REMOVE GRADE MOUNTED CHILLER, ASSOCIATED PIPING,
CONTORLS, AND ACCESSORIES. PATCH ALL HOLES AND
DAMAGE FROM DEMOLITION.
DM5. ALTERNATE BID: REMOVE EXISTING WATER HEATER,
ASSOCIATED PIPING, AND ACCESSORIES. DEMO CW TO
CONNECTION POINT. PATCH ALL HOLES AND DAMAGE
FROM DEMOLITION.
MECHANICAL DEMO KEYNOTES
DM6. REMOVE EXISITING STEAM FAN COIL ALONG WITH ALL
ASSOCIATED PIPING AND ACCESSORIES. PREPARE FOR
INSTALLATION OF NEW HYDRONIC HEATING / DX COOLING
FAN COIL. REMOVE EXISTING CONDENSING UNIT FROM
ROOF ALONG WITH ALL ASSOCIATED PIPING AND
ACCESSORIES. PATCH ALL HOLES AND DAMAGE FROM
DEMOLITION.
DM7. REMOVE AHU, ALL ASSOCIATED PIPING, CONTROLS, AND
ACCESSORIES. REMOVE EXISTING AHU HOUSEKEEPING
PAD. PATCH ALL HOLES AND DAMAGE FROM DEMOLITION.
DM8. CONTRACTOR TO FIELD VERIFY EXISTING DUCT SIZES.
REMOVE SUPPLY AND RETURN DUCTWORK UP TO NEW
CONNECTION POINTS. PATCH ALL HOLES AND DAMAGE
FROM DEMOLITION. PREPARE AREA FOR NEW DUCTWORK.
DM9. REMOVE EXISTING ROOFTOP CONDENSING UNIT ALONG
WITH ALL ASSOCIATED PIPING AND ACCESSORIES.
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/4" = 1'-0"
BASEMENT MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
BASEMENT MECHANICAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM ENLARGED DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
MECHANICAL ROOM ENLARGED PLAN
SCALE: 1/4" = 1'-0"
5 BOILER SECTION
ET-2
EXPANSION TANK
MANUFACTURE: BELL & GOSSETT
MODEL: PT-12
VOLUME: 4.4
ACCEPTANCE: 3.2
CHECK VALVE
BALL VALVE
GAS FIRED
WATER HEATER
TEMPERATURE & PRESSURE
RELIEF VALVE, PIPE
DISCHARGE FULL SIZE
TO WITHIN 4" OF FLOOR
DRAIN
DRAIN PAN
DIELECTRIC
UNION
(TYP.)
HW
1-1/4"CW
FLOOR
TO FLOOR
DRAIN
THERMOMETER
4" CONCRETE PAD
1/2" HWR
STRAINERP-2
BALANCE VALVE
3/4" NG
PLUG VALVE
CONCENTRIC VENT
M800
FLOOR
BOILER
TO FD
NUTRALIZATION KIT BY MANUFACTURER
3/4"
PRV
BACKFLOW
PREVENTOR
3/4" CW
ET-1
AS-1
TO FLOOR
DRAIN
AUTOMATIC VENT
2" NG
BYPASS POT FEEDER
AIR VENT
FUNNEL
DRAIN WITH HOSE CONNECTION P-1
SUPPORT
M800
2" HR 2" HS
3/4"
CONNECT TO EXISTING SUPPLY MAINCONNECT TO EXISTING RETURN MAIN
BALANCING VALVE
CHECK VALVE
BALL VALVE
THERMOMETER
TEMPURATURE WELL
BALL VALVE
PLUG VALVE
2"
6" HOUSE KEEPING PAD
PROVIDE VFD
TRIPLE DUTY VALVE
PRESSURE GAUGE &
1/4" BALL VALVES
FLEXIBLE CONNECTIONREDUCER
(IF REQUIRED)
GROUT FRAME
SEE SCHEMATIC SYSTEM
LAYOUT FOR PIPE SIZING
BUTTERFLY
VALVE
SUCTION
DIFFUSER
PIPE
SUPPORT
4" CONCRETE
HOUSEKEEPING PAD
RETURN
DISCHARGE
M
IN
INTAKE AIR
SHEET METAL STRAP
FOR SUPPORT
EXHAUST AIR
CLAMP
FLASHING
TERMINATION ASSEMBLY
INTAKE AIR
EXHAUST
AIR VENT
BIRDSCREEN
EF-1
HANG UNIT FROM EXISTING
CEILING STRUCTURE WITH
VIBRATION ISOLATION
IN-LINE CABINET EXHAUST FAN
FLEX. CONN.
SEALANT OR
CAULK
6"Ø
FIRST FLOOR
6"Ø EA UP THOUGH ROOF (REFER TO 6/M800)
RECTANGULAR LOW
PRESSURE DUCT
SPIN-INFITTING "GENFLEX"
OR EQUAL COMPLETE W/
V.C.D.
45° COLLAR
VOLUME CONTROL DAMPER
ROUND LOW PRESSURE
DUCT
S U
P P
LY
A
IR
F
LO
W
E X
H A
U S
T /R
E T
U R
N A
IR
F
LO
W
LOW VELOCITY
RECTANGULAR DUCT
ROUND LOW
VELOCITY DUCT
ROOF CURB
ROOFING
ROOF INSULATION
ROOF DECK
DUCT
INSECT SCREEN
VIBRATION ISOLATION NEOPRENE PAD. (TYP.)
NEW 4" CONCRETE EQUIPMENT PAD
BY MECH. INSTALLER.
EXISTING GRADE LINE
CU-1
REFRIGERANT SUPPLY AND RETURN
OUTSIDE WALL
FLASHING
GALVANIZED METAL SHEET, PAINT TO
MATCH BUILDING EXTERIOR
3" RIGID INSULATION
GALVANIZED METAL SHEET
40"x22" INSULATED SUPPLY & RETURN DUCT
EXISTING LOUVER
OUTSIDE WALL
3" RIGID INSULATION
GALVANIZED METAL SHEET,
PAINT TO MATCH BUILDING
EXTERIOR.
GALVANIZED METAL SHEET
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S
M D
Y
R O
B E
R T
C H
A L
L R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs \i s a a c .f ra n k \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P
C E
N T
R A
L is a a c .f ra n k .r v t
/2
/2
:5 :2
P
M
M
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R
M
IC
H
IG
A N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: NONE5/M700
1 ALTERNATE BID: WATER HEATER DETAIL
SCALE: NONE
2 BOILER SCHEMATIC
SCALE: NONE5/M700
3 BASE MOUNTED PUMP DETAIL
SCALE: NONE4/M700
4 CONCENTRIC VENT DETAIL
SCALE: NONE4/M700
5 INLINE EXHAUST FAN DETAIL
SCALE: NONE
7 DUCT TAKEOFF
SCALE: NONE
6 EXHAUST DUCT GOOSENECK
SCALE: NONE
8 GRADE MOUNTED CONDENSING UNIT
SCALE: NONE1/M510
9 DUCT EXTERIOR WALL PENETRATION
SCALE: NONE1/M510
10 LOUVER CAP
EX. MAIN DISTRIBUTION PANEL
400A, 208Y/120V
EX. AUTOMATIC TRANSFER SWITCH
70A, 208Y/120V
EX. PANEL 'E'
60A, 208Y/120V
EX. ELECTRIC METER
EX. PANEL 'D'
200A, 120/208V
EX. PANEL 'C'
40A, 120/208V
EX. PANEL 'B'
200A, 120/208V
EX. PANEL 'A'
70A, 208Y/120V
EX. UPS PANEL
60A, 120/208V
EX. PANEL 'D1'
70A, 120/208V
CHILLER TO BE REMOVED
128.4A @ 208V,3PH
AIR HANDLER TO BE REMOVED
22.5A @ 208V,3PH
PUMPS TO BE REMOVED
4.6A @ 120V EACH
UNIT HEATER TO
BE REMOVED
COMBINATION MOTOR STARTER
TO BE REMOVED
DE1
DE1
DE2
DE3
DE3
DE4
CHILLER DISCONNECT SWITCH
TO BE REMOVED AND REUSED
FOR NEW EQUIPMENT
DE5
DE6
FAN COIL UNIT AND CONDENSING
UNIT (ON ROOF) TO BE REMOVED
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S M
D
Y
R O
B E
R T
C
H A
L L
R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs
\k e it h .m a rt in e z \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P C
E N
T R
A L k e it h .m a rt in e z b y c e
.c o m
.r v t
/2
/2
:5 :2
P
M
D E
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R M
IC
H
IG
A
N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
DEMOLITION KEYNOTES
DE1 REMOVE CONDUIT AND WIRING BACK TO NEAREST JUNCTION
BOX. CIRCUIT TO BE EXTENDED TO LOCATION OF NEW
EQUIPMENT. SEE SHEET E100.
DE2 REMOVE COMBINATION MOTOR STARTER, CONDUIT, AND WIRING
BACK TO FUSIBLE SWITCH IN MAIN DISTRIBUTION PANEL. MARK
SWITCH AS 'SPARE'.
DE3 REMOVE (3) 120V CIRCUITS FOR PUMPS BEING REMOVED. ONE
CIRCUIT FOR EACH PUMP AND ONE ADDITIONAL CIRCUIT FOR
PUMP CONTROLS. REMOVE CONDUIT AND WIRING BACK TO
PANEL 'A'.
DE4 REMOVE CONDUIT AND WIRING BACK TO DISCONNECT SWITCH
NEAR UNIT. REMOVE WIRING BACK TO MAIN DISTRIBUTION PANEL.
FUSIBLE SWITCH IN MDP, CONDUIT, AND DISCONNECT TO BE
REUSED FOR FEED TO NEW EQUIPMENT. SEE SHEET E100.
DE5 FAN COIL UNIT AND ASSOCIATED CONDENSING UNIT ON ROOF TO
BE REMOVED. REMOVE CONDUIT AND WIRING FOR EACH UNIT
BACK TO NEAREST. CIRCUITS TO BE RE-USED FOR NEW
EQUIPMENT. SEE SHEET E100. FAN COIL UNIT CIRCUIT BREAKER
IS 15A,2P IN PANEL 'A' AND CONDENSING UNIT CIRCUIT BREAKER
IS 30A,3P IN PANEL 'A'.
DE6 REMOVE CONDUIT AND WIRING FOR ELECTRIC WATER HEATER
(21.6A@208V,1PH) BACK TO SOURCE OF SUPPLY. LABEL CIRCUIT
BREAKER AS 'SPARE'.
DE7 REMOVE CONDUIT AND WIRING BACK FOR CONDENSATE PUMPS
(14.4A@120V) TO SOURCE OF SUPPLY. LABEL CIRCUIT BREAKER
AS 'SPARE'.
DE8 REMOVE CONDUIT AND WIRING BACK TO NEAREST JUNCTION
BOX. CIRCUIT TO BE REUSED FOR NEW BASEMENT UNIT
HEATERS. SEE BASEMENT ELECTRICAL PLAN, THIS SHEET.
M
M
M
M
M
M
POST-COMMANDER'S
OFFICE
AHU-1
EX. MAIN DISTRIBUTION PANEL
400A, 208Y/120V
EX. AUTOMATIC TRANSFER SWITCH
70A, 208Y/120V
EX. PANEL 'E'
60A, 208Y/120V
EX. ELECTRIC METER
EX. PANEL 'D'
200A, 120/208V
EX. PANEL 'C'
40A, 120/208V
EX. PANEL 'B'
200A, 120/208V EX. PANEL 'A'
70A, 208Y/120V
EX. UPS PANEL
60A, 120/208V
EX. PANEL 'D1'
70A, 120/208V
P-1
WH-1
B-1
UH-1
WP
E1
E3
E3
E4
E8
P-2
CU-1
30A SWITCH, 30A FUSES,
3-#10, #10G, 3/4"C
RELOCATED 200A DISCONNECT.
EXTEND EXISTING CONDUIT
THROUGH WALL.
D
D
PROVIDE AND INSTALL DUCT
SMOKE DETECTORS ON SUPPLY
AND RETURN AIR DUCTS
EF-1
FAN COIL UNIT
(REPLACED)
30A SWITCH, 15A FUSES,
2-#12, #12G, 3/4"C
D-2
D-1
D-3
CONTROL TRANSFORMER
FOR DAMPER MOTORS
T E5
E5
E3
E6
E7
E2
PANEL 'E'
(EXISTING)
NATURAL GAS GENERATOR
30 KW, 208Y/120V, 3PH
(EXISTING)
G
AUTOMATIC
TRANSFER SWITCH
70A, 208Y/120V, 3PH
(EXISTING)
MAIN DISTRIBUTION PANEL
400A, 208Y/120V, 3PH, 4W (EXISTING)
400A 3P
M
60A 3P
PANEL 'D'
(EXISTING)
PANEL 'B'
(EXISTING)
PANEL 'A'
(EXISTING)
PANEL 'C'
(EXISTING)
200A 2P
60A 3P
AIR HANDLING UNIT
TO BE REMOVED
COMBINATION
MOTOR STARTER
TO BE REMOVED
200A 3P
CHILLER TO BE
REMOVED
DISCONNECT SWITCH RE-USED
FOR AIR HANDLING UNIT
INSTALL NEW 175A FUSES
UTILITY ELECTRIC METER
(EXISTING)
AIR HANDLING UNIT
AHU-1
UTILITY ELECTRIC SERVICE
(EXISTING)
175A 3P
3-#2/0, #6 GROUND,
2" CONDUIT
3-#2/0, #6 GROUND,
IN EXISTING 2" CONDUIT
OUTLET SCHEDULE
P R
O V
I D
E D
B Y
I N
S T
A L L E
D B
Y
W I R
E D
B Y
S Y
M B
O L
C O
N D
U I T
S
O U
T L E
T S
B Y
M .H
T
O
C E
N T
E R
DESCRIPTION
E = ELECTRICAL
M = MECHANICAL
X = OTHERS
E E E E MANUAL MOTOR STARTERM
E E E E CIRCUIT BREAKER PANEL, SURFACE MOUNTED
E E E E SMOKE DETECTOR, D = DUCT SMOKE DETECTOR
E E E E DISCONNECT SWITCH W/ FUSES TO SUIT
E E E E TRANSFORMERT
E E E E CIRCUIT BREAKER PANEL, FLUSH MOUNTED
E E E E GFCI RECEPTACLE, WP = WEATHERPROOF HINGED IN-USE COVER
E E E E DISTRIBUTION PANEL
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S M
D
Y
R O
B E
R T
C
H A
L L
R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs
\k e it h .m a rt in e z \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P C
E N
T R
A L k e it h .m a rt in e z b y c e
.c o m
.r v t
/2
/2
:5 :2
P
M
E
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R M
IC
H
IG
A
N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL PLAN
SCALE: NONE
1 ONE-LINE DIAGRAM
ELECTRICAL KEYNOTES
E1 PROVIDE CONDUIT AND WIRING TO CONNECT NEW UNIT HEATER
TO 120V CIRCUIT WHICH FED PREVIOUS HEATER. SEE SHEET
DE100.
E2 CONNECT AIR HANDLING UNIT AHU-1 (137A@208V,3PH) SAME
FUSIBLE SWITCH CIRCUIT IN PANEL 'MDP' WHICH PREVIOUSLY FED
CHILLER. ROUTE 3-#2/0, #6G IN EXISTING 2" CONDUIT BACK TO
'MDP'. RELOCATE LOCAL DISCONNECT TO OTHER SIDE OF WING
WALL AND EXTEND EXISTING CONDUIT THROUGH WALL TO NEW
DISCONNECT LOCATION. FUSE AT 175A.
E3 PROVIDE CONDUIT AND WIRING TO CONNECT WATER HEATER
WH-1 (1A), CIRCULATION PUMP P-2 (0.74A), AND BOILER B-1 (8A) TO
NEW 20A,1P CIRCUIT BREAKER IN PANEL 'A' FROM KEYED NOTE
DE3, SHEET DE100.
E4 PROVIDE CONDUIT AND WIRING TO CONNECT PUMP P-1 (13.8A) TO
NEW 20A,1P CIRCUIT BREAKER IN PANEL 'A' FROM KEYED NOTE
DE3, SHEET DE100..
E5 PROVIDE CONDUIT AND WIRING TO CONNECT EXHAUST FAN EF-1
AND 100VA 120V:24V CONTROL TRANSFORMER FOR DAMPER
MOTORS D-1, D-2, AND D-3.
E6 PROVIDE CONDUIT AND WIRING SHOWN TO CONNECT
REPLACEMENT CONDENSING UNIT CU-1 TO SAME 30A,3P CIRCUIT
BREAKER IN PANEL 'A' WHICH FED PREVIOUS CONDENSING UNIT.
E7 PROVIDE CONDUIT AND WIRING SHOWN TO CONNECT
REPLACEMENT FAN COIL UNIT TO SAME 15A,2P CIRCUIT BREAKER
WHICH FED PREVIOUS FAN COIL UNIT.
E8 CONNECT NEW GFCI RECEPTACLE TO NEAREST AVAILABLE 120V
RECEPTACLE CIRCUIT.
E9 PROVIDE CONDUIT AND WIRING TO CONNECT BOTH NEW UNIT
HEATERS(1/12 HP AND 1/8 HP) TO SAME CIRCUIT WHICH FED
PREVIOUS HEATER.
E110
MM UH-3UH-2
E9E9
ELECTRIC WATER HEATER
TO BE REMOVED
4500W, 208V, 1PH
UNIT HEATER TO
BE REMOVED
CONDENSATE PUMPS
TO BE REMOVED
(2x 1/3 HP, 120V)
DE7
DE8
DE9
S U
N U
M E
P L
U R
IB
U
T U E B O R
I N
E P
S I
R A
U Q
I S
M A
N E
C M
A M
A L
U S
N
C R
S M
P U
C I
C I
E
Created by Robert W. Loftis 1991
B y c e a s s o c ia t e s in c
E N
G
IN
E E
C
H
IT
E C
T S
P o r t a g e
S t r e e t k a l a m a z o o m i 4
C o r p o r a te b yc e
.c o m
T e l
F a x
P lo tt e d
B y w w w b y c e c o m
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
S T
A T
E O
F M
IC
H
IG
A
N
J O
B N
O
IN
D
E X
N O
F
IL
E N
O
P R
E L
IM
IN
A
R Y
C O
N S
T R
U C
T
IO
N
F
IN
A L R
E C
O R
D
D E
S
IG
N E
D
D R
A W
N
C H
E C
K E
D
A P
P R
O V
E D
/1
.S M
D
Y
R O
B E
R T
C
H A
L L
R
A N
C A
R B
D
IR
E
C T
O R
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
P R
O C
U R
E M
E N
T A
N D
R E
A L
E S
T A
T E
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
C U s e rs
\k e it h .m a rt in e z \D o c u m e n ts
\1
C o ld w a te r B o ile r R e p la c e m e n t_
M E
P C
E N
T R
A L k e it h .m a rt in e z b y c e
.c o m
.r v t
/2
/2
:5 :2
P
M
E
E
A S
T S
T A
T E
S T
R E
E T
C
O L D
W A
T E
R M
IC
H
IG
A
N
C O
L D
W A
T E
R S
T A
T E
P O
L
IC
E P
O S
T B o ile r R e p la c e m e n t fo r:
/2
/2
SCALE: 1/4" = 1'-0"
BASEMENT ELECTRICAL PLAN
SCALE: 1/4" = 1'-0"
BASEMENT ELECTRICAL DEMOLITION PLAN
DEMOLITION KEYNOTES
DE1 REMOVE CONDUIT AND WIRING BACK TO NEAREST JUNCTION
BOX. CIRCUIT TO BE EXTENDED TO LOCATION OF NEW
EQUIPMENT. SEE SHEET E100.
DE2 REMOVE COMBINATION MOTOR STARTER, CONDUIT, AND WIRING
BACK TO FUSIBLE SWITCH IN MAIN DISTRIBUTION PANEL. MARK
SWITCH AS 'SPARE'.
DE3 REMOVE (3) 120V CIRCUITS FOR PUMPS BEING REMOVED. ONE
CIRCUIT FOR EACH PUMP AND ONE ADDITIONAL CIRCUIT FOR
PUMP CONTROLS. REMOVE CONDUIT AND WIRING BACK TO
PANEL 'A'.
DE4 REMOVE CONDUIT AND WIRING BACK TO DISCONNECT SWITCH
NEAR UNIT. REMOVE WIRING BACK TO MAIN DISTRIBUTION PANEL.
FUSIBLE SWITCH IN MDP, CONDUIT, AND DISCONNECT TO BE
REUSED FOR FEED TO NEW EQUIPMENT. SEE SHEET E100.
DE5 FAN COIL UNIT AND ASSOCIATED CONDENSING UNIT ON ROOF TO
BE REMOVED. REMOVE CONDUIT AND WIRING FOR EACH UNIT
BACK TO NEAREST. CIRCUITS TO BE RE-USED FOR NEW
EQUIPMENT. SEE SHEET E100. FAN COIL UNIT CIRCUIT BREAKER
IS 15A,2P IN PANEL 'A' AND CONDENSING UNIT CIRCUIT BREAKER
IS 30A,3P IN PANEL 'A'.
DE6 REMOVE CONDUIT AND WIRING FOR ELECTRIC WATER HEATER
(21.6A@208V,1PH) BACK TO SOURCE OF SUPPLY. LABEL CIRCUIT
BREAKER AS 'SPARE'.
DE7 REMOVE CONDUIT AND WIRING BACK FOR CONDENSATE PUMPS
(14.4A@120V) TO SOURCE OF SUPPLY. LABEL CIRCUIT BREAKER
AS 'SPARE'.
DE8 REMOVE CONDUIT AND WIRING BACK TO NEAREST JUNCTION
BOX. CIRCUIT TO BE REUSED FOR NEW BASEMENT UNIT
HEATERS. SEE BASEMENT ELECTRICAL PLAN, THIS SHEET.
ELECTRICAL KEYNOTES
E1 PROVIDE CONDUIT AND WIRING TO CONNECT NEW UNIT HEATER
TO 120V CIRCUIT WHICH FED PREVIOUS HEATER. SEE SHEET
DE100.
E2 CONNECT AIR HANDLING UNIT AHU-1 (137A@208V,3PH) SAME
FUSIBLE SWITCH CIRCUIT IN PANEL 'MDP' WHICH PREVIOUSLY FED
CHILLER. ROUTE 3-#2/0, #6G IN EXISTING 2" CONDUIT BACK TO
'MDP'. RELOCATE LOCAL DISCONNECT TO OTHER SIDE OF WING
WALL AND EXTEND EXISTING CONDUIT THROUGH WALL TO NEW
DISCONNECT LOCATION. FUSE AT 175A.
E3 PROVIDE CONDUIT AND WIRING TO CONNECT WATER HEATER
WH-1 (1A), CIRCULATION PUMP P-2 (0.74A), AND BOILER B-1 (8A) TO
NEW 20A,1P CIRCUIT BREAKER IN PANEL 'A' FROM KEYED NOTE
DE3, SHEET DE100.
E4 PROVIDE CONDUIT AND WIRING TO CONNECT PUMP P-1 (13.8A) TO
NEW 20A,1P CIRCUIT BREAKER IN PANEL 'A' FROM KEYED NOTE
DE3, SHEET DE100..
E5 PROVIDE CONDUIT AND WIRING TO CONNECT EXHAUST FAN EF-1
AND 100VA 120V:24V CONTROL TRANSFORMER FOR DAMPER
MOTORS D-1, D-2, AND D-3.
E6 PROVIDE CONDUIT AND WIRING SHOWN TO CONNECT
REPLACEMENT CONDENSING UNIT CU-1 TO SAME 30A,3P CIRCUIT
BREAKER IN PANEL 'A' WHICH FED PREVIOUS CONDENSING UNIT.
E7 PROVIDE CONDUIT AND WIRING SHOWN TO CONNECT
REPLACEMENT FAN COIL UNIT TO SAME 15A,2P CIRCUIT BREAKER
WHICH FED PREVIOUS FAN COIL UNIT.
E8 CONNECT NEW GFCI RECEPTACLE TO NEAREST AVAILABLE 120V
RECEPTACLE CIRCUIT.
E9 PROVIDE CONDUIT AND WIRING TO CONNECT BOTH NEW UNIT
HEATERS(1/12 HP AND 1/8 HP) TO SAME CIRCUIT WHICH FED
PREVIOUS HEATER.
| G001 - Project Cover |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| G001 - Project Cover |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| S310 - Slab Plan & Details |
| Sheets |
| DE110 - Electrical Demolition Plan |
| DM510 - Mechanical Demoltion Plans |
| E110 - Electrical Plan |
| E500 - Enlarged Electrical Plans |
| G001 - Project Cover |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| S310 - Slab Plan & Details |
| DM510 - Mechanical Demoltion Plans |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M001 - Mechanical Schedules |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M110 - Natural Gas Site Plan |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M410 - First Floor Hydronic Plan |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M510 - First Floor Mechanical Plan |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M700 - Mechanical Enlarged Plans |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| M800 - Mechanical Details |
| Sheets |
| DM510 - Mechanical Demoltion Plans |
| M001 - Mechanical Schedules |
| M110 - Natural Gas Site Plan |
| M410 - First Floor Hydronic Plan |
| M510 - First Floor Mechanical Plan |
| M700 - Mechanical Enlarged Plans |
| M800 - Mechanical Details |
| DE110 - Electrical Demolition Plan |
| Sheets |
| DE110 - Electrical Demolition Plan |
| E110 - Electrical Plan |
| E500 - Enlarged Electrical Plans |
| E110 - Electrical Plan |
| Sheets |
| DE110 - Electrical Demolition Plan |
| E110 - Electrical Plan |
| E500 - Enlarged Electrical Plans |
| E500 - Enlarged Electrical Plans |
| Sheets |
| DE110 - Electrical Demolition Plan |
| E110 - Electrical Plan |
| E500 - Enlarged Electrical Plans |
File details come from the government source that posted it. Updated .