Drawings_13444.pdf
PDF 31 MB Posted
- Solicitation number
- 0000038412
- Issued by
- Fresno County, California
About this file
This is a construction drawings document prepared for the California Department of Transportation (DOT) District 6 and the California Department of General Services for an Electric Vehicle Charging Station Infrastructure project located at 30933 W Gale Avenue, Coalinga, California. The project comprises site and electrical infrastructure improvements for the installation of two EV charging stations: one dual-port Level 2 charger (EVCS-1) with two charging ports and one single-port Level 2 charger (EVCS-2) with one charging port, for a total of three fleet charging ports. The chargers are ChargePoint pedestal-style units (CP6021B and CP6011B models) rated at 80 full load amps each and are intended exclusively for designated fleet vehicles, not for public use. Construction work includes demolition of existing concrete and asphalt surfaces, installation of electrical conduit (both above and below ground), trenching and backfilling, construction of concrete pads for charger installation, bollard and signage installation, and restoration of affected pavement surfaces. The project site is located within Flood Hazard Zone X in Fresno County. The contract is advertised under number 25-303883, with a project number of 13444. Bids must be submitted electronically to Eric.Waddell@dgs.ca.gov before April 22, 2026, at 2:00 PM.
This project is restricted to Small Business and Micro Business contractors certified through the California Department of General Services, Office of Small Business and DVBE Services and requires a C-10 contractor license. The work involves integration with an existing 400-amp, 208Y/120V three-phase service and switchboard (400-amp main breaker) serving the site, with new branch breakers of 100 amps each installed for the two chargers. Electrical improvements include a 3-inch rigid metallic conduit home run from the existing service to junction boxes, 2.5-inch PVC conduits extending underground to each charger with #1 AWG copper conductors and #4 AWG ground conductors, and make-ready installations with stub and cap provisions. All work must comply with the 2022 California Building Code, California Electrical Code, California Fire Code, and applicable sections of the National Electrical Code (2020). Prior to contract execution, contractors must submit valid Certificates of Reported Compliance for any fleet vehicles subject to California Air Resources Board In-Use Off-Road Diesel-Fueled Fleet Regulations. The site plan indicates zero impacted existing parking spaces, and the approval documents are dated July 30, 2024, with plan check number 24-2556 and state fire marshal approval granted on October 10, 2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_13444.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date Signed:
07-30-2024 SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _t i0 1.
dw g;
L ay ou t1
BC
F.
ct b Pl ot b y:
d he rn an de z F eb
2,
- 7 :1
2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
TITLE SHEET
T1.0
SHEET INDEX
SHEET NO. TITLE
T1.0 TITLE SHEET
C1.0 OVERALL SITE PLAN
C2.0 DEMOLITION PLAN
C3.0 SITE PLAN
C4.0 DETAILS
E1.0 ELECTRICAL CONDUIT PLAN
E2.0 CONDUIT SECTIONS & DETAILS
E3.0 ELECTRICAL SCHEDULE & CIRCUITS
R1.0 REFERENCE DRAWINGS
R1.1 REFERENCE DRAWINGS
R1.2 REFERENCE DRAWINGS
R2.0 TITLE 24 DOCUMENTS
TOTAL NUMBER OF SHEETS = 12
LOCATION MAP
NOT TO SCALE
ANCHORAGE NOTES:
1. ANCHOR SYSTEMS:
A. EPOXY ANCHORS: COMPLYING WITH ICC ESR-2508, OR ICC ESR-3187, OR ICC ESR-3298.
B. MECHANICAL ANCHORS: COMPLYING WITH ICC ESR-4266, OR ICC ESR-2502
2. INSTALLATION: SEE MANUFACTURER'S WRITTEN INSTRUCTIONS AND REFERENCED ICC ES
REPORT.
A. MATERIALS NOT TO BE PENETRATED BY FASTENERS OR ANCHORS: POST-TENSIONED
CONCRETE AND PRECAST CONCRETE, PRESTRESSED CONCRETE UNLESS SPECIFICALLY
DETAILED HEREIN OR AS ACCEPTED IN WRITING BY ARCHITECT (STRUCTURAL ENGINEER).
WHEN INSTALLATION IS PERMITTED, LOCATE PRESTRESSING AND POST-TENSIONED
TENDONS ACCURATELY PRIOR TO INSTALLATION.
B. DRILLING HOLES IN EXISTING CONCRETE FOR ANCHORS: USE NON-PNEUMATIC, ROTARY
HAMMER TOOLS WITH ANSI COMPLIANT NON-REBAR CUTTING DRILL BITS TO DRILL HOLES
TO PROPER TOLERANCE. LOCATE EXISTING REBAR INCLUDING PRESTRESSING AND
POST-TENSIONING TENDONS USING NON-HAZARDOUS, NON-DESTRUCTIVE METHODS
WITH ACCURATE LOCATION TOLERANCES (PLUS OR MINUS ONE INCH PRIOR TO DRILLING
HOLES TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING OR
PRESTRESSING/POST-TENSIONING TENDONS. HOLES SHALL BE THOROUGHLY CLEANED
PER THE MANUFACTURERS WRITTEN RECOMMENDATIONS PRIOR TO INSTALLATION OF
ANCHORS.
C. DELETERIOUS MATERIALS: KEEP ANCHORS, INCLUDING HOLES FOR DRILL AND EPOXY
ANCHORS AND MECHANICAL ANCHORS FREE OF DUST, GREASE, AND OTHER MATERIALS
THAT IMPAIR CHEMICAL AND MECHANICAL BOND.
3. TESTING FOR EXPANSION ANCHORS:
A. SPECIAL INSPECTION: SPECIAL INSPECTOR WILL PERFORM CONTINUOUS SPECIAL
INSPECTION DURING INSTALLATION.
B. TEST QUANTITY: INSPECTOR SHALL TEST 50% OF ANCHORS USED FOR
EQUIPMENT/NON-STRUCTURAL COMPONENT ANCHORAGE.
C. TEST LOADS FOR:
A. 3/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 3/8" EXPANSION ANCHOR: 25 FT-LBS
B. 1/2"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 1/2" EXPANSION ANCHOR: 40 FT-LBS
C. 5/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 5/8" EXPANSION ANCHOR: 60 FT-LBS
D. HIGH-STRENGTH EPOXY ADHESIVE COMPLYING WITH ICC ESR-2508, ICC ESR-3298 OR
ICC ESR-3187
D. TESTING METHOD:
A. HYDRAULIC RAM METHOD: THE ANCHORS SHALL BE TESTED BY DIRECT PULL WITH A
HYDRAULIC JACK. DURING THE TEST, THE ANCHORS SHALL HAVE NO OBSERVABLE
MOVEMENT.
B. TORQUE WRENCH METHOD: THE ANCHORS SHALL BE TESTED BY THE USE OF A
CALIBRATED WRENCH. THE APPLICABLE TEST LOAD SHALL BE REACHED WITHIN
ONE-HALF TURN OF THE NUT.
E. FAILED ANCHORS: IF ANY ANCHOR(S) FAIL IN TESTING, TESTING OF REMAINING ANCHORS
OF THE SAME SIZE AND CATEGORY NOT PREVIOUSLY TESTED SHALL BE COMPLETED.
4. POST-INSTALLED ANCHORAGE: CONTRACTOR SHALL INSTALL ANCHORAGE AT ALL LOCATIONS
ILLUSTRATED IN THE CONSTRUCTION DOCUMENTS. POST-INSTALLED ANCHORS SHALL
CONFORM TO CBC REQUIREMENTS, AND BE INSPECTED BY A SPECIAL INSPECTOR.
CONCRETE NOTES:
1. CONCRETE COMPRESSIVE STRENGTH: ALL CONCRETE SHALL ATTAIN A MINIMUM
COMPRESSIVE STRENGTH AS SHOWN IN THE CONCRETE STRENGTH TABLE BELOW AT 28
DAYS, U.N.O. ON PLANS. SEE ALSO SULFATE CONTENT NOTES
2. AGGREGATES IN CONCRETE: SHALL BE NATURAL SAND AND ROCK (150 LB/CU. FT)
CONFORMING TO ASTM C33. AGGREGATE SHALL HAVE PROVEN SHRINKAGE
CHARACTERISTICS OF LESS THAN 0.04% PER ASTM C157. DO NOT CHANGE SOURCE OF
AGGREGATE DURING COURSE OF WORK WITHOUT WRITTEN CONSENT OF ENGINEER.
3. CEMENT: SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C150. CEMENT SHALL BE
TYPE II OR AS REQUIRED TO SATISFY SITE SOIL CONDITIONS. REFER TO TABLE 4 OF ASTM
C150 FOR CONCRETE CEMENT REQUIREMENTS ON SOIL CONTAINING SULFATE. REFER TO
THE CONCRETE STRENGTH TABLE FOR MAXIMUM WATER TO CEMENT RATIO. USE A MINIMUM
OF (6) SACK OF CEMENT FOR EACH CUBIC YARD OF CONCRETE.
CONCRETE STRENGTH
CONDITION
MIN 28-DAY
COMPRESSIVE
STRENGTH,
F'C
CONCRETE
TYPE*
MAXIMUM
AGGREGATE
SIZE
WATER TO
CEMENT
RATIO
MAX
SLUMP**
SLAB ON
GRADE/
CONC PADS
4,000 PSI
NORMAL-WEIGHT
CONCRETE
(NWC)
3/4" 0.50 4"
* MAXIMUM DRY WEIGHT OF LIGHTWEIGHT CONCRETE SHALL BE 115 PCF.
** SLUMP SHALL BE MEASURED PRIOR TO THE ADDITION OF SUPERPLASTICIZER (IF USED.)
REBAR CLEAR COVER IN CONCRETE: THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN
REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHER
WISE:
REBAR CLEAR COVER FOR CAST-IN-PLACE CONCRETE
CONDITION COVER
SLAB ON GRADE CENTER OF SLAB OR 2" MIN
4. VIBRATION: VIBRATION OF CONCRETE SHALL BE IN ACCORDANCE WITH GENERAL
PROVISIONS OUTLINED IN PORTLAND CEMENT ASSOCIATION SPECIFICATION ST26.
5. CURING: CONCRETE SHALL BE MAINTAINED AT IN A MOIST CONDITION FOR A MINIMUM OF
FIVE DAYS AFTER IS PLACEMENT. FOR CONCRETE OTHER THAN SLAB ON GRADE, APPROVED
CURING COMPOUNDS MAY BE USED IN LIEU OF MOIST CURING. ONLY IF APPROVED BY THE
ENGINEER OR ARCHITECT.
6. INSPECTIONS, TESTING & QUALITY ASSURANCE: REFER TO SHEET SN1 FOR DEPUTY SPECIAL
INSPECTION, TESTING & STRUCTURAL OBSERVATION REQUIREMENT. A MINIMUM OF ONE
COMPRESSION TEST AT 7 DAYS AND 2 TESTS AT 28 DAYS FOR ALL CONCRETE SAMPLES.
TAKE TEST AT A FREQUENCY OF ONCE EVERY 150 CU. YDS OR 5,000 SQ. FT MINIMUM.
7. DOWELS, INSERTS: SHALL BE TIED IN PLACE PRIOR TO POURING CONCRETE.
8. ANCHOR BOLTS: SHALL BE WEDGE ANCHORS.
9. CONSTRUCTION AND POUR JOINTS: LOCATIONS SHALL BE APPROVED BY ENGINEER PRIOR
TO POURING CONCRETE.
10. FORMWORK: FORMWORK TOLERANCE SHALL BE IN ACCORDANCE WITH THE C.B.C. AND A.C.I
STANDARDS.
11. PIPES IN CONCRETE: PIPES MAY PASS THROUGH STRUCTURAL CONCRETE IN SLEEVES, BUT
SHALL NOT BE EMBEDDED THEREIN. PIPES OR DUCTS EXCEEDING ONE-THIRD THE SLAB OR
WALL THICKNESS SHALL NOT BE PLACED IN THE STRUCTURAL CONCRETE UNLESS
SPECIFICALLY DETAILED.
12. EXPOSED CORNERS: PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS.
13. DRYPACK OR GROUT: SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI AND BE
COMPOSED OF ONE PART PORTLAND CEMENT TO NOT MORE THAN THREE PARTS SAND.
14. FLY ASH: NOT PERMITTED.
DESIGN INFORMATION & PARAMETERS:
1. BASIC WIND SPEED (100 MPH) AND WIND EXPOSURE CATEGORY C.
2. LATITUDE = 36.179766, LONGITUDE = -120.353143
3. S1 = 0.58G, SD1 = 0.94G, SS = 2.03G, SDS = 1.49G (SITE CLASS D ASSUMED)
NOTES:
1. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE
WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE
AUTHORITIES HAVING JURISDICTION (AHJ) AND THEIR LATEST ADOPTED EDITIONS (IN
EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING
PUBLICATIONS:
- CALIFORNIA CODE OF REGULATIONS TITLE 24:
· 2022 CALIFORNIA ELECTRICAL CODE (CEC)
· 2022 CALIFORNIA FIRE CODE (CFC)
· 2022 CALIFORNIA BUILDING CODE (CBC)
· 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)
· 2022 CALIFORNIA REFERENCED STANDARDS CODE (CRSC)
· 2020 NATIONAL ELECTRICAL CODE (NEC)
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
· AMERICANS WITH DISABILITIES ACT (ADA)
· TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
· APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE
2. PRIOR TO MAKING REVISIONS TO THE EXISTING PHASE SERVICE, VERIFY EXISTING
SEQUENCE OF THE CIRCUITS AND MAKE CERTAIN THAT EVERY ITEM IS THOROUGHLY
PREPARED. PRIOR TO SCHEDULED OUTAGES MAKE CERTAIN THAT EVERY ITEM IS
THOROUGHLY PREPARED, THAT ALL REQUIRED MATERIALS ARE ON-SITE 7 DAYS PRIOR
TO THE SCHEDULED OUTAGE, THAT SPARE MATERIALS ARE AVAILABLE IN THE EVENT
OF DAMAGE OR DEFECTS, AND THAT THE REQUIRED PERSONNEL ARE AVAILABLE TO
COMPLETE THE WORK DURING THE SCHEDULED OUTAGE. DO THE ACTUAL WORK AT AN
OFF-PEAK TIME, OR OVERTIME, AS ARRANGED WITH THE STATE'S PROJECT DIRECTOR
OR AS HEREINAFTER SPECIFIED. ONCE THE WORK IS STARTED, VIGOROUSLY
PROSECUTE IT TO COMPLETION TO KEEP DOWNTIME TO A MINIMUM. ENSURE THAT
EXISTING ELECTRICAL PHASE SEQUENCE (ELECTRICAL PHASE ROTATION) OF THE
SYSTEM IS MAINTAINED. BE PREPARED TO TEMPORARILY SERVE THE EXISTING SERVICE
OR DISCONTINUE THE NECESSARY REVISIONS IN THE EVENT OF AN EMERGENCY OR
OTHER CONDITION WHICH MAKES IT IMPOSSIBLE TO FINISH THE SCHEDULED WORK ON
TIME.
3. NAMEPLATES:
A. PROVIDE NAMEPLATES ON EQUIPMENT, DEVICES, PANELS AND FIELD MOUNTED
INSTRUMENTS (PRESSURE SWITCHES, LIMIT SWITCHES, ETC.) TO IDENTIFY EACH ITEM
WITH ITS RESPECTIVE SERVICE OR FUNCTION. USE BLACK-ON-WHITE LAMINATED
PLASTIC (WHITE LETTERING ON BLACK BACKGROUND), WITH BEVELED EDGES AND
ENGRAVED LETTERING NOT LESS THAN 1/4 INCH HIGH UNLESS OTHERWISE NOTED.
ATTACH WITH 1/4-INCH-LONG NO. 4 PHILLIPS, ROUND HEAD, COARSE THREAD, TYPE
410 STAINLESS STEEL, THREAD-CUTTING SCREWS WITH BLUNT POINT UNLESS
OTHERWISE SPECIFIED. FOR EXTERIOR NAMEPLATES, PROVIDE SILICON SEAL FOR
SCREW PENETRATIONS. FOR CAST IRON ENCLOSURES MOUNT NAMEPLATES WITH
SETON TUFF-BOND #TB2 ADHESIVE.
B. PROVIDE NAMEPLATES FOR INTERNAL DEVICES OF EQUIPMENT (CONTROL RELAYS,
CONTACTORS, TIMERS, TERMINAL BLOCKS, ETC.). MOUNT NAMEPLATES ADJACENT
TO, NOT ON, THE DEVICE.
C. PROVIDE SINGLE, DEDICATED NAMEPLATES FOR DEVICES MOUNTED WITHIN AND ON
EQUIPMENT. PROVIDE AS A MINIMUM A SINGLE DEDICATED NAMEPLATE FOR EACH
DEVICE (RELAY, SWITCH, TERMINAL BLOCK, METER, ETC.). NAMEPLATE SHALL AGREE
WITH IDENTIFICATION ON MANUFACTURER'S DRAWING. ON DEVICES MOUNTED IN
FRONT COMPARTMENT DOORS, PROVIDE EACH DEVICE WITH TWO NAMEPLATES, ONE
ON THE FRONT AND ONE ON THE BACK OF THE FRONT COMPARTMENT DOOR. THE
NAMEPLATES MOUNTED ON THE BACK OF THE DOOR SHALL BE STICK-ON TYPE.
FIRE SAFETY NOTES:
1. FIRE DEPARTMENT ACCESS ROAD SHALL BE MAINTAINED AT ALL TIMES, AND SHALL BE
PROVIDED TO BE WITHIN 100 FEET OF TEMPORARY FIRE DEPARTMENT CONNECTIONS.
(2022 CFC SECTION 3310)
2. FIRE SAFETY DURING DEMOLITION AND CONSTRUCTION SHALL COMPLY WITH CBC
CHAPTER 33 AND CFC CHAPTER 33.
3. FIRE SAFETY DURING DEMOLITION SHALL COMPLY WITH THE APPLICABLE
REQUIREMENTS OF CHAPTER 33 OF THE CBC AND THE APPLICABLE PROVISIONS OF
CHAPTER 33 OF THE CFC. THESE REQUIREMENTS SEEK TO MAINTAIN REQUIRED LEVELS
OF FIRE PROTECTION, LIMIT FIRE SPREAD, ESTABLISH THE APPROPRIATE OPERATION
OF EQUIPMENT, AND PROMOTE PROMPT RESPONSE DURING FIRE EMERGENCIES.
4. MUST ADHERE TO CFC CHAPTER 3 FIELD DEPUTY TO VERIFY.
FLOOD ZONE NOTES:
1. PROJECT SITE LOCATED WITHIN FLOOD HAZARD ZONE X; AREAS OF 0.2% ANNUAL
CHANCE FLOOD WITH AVERAGE DEPTHS OF LESS THAN 1 FOOT OR WITH DRAINAGE
AREAS LESS THAN 1 SQUARE MILE; AND AREAS PROTECTED BY LEVEES FROM 1%
ANNUAL CHANCE FLOOD.
2. FIRM PANEL: 06019C3211H
3. MAP EFFECTIVE DATE; FEBRUARY 18, 2009
4. MAP IS FRESNO COUNTY, CALIFORNIA; PANEL 3211 OF 3525
GENERAL CONTRACT NOTES:
1. CONTRACTOR SHALL PROVIDE ALL MATERIALS SUCH AS TOOLS, EQUIPMENT, LABOR, AND
INCIDENTALS REQUIRED INCLUDING THE CONSTRUCTION OF ALL PROPOSED IMPROVEMENTS
SHOWN ON THE PLANS AND AS SPECIFIED BY THE GOVERNING STANDARDS AND/OR THE
CIVIL AND ELECTRICAL ENGINEERS.
2. CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL EXISTING UTILITIES PRIOR TO
CONSTRUCTION OF THE PROPOSED IMPROVEMENTS.
3. IF DAMAGED DURING CONSTRUCTION, THE CONTRACTOR SHALL REPLACE IN KIND ALL
EXISTING STRUCTURES, WALKWAYS, CURB & GUTTER, LANDSCAPING, AND/OR OTHER
IMPROVEMENTS TO AN EXISTING OR BETTER CONDITION.
4. CONTRACTOR SHALL REPLACE ALL EXISTING STRIPING, SIGNAGE AND MARKINGS DAMAGED
DUE TO PROJECT CONSTRUCTION ACTIVITIES. CONTRACTOR TO REMOVE EXISTING
STRIPING BEFORE PLACING PROPOSED STRIPING PATTERNS.
5. ALL WORK SHALL BE CONFINED WITHIN THE EASEMENTS AND/OR CONSTRUCTION LIMITS AS
SHOWN ON THE PLANS.
6. APPROVAL OF THESE PLANS BY THE AUTHORITIES HAVING JURISDICTION DOES NOT
AUTHORIZE ANY WORK TO BE PERFORMED UNTIL A PERMIT OR NOTICE TO PROCEED HAS
BEEN ISSUED.
7. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL NOTIFY ALL UTILITY AUTHORITIES
OR UTILITY COMPANIES HAVING POSSIBLE INTEREST IN THE WORK OF THE CONTRACTOR'S
INTENTION TO EXCAVATE PROXIMATE TO EXISTING FACILITIES AND THE CONTRACTOR SHALL
VERIFY THE LOCATION OF ANY UTILITIES IN THE WORK AREA. THE CONTRACTOR SHALL
NOTIFY UNDERGROUND SERVICE ALERT (U.S.A.) TWO (2) DAYS PRIOR TO BEGINNING ANY
EXCAVATION.
8. THE CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION FROM ANY PROPERTY OWNER
GIVING HIM PERMISSION TO ENTER HIS PROPERTY FOR THE PURPOSE OF CONSTRUCTING
THE IMPROVEMENTS DELINEATED ON THE PLANS AND TRANSITION THERETO.
9. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL BE PROVIDED AS SPECIFIED WITHIN THIS
SET OR APPROVED EQUAL. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL MATCH THE
SAME QUALITY AND CAPACITY AS INDICATED HEREIN.
10. CONTRACTOR MUST IMMEDIATELY NOTIFY THE ENGINEER OF RECORD, IDENTIFIED BY THE
PROFESSIONAL ENGINEERING SEAL AND SIGNATURE ON THESE PLANS, OF ANY SITE
CONDITION(S) AND/OR DESIGN INFORMATION THAT PREVENTS THE CONTRACTOR FROM
COMPLYING WITH THE LAWS, REGULATIONS AND/OR BUILDING CODES.
11. ALL CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH DGS STANDARD
CONSTRUCTION SPECIFICATIONS.
12. CONTRACTOR TO MAINTAIN THE REQUIRED MEANS OF EGRESS AND ACCESSIBLE MEANS OF
EGRESS SHALL BE MAINTAINED DURING CONSTRUCTION AND DEMOLITION, REMODELING OR
ALTERATIONS AND ADDITIONS TO ANY BUILDING.
PROJECT LOCATION:
PROJECT IS LOCATED AT:
30933 W GALE AVE
COALINGA, CA 93210
APN: 070-041-34ST
SCOPE OF EV IMPROVEMENT WORK:
1. SITE AND ELECTRICAL INFRASTRUCTURE IMPROVEMENTS FOR INSTALLATION OF EV
CHARGERS.
2. IMPACTED EXISTING PARKING = 0 TOTAL SPACES; 0 STANDARD SPACES
3. ALL EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR
USE BY A DESIGNATED VEHICLE OR DRIVER. LIST OF CONSULTANTS:
STRUCTURAL: ELECTRICAL:
BRIAN BROOKS
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
BRIAN DUFFY
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
SINA ROUDBARI
PROJECT DIRECTOR I
OFFICE OF SUSTAINABILITY - CLEAN TRANSPORTATION UNIT
DEPARTMENT OF GENERAL SERVICES (DGS)
WORK: (279) 799-4343
CELL: (279) 599-2212
EMAIL: SINA.ROUDBARI@DGS.CA.GOV
OWNER/REPRESENTATIVE
INFORMATION:
DOT - DISTRICT 6 COALINGA
30933 W GALE AVE
COALINGA, CA 93210
EMAIL: GINA.ROUDBARI@DGS.CA.GOV
CONTACT: GINA ROUDBARI
UTILITY NOTE:
UTILITY INFORMATION SHOWN HEREON IS BASED ON OBSERVATION OF VISIBLE EVIDENCE BY A
FIELD SURVEY. THE ENGINEER CAN MAKE NO GUARANTEE AS TO THE ACCURACY OR
COMPLETENESS OF THE UNDERGROUND UTILITY FACILITIES SHOWN. PRIOR TO ANY SITE
EXCAVATIONS, THE CONTRACTOR SHALL CONTACT THE OWNER AND UNDERGROUND SERVICE
ALERT (U.S.A.) AND REQUEST THAT THEY IDENTIFY THE LOCATION OF ALL UNDERGROUND
UTILITIES AT THE SITE. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
DESIGN CRITERIA:
CALIFORNIA ADMINISTRATIVE CODE (CAC) 2022
CALIFORNIA BUILDING CODE (CBC) 2022
CALIFORNIA ELECTRICAL CODE (CEC) 2022
CALIFORNIA FIRE CODE (CFC) 2022
CALIFORNIA REFERENCED STANDARDS CODE (CRSC) 2022
NATIONAL ELECTRICAL CODE (NEC) 2020
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
ARC-FLASH NOTE:
1. ALL NEW ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANELBOARDS SHALL BE
PROVIDED WITH AN ARC-FLASH HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL
CONTRACTOR, IN COMPLIANCE TO THE THE REQUIREMENTS OF THE LATEST CEC 110.16. AN
ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE LATEST NFPA 70E - 130.5,
SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD WARNING
LABEL/MARKING TEMPLATE/S SHALL BE SIGNED AND SEALED BY POWER SYSTEMS ANALYSIS
SPECIALIST.
PROPOSED EV CHARGER TABULATION
EV CHARGER NO. OF EVCS(S) NO. OF FLEET PORT(S)
SINGLE (LEVEL 2) 1 1
DUAL (LEVEL 2) 1 2
TOTAL TOTAL EVCS(S) = 2 TOTAL PORT(S) = 3
CBC 11B-228.3.2 EXCEPTION #1: EVCS NOT AVAILABLE TO THE GENERAL PUBLIC AND INTENDED
FOR USE BY A DESIGNATED VEHICLE OR DRIVER SHALL NOT BE REQUIRED TO COMPLY WITH
SECTION 11B-228.3.2
PROJECT
LOCATION
W GALE AVE
O
IL
C
IT
Y R
D C
O D
Y
ST
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
DOT D6 - Electric Vehicle Supply Equipment - Coalinga
PROJECT NUMBER: 000000000013444; 03/13/26
PP
GAS
BOBOBOBOBOBO
IVAIVAIVA
HB
BO
BO
BO
BO
WV
RD RD
RDRD
HB
CO
CO
PPPP
GUYGUY
LP
PP
HB
GV
MB
RD
CO
GUY
EPB
EPB
EPB
OWNER: NBINV AF4 LLC
APN: 070-041-35S
W GALE AVE
OWNER: DUST BOWL FARMS LLC
APN: 070-041-53S
OWNER: DUST BOWL FARMS LLC
APN: 070-041-25S
OWNER: TERRY JOHNSON
APN: 070-041-37
OWNER: TERRY JOHNSON
APN: 070-041-27
OWNER: TERRY JOHNSON
APN: 070-041-28S
OWNER: EQUILON
ENTERPRISES LLC
APN: 070-041-19S
OWNER: EQUILON
ENTERPRISES LLC
APN: 070-041-20S
OWNER: TERRY J JOHNSON
/ JOHNSON DEANNA I
TRUSTEE
APN: 070-041-18S
OWNER: CHEVRON U S A INC
APN: 070-041-09
OWNER: LATCHKEY
PIONEERS LLC
APN: 070-041-51S
OWNER: LATCHKEY
PIONEERS LLC
APN: 070-041-52S
OWNER: 9820 CODY
STREET LLC
APN: 070-120-10S
OWNER: FERDOSE RANCH LLC
APN: 070-120-11S
OWNER: SYLVESTA M HALL
APN: 070-120-05S
OWNER: STATE OF
CALIFORNIA
APN: 070-041-34ST
OWNER: COALINGA CITY OF
APN: 070-120-08ST
OWNER: WEST HILLS JOINT
COMMUNITY COLLEGE
APN: 070-041-15ST
OWNER: WEST HILLS JOINT
COMMUNITY COLLEGE
APN: 070-041-16ST
O
IL
C
IT
Y R
D
C O
D Y
ST
OWNER: UNKNOWN
APN: UNKNOWN
OVERALL SITE PLAN
C1.0
0 100 200 300 600
SCALE IN FEET
SCALE: 1" = 300'
Date Signed:
07-30-2024 SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _s i0 1.
dw g;
C 1.
O ve ra ll Si te M ap
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
1 1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
PROJECT LOCATION SEE
DEMOLITION PLAN ON SHEET
C2.0, SITE PLAN ON SHEET
C3.0, AND ELECTRICAL
CONDUIT PLAN ON SHEET E1.0
SYMBOL LEGEND:
EXISTING PROPERTY LINE
AREA OF WORK
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
BOBOBOBOBOBO
IVAIVAIVA
HB
BO
BO
BO
BO
WV
RD RD
RDRD
HB
CO
CO
PPPP
GUYGUY
LP
PP
HB
GV
MB
RD
CO
GUY
W GALE AVE
EXISTING SERVICE CT
METER 1009502735 AND
SWITCHBOARD 400A,
208Y/120V, 3Ø, 4W
EXISTING OVERHEAD
TRANSFORMER
120162636, 208Y/120V
EPB
EPB
EPB
G
G
G
G
G
W
W
W
W
W
W
W
W
W
W
W
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
SD SD SD
BOBO
BOBO
JB
Date Signed:
07-30-2024 SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _t s0 1.
dw g;
C 2.
To po gr ap hi c Su rv ey
BC
F.
ct b Pl ot b y:
d he rn an de z F eb
2,
- 7 :1
2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
1 1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
DEMOLITION PLAN
C2.0
SCALE IN FEET
0 5 10 20
SCALE: 1" = 10'
EXISTING SYMBOL LEGEND:
BOLLARD
DOOR/GATE
ELECTRICAL PULL BOX
ELECTRICAL METER
ELECTRICAL RISER
ELECTRICAL TRANSFORMER
FIRE HYDRANT
FIRE INDICATOR POST
GAS MANHOLE
GAS VALVE
GUY POLE
GUY WIRE ANCHOR
HOSE BIB
IRRIGATION VALVE
LIGHT POST
POWER POLE
ROOF DRAIN
ROLL GATE
SEWER CLEANOUT
SIGN
TREE; SPREAD SHOWN
GRAPHICALLY
WATER VALVE
EXISTING ASPHALT CONCRETE
PAVEMENT
EXISTING BUILDING
EXISTING CONCRETE
CHAIN LINK FENCE
BUILDING OVERHANG
EDGE OF ASPHALT CONCRETE
PAVEMENT
GRADE BREAK
STRIPING
ELECTRICAL LINE
GAS LINE
OVERHEAD ELECTRICAL LINE
WATER LINE
BO
EPB
E
ELR
ET
FIP
G
GV
GP
GUY
HB
IVA
LP
PP
RD
CO
WV
DEMOLITION NOTES:
1. THE "LIMIT OF DEMOLITION" SHOWN IS APPROXIMATE AND IS
GENERALLY CONSIDERED TO BE THE MINIMUM REMOVAL
REQUIREMENTS. CONTRACTOR MUST COORDINATE AS NOTED IN
THE LEGEND.
2. CONTRACTOR SHALL LEGALLY DISPOSE OF ALL DEMOLISHED
MATERIALS OFF SITE.
3. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITY
IMPROVEMENTS NOT SPECIFICALLY DESIGNATED FOR REMOVAL.
4. THE ON-SITE UNDERGROUND UTILITIES SHOWN ON THIS SHEET ARE
AT AN APPROXIMATE LOCATION. THE EXTENT, LOCATIONS AND SIZES
ARE UNKNOWN. THE CONTRACTOR SHALL POTHOLE TO LOCATE AND
VERIFY THE UNDERGROUND UTILITY LINES PRIOR TO REMOVAL.
5. CONTRACTOR TO PROTECT AND PRESERVE IN PLACE ANY FOUND
SURVEY MONUMENTS. ANY MONUMENTS DISTURBED SHALL BE
RESET BY A LICENSED SURVEYOR AND THE APPROPRIATE
PAPERWORK FILED WITH THE CITY OR COUNTY.
6. ALL HAZARDOUS MATERIALS ENCOUNTERED DURING SITE
DEMOLITION SHALL BE REMEDIATED AND DISPOSED OF PER STATE
AND EPA REQUIREMENTS.
7. CONTRACTOR SHALL CONTACT AND COORDINATE WITH ALL UTILITY
AGENCIES PRIOR TO THE START OF ANY DEMOLITION OR
CONSTRUCTION.
8. ANY EXISTING UTILITIES AND/OR IMPROVEMENTS THAT BECOME
DAMAGED DURING CONSTRUCTION SHALL BE COMPLETELY
RESTORED TO THE SATISFACTION OF THE OWNER AND AGENCY
HAVING AUTHORITY, AT THE CONTRACTOR'S SOLE EXPENSE.
DEMOLITION LEGEND:
PROTECT EXISTING ASPHALT CONCRETE
PAVEMENT TO REMAIN
PROTECT EXISTING BLOCK WALL TO REMAIN
PROTECT EXISTING BUILDING TO REMAIN
PROTECT EXISTING CONCRETE CURB TO REMAIN
PROTECT EXISTING CONCRETE SIDEWALK TO
REMAIN
PROTECT EXISTING UTILITY TO REMAIN
REMOVE AND LAWFULLY DISPOSE OF CONCRETE:
### S.F.
REMOVE EXISTING IMPROVEMENTS AS NECESSARY
TO CONSTRUCT NEW IMPROVEMENTS SHOWN ON
THESE PLANS UNLESS OTHERWISE NOTED ON THE
PLAN. THE REMOVAL OF IMPROVEMENTS MUST BE
COORDINATED WITH ALL PLAN SHEETS.
CONTRACTOR MUST ALSO COORDINATE REMOVAL
OF IMPROVEMENTS WITH UTILITY AGENCIES.
PROTECT ALL IMPROVEMENTS NOT DESIGNATED
FOR REMOVAL. SEE NOTE 1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
BOBOBOBOBOBO
IVAIVAIVA
HB
BO
BO
BO
BO
WV
RD RD
RDRD
HB
CO
CO
PPPP
GUYGUY
LP
PP
HB
GV
MB
RD
CO
GUY
W GALE AVE
EXISTING SERVICE CT
METER 1009502735 AND
SWITCHBOARD 400A,
208Y/120V, 3Ø, 4W
EXISTING OVERHEAD
TRANSFORMER
120162636, 208Y/120V
EPB
EPB
EPB
BOBO
BOBO
JB
(TYP)
A
(TYP)
B
(TYP)
C
(TYP)
D
E
F
F1
F2
F3
9'
20'
9' 9'
'-6
'-8
4' -6
9'
4' -6
SCALE IN FEET
0 5 10 20
SCALE: 1" = 10'
Date Signed:
07-30-2024 SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _s i0 2.
dw g;
C 3.
Si te
G ra di ng
P la n
- B
C F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
1 1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
CONSTRUCTION LEGEND:
2' WIDE ELECTRICAL UTILITY TRENCH. TRENCH,
BACKFILL AND RESURFACING PER DETAIL [C/E2.0]
CONSTRUCT CONCRETE PAD PER DETAIL [B/E2.0]
FOR MAKE READY INSTALLATION WITH STUB & CAP
FURNISH AND INSTALL FIXED BOLLARDS PER DETAIL
[A/C4.0]
FURNISH AND INSTALL FIXED FLEET CHARGING
SIGN PER DETAIL [B/C4.0]
PAINT 4" WIDE GREEN STRIPE
SEE ELECTRICAL CONDUIT PLAN FOR ADDITIONAL
ELECTRICAL IMPROVEMENTS
PROPOSED CHARGEPOINT [MODEL
CP6011B-80A-L7-CHIP] SINGLE CHARGE PORT
PEDESTAL STYLE CHARGERS TO BE INSTALLED BY
OTHERS. SEE DETAIL [A/R1.1] (SHOWN FOR
REFERENCE ONLY)
PROPOSED CHARGEPOINT [MODEL
CP6021B-80A-L7-CHIP] DUAL CHARGE PORT
PEDESTAL STYLE CHARGERS TO BE INSTALLED BY
OTHERS. SEE DETAILS [A/R1.0] (SHOWN FOR
REFERENCE ONLY)
PROPOSED (OSHA SAFETY GREEN - 14120) STRIPING
IMPROVEMENTS
LIMITS OF ASPHALT CONCRETE PAVEMENT
IMPROVEMENTS
LIMITS OF CONCRETE IMPROVEMENTS
A
B
C
D
E
F
PROPOSED EV CHARGER
EVCS-# WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS CHARGE PORT #
POWER
SELECT
(FLA)
POWER
SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL - N/A FLEET
2 PEDESTAL SINGLE - N/A FLEET
NOTES:
-(FLA) STANDS FOR, FULL LOADS AMPS
-(Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
F1 F2
F3
SITE PLAN
C3.0
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
DETAILS
C4.0
A C4.0
FIXED BOLLARD
NOT TO SCALE
Date Signed:
07-30-2024 SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _d t0 1.
dw g;
C 4.
D et ai ls
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
1 1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
B C4.0
FIXED FLEET
CHARGING SIGN
NOT TO SCALE
NOTES:
1. LOCATE FIXED BOLLARDS SO THAT THEY DO NOT INTERFERE
WITH THE OPENING OF EQUIPMENT DOORS.
2. CLEAR ALL DIRT AND DEBRIS IN THE GENERAL LOCATIONS
INDICATED FOR INSTALLATION.
3. SUPPORT AND BRACE BOLLARDS IN POSITION UNTIL
CONCRETE HAS CURED.
4. FIXED BOLLARDS TO BE CONSTRUCTED PER THE
CALIFORNIA FIRE CODE (CFC) SECTION 312.
16"
4" 3'
(M
IN
4'
(M
IN
FIELD PRIME
BOLLARDS WITH 2
COATS OF ZINC-RICH
PRIMER. PAINT
BOLLARDS WITH 2
COATS OF INDUSTRIAL
YELLOW ENAMEL
4" GALVANIZED SCH.40
STEEL POST (WEIGHT
= 9.1 LBS/FT) SEE PLAN
FOR LOCATION
3" WIDE REFLECTING
TAPE
MOUNDING TOP
SURFACE (CROWN)
TO SHED WATER
FINISHED
SURFACE
CLASS "B"
CONCRETE
FOOTING
FILL BOLLARDS
SOLIDLY WITH
CONCRETE
FINISHED CONCRETE
OR GROUND SURFACE
2" SCH. 40 GALV. STEEL POST
18 GA STEEL WITH FIELD OF
GREEN, 1/2" WHITE BORDER,
AND WHITE LETTERING, ALL
OF REFLECTIVE SHEETING
FASTENER: 1/4" DIA. HEX. BOLT W/
LOCK WASHER 1-1/2" FROM TOP
AND BOTTOM OF SIGN
GALV.
STEEL POST
CAP
CONCRETE
12"
1"
6' -8
M
IN
C
LE
AR
3'
(M
IN
3"
8"
4"
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
BOBOBOBOBOBO
IVAIVAIVA
HB
BO
BO
BO
BO
WV
RD RD
RDRD
HB
CO
CO
PPPP
GUYGUY
LP
PP
HB
GV
MB
RD
CO
GUY
W GALE AVE
EXISTING SERVICE CT
METER 1009502735 AND
SWITCHBOARD 400A,
208Y/120V, 3Ø, 4W
EXISTING OVERHEAD
TRANSFORMER
120162636, 208Y/120V
EPB
EPB
EPB
G
G
G
G
G
W
W
W
W
W
W
W
W
W
W
W
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
SD SD SD
BOBO
BOBO
JB
F1
A
(TYP)
(K2)
(EVCS-1) F2
F3
(EVCS-2)
(K3)
(K1)
B
C
D
(TYP)
E
'-6
'-4
BREAKER
DISCONNECTING MEANS
LOCATED HERE WITH
EXISTING SERVICE CT
METER
ELECTRICAL CONDUIT PLAN
E1.0
SCALE IN FEET
0 5 10 20
SCALE: 1" = 10'
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _e l0 1.
dw g;
E 1.
El ec tri ca l C on du it Pl an
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
A E1.0
CONDUIT SCHEDULE
CONDUIT SCHEDULE
CONDUIT
NUMBER FROM TO CONDUCTORS ALL 90°C THWN-2 OR
SIMILAR UNLESS NOTED OTHERWISE
CONDUCTOR
LENGTH (FT)
VOLTAGE
DROP
CONDUIT SIZE
AND TYPE COMMENTS
K1 EXISTING CT METER AND MAIN
SWITCHBOARD K2-K4 T-TYPE CONDUIT BODIES (6) #1 AWG Cu, (3) #4 AWG Cu GND 3" RMC HOME RUN
K2 K2 T-TYPE CONDUIT BODY EVCS-1
(4) #1 AWG Cu, (2) #4 AWG Cu GND, TAGGED
(EVCS-1, L1, L2, GROUND) 135 1.8 % 2-1/2" RMC/PVC
K3 K3 T-TYPE CONDUIT BODY EVCS-2
(2) #1 AWG Cu, (1) #4 AWG Cu GND, TAGGED
(EVCS-2, L1, L2, GROUND)
PULL, (1) PULL TAPE THROUGH AND LEAVVE
WITHIN CONDUIT FOR FUTURE USE
149 1.9 % 2-1/2" RMC/PVC
ELECTRICAL NOTES:
1. ELECTRICAL UTILITY LINE TO BE PROTECTED IN PLACE WHEN POSSIBLE. IF EXISTING
LINES INTRODUCE EXCESSIVE CONSTRAINTS DURING THE INSTALLATION OF THE
ELECTRICAL EQUIPMENT, REMOVE AND RELOCATE EXISTING LINES AS NEEDED,
USING THE PROPOSED UTILITY TRENCH. IF THE ELECTRICAL LINE CANNOT BE
SALVAGED THE CONTRACTOR MUST LAWFULLY DISPOSE OF THE ELECTRICAL LINE
AND REPLACE WITH LIKE-IN-KIND.
2. ALL ELECTRICAL POWER IN CLOSE PROXIMITY TO THE INSTALLATION OF THE
ELECTRICAL EQUIPMENT MUST BE POWERED OFF PRIOR TO THE START OF
CONSTRUCTION, TO PREVENT ANY ELECTRICAL INJURIES.
3. HAND DIG ALL UTILITIES IN CLOSE PROXIMITY TO THE INSTALLATION OF THE
ELECTRICAL EQUIPMENT TO AVOID DAMAGING ANY UTILITY LINE.
4. SEE SINGLE LINE DIAGRAM ON SHEET E3.0.
5. SEE CONDUIT SCHEDULE FOR WIRE SIZE, CONDUIT FILL AND WIRE TAGS.
6. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO
COMPLY WITH GROUNDING AND BONDING OF ELECTRICAL SYSTEMS AND
NON-CURRENT CARRYING CONDUCTIVE MATERIALS, ENCLOSURES, OR ITEMS
FORMING PART OF ANY SUCH EQUIPMENT THAT ENCLOSES OR CARRIES
ELECTRICAL CONDUCTOR OR EQUIPMENT THAT IS LIKELY TO BECOME
ENERGIZED. SEE CEC/NEC 250.4(A)(1) THROUGH (5) FOR FURTHER DESCRIPTION.
7. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM
SEPARATION SHALL BE 6' PER CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF
ELECTRODES.
8. MINIMUM CONDUIT BURIAL DEPTH SHALL BE 24".
9. PER CEC/NEC 110.26 "ACCESS AND WORKING SPACE SHALL BE PROVIDED AND
MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE
OPERATION AND MAINTENANCE OF SUCH EQUIPMENT."
10. CONDUIT BODIES SHALL BE USED AS NEEDED TO MAINTAIN LESS THAN 360° OF
CONDUIT BENDS BETWEEN PULL POINTS.
11. EACH CHARGER SHALL HAVE A 1-1/2" PVC CONDUIT STUBBED AND CAPPED.
12. ALL ABOVE GRADE CONDUIT CONSTRUCTION SHALL FOLLOW CEC/NEC 342, 344, 350,
OR 358 FOR IMC, RMC, LFMC OR EMT CONSTRUCTION.
ELECTRICAL LEGEND:
EXISTING SERVICE CT METER AND MAIN SWITCHBOARD, 208Y/120V,
400 AMP, 3Ø, 4W, PER DETAILS [A/E2.0] AND [A/E3.0].
FURNISH AND INSTALL MAKE READY INSTALLATION WITH STUB &
CAP. CONSTRUCT PER DETAIL [B/E2.0] AND NOTE 11
SEE DETAIL [D/E2.0] FOR THE FURNISHING AND INSTALLATION OF
ABOVE GRADE RMC CONDUIT. SEE CONDUIT SCHEDULE FOR
COUNT AND CONDUIT SIZE
SEE DETAIL [C/E2.0] FOR THE FURNISHING AND INSTALLATION OF
BELOW GRADE PVC CONDUIT. SEE CONDUIT SCHEDULE FOR
COUNT AND CONDUIT SIZE
FURNISH AND INSTALL 24"x24"X10"(D) JUNCTION BOX.
PROPOSED CHARGEPOINT [MODEL CP6011B-80A-L7-CHIP] SINGLE
CHARGE PORT PEDESTAL STYLE CHARGERS TO BE INSTALLED BY
OTHERS. SEE DETAIL [A/R1.1] (SHOWN FOR REFERENCE ONLY)
PROPOSED CHARGEPOINT [MODEL CP6021B-80A-L7-CHIP] DUAL
CHARGE PORT PEDESTAL STYLE CHARGERS TO BE INSTALLED BY
OTHERS. SEE DETAILS [A/R1.0] (SHOWN FOR REFERENCE ONLY)
ELECTRICAL CONDUIT; SIZE AND COUNT AS NOTED
A
B
C
D
E
PROPOSED EV CHARGER
EVCS-# WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS CHARGE PORT #
POWER
SELECT
(FLA)
POWER
SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL - N/A FLEET
2 PEDESTAL SINGLE - N/A FLEET
NOTES:
-(FLA) STANDS FOR, FULL LOADS AMPS
-(Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
F1 F2
F3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
6'
3' -3
2'
-9
6'
7' -8
6' 6"6"
PLAN VIEW SECTION A-A
BILL OF MATERIALS
REFERENCE
NUMBER ITEM
1 BRANCH BREAKER, 208 VOLT, 100 AMP, 3 POLE
2 3" GROUND HUB, NEMA 3R OR EQUAL
3 STYLE LB, 3" CONDUIT BODY
4 STYLE LR, 3" CONDUIT BODY
5 3" RMC CONDUIT
6 #1 CU CONDUCTOR THWN-2
7 #4 CU CONDUCTOR GRN INSULATION THWN-2
MAKE READY INSTALLATION
SECTION A-A
3" C
LR
(T
YP
2'
M
IN
IM
U
M C
O N
D U
IT
B
U R
IA
L
D
EP
TH
S
H
AL
L
BE
3" CLR.
(TYP)
#4 @ 12" O.C.
EACH WAY
FINISHED
GRADE
RIGID METALLIC CONDUIT
THREADED PLUG
SCH. 40 PVC THREADED
MALE ADAPTER
SCH. 40 PVC CONDUIT SWEEP
(K#)
TRIM EXISTING PVC
CONDUIT 12" ABOVE
CONCRETE SURFACE.
PROTECT CONDUCTORS,
TO REMAIN.
PROPOSED PVC
FROM
DISTRIBUTION
PANEL TO EVCS
CHARGER
SCH. 40 PVC CONDUIT
(AS NEEDED)
SCH. 40 PVC COUPLER
(TYP)
SCH. 40 PVC CONDUIT (TYP).
1' 1'
2'
1' 1'
2'
PLAN VIEW
FRONT
BACK
3.74" DIA. CONDUIT STUB-UP
OPENING WITHIN THIS AREA
A A
PVC ELECTRICAL
CONDUIT STUB
AND CAP
PROPOSED 4,000 PSI
CONCRETE PAD
M
IN
6" (M
IN
2"
VARIES
(SEE PLAN)
7-INCH OF 3/4-INCH MEDIUM, TYPE B ASPHALT CONCRETE
SAWCUT T-SECTION AND MATCH ADJACENT
ASPHALT CONCRETE
METALLIC WARNING TAPE
95% MINIMUM RELATIVE
COMPACTED NATIVE
BACKFILL UNDER CONCRETE
AND ASPHALT AREAS, PER
ASTM D1557. 90% MINIMUM
RELATIVE COMPACTED
NATIVE BACKFILL UNDER
LANDSCAPE AREAS, PER
ASTM D1556 AND ASTM
D1557. SEE NOTE 3 ELECTRICAL CONDUIT,
SEE ELECTRICAL PLANS
FOR SIZE AND COUNT
(TYP). SEE NOTE 3
24" (MAX) DEPTH, AT LEAST 12" ABOVE
CONDUIT (SEE NOTE 1)
EXISTING ELECTRICAL CONDUIT WHERE
APPLICABLE
EXISTING ELECTRICAL
CONDUIT CROSSING
WHERE APPLICABLE
MINIMUM CONDUIT
BURIAL DEPTH
SHALL BE 24".
TRENCH RESURFACING
IN CONCRETE AREA
TRENCH RESURFACING
IN ASPHALT AREA
95% MINIMUM RELATIVE
COMPACTED NATIVE
MATERIAL IN TOP 2' OF
TRENCH
SAWCUT AND
MATCH
ADJACENT
CONCRETE
6"
(MIN)
CALTRANS CLASS 3
CONCRETE
EXISTING CONCRETE
6"
EXISTING ASPHALT CONCRETE PAVEMENT
EXISTING
CURB
6"
SEE NOTE 2
NOTES:
1. PER NEC 300.5 (D)(3), UNDERGROUND
SERVICE CONDUCTORS THAT ARE
NOT ENCASED IN CONCRETE AND
THAT ARE BURIED 450MM (18") OR
MORE BELOW GRADE SHALL HAVE
THEIR LOCATION IDENTIFIED BY A
WARNING RIBBON THAT IS PLACED IN
THE TRENCH AT LEAST 300MM (12")
ABOVE THE UNDERGROUND
INSTALLATION.
2. APPLY SLURRY COAT IN A UNIFORM
THICKNESS IN ACCORDANCE WITH
ASTM D3910 AND ALLOW TO CURE
FOR A MINIMUM OF 5 DAYS. ROLL
SLURRY SEAL TO REMOVE RIDGES
AND PROVIDE A UNIFORM, SMOOTH
SURFACE.
3. DIRECT BURIED UTILITY TRENCH
BACKFILL SHALL COMPLY WITH THE
FOLLOWING SPECIFICATIONS:
- SECTION 31 20 00, EARTH MOVING
- SECTION 26 05 43, UNDERGROUND
DUCTS AND RACEWAYS FOR
ELECTRICAL SYSTEMS
- SECTION 32 12 16, ASPHALT PAVING
- SECTION 03 30 00, CAST-IN-PLACE
CONCRETE3" CLEAN SAND BEDDING
TO BE PLACED BELOW
AND ABOVE CONDUIT
PER ASTM C33/C33M;
FINE AGGREGATE
EXISTING WALL SEE CONDUIT SCHEDULE
ON SHEET E1.0.
T BODY CONDUIT CAN
BE REPLACED BY LR
OR LL CONDUIT BODY
IF END OF RUN
10'-0" MAX INTERVAL, 3'-0" MAX
FROM EACH JUNCTION/PULL BOX,
CABINET OR OTHER TERMINATION.
BILL OF MATERIALS
REFERENCE
NUMBER ITEM
1 STANDARD PINCH CLAMP
2 GALVANIZED STRUT SQUARE POST BASE
3 3/8" BOLT ANCHOR WITH 2-3/8" MIN
PENETRATION BOLT IN CONCRETE.
EXISTING
WALL
NOTE:
1. BOXES AND CONDUIT BODIES USED AS PULL OR JUNCTION BOXES SHALL COMPLY
WITH NEC 314.28(A) THROUGH (E); PULL AND JUNCTION BOXES AND CONDUIT BODIES.
CONDUIT SIZE
AND TYPE
PER PLANS
EXISTING WALL
SEE CONDUIT SCHEDULE
ON SHEET E1.0.
EMERGENCY SHUT-OFF
EVCS-#
LOCATED IN/AT
(PANEL __)
5"
1/
2"
1/4"
(TYP)
1/4"
(TYP)
7/ 8"
1/ 4"
1/ 4"
1/ 4"
1/ 4"
1/ 4"
1/ 4"
1/ 4"
7/ 8"
3/ 4"
2" 3/
4"
3/8" 4 3/8" 3/8"
SEE NOTES 1, 4 & 6
SEE NOTES 1, 2, 3 & 5. TEXT TO BE PRINTED
IN THE COLOR WHITE NOT BLACK
SEE NOTE 1
NOTES:
1. ELECTRICAL VEHICLE CHARGING
STATION SHUT-OFF LABEL TO HAVE
WHITE LETTERS ON RED FIELD. WITH
RED AND WHITE DIAGONAL STRIPED
BORDER.
2. EMERGENCY SHUT-OFF LABEL SHALL
READ THE EVCS-# THAT IS CORRELATED
WITH ONE ANOTHER. SEE BELOW FOR
EXAMPLE:
EMERGENCY SHUT-OFF
EVCS-1
LOCATED IN/AT
(PANEL __)
3. FOR EVCS-# AND LABELING, SEE
ELECTRICAL SCHEDULE & CIRCUITS ON
SHEET ___.
4. EMERGENCY SHUT-OFF LABEL TO BE
SELF-ADHESIVE: VINYL, THERMAL,
TRANSFER-PRINTED, 5.5-MIL-THICK,
MULTICOLOR, WEATHER AND
UV-RESISTANT, PRESSURE-SENSITIVE
ADHESIVE LABELS, CONFIGURED FOR
INTENDED USE AND LOCATION.
5. THE TEXT HEIGHT SHALL BE 1/4" HIGH
WITH WHITE LETTERING.
6. EMERGENCY -SHUT-OFF LABEL SHALL
COMPLY WITH THE FOLLOWING
SPECIFICATION:
- SECTION 26 05 53, IDENTIFICATION FOR
ELECTRICAL SYSTEMS
7. PLACE EMERGENCY SHUT-OFF LABEL
ON EACH EVCS CHARGER.
BILL OF MATERIALS
REFERENCE
NUMBER ITEM
1 STYLE T, 3" CONDUIT BODY
2 3" PIPE CLAMP
3 3" RMC CONDUIT
4 2-1/2" PIPE CLAMP
5 2-1/2" RMC CONDUIT
BILL OF MATERIALS
REFERENCE
NUMBER ITEM
1 STYLE LR, 3" CONDUIT BODY
2 3" PIPE CLAMP
3 3" RMC CONDUIT
CONDUIT SECTIONS & DETAILS
E2.0
B E2.0
MAKE READY INSTALLATION WITH STUB AND CAP
NOT TO SCALE
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _d t0 2.
dw g;
E 2.
C on du it Se ct io ns
D et ai ls
BC
F.
ct b Pl ot b y:
d he rn an de z F eb
2,
- 7 :1
2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
A E2.0
EXISTING SERVICE CT METER AND MAIN SWITCHBOARD
NOT TO SCALE
C E2.0
TYPICAL ELECTRICAL UTILITY TRENCH
NOT TO SCALE
E E2.0
HOME RUN
NOT TO SCALE
D E2.0
TYPICAL WALL MOUNTING DETAIL
NOT TO SCALE
F E2.0
LR CONDUIT BODY
NOT TO SCALE
E E2.0
EMERGENCY LABEL SHUT OFF
NOT TO SCALE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
YΔ
M
75kVA, 208/120V, 3Ø, 4W
SERVICE CT METER AND MAIN SWITCHBOARD,
400 AMP BUS, 400 AMP MAIN,
208Y/120V, 3Ø, 4W
(NEMA 3R)
EXISTING OVERHEAD
TRANSFORMER
(kVA RATING PER PG&E)
PULL SECTION CT
METERING
SECTION
LANDING
LUGS (TYP)
MAIN
400A 3P
TO EXISTING
PANEL A
TO EXISTING
PANEL B
TO EXISTING
PANEL C
TO EXISTING
PANEL D
UNKNOWN
2P 100A
TO EVCS-1
CHARGE PORT 1 & 2
(80 FLA + 80 FLA)
2P 100A
TO EVCS-2
CHARGE PORT 3
(80 FLA)
2-1/2" A.G. RMC
TO TRANSITION TO
2-1/2" U.G. PVC WITH
(2) #1 Cu AND
(1) #4 Cu GND
(1) PULL TAPE
3" A.G. RMC WITH
(6) #1 Cu AND
(3) #4 Cu GND
100A 3P
200A 3P
70A 3P
100A 3P
60A 3P
TO EXISTING
WELDER
70A 2P
2P 100A
2-1/2" A.G. RMC
TO TRANSITION TO
2-1/2" U.G. PVC WITH
(4) #1 Cu AND
(2) #4 Cu GND
EXISTING SERVICE CT METER AND MAIN SWITCHBOARD
BUS AMPS: 400 NEMA: 3R MFR: Z-POWER LOC: DOT - DISTRICT 6 CALTRANS
COALINGA MTG: SURFACE MAIN AMPS: 400
PHASE: 3 WIRES: 4 VOLTS: 208Y/120V FEEDER: BUS FEED FEEDER ENTRY AT: BOTTOM AIC RATING:
DESCRIPTION
VOLT-AMPS
BKR TRIP CKT
L1 L2 L3
CKT BKR TRIP
VOLT-AMPS
DESCRIPTION
L1 L2 L3 L1 L2 L3
EXISTING PANEL "A"
0.0 0.0 0.0
100A/3P
1 2
200A/3P
0.0 0.0 0.0
EXISTING PANEL "B"0.0 0.0 0.0 3 4 0.0 0.0 0.0
0.0 0.0 0.0 5 6 0.0 0.0 0.0
EXISTING PANEL "C"
0.0 0.0 0.0
70A/3P
7 8
100A/3P
0.0 0.0 0.0
EXISTING PANEL "D"0.0 0.0 0.0 9 10 0.0 0.0 0.0
0.0 0.0 0.0 11 12 0.0 0.0 0.0
UNKNOWN EXISTING LOAD
0.0 0.0 0.0
60A/3P
13 14
70A/2P
0.0 0.0 0.0
EXISTING WELDER0.0 0.0 0.0 15 16 0.0 0.0 0.0
0.0 0.0 0.0 17 18 0.0 0.0 0.0
PROPOSED EVCS-1
(CHARGE PORT 1)
8320.0 0.0 0.0 100A/2P
19 20 - 0.0 0.0 0.0 -
0.0 8320.0 0.0 21 22 - 0.0 0.0 0.0 -
PROPOSED EVCS-1
(CHARGE PORT 2)
0.0 0.0 8320.0 100A/2P
23 24 - 0.0 0.0 0.0 -
8320.0 0.0 0.0 25 26 - 0.0 0.0 0.0 -
PROPOSED EVCS-2
(CHARGE PORT 3)
0.0 8320.0 0.0 100A/2P
27 28 - 0.0 0.0 0.0 -
0.0 0.0 8320.0 29 30 - 0.0 0.0 0.0 -
- 0.0 0.0 0.0 - 31 32 - 0.0 0.0 0.0 -
- 0.0 0.0 0.0 - 33 34 - 0.0 0.0 0.0 -
- 0.0 0.0 0.0 - 35 36 - 0.0 0.0 0.0 -
CONNECTED LOAD > 16640.0 16640.0 16640.0 ESTIMATED TOTAL VOLT-AMPERES 0.0 0.0 0.0 < CONNECTED LOAD
LINE 1 AMP: 138.7A L1 L2 L3 REMARKS:
LINE 2 AMP: 138.7A
16640.0 VA 16640.0 VA 16640.0 VA
49.9KVA TOTAL ESTIMATED CONNECTED LOAD: 173.2A @ 3PH, 208V
(AT 125% CONTINUOUS LOAD, AT UNITY)LINE 3 AMP: 138.7A
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _d t0 3.
dw g;
E 3.
El ec tri ca l S ch ed ul e
C irc ui ts
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
NOTES:
1. EXISTING TOTAL CONNECTED 3-PH KVA: 14.3 KVA AT UNITY
ADDITIONAL TOTAL CONNECTED 3-PH KVA: 49.920 KVA AT UNITY
TOTAL CONNECTED 3-PH KVA: 64.220 KVA
2. TAGGED (CHARGE PORT-#, L1/L2/GND) TYPICAL FOR ALL STATIONS.
3. DO NOT USE GFCI BREAKERS
4. STANDARD RATED SERVICE PANELS, OVER CURRENT PROTECTION DEVICES AND WIRE SIZES BASED ON CEC/NEC REQUIREMENTS AT 125% CONTINUOUS LOAD. 100% RATED SERVICE PANELS, OVER CURRENT PROTECTION DEVICES AND WIRE SIZES BASED ON CEC/NEC REQUIREMENTS AT 100% CONTINUOUS LOAD.
5. TRANSFORMER LOADING BASED ON KVA REQUIREMENTS OF CHARGER AT 0.95 PF (16.640 KVA/CHARGER).
6. DISTRIBUTION PANEL AND STEP DOWN TRANSFORMER TO SHARE GROUND RODS.
7. , INDIVIDUAL CHARGE PORT NUMBER. THIS IS NOT BREAKER SPACE OR EVCS NUMBER. LOAD
SCHEDULE INDICATES BREAKER SPACE FOR EACH CHARGE PORT.
8. , INDIVIDUAL CHARGE PORT NUMBER TYPICAL FOR PORTS THROUGH .
9. ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH
ADMINISTRATION.
10. PER CEC/NEC 210.19 (A) INFORMATIONAL NOTE #4, "CONDUCTORS FOR BRANCH CIRCUITS AS DEFINED IN ARTICLE 100, SIZED TO PREVENT A VOLTAGE DROP EXCEEDING 3 PERCENT AT THE FARTHEST OUTLET OF POWER, HEATING, AND LIGHTING LOADS, OR COMBINATION OF SUCH LOADS, AND WHERE THE MAXIMUM TOTAL VOLTAGE DROP ON BOTH FEEDERS AND BRANCH CIRCUITS TO THE FARTHEST OUTLET DOES NOT
EXCEED 5%."
11. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH GROUNDING
AND BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING CONDUCTIVE MATERIALS,
ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT THAT ENCLOSES OR CARRIES
ELECTRICAL CONDUCTOR OR EQUIPMENT THAT IS LIKELY TO BECOME ENERGIZED. SEE CEC/NEC
250.4(A)(1) THROUGH (5) FOR FURTHER DESCRIPTION.
12. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION SHALL BE 6' PER
CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
13. MAXIMUM VOLTAGE DROP FOR CONDUCTORS:
FROM EXISTING 400A SERVICE CT METER AND MAIN SWITCHBOARD TO EVCS-2:
#1 WIRE = 1.9%
14. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED FOR TERMINATION OF ELECTRICAL CONDUCTORS RATED
75°C OR HIGHER.
15. ALL BREAKERS INSTALLED UNDER THIS DESIGN SHALL BE ABLE TO BE LOCKED IN THE OPEN POSITION
PER NEC 625.43 AND 110.25.
16. NEW BREAKERS SHALL MATCH EXISTING PANEL MANUFACTURER SPECIFICATIONS AND KAIC RATING.
17. COLOR-CODING FOR PHASE- AND VOLTAGE-LEVEL IDENTIFICATION, 600V OR LESS: USE COLORS LISTED
BELOW FOR UNDERGROUND SERVICE, FEEDER, AND BRANCH-CIRCUIT CONDUCTORS.
COLORS FOR 208/120-V CIRCUITS:
A. PHASE A: BLACK
B. PHASE B: RED
C. PHASE C: BLUE
18. METER PHYSICAL CHARACTERISTICS:
1. DISPLAY: BACKLIT LCD WITH ANTIGLARE AND SCRATCH-RESISTANT LENS.
2. DISPLAY OF METERED VALUES: ONE SCREEN TO SHOW AT LEAST FOUR LINES OF USER-SELECTED
VALUES ON ONE SCREEN AT THE SAME TIME. PROVIDE GRAPHICAL REPRESENTATION OF
USER-SELECTED VALUES. THE SCREEN SELECTIONS AVAILABLE AT THE DISPLAY MUST INCLUDE THE
FOLLOWING:
A. METERS, INCLUDING THOSE LISTED UNDER THE FOLLOWING:
1) MEASUREMENTS.
2) THD.
3) ENERGY.
4) DEMAND.
5) MINIMUM AND MAXIMUM VALUES.
6) POWER DEMAND.
3. ELECTRICAL POWER MONITORING TO COMPLY WITH SECTION 26 09 13
19. ALL EXISTING ELECTRICAL EQUIPMENT RATINGS, SIZES, AND CONDUITS ARE TAKEN FROM SITE WALK.
CONTRACTOR TO VERIFY EQUIPMENT ON-SITE AND ALERT ENGINEERING TEAM IMMEDIATELY IF ANY
DISCREPANCIES ARE FOUND.
20. CONTRACTOR TO VERIFY THE EXISTING LOAD DRAWN BY EXISTING PANEL AND VERIFY THAT THE
EXISTING PANEL WILL HAVE THE CAPACITY TO
SUPPORT THE PROPOSED LOADS.
21. EXISTING SWITCHBOARD LOAD CALCULATIONS:
- EXISTING MAX DEMAND PER UTILITY RECORDS: 39.69 @ 208Y = 14.3 KVA
- ADJUST EXISTING MAX DEMAND PER NEC SECTION 220.87(2): 17.88 KVA
- ADDITIONAL DEMAND FROM CHARGERS: 49.92 KVA
- 125% CONTINUOUS DEMAND FROM CHARGERS: 62.40 KVA
- NEW TOTAL DEMAND: 80.28 KVA
- RESULTS IN TOTAL CURRENT OF 222.83 AMPS @ 208Y VOLTS
(55.71% OF 400 AMP MAIN BREAKER OCPD)
A E3.0
SINGLE LINE DIAGRAM
NOT TO SCALE
B E3.0
LOAD SCHEDULE
NOT TO SCALE
BREAKER TRIP SETTINGS:
1. WHEN SELECTING FOR ADJUSTABLE LSIG BREAKERS, USE THE FOLLOWING GUIDELINES.
- FOR LONG DELAY, SHORT DELAY, AND INSTANTANEOUS CURRENT SETTINGS, USE THE MINIMUM CURRENT SETPOINTS AVAILABLE, NOT LESS THAN THE CURRENT RATING OF THE INSTALLED TRIP PLUG.
- FOR LONG DELAY AND SHORT DELAY TIME SETTINGS, USE THE SHORTEST TIME DELAY AVAILABLE, UNLESS A LINGER DELAY IS REQUIRED TO ALLOW FOR INRUSH CURRENT.
- FOR GROUND FAULT CURRENT SETTING, USE THE MINIMUM SETPOINT AVAILABLE.
- FOR GROUND FAULT TIME SETTING, USE THE SHORTEST TIME DELAY AVAILABLE.
- IF QUESTIONS OR CONCERNS ARISE ABOUT THESE SETPOINT GUIDELINES, CONTACT ENGINEER OF
RECORD IMMEDIATELY.
2. IF THE BREAKER INCLUDES AN ARC ENERGY REDUCTION OR MAINTENANCE MODE SETTING, PLEASE USE THE
SETPOINT CORRESPONDING TO THE MINIMUM PICKUP CURRENT AND MAXIMUM ARC ENERGY REDUCTION.
ELECTRICAL SCHEDULE & CIRCUITS
E3.0
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _d t0 4.
dw g;
R 1.
R ef er en ce
D ra w in gs
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
REFERENCE DRAWINGS
R1.0A R1.0
CHARGEPOINT CP6000
DUAL PORT PEDESTAL INSTALLATION
NOT TO SCALE
B E2.0
E E2.0
1'-115 16"
8"
SECTION A-A
WEIGHT = 337 LBS
EMERGENCY SHUT-OFF
EVCS-#
LOCATED IN/AT
(PANEL __)
EACH BOLT MUST EXTEND BETWEEN 2.4" AND 4"
ABOVE CONCRETE SURFACE
CHARGEPOINT CONCRETE MOUNTING
TEMPLATE KIT (CMT), INSTALL PER
MANUFACTURER'S RECOMMENDATIONS
EXISTING CONDUIT
TRIM EXISTING PVC CONDUIT 12" ABOVE CONCRETE
SURFACE. PROTECT CONDUCTORS, TO REMAIN.
MAKE READY INSTALLATION
WITH STUB & CAP PER
DETAIL
EMERGENCY SHUT-OFF
LABEL PER DETAIL
4' -8
9 16
5' -1
11 2" C
H
AR
G
EP
O
IN
T C
M K
AT
TA
C H
M
EN
T H
EI
G
H T
IS
D
EP
EN
D
AN
T O
N M
O D
EL
C
H O
SE
N
8' -0
3 4" C
H
AR
G
EP
O
IN
T C
M K
AT
TA
C H
M
EN
T H
EI
G
H T
IS
D
EP
EN
D
AN
T O
N M
O D
EL
C
H O
SE
N
2' -1
13 8"
3" C
LR
3" C
LR
2'
3" CLR.
(TYP)
4' (M
AX
1'
#4 @ 12" O.C.
EACH WAY
INSTALL PER CHARGEPOINT
STRUCTURAL AND
MANUFACTURER'S
INSTRUCTIONS
81 2" 2"
11 2" 215 16
3 16
37 8"
1 2"
7 16
1 16
2' A A
8" 2 5
16" 2 9 16" 2 9
16" 2 5 16"
9 7 16" 2 9
16" 2 9 16"
PLAN VIEW
FRONT
BACK
CMK AND PEDESTAL
FOOTPRINT
0.63" DIA. BOLT OR
ANCHOR OPENING
(TYP OF 3)5.87" DIA. BOLT
OR ANCHOR
CIRCLE
3.74" DIA. CONDUIT
STUB-UP OPENING
WITHIN THIS AREA
CHARGEPOINT
UPPER TEMPLATE
PROPOSED 4,000 PSI
CONCRETE PAD
9 7 16"
8"
2'
6" 6"
6"
B R1.0
CHARGEPOINT CP6000 HARDWARE / MODEL
NOT TO SCALE
D R1.0
CHARGEPOINT CP6000 SPECIFICATIONS
NOT TO SCALE
C R1.0
CHARGEPOINT CP6000 DUAL AND SINGLE
PORT PEDESTAL DIMENSIONS
NOT TO SCALE
NOTE:
1. REFER TO INSTALLATION MANUAL FOR ADDITIONAL INFORMATION.
NO POWER SELECT,
CHARGER TO BE AT
80FLA
NOTE:
1. REFER TO INSTALLATION MANUAL FOR ADDITIONAL INFORMATION.
NOTE:
1. REFER TO INSTALLATION MANUAL FOR ADDITIONAL INFORMATION.
NO POWER SELECT,
CHARGER TO BE AT
80FLA
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2556
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF TRANSPORTATION
7-30-2024 12
RF
RC
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
DOT 6 - DISTRICT 6 COALINGA
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g:
P
:\2
\2
-0
2\ Si te \D
O T
- D is tri ct
C al tra ns _C oa lin ga \C on st ru ct io n
D oc um en t\P ro du ct io nD ra w in gs
\2
2_
D O
TD
6C
C _d t0 4.
dw g;
R 1.
R ef er en ce
D ra w in gs
BC
F.
ct b
Pl ot b y:
d he rn an de z
F eb
2,
- 7
:1 2a m
PROJECT #: 000000000013444
PLAN CHECK NUMBER: 24-2556
Date Signed:
07-30-2024
1ST COMMENTS
30933 W GALE AVE, COALINGA, CA 93210
V3
REFERENCE DRAWINGS
R1.1
NOTE:
1. REFER TO INSTALLATION MANUAL FOR ADDITIONAL INFORMATION.
A R1.1
CHARGEPOINT CP6000
SINGLE PORT PEDESTAL INSTALLATION
NOT TO SCALE
WEIGHT = 324 LBS
EMERGENCY SHUT-OFF
EVCS-#
LOCATED IN/AT
(PANEL __)
1'-115 16"
8"
EACH BOLT MUST EXTEND BETWEEN 2.4" AND 4"
ABOVE CONCRETE SURFACE
CHARGEPOINT CONCRETE MOUNTING
TEMPLATE KIT (CMT), INSTALL PER
MANUFACTURER'S RECOMMENDATIONS
EXISTING CONDUIT
TRIM EXISTING PVC CONDUIT 12" ABOVE CONCRETE
SURFACE. PROTECT CONDUCTORS, TO REMAIN.
MAKE READY INSTALLATION
WITH STUB & CAP PER
DETAIL
EMERGENCY SHUT-OFF
LABEL PER DETAIL
4' -8
9 16
5' -1
11 2" C
H
AR
G
EP
O
IN
T C
M K
AT
TA
C H
M
EN
T H
EI
G
H T
IS
D
EP
EN
D
AN
T O
N M
O D
EL
C
H O
SE
N
8' -0
3 4" C
H
AR
G
EP
O
IN
T C
M K
AT
TA
C H
M
EN
T H
EI
G
H T
IS
D
EP
EN
D
AN
T O
N M
O D
EL
C
H O
SE
N
2' -1
13 8"
4' (M
AX
1'
81 2" 2"
11 2" 215 16
3 16
37 8"
1 2"
7 16
1 16
2' A A
8" 2 5
16" 2 9 16" 2 9
16" 2 5 16"
9 7 16" 2 9
16" 2 9 16"
PLAN VIEW
FRONT
BACK
CMK AND PEDESTAL
FOOTPRINT
0.63" DIA. BOLT OR
ANCHOR OPENING
(TYP OF 3)5.87" DIA. BOLT
OR ANCHOR
CIRCLE
3.74" DIA. CONDUIT
STUB-UP OPENING
WITHIN THIS AREA
CHARGEPOINT
UPPER TEMPLATE
PROPOSED 4,000 PSI
CONCRETE PAD
9 7 16"
8"
2'
B E2.0
E E2.0
SECTION A-A
3" C
LR
3" C
LR
2'
3" CLR.
(TYP)
#4 @ 12" O.C.
EACH WAY
INSTALL PER CHARGEPOINT
STRUCTURAL AND
MANUFACTURER'S
INSTRUCTIONS
6" 6"
6"
B R1.1
CHARGEPOINT CP6000 HARDWARE / MODEL
NOT TO SCALE
D R1.1
CHARGEPOINT CP6000 SPECIFICATIONS
NOT TO SCALE
C R1.1
CHARGEPOINT CP6000 DUAL AND SINGLE
PORT PEDESTAL DIMENSIONS
NOT TO SCALE
NOTE:
1. REFER TO INSTALLATION MANUAL FOR ADDITIONAL INFORMATION.
NO POWER SELECT,
CHARGER TO BE AT
80FLA
OFFICE OF THE STATE FIRE MARSHAL
shall be…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .