This document is a draft technical specification for switchboards (Section 26 24 13) for the Power Independence Mission Control Station project at Buckley Space Force Base in Colorado. The specification provides comprehensive technical requirements for switchboard design, construction, components, testing, and installation, covering detailed technical specifications including:

Key technical requirements include NEMA PB 2 and UL 891 compliance, specifications for bus bars, protective devices (circuit breakers), electronic trip units, metering, microprocessor control logic, and grounding systems. The specification mandates specific testing protocols, including visual and mechanical inspections, electrical tests, and follow-up verification procedures. The switchboard is intended for a 480Y/277 volt, three-phase electrical system with specific requirements for enclosure construction, circuit breaker types (including insulated-case and molded-case breakers), and advanced control and monitoring capabilities through a microprocessor-based controller with color display and extensive configuration options.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Power I ndependence, Mi ssi on Cont r ol St at i on - Buckl ey SFB, CO BUCO00102

SECTI ON TABLE OF CONTENTS

DI VI SI ON 26 - ELECTRI CAL

SECTI ON 26 24 13

SWI TCHBOARDS

08/ 21

PART 1 GENERAL

1. 1 REFERENCES

1. 2 RELATED REQUI REMENTS

1. 3 SUSTAI NABI LI TY REQUI REMENTS

1. 4 DEFI NI TI ONS

1. 5 SUBMI TTALS

1. 6 QUALI TY ASSURANCE

1. 6. 1 Pr oduct Dat a

1. 6. 2 Swi t chboar d Dr awi ngs

1. 6. 3 Regul at or y Requi r ement s

1. 6. 4 St andar d Pr oduct s

1. 6. 4. 1 Al t er nat i ve Qual i f i cat i ons

1. 6. 4. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

1. 7 MAI NTENANCE

1. 7. 1 Swi t chboar d Oper at i on and Mai nt enance Dat a

1. 7. 2 Assembl ed Oper at i on and Mai nt enance Manual s

1. 8 WARRANTY

PART 2 PRODUCTS

2. 1 PRODUCT COORDI NATI ON

2. 2 SWI TCHBOARD

2. 2. 1 Rat i ngs

2. 2. 2 Const r uct i on

2. 2. 2. 1 Encl osur e

2. 2. 2. 2 Bus Bar s

2. 2. 2. 3 Mai n Sect i on

2. 2. 2. 4 Di st r i but i on Sect i ons

2. 2. 2. 5 Auxi l i ar y Sect i ons

2. 2. 2. 6 Handl es

2. 2. 3 Pr ot ect i ve Devi ce

2. 2. 3. 1 I nsul at ed- Case Br eaker

2. 2. 3. 2 Mol ded- Case Ci r cui t Br eaker

2. 2. 4 El ect r oni c Tr i p Uni t s

2. 2. 5 Mi cr opr ocessor Cont r ol Logi c

2. 2. 6 Cont r ol l er and Keypad

2. 2. 7 Ter mi nal Boar ds

2. 2. 8 Wi r e Mar ki ng

2. 3 MANUFACTURER' S NAMEPLATE

2. 4 FI ELD FABRI CATED NAMEPLATES

2. 5 SOURCE QUALI TY CONTROL

2. 5. 1 Equi pment Test Schedul e

2. 5. 2 Swi t chboar d Desi gn Test s

2. 5. 2. 1 Desi gn Test s

2. 5. 2. 2 Addi t i onal Desi gn Test s

SECTI ON 26 24 13 Page 1

2. 5. 3 Swi t chboar d Pr oduct i on Test s

2. 6 COORDI NATED POWER SYSTEM PROTECTI ON

2. 7 ARC FLASH WARNI NG LABEL

2. 8 SURGE PROTECTI VE DEVI CE( S)

PART 3 EXECUTI ON

3. 1 I NSTALLATI ON

3. 2 SEQUENCE OF OPERATI ONS ( Ref er ence Sheet EP601, MECHANI CAL

SWI TCHBOARD A & B)

3. 2. 1 Nor mal Condi t i ons ( Power at Br eaker " M1" and at Br eaker " M2" )

3. 2. 2 Emer gency Condi t i on 1 ( Loss of Power at Br eaker " M1" and

Power Pr esent at Br eaker " M2" )

3. 2. 3 Emer gency Condi t i on 2 ( Power Pr esent at Br eaker " M1" and Loss of Power at Br eaker " M2" )

3. 3 GROUNDI NG

3. 3. 1 Equi pment Gr oundi ng

3. 3. 2 Connect i ons

3. 3. 3 Gr oundi ng and Bondi ng Equi pment

3. 4 I NSTALLATI ON OF EQUI PMENT AND ASSEMBLI ES

3. 4. 1 Swi t chboar d

3. 4. 2 Met er s and I nst r ument Tr ansf or mer s

3. 4. 3 Fi el d Appl i ed Pai nt i ng

3. 4. 4 Gal vani z i ng Repai r

3. 4. 5 Fi el d Fabr i cat ed Namepl at e Mount i ng

3. 5 FOUNDATI ON FOR EQUI PMENT AND ASSEMBLI ES

3. 5. 1 I nt er i or Locat i on

3. 6 FI ELD QUALI TY CONTROL

3. 6. 1 Per f or mance of Accept ance Checks and Test s

3. 6. 1. 1 Swi t chboar d Assembl i es

3. 6. 1. 2 Ci r cui t Br eaker s - Low Vol t age - Power

3. 6. 1. 3 Ci r cui t Br eaker s

3. 6. 1. 4 Cur r ent Tr ansf or mer s

3. 6. 1. 5 Met er i ng and I nst r ument at i on

3. 6. 1. 6 Gr oundi ng Syst em

3. 6. 1. 7 Cyber secur i t y I nst al l at i on Cer t i f i cat i on

3. 6. 2 Fol l ow- Up Ver i f i cat i on

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 26 24 13 Page 2

SECTI ON 26 24 13

SWI TCHBOARDS

08/ 21

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )

ANSI C12. 1 ( 2014; Er r at a 2016) El ect r i c Met er s - Code f or El ect r i c i t y Met er i ng

ASTM I NTERNATI ONAL ( ASTM)

ASTM A123/ A123M ( 2017) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s

ASTM A153/ A153M ( 2016a) St andar d Speci f i cat i on f or Zi nc Coat i ng ( Hot - Di p) on I r on and St eel Har dwar e

ASTM A240/ A240M ( 2022b) St andar d Speci f i cat i on f or Chr omi um and Chr omi um- Ni ckel St ai nl ess St eel Pl at e, Sheet , and St r i p f or Pr essur e Vessel s and f or Gener al Appl i cat i ons

ASTM A653/ A653M ( 2022) St andar d Speci f i cat i on f or St eel Sheet , Zi nc- Coat ed ( Gal vani zed) or Zi nc- I r on Al l oy- Coat ed ( Gal vanneal ed) by t he Hot - Di p Pr ocess

ASTM A780/ A780M ( 2020) St andar d Pr act i ce f or Repai r of Damaged and Uncoat ed Ar eas of Hot - Di p Gal vani zed Coat i ngs

ASTM D149 ( 2020) Di el ect r i c Br eakdown Vol t age and Di el ect r i c St r engt h of Sol i d El ect r i cal I nsul at i ng Mat er i al s at Commer ci al Power Fr equenci es

ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s

ASTM D1535 ( 2014; R 2018) St andar d Pr act i ce f or Speci f y i ng Col or by t he Munsel l Syst em

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 81 ( 2012) Gui de f or Measur i ng Ear t h Resi st i v i t y, Gr ound I mpedance, and Ear t h

SECTI ON 26 24 13 Page 3

Sur f ace Pot ent i al s of a Gr ound Syst em

I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms

I EEE C2 ( 2023) Nat i onal El ect r i cal Saf et y Code

I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment

- Encl osur e I nt egr i t y

I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)

NETA ATS ( 2021) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

ANSI / NEMA PB 2. 1 ( 2013) Gener al I nst r uct i ons f or Pr oper Handl i ng, I nst al l at i on, Oper at i on and Mai nt enance of Deadf r ont Di st r i but i on Swi t chboar ds Rat ed 600 V or Less

NEMA I CS 6 ( 1993; R 2016) I ndust r i al Cont r ol and Syst ems: Encl osur es

NEMA PB 2 ( 2011) Deadf r ont Di st r i but i on Swi t chboar ds

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2023) Nat i onal El ect r i cal Code

UNDERWRI TERS LABORATORI ES ( UL)

UL 467 ( 2022) UL St andar d f or Saf et y Gr oundi ng and Bondi ng Equi pment

UL 489 ( 2016; Rev 2019) UL St andar d f or Saf et y Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches and Ci r cui t - Br eaker Encl osur es

UL 891 ( 2019) UL St andar d f or Saf et y Swi t chboar ds

1. 2 RELATED REQUI REMENTS

Sect i on 26 08 00 APPARATUS I NSPECTI ON AND TESTI NG appl i es t o t hi s sect i on, wi t h t he addi t i ons and modi f i cat i ons speci f i ed her ei n.

1. 3 SUSTAI NABI LI TY REQUI REMENTS

Mat er i al s i n t hi s t echni cal speci f i cat i on may cont r i but e t owar ds cont r act compl i ance wi t h sust ai nabi l i t y r equi r ement s. See Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG f or pr oj ect r equi r ement s.

1. 4 DEFI NI TI ONS

Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, ar e as def i ned i n

SECTI ON 26 24 13 Page 4

I EEE 100.

1. 5 SUBMI TTALS

The Cont r act or shal l not submi t nor shal l submi t t al s be consi der ed appr oved f or i nst al l at i on on any el ect r i cal equi pment cont ai ni ng over cur r ent pr ot ect i ve devi ces or r equi r i ng a shor t c i r cui t r at i ng or an ar c f l ash r at i ng unt i l t he Pr ot ect i ve Coor di nat i on wi t h Ar c Fl ash Hazar d St udy ( Sect i on 26 28 01. 00 10) has been submi t t ed f or r evi ew by t he Cont r act or and unt i l i t has been appr oved ( t r ansmi t t al " A" or " B" Act i on) by t he r evi ewi ng agent . Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e [ f or Cont r act or Qual i t y Cont r ol appr oval . ] [ f or i nf or mat i on onl y. When used, a code f ol l owi ng t he " G" c l assi f i cat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . ]

On r e- submi t t al s, t he cont r act or shal l i ncl ude t he acknowl edgement of and/ or r esponse t o al l comment s f r om t he pr i or submi t t al , i ncl udi ng i dent i f i cat i on of wher e changes ar e made i ncor por at i ng t he r evi ew comment s. Changes t o pr evi ousl y- appr oved i t ems or subpor t i ons of i t ems shal l be c l ear l y i dent i f i ed and i ncl ude a st at ement r egar di ng t he pur pose of t he change.

When submi t t i ng mul t i pl e i t ems, c l ear l y i dent i f y t he pages r el evant t o t he speci f i c i t ems r ef er enced by i t em number and i t em name. A cover sheet wi t h t he i t em number and i t em name i mmedi at el y bef or e t he f i r st page of i nf or mat i on per t ai ni ng t o a gi ven i t em i s accept abl e.

On pr oduct dat a cut sheet s submi t t ed wi t h mul t i pl e var i ant s ( model s, opt i ons, et c. ) , i dent i f y t he speci f i c model t ype( s) , opt i on( s) , et c. , whi ch wi l l be used.

Wher e mul t i pl e par t i es cont r i but e t o t he cont ent s of a par t i cul ar submi t t al i t em or l ogi cal l y- gr oup set of i t ems, al l i t ems shal l be submi t t ed i n one cohesi ve t r ansmi t t al package f or r evi ew ( t hat i s, por t i ons of i t ems shal l not be pi ecemeal ed acr oss mul t i pl e submi t t al s and/ or i nappr opr i at el y- assi gned submi t t al i t ems) .

The Cont r act or shal l submi t t he f ol l owi ng submi t t al s ( and subsequent r esubmi t t al s) t oget her :

26 20 00 I t em: Panel boar ds 26 20 00 I t em: Ci r cui t Br eaker s 26 13 01 I t em: Dead- Fr ont Ai r I nsul at ed Swt i chgear 26 13 13 I t em: Met al - Cl ad Swi t chgear

I f submi t t ed separ at el y, t he r evi ew per i od shal l st ar t upon r ecei pt of t he l ast submi t t al ( or r esubmi t t al ) i n t he package. Al l ow a mi ni mum of 40 cal endar days excl usi ve of mai l i ng f or Gover nment r evi ews and appr oval s.

Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL

PROCEDURES:

SD- 02 Shop Dr awi ngs

Swi t chboar d Dr awi ngs; G, DO[ , [ _____] ]

Swi t chboar d dr awi ngs shal l i ncl ude det ai l ed connect i on wi r i ng di agr ams and i ndi cat e al l pr ocessor s/ pl at f or ms and connect i ons t o

SECTI ON 26 24 13 Page 5 ot her syst ems such as SCADA, UMCS, Smar t Met er i ng or ot her .

I dent i f y t he smar t met er ( ut i l i t y met er i ng) encl ave and SCADA encl ave. Pr ovi de al l document at i on necessar y f or Ri sk Management Fr amewor k. Ref er t o Sect i on 25 05 11 Cyber secur i t y of Faci l i t y- Rel at ed Cont r ol Syst ems. "

Thi s i t em may ( and i s encour aged t o) be submi t t ed f or pr el i mi nar y r evi ew onl y pr i or or concur r ent t o t he submi t t al and appr oval of t he Sect i on 26 28 01. 00 10 anal yses.

Submi t t hi s i t em af t er or concur r ent t o Sect i on 26 20 00 I t em:

CFCI Equi pment El ect r i cal Dat a.

Al l ow a mi ni mum of 35 cal endar days excl usi ve of mai l i ng f or Gover nment r evi ews and appr oval s.

SD- 03 Pr oduct Dat a

Swi t chboar d; G, DO[ , [ _____] ]

Thi s i t em may ( and ar e encour aged t o) be submi t t ed f or pr el i mi nar y r evi ew onl y pr i or or concur r ent t o t he submi t t al and appr oval of t he Sect i on 26 05 73 POWER SYSTEMS STUDI ES.

Submi t t hi s i t em af t er or concur r ent wi t h Sect i on 26 20 00 I t em:

CFCI Equi pment El ect r i cal Dat a.

Al l ow a mi ni mum of 35 cal endar days excl usi ve of mai l i ng f or Gover nment r evi ews and appr oval s.

Met er i ng; G, DO

SD- 06 Test Repor t s

Swi t chboar d Desi gn Test s; G, DO[ , [ _____] ]

Swi t chboar d Pr oduct i on Test s; G, DO[ , [ _____] ]

Accept ance Checks and Test s; G, DO[ , [ _____] ]

SD- 07 Cer t i f i cat es

Cyber secur i t y I nst al l at i on Cer t i f i cat i on; G, DO[ , [ _____] ]

Submi t cer t i f i cat i on i ndi cat i ng conf or mance wi t h t he par agr aph

CYBERSECURI TY I NSTALLATI ON CERTI FI CATI ON.

SD- 10 Oper at i on and Mai nt enance Dat a

Swi t chboar d Oper at i on and Mai nt enance, Dat a Package 5; G, RO[ , SD- 11 Cl oseout Submi t t al s

Assembl ed Oper at i on and Mai nt enance Manual s; G, RO[ , [ _____] ]

Equi pment Test Schedul e; G, RO[ , [ _____] ]

[ Request f or Set t i ngs; G, RO[ , [ _____] ]

SECTI ON 26 24 13 Page 6

] [ Requi r ed Set t i ngs; G, RO[ , [ _____] ] [ Ser vi ce Ent r ance Avai l abl e Faul t Cur r ent Label ; G[ , [ _____] ]

] 1. 6 QUALI TY ASSURANCE

1. 6. 1 Pr oduct Dat a

I ncl ude manuf act ur er ' s i nf or mat i on on each submi t t al f or each component , devi ce and accessor y pr ovi ded wi t h t he swi t chboar d i ncl udi ng:

a. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.

b. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce.

1. 6. 2 Swi t chboar d Dr awi ngs

I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. I dent i f y c i r cui t t er mi nal s on wi r i ng di agr ams and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . I ndi cat e on t he dr awi ngs adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces. I ncl ude t he namepl at e dat a, s i ze, and capaci t y on submi t t al . Al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences on submi t t al s.

I ncl ude t he f ol l owi ng:

a. One- l i ne di agr am i ncl udi ng br eaker s[ , f uses] [ , cur r ent t r ansf or mer s, and met er s] .

b. Out l i ne dr awi ngs i ncl udi ng f r ont el evat i on, sect i on v i ews, f oot pr i nt , and over al l di mensi ons.

c. Bus conf i gur at i on i ncl udi ng di mensi ons and amper e r at i ngs of bus bar s.

d. Mar ki ngs and NEMA namepl at e dat a[ , i ncl udi ng f use i nf or mat i on ( manuf act ur er ' s name, cat al og number , and r at i ngs) ] .

e. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.

f . Wi r i ng di agr ams and el ement ar y di agr ams wi t h t er mi nal s i dent i f i ed, and i ndi cat i ng pr ewi r ed i nt er connect i ons bet ween i t ems of equi pment and t he i nt er connect i on bet ween t he i t ems.

g. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce. Use t hi s i nf or mat i on ( desi gner of r ecor d) t o pr ovi de br eaker set t i ngs t hat ensur es pr ot ect i on and coor di nat i on ar e achi eved. [ For Navy i nst al l at i ons, pr ovi de el ect r oni c f or mat cur ves usi ng SKM' s Power Tool s f or Wi ndows devi ce l i br ar y el ect r oni c f or mat or EasyPower devi ce l i br ar y f or mat dependi ng on i nst al l at i on model i ng sof t war e r equi r ement s. ]

SECTI ON 26 24 13 Page 7

[ h. Pr ovi s i ons f or f ut ur e expansi on by addi ng swi t chboar d sect i ons.

Swi t chboar d dr awi ngs shal l i ndi cat e t he l oad i nt ended f or each ci r cui t br eaker . A coor di nat i ng l egend/ schedul e i s accept abl e.

1. 6. 3 Regul at or y Requi r ement s

I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " or " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Pr ovi de equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.

1. 6. 4 St andar d Pr oduct s

Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p, and:

a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng i ncl udi ng appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.

b. Have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.

c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.

1. 6. 4. 1 Al t er nat i ve Qual i f i cat i ons

Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s f ur ni shed.

1. 6. 4. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e

Pr oduct s manuf act ur ed mor e t han one year pr i or t o dat e of del i ver y t o s i t e ar e not accept abl e.

1. 7 MAI NTENANCE

1. 7. 1 Swi t chboar d Oper at i on and Mai nt enance Dat a

Submi t Oper at i on and Mai nt enance Manual s i n accor dance wi t h Sect i on

01 78 23 OPERATI ON AND MAI NTENANCE DATA.

1. 7. 2 Assembl ed Oper at i on and Mai nt enance Manual s

Assembl e and secur el y bi nd manual s i n dur abl e, har d cover ed, wat er

SECTI ON 26 24 13 Page 8 r esi st ant bi nder s. Assembl e and i ndex t he manual s i n t he f ol l owi ng or der wi t h a t abl e of cont ent s:

a. Manuf act ur er ' s O&M i nf or mat i on r equi r ed by t he par agr aph SD- 10, OPERATI ON AND MAI NTENANCE DATA.

b. Cat al og dat a r equi r ed by t he par agr aph SD- 03, PRODUCT DATA.

c. Dr awi ngs r equi r ed by t he par agr aph SD- 02, SHOP DRAWI NGS.

d. Pr i ces f or spar e par t s and suppl y l i s t .

[ e. I nf or mat i on on met er i ng.

] f . Desi gn t est r epor t s.

g. Pr oduct i on t est r epor t s.

[ 1. 7. 3 Spar e Par t s

Pr ovi de spar e par t s as speci f i ed bel ow. Pr ovi de spar e par t s t hat ar e of t he same mat er i al and wor kmanshi p, meet t he same r equi r ement s, and ar e i nt er changeabl e wi t h t he cor r espondi ng or i gi nal par t s f ur ni shed.

a. Quant i t y 2 - Fuses of each t ype and si ze.

[ b. [ _____]

] ] 1. 8 WARRANTY

Pr ovi de equi pment i t ems t hat ar e suppor t ed by ser vi ce or gani zat i ons r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .

PART 2 PRODUCTS

2. 1 PRODUCT COORDI NATI ON

Pr oduct s and mat er i al s not consi der ed t o be swi t chboar ds and r el at ed accessor i es ar e speci f i ed i n Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON, and Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.

2. 2 SWI TCHBOARD

NEMA PB 2 and UL 891.

2. 2. 1 Rat i ngs

Pr ovi de equi pment wi t h t he f ol l owi ng r at i ngs:

a. Vol t age r at i ng: [ 480Y/ 277] [ 208Y/ 120] [ _____] vol t s AC, [ t hr ee- phase, [ 3] [ 4] - wi r e] [ as i ndi cat ed] .

b. Cont i nuous cur r ent r at i ng of t he mai n bus: [ _____ amper es] [ as i ndi cat ed] .

c. Shor t - c i r cui t cur r ent r at i ng: [ _____ r ms symmet r i cal amper es] [ The gr eat er of as i ndi cat ed] . on t he pl ans and t he val ue cal cul at ed i n

SECTI ON 26 24 13 Page 9

Sect i on 26 05 73 POWER SYSTEMS STUDI ES

d. UL l i s t ed and l abel ed[ as ser vi ce ent r ance equi pment ] .

2. 2. 2 Const r uct i on

Pr ovi de t he f ol l owi ng f or al l swi t chboar ds:

a. Swi t chboar d: consi st i ng of one or mor e ver t i cal sect i ons[ bol t ed t oget her t o f or m a r i gi d assembl y] and [ r ear ] [ f r ont and r ear ] al i gned[ as i ndi cat ed] .

b. Al l c i r cui t br eaker s: f r ont accessi bl e.

[ c. Rear al i gned swi t chboar ds: f r ont accessi bl e l oad connect i ons.

] [ d. Fr ont and r ear al i gned swi t chboar ds[ : r ear accessi bl e l oad connect i ons] .

] e. Wher e i ndi cat ed, " space f or f ut ur e" or " space" means t o i ncl ude a ver t i cal bus pr ovi ded behi nd a bl ank f r ont cover . Wher e i ndi cat ed, " pr ovi s i on f or f ut ur e" means f ul l har dwar e pr ovi ded t o mount a br eaker sui t abl e f or t he l ocat i on.

f . Compl et el y f act or y engi neer ed and assembl ed, i ncl udi ng pr ot ect i ve devi ces and equi pment i ndi cat ed wi t h necessar y i nt er connect i ons, i nst r ument at i on, and cont r ol wi r i ng.

2. 2. 2. 1 Encl osur e

Pr ovi de t he f ol l owi ng:

a. Encl osur e: NEMA I CS 6 Type [ 3R] [ 1] [ _____] [ as i ndi cat ed] [ f abr i cat ed ent i r el y of mi ni mum 12 gauge ASTM A240/ A240M t ype 304 or 304L st ai nl ess st eel ] .

b. Encl osur e: bol t ed t oget her wi t h r emovabl e bol t - on s i de and[ hi nged] r ear cover s[ , and sl opi ng r oof downwar d t owar d r ear ] .

[ c. Fr ont [ and r ear ] door s: pr ovi ded wi t h[ st ai nl ess st eel ] padl ockabl e vaul t handl es wi t h a t hr ee poi nt cat ch.

] [ d. Bases, f r ames and channel s of encl osur e: cor r osi on r esi st ant and f abr i cat ed of [ ASTM A240/ A240M t ype 304 or 304L st ai nl ess st eel ] [ or ] [ gal vani zed st eel ] . Separ at e sect i ons usi ng ver t i cal st eel bar r i er s.

] e. Base: i ncl udes any par t of encl osur e t hat i s wi t hi n 3 i nches of concr et e pad.

[ f . Gal vani zed st eel : ASTM A123/ A123M, ASTM A653/ A653M G90 coat i ng, and ASTM A153/ A153M, as appl i cabl e. Gal vani ze af t er f abr i cat i on wher e pr act i cabl e.

] g. Pai nt col or : ASTM D1535 l i ght gr ay No. 61 or No. 49 over r ust i nhi bi t or .

[ h. Pai nt coat i ng syst em: compl y wi t h[ I EEE C57. 12. 28 f or gal vani zed st eel ] [ and] [ I EEE C57. 12. 29 f or st ai nl ess st eel ] .

SECTI ON 26 24 13 Page 10

] 2. 2. 2. 2 Bus Bar s

Pr ovi de t he f ol l owi ng:

a. Bus bar s: [ copper wi t h s i l ver - pl at ed cont act sur f aces] [ or ] [ al umi num wi t h t i n- pl at ed cont act sur f aces] .

( 1) Phase bus bar s: [ uni nsul at ed] [ i nsul at ed wi t h a t ape wr ap or i nsul at i ng s l eeve pr ovi di ng a mi ni mum br eakdown vol t age of 16, 000 vol t s per ASTM D149] .

( 2) Neut r al bus: r at ed [ 100] [ _____] per cent of t he mai n bus cont i nuous cur r ent r at i ng[ as i ndi cat ed] .

b. Make bus connect i ons and j oi nt s wi t h har dened st eel bol t s.

c. Mai n- bus ( t hr ough bus) : r at ed at t he f ul l ampaci t y of t he mai n t hr oughout t he swi t chboar d.

d. Mi ni mum one- quar t er by 2 i nch copper gr ound bus secur ed t o each ver t i cal sect i on al ong t he ent i r e l engt h of t he swi t chboar d.

2. 2. 2. 3 Mai n Sect i on

Pr ovi de t he mai n sect i on consi st i ng of [ a combi nat i on sect i on wi t h[ mol ded- case ci r cui t br eaker s] f or t he[ mai n and] br anch devi ces as i ndi cat ed] [ mai n l ugs onl y] [ an i ndi v i dual l y mount ed [ f i xed] [ dr awout ] [ ai r power c i r cui t br eaker [ wi t h cur r ent - l i mi t i ng f uses] ] [ i nsul at ed- case ci r cui t br eaker ] [ mol ded- case ci r cui t br eaker ] ] [ and ut i l i t y t r ansf or mer compar t ment ] .

[ 2. 2. 2. 4 Di st r i but i on Sect i ons

Pr ovi de t he di st r i but i on sect i on[ s] consi st i ng of [ [ i ndi v i dual l y mount ed, ] [ dr awout , ] ] [ ai r power c i r cui t br eaker s[ wi t h cur r ent - l i mi t i ng f uses] ] [ i nsul at ed- case ci r cui t br eaker s] [ mol ded- case ci r cui t br eaker s] [ and ut i l i t y t r ansf or mer compar t ment s] as i ndi cat ed.

] [ 2. 2. 2. 5 Auxi l i ar y Sect i ons

Pr ovi de auxi l i ar y sect i ons consi st i ng of i ndi cat ed[ i nst r ument s, ] [ met er i ng equi pment , ] [ cont r ol equi pment , ] [ t r ansf or mer , ] [ and] [ cur r ent t r ansf or mer compar t ment s] as i ndi cat ed. Auxi l i ar y component s may be l ocat ed i n di st r i but i on sect i ons, space and manuf act ur er per mi t t i ng.

] [ 2. 2. 2. 6 Handl es

Pr ovi de handl es f or i ndi v i dual l y mount ed devi ces of t he same desi gn and met hod of ext er nal oper at i on. Label handl es pr omi nent l y t o i ndi cat e devi ce amper e r at i ng, col or coded f or devi ce t ype. I dent i f y ON- OFF i ndi cat i on by handl e posi t i on and by pr omi nent mar ki ng.

] 2. 2. 3 Pr ot ect i ve Devi ce

Pr ovi de[ mai n, t i e, and] br anch pr ot ect i ve devi ces as i ndi cat ed.

The ci r cui t br eaker r at i ngs i ndi cat ed on t he one- l i ne di agr am and panel schedul es ar e est i mat es based on basi s of desi gn equi pment or st andar d r at i ngs. Bot h sol i d- st at e and t her mal magnet i c- t ype ci r cui t br eaker

SECTI ON 26 24 13 Page 11 r at i ngs and/ or set t i ngs ar e subj ect t o change based on t he manuf act ur er r ecommendat i ons f or equi pment t o be pr ovi ded i n t hi s cont r act , i ncl udi ng t r ansf or mer i nr ush val ues and val ues f or equi pment not l i s t ed on t he " Equi pment El ect r i cal Connect i on Schedul e" but i s pr ovi ded as equi pment i nst al l ed under t he cont r act . Cont r act or shal l coor di nat e t he pr ot ect i on devi ce r at i ngs wi t h t he equi pment appr oved t o be i nst al l ed, i s r esponsi bl e f or pr ovi di ng t he appr opr i at e r at i ngs/ set t i ngs, and shal l i ndi cat e devi at i ons f r om t he desi gn r at i ngs i n t he submi t t al pr ocess, par t i cul ar l y when conduct or pr ot ect i on i s i mpact ed by changes i n pr ot ect i on r at i ng.

Ci r cui t br eaker t ypes must l be based on t he pr ot ect i ve coor di nat i on st udy t o sel ect i vel y coor di nat e t o t he degr ee i ndi cat ed i n Sect i on 26 05 73 POWER SYSTEM STUDI ES, such as changi ng f r om one t ype of t her mal magnet i c c i r cui t br eaker t o anot her wi t hi n t he same manuf act ur er ( i e, f r om Si emens BQD t o Si emens NGB, et c. ) . Ci r cui t br eaker s shal l not be consi der ed accept ed unt i l power syst em st udy i s accept ed wi t h " A" or " B" act i on.

[ 2. 2. 3. 1 Power Ci r cui t Br eaker

Pr ovi de t he f ol l owi ng:

a. I EEE C37. 13. [ 120 Vac] [ el ect r i cal l y] [ manual l y] oper at ed [ st at i onar y] [ dr awout ] , [ unf used] [ f used] , l ow- vol t age power c i r cui t br eaker wi t h a shor t - c i r cui t cur r ent r at i ng[ of [ _____] r ms amper es symmet r i cal ] [ as i ndi cat ed] at [ _____] vol t s.

b. Br eaker f r ame si ze: [ as i ndi cat ed] [ [ _____] amper es] .

[ c. Equi p el ect r i cal l y oper at ed br eaker s wi t h mot or - char ged, st or ed- ener gy c l osi ng mechani sm t o per mi t r api d and saf e c l osi ng of t he br eaker agai nst f aul t cur r ent s wi t hi n t he shor t t i me r at i ng of t he br eaker , i ndependent of t he oper at or ' s st r engt h or ef f or t i n c l osi ng t he handl e.

] ] [ 2. 2. 3. 1 I nsul at ed- Case Br eaker

Pr ovi de t he f ol l owi ng:

a. Mai n and Ti e Br eaker s must be UL 489. UL l i s t ed and l abel ed, [ 100 per cent r at ed mai n br eaker ] [ st andar d r at ed br anch br eaker s] , [ t r ue t wo st ep st or ed ener gy devi ces, el ect r i cal l y] [ manual l y] oper at ed unl ess ot her wi se i ndi cat ed on t he cont r act doument s. , Ci r cui t br eaker s ar e t o be l ow vol t age, i nsul at ed- case ci r cui t br eaker , wi t h a shor t - c i r cui t cur r ent r at i ng[ of [ _____] r ms symmet r i cal amper es] [ as i ndi cat ed] at 480[ _____] vol t s and have 3 cycl e shor t - t i me ci r cui t wi t hst and r at i ngs.

b. Br eaker f r ame si ze: [ [ _____] amper es] [ as i ndi cat ed] .

c. Ser i es r at ed ci r cui t br eaker s ar e unaccept abl e.

d. Al l i nsul at ed case ci r cui t br eaker s must have a namepl at e c l ear l y mar ki ng any el ect r i cal accessor i es t hat ar e mount ed i n t he br eaker at t he i nst al l at i on. The accessor y shal l have a l abel t hat wi l l i ndi cat e i t s f unct i on and vol t age. Al l accessor i es shal l be modul ar , pl ug and l ock t ype, and UL l i s t ed f or easy f i el d i nst al l at i on.

e. The br eaker cont r ol i nt er f ace must have col or - coded vi sual i ndi cat or s t o i ndi cat e cont act open or c l osed posi t i ons as wel l as mechani sm char ged and di schar ged posi t i ons. Manual cont r ol pushbut t ons on t he

SECTI ON 26 24 13 Page 12 br eaker f ace shal l be pr ovi ded f or openi ng and cl osi ng t he br eaker .

The power c i r cui t br eaker shal l have a " Posi t i ve On" f eat ur e. The br eaker f l ag wi l l r ead " Cl osed" i f t he cont act s ar e wel ded and t he br eaker i s at t empt ed t o be t r i pped or opened.

] [ 2. 2. 3. 2 Mol ded- Case Ci r cui t Br eaker

Pr ovi de t he f ol l owi ng:

a. UL 489. UL l i s t ed and l abel ed, [ 100 per cent r at ed mai n br eaker ] [ st andar d r at ed br anch br eaker s] , [ el ect r i cal l y] [ manual l y] oper at ed, l ow vol t age mol ded- case ci r cui t br eaker , wi t h a shor t - c i r cui t cur r ent r at i ng of [ [ _____] r ms symmet r i cal amper es] [ as i ndi cat ed] at [ _____] 480Y/ 277vol t s. UL 489 sol i d- st at e c i r cui t br eaker s shal l be used wher e i ndi cat ed i n 26 05 73 POWER SYSTEM STUDI ES.

b. Br eaker f r ame si ze: [ [ _____] amper es] [ as i ndi cat ed] .

c. Ser i es r at ed ci r cui t br eaker s ar e unaccept abl e.

] [ 2. 2. 3. 3 Fusi bl e Swi t ches

Pr ovi de t he f ol l owi ng:

a. Fusi bl e Swi t ches: qui ck- make, qui ck- br eak, hi nged- door t ype.

[ b. Swi t ches ser vi ng as mot or di sconnect s: hor sepower r at ed.

] c. Fuses: cur r ent - l i mi t i ng car t r i dge t ype conf or mi ng t o[ UL 198M, Cl ass J f or 0 t o 600 amper es and Cl ass L f or 601 t o 6000 amper es] [ UL 198M, Cl ass [ RK1] [ RK5] f or 0 t o 600 amper es] .

d. Fusehol der s: [ UL 4248- 1] [ UL 4248- 12] .

] [ 2. 2. 3. 4 I nt egr al Combi nat i on Br eaker and Cur r ent - Li mi t i ng Fuses

Pr ovi de t he f ol l owi ng:

a. UL 489.

b. I nt egr al combi nat i on mol ded- case ci r cui t br eaker and cur r ent - l i mi t i ng f uses: [ as i ndi cat ed] [ r at ed [ _____] amper es] wi t h a mi ni mum shor t - c i r cui t - cur r ent r at i ng equal t o t he shor t - c i r cui t - cur r ent r at i ng of t he swi t chboar d i n whi ch t he ci r cui t br eaker wi l l be mount ed.

c. Ser i es r at ed ci r cui t br eaker s ar e unaccept abl e.

d. Coor di nat i on of over cur r ent devi ces of t he c i r cui t br eaker and cur r ent - l i mi t i ng f uses: f or over l oads or f aul t cur r ent s of r el at i vel y l ow val ue, t he over cur r ent devi ce of t he br eaker oper at es t o c l ear t he f aul t . The cur r ent - l i mi t i ng f uses oper at e t o c l ear t he f aul t f or hi gh magni t ude shor t c i r cui t s above a pr edet er mi ned val ue[ cr ossover poi nt ] .

e. Housi ng f or t he cur r ent - l i mi t i ng f uses: an i ndi v i dual mol di ng r eadi l y r emovabl e f r om t he f r ont and l ocat ed at t he l oad si de of t he c i r cui t br eaker . I f t he f use housi ng i s r emoved, a bl own f use i s r eadi l y evi dent by means of a v i s i bl e i ndi cat or .

f . Removal of f use housi ng causes t he br eaker cont act s t o open, and t he

SECTI ON 26 24 13 Page 13 br eaker cont act s can not c l ose wi t h t he f use housi ng r emoved. The f use housi ng can not be i nser t ed wi t h a bl own f use or wi t h one f use mi ssi ng. The bl owi ng of any of t he f uses causes t he ci r cui t br eaker cont act s t o open.

] [ 2. 2. 4 Dr awout Br eaker s

Pr ovi de dr awout br eaker s[ as i ndi cat ed] [ _____] . Equi p dr awout br eaker s wi t h di sconnect i ng cont act s, wheel s, and i nt er l ocks f or dr awout appl i cat i on. Pr ovi de mai n, auxi l i ar y, and cont r ol di sconnect i ng cont act s wi t h s i l ver - pl at ed, mul t i f i nger , posi t i ve pr essur e, sel f - al i gni ng t ype.

Pr ovi de each dr awout br eaker wi t h f our - posi t i on oper at i on wi t h each posi t i on c l ear l y i dent i f i ed by an i ndi cat or on t he ci r cui t br eaker f r ont panel as f ol l ows.

a. Connect ed Posi t i on: Pr i mar y and secondar y cont act s ar e f ul l y engaged. Br eaker must be t r i pped bef or e r acki ng i nt o or out of posi t i on.

b. Test Posi t i on: Pr i mar y cont act s ar e di sconnect ed but secondar y cont act s r emai n f ul l y engaged. Thi s posi t i on al l ows compl et e t est and oper at i on of t he br eaker wi t hout ener gi z i ng t he pr i mar y c i r cui t .

c. Di sconnect ed Posi t i on: Pr i mar y and secondar y cont act s ar e di sconnect ed.

d. Wi t hdr awn ( Removed) Posi t i on: Pl aces br eaker compl et el y out of compar t ment , r eady f or r emoval . Removal of t he br eaker act uat es assembl y t hat i sol at es t he pr i mar y st abs.

] 2. 2. 4 El ect r oni c Tr i p Uni t s

Equi p[ mai n and] [ di st r i but i on] br eaker s[ as i ndi cat ed] wi t h a sol i d- st at e t r i ppi ng syst em consi st i ng of t hr ee cur r ent sensor s and a mi cr opr ocessor - based t r i p uni t t hat pr ovi des t r ue r ms sensi ng adj ust abl e t i me- cur r ent c i r cui t pr ot ect i on. I ncl ude t he f ol l owi ng:

a. Cur r ent sensor s amper e r at i ng: [ as i ndi cat ed] [ [ _____] amper es] [ t he same as t he br eaker f r ame r at i ng] .

b. Tr i p uni t amper e r at i ng: [ as i ndi cat ed] [ [ _____] amper es] .

[ c. Gr ound f aul t pr ot ect i on: [ as i ndi cat ed] [ zer o sequence sensi ng] [ r esi dual t ype sensi ng] .

] [ d. El ect r oni c t r i p uni t s: pr ovi de addi t i onal f eat ur es[ as i ndi cat ed] :

[ ( 1) [ I ndi cat ed ] Br eaker s: i ncl ude l ong del ay pi ck- up and t i me set t i ngs, and LED i ndi cat i on of cause of c i r cui t br eaker t r i p.

] [ ( 2) Mai n br eaker s: i ncl ude shor t del ay pi ck- up and t i me set t i ngs, i nst ant aneous set t i ngs gr ound f aul t set t i ngs[ shor t del ay pi ck- up and t i me set t i ngs] [ and] [ , i nst ant aneous set t i ngs] [ and] [ gr ound f aul t set t i ngs] [ as i ndi cat ed] .

] [ ( 3) Di st r i but i on br eaker s: i ncl ude[ shor t del ay pi ck- up and t i me set t i ngs] [ , i nst ant aneous set t i ngs] [ , and gr ound f aul t set t i ngs] [ as i ndi cat ed] .

SECTI ON 26 24 13 Page 14

] [ ( 4) [ Mai n ] Br eaker s: i ncl ude a di gi t al di spl ay f or phase and gr ound cur r ent .

] [ ( 5) [ Mai n ] Br eaker s: i ncl ude a di gi t al di spl ay f or wat t s, var s, VA, kWh, kvar h, and kVAh.

] [ ( 6) [ Mai n ] Br eaker s: i ncl ude a di gi t al di spl ay f or phase vol t age, and per cent THD vol t age and cur r ent .

] [ ( 7) [ Mai n ] Br eaker s: i ncl ude pr ovi s i ons f or communi cat i on v i a a net wor k t wi st ed pai r cabl e f or r emot e moni t or i ng and cont r ol .

Pr ovi de t he f ol l owi ng communi cat i ons pr ot ocol : [ DNP3] [ Modbus] [ I EC 61850] .

] [ ( 8) For el ect r oni c t r i p uni t s t hat ar e r at ed f or or can be adj ust ed t o 1, 200 amper es or hi gher , pr ovi de ar c ener gy r educt i on capabi l i t y wi t h an ener gy- r educi ng mai nt enance swi t ch wi t h l ocal st at us i ndi cat or .

] [ 2. 2. 5 Met er i ng

[ 2. 2. 5. 1 Di gi t al Met er s

I EEE C37. 90. 1 f or sur ge wi t hst and. Pr ovi de t r ue r ms, pl us/ mi nus one per cent accur acy, pr ogr ammabl e, mi cr opr ocessor - based met er encl osed i n a seal ed case wi t h t he f ol l owi ng f eat ur es.

a. Di spl ay capabi l i t y :

[ ( 1) Mul t i - Funct i on Met er : Di spl ay a sel ect ed phase t o neut r al vol t age, phase t o phase vol t age, per cent phase t o neut r al vol t age THD, per cent phase t o phase vol t age THD; a sel ect ed phase cur r ent , neut r al cur r ent , per cent phase cur r ent THD, per cent neut r al cur r ent ; sel ect ed t ot al PF, kW, KVA, kVAR, FREQ, kVAh, kWh.

Det ect ed al ar m condi t i ons i ncl ude over / under cur r ent , over / under vol t age, over / under KVA, over / under f r equency, over / under sel ect ed PF/ kVAR, vol t age phase r ever sal , vol t age i mbal ance, r ever se power , over per cent THD. I ncl ude a For m C KYZ pul se out put r el ay on t he met er .

] [ ( 2) Power Met er : Di spl ay Wat t s, VARs, and sel ect ed KVA/ PF. Det ect ed al ar m condi t i ons i ncl ude over / under KVA, over / under PF, over / under VARs, over / under r ever se power .

] [ ( 3) Vol t Met er : Pr ovi de capabi l i t y t o be sel ect abl e bet ween di spl ay of t he t hr ee phases of phase t o neut r al vol t ages and di spl ay of t he t hr ee phases of t he phase t o phase vol t ages. Det ect ed al ar m condi t i ons i ncl ude over / under vol t age, over / under vol t age i mbal ance, over per cent THD.

] [ ( 4) Ammet er : Di spl ay phase A, B, and C cur r ent s. Det ect ed al ar m condi t i ons i ncl ude over / under cur r ent , over per cent THD.

] [ ( 5) Di gi t al Wat t hour Met er : Pr ovi de a s i ngl e sel ect abl e di spl ay f or wat t s, t ot al k i l owat t hour s ( kWh) and wat t demand ( Wd) . I ncl ude a For m C KYZ pul se out put r el ay on t he met er .

] b. Desi gn met er s t o accept [ i nput f r om st andar d 5A secondar y i nst r ument t r ansf or mer s] [ and] [ di r ect vol t age moni t or i ng r ange t o [ 300] [ 600]

SECTI ON 26 24 13 Page 15 vol t s, phase t o phase] .

c. Pr ovi de pr ogr ammi ng vi a a f r ont panel di spl ay and a communi cat i on i nt er f ace accessi bl e by a comput er .

d. Pr ovi de passwor d secur ed pr ogr ammi ng st or ed i n non- vol at i l e EEPROM memor y.

e. Pr ovi de di gi t al communi cat i ons i n a Modbus [ RTU] pr ot ocol v i a a [ RS232C] [ RS485] ser i al por t [ and an i ndependent l y addr essabl e [ RS232C] [ RS485] ser i al por t ] .

f . Pr ovi de met er t hat cal cul at es and st or es aver age max/ mi n demand val ues wi t h t i me and dat e f or al l r eadi ngs based on a user sel ect abl e s l i di ng wi ndow aver agi ng per i od.

g. Pr ovi de met er wi t h pr ogr ammabl e hi / l ow set l i mi t s wi t h t wo For m C dr y cont act r el ays when exceedi ng al ar m condi t i ons.

[ h. Pr ovi de met er wi t h a di spl ay of Tot al Har moni c Di st or t i on ( THD) measur ement t o a mi ni mum of t he t hi r t y- f i r st or der .

] [ i . I ncl ude hi st or i cal t r end l oggi ng capabi l i t y wi t h t he abi l i t y t o st or e up t o 100, 000 dat a poi nt s wi t h i nt er val s of 1 second t o 180 mi nut es.

Pr ovi de a uni t t hat can st or e and t i me st amp up t o 1000 pr ogr ammabl e t r i gger ed condi t i ons.

] [ j . Pr ovi de event wavef or m r ecor di ng t r i gger ed by t he r ms of 2 cycl es of vol t age or cur r ent exceedi ng pr ogr ammabl e set poi nt s. St or e wavef or ms f or al l 6 channel s of vol t age and cur r ent f or a mi ni mum of 10 cycl es pr i or t o t he event and 50 cycl es past t he event .

] ] [ 2. 2. 5. 2 El ect r oni c Wat t hour Met er

[ Pr ovi de as speci f i ed i n Sect i on [ 26 27 14. 00 20 ELECTRI CI TY METERI NG] [

26 27 13. 10 30 ELECTRI C METERS] .

] [ ANSI C12. 1. Pr ovi de a swi t chboar d st y l e el ect r oni c pr ogr ammabl e wat t hour met er , semi - f l ush mount ed, as i ndi cat ed. Met er can be ei t her pr ogr ammed at t he f act or y or pr ogr ammed i n t he f i el d. Tur n f i el d pr ogr ammi ng devi ce over t o t he Cont r act i ng Of f i cer at compl et i on of pr oj ect . Coor di nat e met er t o syst em r equi r ement s.

a. Desi gn: Pr ovi de met er desi gned f or use on a 3- phase, 4- wi r e, [ 208Y/ 120] [ 480Y/ 277] vol t syst em wi t h 3 cur r ent t r ansf or mer s. I ncl ude necessar y KYZ pul se i ni t i at i on har dwar e f or Ener gy Moni t or i ng and Cont r ol Syst em ( EMCS) .

b. Coor di nat i on: Pr ovi de met er coor di nat ed wi t h r at i os of cur r ent t r ansf or mer s and t r ansf or mer secondar y vol t age.

c. Cl ass: 20. Accur acy: pl us or mi nus 1. 0 per cent . Fi ni sh: Cl ass I I .

d. Ki l owat t - hour Regi st er : f i ve di gi t el ect r oni c pr ogr ammabl e t ype.

e. Demand Regi st er :

( 1) Pr ovi de sol i d st at e.

SECTI ON 26 24 13 Page 16

( 2) Met er r eadi ng mul t i pl i er : I ndi cat e mul t i pl i er on t he met er f ace.

( 3) Demand i nt er val l engt h: pr ogr ammed f or [ 15] [ 30] [ 60] mi nut es wi t h r ol l i ng demand up t o s i x subi nt er val s per i nt er val .

f . Met er f usi ng: Pr ovi de a f use bl ock mount ed i n t he met er i ng compar t ment cont ai ni ng one f use per phase t o pr ot ect t he vol t age i nput t o t he wat t hour met er . Si ze f uses as r ecommended by t he met er manuf act ur er .

g. Pr ovi de met er wi t h a communi cat i ons por t , RS485, wi t h Modbus RTU ser i al or Et her net , Modbus- TCP communi cat i ons.

I EEE C57. 13. Pr ovi de si ngl e r at i o t r ansf or mer s, 60 her t z, [ _____] t o 5- amper e r at i o, [ _____] r at i ng f act or , wi t h a met er i ng accur acy c l ass of

0. 3 t hr ough [ _____] .

[ Pr ovi de a f use bl ock mount ed i n t he met er i ng compar t ment cont ai ni ng one f use per phase t o pr ot ect t he vol t age i nput t o vol t age sensi ng met er s.

Si ze f uses as r ecommended by t he met er manuf act ur er .

] ] ] [ 2. 2. 5. 3 Submet er i ng

ASHRAE 90. 1 - I P. Pr ovi de submet er i ng f or [ _____] .

] ] [ 2. 2. 6 Tr ansf or mer

Pr ovi de t r ansf or mer sect i on i n swi t chboar d i n accor dance wi t h UL 891 and as i ndi cat ed. Pr ovi de t he t r ansf or mer and sect i on t hat i s sui t abl e f or t he i nst al l at i on. [ Test t r ansf or mer s gr eat er t han 10 kVA i n accor dance wi t h UL 891. ] Pr ovi de a t r ansf or mer conf or mi ng t o t he r equi r ement s of Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.

] [ 2. 2. 7 Heat er s

Pr ovi de 120- vol t heat er s i n each swi t chboar d sect i on. Pr ovi de heat er s of suf f i c i ent capaci t y t o cont r ol moi st ur e condensat i on i n t he sect i on, 250 wat t s mi ni mum, and cont r ol l ed by a t her most at [ and humi di st at ] l ocat ed i n t he sect i on. Pr ovi de i ndust r i al t ype t her most at , hi gh l i mi t , t o mai nt ai n sect i ons wi t hi n t he r ange of 60 t o 90 degr ees F. [ Pr ovi de humi di st at wi t h a r ange of 30 t o 60 per cent r el at i ve humi di t y. ] Obt ai n suppl y vol t age f or t he heat er s f r om a cont r ol power t r ansf or mer wi t hi n t he swi t chboar d. I f heat er vol t age i s di f f er ent t han swi t chboar d vol t age, pr ovi de t r ansf or mer r at ed t o car r y 125 per cent of heat er f ul l l oad r at i ng. Pr ovi de t r ansf or mer wi t h a 220 degr ees C i nsul at i on syst em wi t h a t emper at ur e r i se not exceedi ng 115 degr ees C and conf or mi ng t o NEMA ST 20. [ Ener gi ze el ect r i c heat er s i n swi t chboar d assembl i es whi l e t he equi pment i s i n st or age or i n pl ace pr i or t o bei ng pl aced i n ser vi ce. Pr ovi de met hod f or easy connect i on of heat er t o ext er nal power sour ce. Pr ovi de t empor ar y, r el i abl e ext er nal power sour ce i f commer ci al power at r at ed vol t age i s not avai l abl e on si t e. ]

] 2. 2. 5 Mi cr opr ocessor Cont r ol Logi c

a. Mechani cal Swi t chboar d A i s t o be pr ovi ded wi t h an mi cr opr ocessor cont r ol l er aut omat i c l ogi c cont r ol l er . Oper at i on of Mechani cal Swi t chboar d A and B mai n br eaker s( " M1" and " M2" ) and moni t or i ng of bot h sour ces shal l be managed by t he cont r ol l er al ong wi t h Ti e Br eaker " T2" l ocat ed wi t hi n Mechani cal Swi t cboar d A. The cont r ol l er shal l be har dened agai nst t r ansi ent vol t ages.

SECTI ON 26 24 13 Page 17

b. The cont r ol l er shal l have an oper at i ng t emper at ur e r ange f r om - 20 t o +70 degr ees C ( - 4 t o +158 degr ees F) and a st or age t emper at ur e r ange f r om - 30 t o +85 degr ees C ( - 22 t o +185 degr ees F.

c. The cont r ol l er shal l be capabl e of accept i ng 120Vac der i ved f r om sour ce 1 and sour ce 2. An ext er nal 125 Vdc suppl y shal l be accept ed f or cont i nued cont r ol l er oper at i on i f bot h sour ces have f ai l ed.

2. 2. 6 Cont r ol l er and Keypad

a. The mi cr opr ocessor - based cont r ol l er f acepl at e shal l be UV r esi st ant and i ncl ude a 4. 3- i nch, col or TFT ( 480x272) backl i t di spl ay. The cont r ol l er shal l be capabl e of di spl ayi ng sour ce 1, 2, and t i e br eaker st at us, par amet er s, set poi nt s, and di agnost i c dat a. Abbr evi at i ons or codes shal l be l i mi t ed f or i nt ui t i ve oper at i on. Al l set poi nt par amet er s shal l be passwor d pr ot ect ed

b. The mi cr opr ocessor - based cont r ol l er shal l i ncl ude one ( 1) uni t st at us LED ( 3mm) and a mi mi c power bus consi st i ng of s i x ( 6) LED' s ( 3mm) f or i ndi cat i ng t he f ol l owi ng:

c. The cont r ol l er keypad shal l i ncl ude t he f ol l owi ng pushbut t on cont r ol s:

d. The cont r ol l er shal l di spl ay on t he mai n over vi ew scr een:

e. The cont r ol l er shal l di spl ay t he vol t age dr opout and pi ckup set poi nt s, f or sour ce 1 and sour ce 2, i n vol t s and as a per cent age of nomi nal vol t age f . The cont r ol l er shal l di spl ay t he f r equency dr opout and pi ckup set poi nt s, f or sour ce 1 and sour ce 2, i n her t z and as a per cent age of nomi nal f r equency.

g. The cont r ol l er shal l moni t or vol t age ( Vab, Vbc, Vca) and f r equency ( Hz) f or sour ce 1, sour ce 2, and l oad.

h. The cont r ol l er shal l have a vol t age r ange of 0- 720 Vr ms wi t h an accur acy of +/ - 1%. Nomi nal vol t age shal l be adj ust abl e i n 1 vol t i ncr ement s f r om 120 t o 600Vac. The number of vol t age phases shal l be adj ust abl e as 1 or 3.

i . The cont r ol l er shal l have a f r equency r ange of 40- 80 Hz wi t h an accur acy of +/ - 0. 2 Hz. Nomi nal f r equency shal l be adj ust abl e as 50 or 60Hz.

j . The cont r ol l er shal l i ncl ude a phase sequence check f or sour ce 1 and sour ce 2, adj ust abl e t o OFF, ABC, or CBA.

k. Vol t age and f r equency dr opout and pi ckup set poi nt s, f or sour ce 1 and sour ce 2, shal l be adj ust abl e as a per cent age of nomi nal per t he t abl e bel ow. Pi ckup and dr opout set poi nt s f or over vol t age, under f r equency, over f r equency, and vol t age unbal ance / phase l oss shal l be capabl e of bei ng di sabl ed.

SECTI ON 26 24 13 Page 18

Set poi nt Sour ces Dr opout Pi ckup

Under vol t age Sour ce 1 and 2 70 - 97% ( Do +2%) t o 99$

Over vol t age Sour ce 1 and 2 105 - 120% 103% t o ( DO - 2%)

Under f r equency Sour ce 1 and 2 90 - 97% ( DO + 1HZ) t o 99%

Over f r equency Sour ce 1 and 2 103 - 110% 101% t o ( DO - 1Hz)

Vol t age Unbal ance Sour ce 1 and 2 5 - 20% 3% t o ( DO - 2%)

Vol t age Unbal ance Phase Loss ( wi t h negat i ve sequence det ect i on)

Sour ce 1 and 2 20 - 60% 18% t o ( DO - 2%) l . The cont r ol l er shal l i ncl ude an al gor i t hm t hat i s capabl e of det ect i ng a vol t age unbal ance / phase l oss condi t i on at ei t her power sour ce when t he power sour ce i s unl oaded and r egener at ed, or phant om vol t age i s pr esent . Once det ect ed, t he al gor i t hm shal l be capabl e of pr event i ng a l oad t r ansf er i nt o a r egener at ed vol t age condi t i on.

m. A set poi nt shal l be pr ovi ded f or conf i gur i ng a " pr ef er r ed sour ce" , adj ust abl e t o none, sour ce 1, or sour ce 2. The cont r ol l er shal l seek connect i on of t he l oad t o t he pr ef er r ed sour ce ( when i t i s avai l abl e) . The cont r ol l er shal l al so be capabl e of accept i ng an ext er nal dr y cont act f or r emot el y conf i gur i ng sour ce 1 or sour ce 2 as t he pr ef er r ed sour ce.

2. 2. 7 Ter mi nal Boar ds

Pr ovi de wi t h engr aved pl ast i c t er mi nal st r i ps and scr ew t ype t er mi nal s f or ext er nal wi r i ng bet ween component s and f or i nt er nal wi r i ng bet ween r emovabl e assembl i es. Pr ovi de shor t - c i r cui t i ng t ype t er mi nal boar ds associ at ed wi t h cur r ent t r ansf or mer . Ter mi nat e conduct or s f or cur r ent t r ansf or mer s wi t h r i ng- t ongue l ugs. Pr ovi de t er mi nal boar d i dent i f i cat i on t hat i s i dent i cal i n s i mi l ar uni t s. Pr ovi de col or coded ext er nal wi r i ng t hat i s col or coded consi st ent l y f or s i mi l ar t er mi nal boar ds.

2. 2. 8 Wi r e Mar ki ng

Mar k cont r ol and met er i ng conduct or s at each end. Pr ovi de f act or y i nst al l ed, whi t e, pl ast i c t ubi ng, heat st amped wi t h bl ack bl ock t ype l et t er s on f act or y- i nst al l ed wi r i ng. On f i el d- i nst al l ed wi r i ng, pr ovi de whi t e, pr epr i nt ed, pol yvi nyl chl or i de ( PVC) s l eeves, heat st amped wi t h bl ack bl ock t ype l et t er s. Pr ovi de a s i ngl e l et t er or number on each sl eeve, el l i pt i cal l y shaped t o secur el y gr i p t he wi r e, and keyed i n such a manner t o ensur e al i gnment wi t h adj acent s l eeves. Pr ovi de speci f i c wi r e mar ki ngs usi ng t he appr opr i at e combi nat i on of i ndi v i dual s l eeves.

I ndi cat e on each wi r e mar ker t he devi ce or equi pment , i ncl udi ng speci f i c t er mi nal number t o whi ch t he r emot e end of t he wi r e i s at t ached.

2. 3 MANUFACTURER' S NAMEPLATE

Pr ovi de a namepl at e on each i t em of equi pment bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a

SECTI ON 26 24 13 Page 19 conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent i s not accept abl e. Thi s namepl at e and met hod of at t achment may be t he manuf act ur er ' s st andar d i f i t cont ai ns t he r equi r ed i nf or mat i on.

2. 4 FI ELD FABRI CATED NAMEPLATES

ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each swi t chboar d, equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t hi s sect i on or as i ndi cat ed on t he dr awi ngs.