This special notice announces an industry day for the Yard, Repair, Berthing and Messing Barge (YRBM) program. The Navy intends to procure up to twenty-six non-self-propelled YRBM craft over fifteen years to accommodate berthing needs for up to 199 personnel and messing for 300 personnel. The first contract is anticipated as a small business set aside. The industry day will provide information on program schedule, contract requirements, and draft performance specifications. It will be held virtually on October 13, 2020 from 1300-1600 EDT using Microsoft Teams. Interested shipyards and potential industry sources should register by October 5th. The event aims to inform industry and gain feedback to assist the market research process for a potential YRBM solicitation. The agenda includes an overview of roles, mission, schedule, specifications, rules and standards, data rights, administration and oversight.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Requirements
| ATTACHMENT 1 | ||
| YRBM Berthing Barge - Requirements Matrix | ||
| ITEM NO. | DESCRIPTION | |
| 041 | Configuration Management | Configuration management shall be exercised by the Contractor to ensure that each YRBM craft is identical to the first YRBM craft delivered, except where a deviation has been specifically authorized by a Government representative. |
| 070 | General Requirements for Detail Design and Construction | |
| 070a | General | The YRBM craft shall provide living accommodations during a ship repair or overhaul period and is intended to operate in pierside locations. The YRBM craft shall be non-self-propelled and will usually be employed in or near U.S. Navy and civilian shore facilities, and shall depend on shore supply for utility services. It shall be capable of being towed, unmanned, in open-ocean and coastal environments. |
070b Regulatory Body Requirements The American Bureau of Shipping (ABS) shall class the YRBM craft as A1 Accommodation Barge, Harbor Service. The modifications to the ABS Guide for Building and Classing Accommodation Barges, Appendix 1 apply for the YRBM craft due to the vessel’s intended operational location.
The YRBM craft shall be equipped to satisfy the Panama Canal Authority regulations for transit.
The YRBM craft shall comply with the International Convention on Load Lines.
The YRBM craft shall meet the following sanitary construction requirements within the Centers for Disease Control and Prevention/U.S. Public Health Service (CDC/USPHS) Vessel Sanitation Program (VSP) 2011 Construction Guidelines, unless specified elsewhere.
| a) | Size and Flow (CDC VSP Construction Guidelines, Section 6.1) |
| b) | Equipment Surface (CDC VSP Construction Guidelines, Section 6.3) |
| c) | Bulkheads, Deckheads, and Decks (CDC VSP Construction Guidelines, Section 6.4) |
| d) | Deck Drains, Deck Sinks, and Scuppers (CDC VSP Construction Guidelines, Section 6.5) |
| e) | Ramps (CDC VSP Construction Guidelines, Section 6.6) |
| f) | Gray and Black Water Drain Lines (CDC VSP Construction Guidelines, Section 6.7) |
| g) | Handwashing Stations (CDC VSP Construction Guidelines, Section 7.1) |
| h) | Equipment placement and mounting (CDC VSP Construction Guidelines, Section 8.0) |
| i) | Fasteners and requirements for securing and sealing equipment (CDC VSP Construction Guidelines, Section 9.0) |
| j) | Equipment drain lines (CDC VSP Construction Guidelines, Section 12) |
| k) | Electrical connections, pipelines, service lines, and attached equipment (CDC VSP Construction Guidelines, Section 13) |
| l) | Hood systems (CDC VSP Construction Guidelines, Section 14) |
070b (continued) Regulatory Body Requirements m) Provision Rooms, Walk-in Refrigerators and Freezers, and Food Transportation Corridors (CDC VSP Construction Guidelines, Section 15
n) Galley, food preparation rooms, and pantries (CDC VSP Construction Guidelines, Section 16)
o) Buffet lines, waiter stations, bars, and other similar food service areas (CDC VSP Construction Guidelines, Section 17)
p) Warewashing (CDC VSP Construction Guidelines, Section 18)
q) Lighting (CDC VSP Construction Guidelines, Section 19)
r) Cleaning materials, filters, and drinking fountains (CDC VSP Construction Guidelines, Section 20)
s) Potable water system (exclude storage and production capacity, storage tanks, pressure tanks, Evaporators and Reverse Osmosis Plants, Halogenation requirements) (CDC VSP Construction Guidelines, Section 22)
t) Cross-connection control (CDC VSP Construction Guidelines, Section 23)
u) Heat exchangers used for cooling or heating sanitary seawater and potable water (CDC VSP Construction Guidelines, Section 24).
The Contractor shall provide the materials, equipment, and outfitting items required for the YRBM craft to operate in compliance with 33 Code of Federal Regulations (CFR), as applicable, and with other Regulatory Body requirements contained within this document.
070c Characteristics The YRBM craft is a non-self-propelled craft and shall be employed as a semi-permanently moored, floating facility, capable of providing berthing for 199 personnel (duty crew), messing for 300 personnel (entire crew), and support for these personnel as described herein. Compartmentation, layout, and furnishings must support a dual gender crew.
The YRBM craft shall interface with shore service connections for potable/fresh water, firemain, sewage water discharge, electric power, LAN and communications (telephone, TV, fax, and Automated Teller Machines (ATM)) at a recessed Shore Connection Station located on the starboard side, with hoses and cables covered by a ramp on the Main Deck so normal traffic, including loading and trash removal, is not impeded. A sewage water discharge station shall also be provided on the port side, which does not require a ramp. Electrical connections shall be shielded from water connections. Local and remote meters to measure and record usage of shore services and inclinometer(s) to monitor list and trim of the YRBM craft shall be provided. Remote meters for shore service usage shall also be located within the Quarterdeck Station.
The YRBM craft shall be designed and built using the metric system of measurement to the maximum extent practica l. In all cases, YRBM craft components, equipment, piping, valves, flanges, fittings, cable, connectors, switches, fixtures, etc., are to be selected based on U.S. commercial marine standards with respect to their design, materials and dimensions, unless otherwise specified. YRBM craft shall be of welded steel hull construction with watertight inner bottom tanks and a raked stern with watertight skeg(s) suitable for coastal and open-ocean tow. Sharp corners or ragged edges of materials that may be hazardous to personnel or equipment and intermittent welds on exterior structures shall be avoided.
To facilitate maximum utilization of pier space and transit through the Panama Canal, and to provide maximum flexibility of mooring in shallow waters, the overall craft dimensions shall not exceed 46 m (152 ft.) for the length and 15 m (50 ft.) for breadth. The YRBM craft shall not exceed a navigational draft of 2.5 m (8 ft.) at any point along the underwater hull in a Full Load Condition. The YRBM craft is in the Full Load Condition when it has one hundred percent (100%) of its stores, machinery, outfitting, furnishings, equipment, liquid loadings, and personnel (199), with personal effects, on board .
| 070d | Certifications | The following certificates are to be supplied to the YRBM craft at the time of delivery: | |
| a) | Certificates required by ABS Classification and Flag State Authority. | ||
| b) | ABS Statement of Compliance stating that the YRBM craft meets a two-compartment standard of flooding as defined by 46CFR171.017(b). | ||
| c) | An International Tonnage Certificate of Admeasurement, in accordance with the requirements of 46CFR69 issued by ABS. | ||
| d) | IMO International Convention on Load Lines, 1966 issued by ABS. | ||
| e) | Panama Canal/Universal Measurement System Net Tonnage Certificate issued by ABS. | ||
| f) | ABS Statement of Compliance for USCG Navigation Rules and Regulations Handbook for navigational lights, for a moored barge and a barge in tow. | ||
| g) | ABS Statement of Compliance for CDC/USPHS VSP 2011 Construction Guidelines for Sanitary Construction, as specified herein. | ||
| h) | ABS Statement of Compliance for Institute of Electrical and Electronic Engineers (IEEE) Standard 45 series. | ||
| i) | ABS Statement of Compliance for NAVSHIP Drawing No. 804-4444650-D, Surface Ship Sewage Discharge Connections for material and design requirements for quick disconnect male coupling and dust cap. | ||
| j) | ABS Statement of Compliance for EPA regulations, as applicable. |
070e Trim, List, and Weight At the pier, the YRBM craft in all operational loading conditions, including Light Ship and Full Load Displacements, shall not have a list exceeding ½ degree on the port side or starboard side and trim shall not exceed 15 cm (6 inches) forward or aft. Ballast is not permitted to meet list and trim requirements.
The Contractor shall consider the weight of crew and effects for the YRBM craft in Table 070e-1:
The weight of a male is approximately 79.4 kg (175 lbs.) and for females 61.2 kg (135 lbs.) The center of gravity is taken as berthed. The Contractor shall consider a 1:7 female-to-male ratio for craft berthing.
070e-1
Crew Weight and Effects
070f Operating Environment The YRBM craft and its systems shall be designed for the operating temperature and humidity cited in Table 070f-1.
Equipment and machinery exposed to weather shall be designed for ambient air temperature from -29° C (-20° F) to 50° C (122° F). Machinery, electrical and electronic equipment internal to the YRBM craft shall be rated at no less than the compartment design temperature in which it is installed.
Electronic equipment spaces shall be maintained at 35%-60% relative humidity when equipment is operating and at 10%-90% relative humidity with no condensation when equipment is not operating.
Masts, superstructure, other structure installed topside, and fittings shall withstand dynamic forces produced by motion of the YRBM craft in a seaway.
070f-1
Operating Temperature and Humidity
070g Seakeeping and Maneuvering The YRBM craft shall be capable of being towed at 2.6 m/s (5 knots), unmanned, in open-ocean and coastal environments in NATO Sea State 4 conditions cited in STANAG 4194 Annex D, Table D-1 by harbor tugboat typically having propulsive power of 1,491 kilowatts (2,000 horsepower). A Bretschneider spectrum is to be used for open-ocean conditions. In addition, a JONSWAP spectrum (with gamma = 3.3) is to be used for coastal conditions as recommended by STANAG-4154 for fetch-limited conditions. The YRBM craft shall be directionally stable under tow.
070h General Requirements for Equipment, Machinery, and Materials Unless otherwise noted, designations, numbering, labeling, nameplates, notices and markings shall be in accordance with best commercial marine practices.
All equipment, machinery and material shall be purchased new, and be protected and handled to maintain such condition.
070i Workmanship Items shall be suited to and of a quality appropriate for their intended operational use and installed in accordance with manufacturer’s instructions.
Corners and crevices in which water and dirt may collect or pool and inaccessible void spaces shall be eliminated. Drain holes shall be cut and watercourses provided to prevent accumulation and retention of liquids and to permit the free flow to drains, scuppers, sumps, and suction pipes.
Shims shall not be used to correct improper fit unless approved by the Government.
Exposed outside corners or sharp edges of interior bulkheads, joiner bulkheads, coamings and other raised structures, and their stiffeners in accommodation and manned spaces shall be rounded to prevent personal injury.
071 Access Compartments, usable spaces and voids within the YRBM craft shall be provided with doors, hatches, scuttles, manholes, arches and removable plates required to afford the most convenient access without compromising watertight integrity, structural strength, or efficient arrangement.
Access routes to spaces containing equipment that cannot be readily disassembled into smaller components and/or is of a size that precludes shipment through a standard access route shall be provided with a means to readily disassemble interferences without hot work (i.e., welding, brazing, or cutting). The temporary shipping access route shall be sized to accommodate the largest piece of equipment or subassembly installed in the particular space .
There shall be a minimum of 3 feet of deck space outboard of the deck house on the main deck. Equipment located in the deck space shall not be a hazard to the free movement of personnel or craft equipment during operations or maintenance activities.
071a Machinery Access Bolted Equipment Removal Plate(s) (BERP) shall be provided for removal of large equipment and components where the size of the item or component to be shipped or unshipped exceeds door or hatch sizes.
Equipment and machinery shall be installed with access areas for operation, maintenance, adjustment, and repair without having to dismantle adjacent machinery, piping ducting, cabling or structure. Maintenance envelopes shall be in accordance with original equipment manufacturer’s instructions.
| 073 | Noise and Vibration | |
| 073a | Noise | Airborne noise performance requirements shall be as specified under USCG Navigation and Vessel Inspection Circular 12-82, Enclosure (6). YRBM craft spaces not readily identifiable by this standard (i.e. classrooms) shall meet an ambient noise level limit not to exceed 65 dB(A). Structure-borne noise from machinery and equipment shall be minimized and isolated to the maximum extent possible from berthing and/or normally occupied spaces. Acoustic insulation in accordance with SNAME T&R Bulletin No. 3-37 shall be installed, as required, to meet the airborne noise performance requirements. |
073b Vibration The YRBM craft and all YRBM craft components shall be free from excessive vibration. Excessive vibration is defined as vibration which interferes with, or threatens to interfere with, operation of the YRBM craft or YRBM craft systems, impairs the comfort or efficiency of personnel, or jeopardizes ship or structural or mechanical integrity.
075 Fasteners Fasteners installed in areas exposed to the weather or in wet locations shall be ASTM F593, stainless steel type 316 (UNS S31600) or type 316L (UNS 31603). Nitronic 50 (UNS S20910), duplex alloy 2205 (UNS S31803), Ferralium 255 (UNS S32550), or alloy AL-6XN (UNS N08367) fasteners may also be used. Fasteners installed in locations where stagnant water is likely to occur shall be hot-dipped galvanized steel. Threaded fasteners, when installed and tightened, shall protrude a distance of between one and nine threads beyond the top of the nut or plastic insert. Removable pins used for securing parts and equipment shall be secured with a lanyard to prevent loss.
076 Reliability, Maintainability, and Availability The Contractor shall select and install commercial shipboard systems and equipment having reliable service life histories and meeting industry standards recognized by the Regulatory Bodies.
Material, furnishings and equipment shall be selected by the following criteria:
| a) | Space functionality |
| b) | Ability to withstand an industrial and marine environment |
| c) | Safety |
| d) | Durability/reliability |
| e) | Maintainability. |
Equipment selection should consider existing availability within the Navy and Department of Defense logistics support infrastructure. Materials and applications which ease cleaning efforts and improve facilities maintenance shall be used throughout, with special emphasis in messing, food preparation, sanitary, and medical spaces.
All application software, including embedded software within systems, and operating systems shall be supportable and provided with the means to be supportable. At delivery of the YRBM craft, all application software and firmware programs, and operating systems shall be delivered with at least three years remaining prior to the software developer's or Original Equipment Manufacturer's end of support date.
The YRBM craft’s structure, including interior non-structural bulkheads, shall have a design service life of 40 years. The approach for meeting this design objective shall be a combination of appropriate sizing of scantlings to include a corrosion allowance and effective corrosion prevention systems. Fabrication techniques shall follow the best commercial marine practices.
The YRBM craft’s docking cycle shall be 10 years to 12 years . Machinery and equipment shall be located and oriented with all due consideration of access, operation and maintenance. Equipment, outfitting, furnishings, and support systems as well as interior non-structural components such as bulkheads, partitions, deck surfaces, and so forth, shall be selected or designed to minimize upkeep and maintenance.
| 077 | Environmental, Safety, and Occupational Health | |
| 077a | General | The Contractor shall incorporate Environmental, Safety and Occupational Health considerations and criteria into the design of ship’s systems, equipment, and arrangements to ensure the safety of personnel, systems, equipment, and the environment, to ensure regulatory compliance with all applicable environmental laws and regulations. |
077b System Safety Safety devices or guards shall be installed over unprotected moving parts of rotating or oscillating equipment and machinery that could pose a hazard to personnel .
077c Pollution Prevention Neither the YRBM craft nor anything provided with the YRBM craft shall contain materials considered hazardous to human health, such as asbestos insulation, coatings containing lead compounds, or Polychlorinated Biphenyl contaminated materials.
Material or equipment that contains or uses chlorofluorocarbon or Class I or II ozone depleting substances, as defined in the Clean Air Act, 42 United States Code, shall not be used in the construction and operation of the YRBM craft. Lead paint shall not be used in the construction of the YRBM craft.
077d Hazardous Materials The prohibited chemicals in Naval Sea Systems Command (NAVSEA) Hazardous Material Avoidance Process Manual T9070-AL-DPC-020/077-2 shall not be used in the construction and operation of the YRBM craft unless excepted as noted in the process manual or otherwise approved. Use of the restricted chemicals in the NAVSEA Hazardous Material Avoidance Process Manual shall be minimized in the construction and operation of the YRBM craft.
| 078 | Materials and Corrosion | |
| 078a | Corrosion Prevention | Materials and equipment shall be properly selected and installed to minimize corrosion due to contact between dissimilar metals. Mating of dissimilar metals shall be avoided wherever possible. When mating of dissimilar metals is unavoidable, a bimetal or durable non-conductive and non-absorbent galvanic barrier (e.g. hard neoprene) shall be installed between the dissimilar metals to reduce galvanic corrosion |
078b Hull Materials and Welding All hull structural materials and welding shall be in accordance with ABS Rules for Materials and Welding. The Contractor shall perform non-destructive testing of hull welds in accordance with ABS Guide for Nondestructive Inspection of Hull Welds, to the satisfaction of ABS.
079 Stability Stability analysis and calculations shall cover the full range of operating conditions up to and including the Load Line draft. The YRBM craft shall meet stability requirements for ABS Guide for Building and Classing Accommodation Barges except that the YRBM craft shall be designed to a two-compartment standard of flooding as defined by 46CFR171.017(b). Service Life Allowances (SLA) for weight and stability shall be in accordance with NAVSEAINST 9096.6.
080 Human Systems Integration The YRBM craft design shall account for the interface with human operators. The human role in operating and supporting the craft shall be addressed at all system levels. Human engineering principles shall be applied to the physical craft design, system and equipment selection, control consoles and operating stations. Switches, levers, pushbuttons, and/or equipment start mechanisms shall be located to prevent the possibility of accidental physical damage and inadvertent activation.
The YRBM craft and its systems shall be designed for the anthropometric dimensions and capabilities of the 5th percentile North American female to the 95th percentile North American male crewmember. Living Space, Normal Working Spaces, and Passageways shall have a minimum unobstructed vertical clearance above the walking surface of 213.4 cm (84 inches).
American Society for Testing and Materials (ASTM) F1166 contains reference data for human engineering and shall be used, where applicable.
ASTM F1166 shall be used to determine type of control, control spacing, color coding, texture coding, location, shape coding, and consistency. Controls shall be selected using the guidelines prescribed in Table 1 “Recommended Manual Controls” of Ch 5, ASTM F1166. Control movement shall be consistent among the same function and application and shall operate according to the design expectations of the intended operators, in accordance with Table 2 “Control Movement Expectations” of Ch 5, ASTM F1166.
Visual displays shall be in accordance with the design guidelines set forth by ASTM F1166. Visual displays shall be used to provide the operator with an indication of equipment or system conditions by providing a positive indication of the state of the equipment such as: ready, running, not running, or “out-of-tolerance,” and/or the current performance level of the equipment or system. Information shall be presented to the operator in a directly usable format that shall not require transposing, computing, interpolating, or mentally translating to other units. Redundancy in the display of information to a single operator shall be avoided unless it is required to achieve specified reliability.
089 Standardization Equipment commonality shall be provided among YRBM craft of the class. Redundant equipment shall have identical manufacturer, make, model, and operating parameters. Standardization shall be incorporated in design and equipment selection for each YRBM craft and across the YRBM craft class.
| 094 | Trials | |
| 094a | Builder's Trials | The Contractor shall perform Builder's Trials (BT) for each YRBM to demonstrate the successful operation of all craft equipment and systems, that the craft meets all contract requirements, and that the craft is ready for Acceptance Trials. SNAME T&R Bulletin 3-39 , Guide for Shop and Installation Tests, as applicable for this craft, shall be used as a guide for demonstrating equipment operation and for testing system operation. Airborne noise and vibration surveys shall be performed during Builder's Trials for the craft. The Contractor shall provide all materials, tools, equipment, instrumentation, fluids, power, and qualified personnel to conduct Builder's Trials. Builder's Trials shall be witnessed by the Government and/or the Government Representative(s) at the discretion of the Government. Completion of Builder's Trials and correction of discrepancies identified during Builder's Trials is a prerequisite to the commencement of Acceptance Trials (AT). |
094b Acceptance Trials Prior to delivery, the Contractor shall conduct AT for each YRBM craft to ensure the YRBM craft is complete, meets the YRBM Performance Specifications and other contract requirements, and is in all respects ready for service. The YRBM craft shall be considered complete when: a) the Acceptance Trials agenda, including test procedures, has been approved by the Government, b) all piping, machinery, ventilation and air handling systems have been safely cleaned, flushed, and pressure tested, as required, in accordance with standard commercial marine practice, c) all equipment, machinery, components and systems have been demonstrated to simulate normal operational conditions, and d) the YRBM craft is clean and free of trash and other industrial debris. Completeness shall be determined and agreed upon by both the Contractor and the Government. SNAME T&R Bulletin 3-39 , Guide for Shop and Installation Tests, as applicable for this craft, shall be used as a guide for demonstrating equipment operation and for testing system operation. The trials shall be conducted by the Contractor and shall be witnessed by the Government. Satisfactory completion of Acceptance Trials shall be a condition for acceptance of the YRBM craft by the Government.
097 Inclining Experiment An inclining test will be required for the first YRBM craft, as near to completion as practical prior to Builder’s Trials, to determine accurately the lightship weight and position of the center of gravity. The vessel shall be substantially complete, with not less than 98% (in terms of Light Ship) of the vessel contracted and outfitted. The inclining experiment shall be performed in accordance with Regulatory Body requirements and ASTM F1321. The inclining experiment will be witnessed by the Government.
For successive YRBM craft built at the same shipyard, a deadweight survey in accordance with ASTM F1321-92 and a procedure approved and witnessed by ABS may be substituted for the inclining test, if there is a record of an inclining test of a sister vessel. A vessel qualifies as a sister vessel if it is built to the same basic drawings and the undocumented weight difference between the two vessels is less than 3 percent of the lightweight displacement of the vessel which was inclined and the location of the longitudinal center of gravity differs less than 1 percent of the vessel's length.
| 100 | General Requirements for Hull Structure | |
| 100a | General | Split pipe fendering shall be provided continuously around the craft for mooring against ships or piers and shall support a maximum tide change of 5.2 m (17 ft.). Fendering shall be within the YRBM craft’s maximum overall dimensional characteristics. |
Structural knife edge crossings shall be avoided. Where knife edge crossings cannot be avoided, knife edge chocks shall be fitted to prevent stress concentrations. Knife-edge crossings are defined as structural members that cross at any angle where they are separated by a structural boundary resulting in localized stress concentrations.
Joiner bulkheads surrounding wet spaces shall have a watertight, continuous coaming extending to 15 cm (6 inches) above deck. Free standing coamings around laundry washing machines, and deck drain(s) in each wet area surrounded by a coaming shall be installed .
Any external opening on the craft not covered by the deck above shall have watersheds to prevent water intrusion. The watersheds shall be seal welded to the bulkhead.
The structure and exterior of the YRBM deckhouse shall be constructed of steel.
| 100b | Top Deck Arrangement | The YRBM craft shall be provided with a permanently installed, open canopy meeting the following requirements: | |
| a) | Located on the top deck. | ||
| b) | 18.3 m (60 ft.) long | ||
| c) | 3.6 m (12 ft.) center height | ||
| d) | 3 m (10 ft.) sidewall height. | ||
| e) | Structurally designed to withstand wind loads of at least 209 km/hr. (130 mph). |
The canopy width shall be the same as the width of the upper deck. The canopy frame members and cover shall be constructed of metal and protected from corrosion. The flow of personnel on the top deck shall not be impeded with the installation of the canopy.
Large condensing units and water heaters shall not be installed beneath the canopy. LAN Room condensing units may be installed beneath the canopy.
An enclosed Recreational Equipment Storeroom of 5 m2 (53.82 ft2) shall be provided beneath the canopy. The height of the storeroom hall be at least 84 inches. The door to the storeroom shall have a minimum width of 54 inches.
A fixed LED lighting system, suitable for weather, shall be provided inside the canopy .
300 General Requirements for Electrical Power System Selection and installation of electrical equipment shall equal or exceed the practices of IEEE Standard 45 series.
The YRBM craft service electrical power system shall be supplied from shore power via multiple, separate 400 amp shunt-trip circuit breakers. The maximum fault-current (shore circuit) contributed by the Navy Standard pier side shore power facility is 100,000 Root Mean Square (RMS) amps at 480 volt AC. The YRBM craft electrical service shall be 450 volt Alternating Current (AC), 60 Hz, three-phase, three-wire, delta, ungrounded type.
YRBM craft distribution systems shall be 120, 230 or 450 volt AC, 60 Hz, 3-phase, 3-wire, ungrounded with distribution to single phase (1-phase) as required.
Electrical distribution equipment shall be provided with arc-flash warning labels in accordance with NFPA 70E. A Kilowatt-hour meter shall be installed on the main switchboard to allow barge managers to verify electricity service charges .
302 Electrical Motors and Associated Eqiupment Three phase induction motors, motors rated greater than 2.2 kilowatts (3 horsepower), motors located in the weather, and motors located in wet areas shall not have aluminum frames or parts. Silicone-bearing materials, which can release silicone vapor into the air stream of totally enclosed motors containing commutators or slip rings, shall not be used.
Motors equipped with lubricated anti-friction bearings shall be provided with tapped holes for lubrication that shall be closed with a screw plug.
Motors for use on weather decks shall be watertight and shall be equipped with sealed insulation.
305 Cables and Marking All cable, except for portable shore power cable, shall be low smoke, halogen-free, non-flammable and low toxicity in accordance with IEEE Std 45 type. Protective devices shall not exceed cable ratings. Protective devices shall be selected to achieve coordinated system protection in a fault event. The protective device(s) closest to the fault shall open first .
Low level signal cables shall be separated from power cables with high content of harmonics and spikes, and shall be protected from electromagnetic interference by installation in separate cable ways or in conduit. Cable separation practices shall be in accordance with IEEE Standard 518, Section 6.4.3, except color coding in that paragraph 6.4.3.7.6 does not apply. Wireway crossings shall be as nearly perpendicular as practical with maximum practical separation. Parallel wireways for cables in power, signal and electronic circuits shall be separated by a minimum of 46 cm (18 inches). Connection of OEM-provided equipment cables to ship's cables shall be via connection boxes. Splicing of cables 12 AWG (4 mm2) and smaller, coaxial cables, and fiber optic cables is not permitted unless approved. Power and Signal cable shall not be painted.
All cables shall be identified by banded metal cable tags, which meet or exceed the operating and environmental requirements of the cable on which it is used. Cable band material shall be compatible with the cable jacket material on which it is used. The cable bands shall be either black or white. All cable tag characters shall be legible, permanently stamped and visible to read without interference. The thickness of the banded metal cable tags shall be no less than 0.254 mm (0.010 inches). These tags are to be placed on cables at each point of termination, on both sides of deck and bulkhead penetrations or other barriers, and at least every 50 feet. Non-metallic labels shall be used when installed inside electrical enclosures .
312 Emergency Electric Power A Transitional Source of Emergency Power shall be provided in accordance with ABS Guide for Building and Classing Accommodation Barges, Section 9/15.7 and Appendix 1/3.7.
A dedicated shore power receptacle shall be provided to connect a Government furnished mobile generator set to the YRBM craft to provide the final emergency power source.
The emergency power receptacle shall be interlocked with the normal shore power connection receptacles to prevent simultaneous input from both power sources.
The required loads powered from the emergency power system shall be in accordance with ABS Guide for Building and Classing Accommodation Barges Section 9, paragraph 15 and with the exceptions provided in Appendix 1, paragraph 3.7.
In addition to the above, Emergency Power shall be provided for the following:
| a) | Refrigeration plants for provisions |
| b) | Galley refrigerators |
| c) | Galley freezers |
| d) | Medical space refrigerator |
| e) | LAN Equipment Room (All electrical power to computer racks. See Sect..401a). |
313 Storage Batteries and Charging Equipment Lead acid batteries shall be sealed, valve regulated, gas recumbent, maintenance free type. Lead acid batteries shall not be connected in parallel. Battery chargers shall have built-in filters and automatic voltage compensation. Lithium-ion battery use and installation shall be approved by ABS and the Government.
The emergency accumulation batteries shall be stored in accordance with ABS Marine Vessel Rules.
| 314 | Power Conversion Equipment | Uninterruptible Power Supply (UPS) shall be wired for an ungrounded system. UPS systems shall provide the required run time at full load for the following, either as a system or as a dedicated battery backup unless otherwise noted. Minimum required run times for UPS systems shall be 30 minutes unless otherwise noted. | |
| a) | Fire and Smoke Detection | ||
| b) | Intrusion Alarms | ||
| c) | Dial Telephone | ||
| d) | Integrated Master Alarm Panel . |
320 General Requirements for Power and Lighting Distribution Systems Power and lighting distribution panels, transformers, and distribution devices shall allow for twenty (20) percent future load growth on all systems (circuit breakers for twenty (20) percent future growth need not be provided). Panel loads shall be phase-balanced. Ground detection devices shall be provided at each distribution switchboard and any part of the distribution system isolated by transformers.
A Fault Current Analysis shall be performed on the electrical system. Each power and lighting distribution switchboard, with circuit breakers, shall be fault-current rated to handle the maximum calculated fault current as determined by the Fault Current Analysis.
320a Shore Power Connections The YRBM craft shall be provided with shore power connections. The number of shore power connections shall be determined from the electric system load and power analysis and shall allow for twenty (20) percent future load growth . The number of shore power connections shall not exceed five (5 ), excluding the separate connection for emergency power.
A phase sequence indicator shall be provided. Each shore power connection shall include a receptacle and a mating plug with a 3.05 m (10 ft.) length of three conductor cable attached.
The YRBM craft shall be provided with cables, plugs, and receptacles to enable the craft shore power system to interface with 400 amp safety plugs in accordance with Military Specification Sheet (MIL-C)-24368(Navy).
The shore power station shall include circuit breakers to trip upon under voltage or loss of phase. Shore power shall be connected to a circuit breaker on the YRBM craft service switchboard. Control circuitry for the shore power station shall allow any number of shore power receptacles to be in use.
Shore power monitoring capability shall be provided. Voltage, current, power factor, and power monitoring shall be provided for the total shore power demand and individual shore power cable phases. The ability to produce reports of kilowatt-hours consumed for any portion of the stored shore power data shall be provided.
The YRBM craft shall be provided with one dedicated 500 Amp Shore Power adapter cable to connect a mobile generator set, LEX Products Corporation, catalog number ADPVIK-CAM, or equal.
320b Emergency Lighting and Power Emergency lighting shall be adequate to permit personnel to readily find their way to the embarkation areas. The lights shall utilize self-contained rechargeable batteries capable of providing power for a minimum of 3 hours . The lights shall illuminate, as a minimum, egress routes, the Post Office, Medical Complex, Electrical Service Support Room, Walk-in Ships Store, General Admin Office No. 1, LAN Equipment Room and Master-at-Arms Office. Illumination levels of the emergency lighting shall be 5 ft-c in accordance with ASTM F1166 preferred levels .
The required loads powered from the emergency power system shall be in accordance with ABS Guide for Building and Classing Accommodation Barges Section 9/15 with the exceptions provided in Appendix 1, paragraph 3.7 of the guide.
320c Receptacles General purpose 120 volt AC single phase receptacle circuits shall be supplied from isolation transformers and shall not supply other types of loads including lighting fixtures except for mirror top light fixtures with integrated receptacles in heads and berthing.
Receptacle circuits shall be supplied by dedicated 15 amp circuit breakers. Circuits shall be zoned by utility. Receptacles throughout the craft shall be labeled with the type of power available and their intended use. Safety ground conductor shall be locally grounded to receptacle enclosure.
Unless otherwise specified, a minimum of two general purpose 120 volt AC, 15 amp duplex receptacles shall be provided in each normally manned space.
A minimum of one assigned general purpose 120 volt AC, 15 amp duplex receptacle shall be provided in normally unmanned spaces. The receptacle shall be installed such that a 7.6 m (25 ft.) extension cord provides total coverage within the spaces.
Open deck areas, excluding the deckhouse top, shall be provided weatherproof, general purpose 120 volt AC, 2015 amp duplex receptacles with a maximum spacing of 15.2 m (50 ft.) apart.
The deckhouse top shall be provided weatherproof, general purpose 120 volt AC, 20 amp duplex receptacles every 7.6m (25 ft) along the perimeter.
120 volt AC power supplied from a false deck (See Sect. 634) shall be provided to the classroom training tables.
In accommodation spaces and offices, receptacle outlets shall be readily accessible and installed at the rate of one outlet for each 3.6 m (12 ft.) (maximum) of bulkhead as measured horizontally along the deck. All compartments and passageways require a minimum of two receptacles and fan rooms require a minimum of one receptacle. Stair towers do not require receptacles. Dedicated receptacles that provide a specific service (e.g., electric shavers at washbowls, convenience outlets in berths, computer stations at desks, cash registers on counters, etc.) shall not be considered when meeting the 3.6 m (12 ft.) rule. Office spaces shall have dedicated outlets for desktop computer systems at each desk; no extension cords shall be required.
General purpose 120 volt AC receptacle circuits serving wet areas such as open decks, heads, Galley, Scullery, mess areas serving lines and laundry shall be fed from ground fault circuit interrupter (GFCI) circuit breakers with 5 mA sensitivity. Receptacles located in the weather and wet areas except sanitary spaces and messrooms shall be provided with watertight covers and shall maintain watertight integrity when not in use and when a cable is plugged into them.
324 Switchboards and Panels for Electrical Power and Lighting Spare circuit breakers comprising 10% or at least two of each type and size used for active feeder circuits up to and including the 400 amp frame size shall be provided. However no less than one breaker shall be supplied for each active frame size on the switchboards and panels. Circuit breakers shall be used in low voltage switchboards and panels.
General Requirements for Lighting Systems
| 400 | General Requirements for Electronic Systems | Individual shipboard equipment selections and installations shall be in accordance with IEEE Standard 45 series. |
| 400a | Installation | Equipment shall be located to ensure natural cooling and to avoid overheating. Units dissipating heat shall be arranged to preclude creating hot pockets within a space. Units shall not be located above or adjacent to heat producing apparatus such as piping and ducts. |
Electronic equipment shall be located away from liquid, spray, drip, splash, or blown droplets; or the equipment shall have protection provided.
Electronic equipment installed within the hull or superstructure envelope shall be mounted by one of the following methods, listed in order of preference:
| a) | Deck mounted |
| b) | Overhead |
| c) | Structural bulkheads only |
| d) | Deck mounted and braced to structural bulkheads |
| e) | Overhead and braced to structural bulkheads |
| f) | Electronic equipment shall not be secured to shell plating. |
Accessory items such as indicators, speakers and junction boxes shall be located in the overhead.
| 401 | General Arrangements for Electronics Systems | |
| 401a | Local Area Network (LAN) Equipment Room | The YRBM craft shall be provided with a dedicated Local Area Network (LAN) Equipment Room to house Unclassified and Classified Navy network equipment. |
The Government will furnish and install network equipment (servers/routers/switches) within and outside the LAN Equipment Room after delivery.
The LAN Equipment Room shall be provided with one desktop computer workstation with desk and chair situated in proximity of dedicated 120 volt AC, 15 amp duplex receptacles for electrical feed.
The LAN Equipment Room shall be provided with a minimum area of 24.2 m2 (260 ft2) of usable space within the total LAN Equipment Room’s total area. Usable space is defined by unobstructed floor space as well as a minimum height of 203.2 cm (80 inches) from the walking surface to any obstructions overhead. The LAN Equipment Room shall have a minimum length of 4 m (13 ft.) and a minimum width of 6 m (20 ft.). The LAN Equipment Room’s space reservation and arrangement shall accommodate the installation of network equipment, equipment maintenance/troubleshooting, furnishings, and services. Access to the LAN Equipment Room shall be from a passageway only. The LAN Equipment Room shall be in close proximity to the Commanding Officer (CO), Executive Officer (XO), and Senior Officer (SO) offices. In addition to the YRBM craft normal air conditioning system, an independent cooling system for the LAN Equipment Room shall be provided. The environmental conditions of the LAN Equipment Room shall be within the temperature range of 18°C (64.4°F) to 27°C (80.6°F). The Contractor’s cooling load calculations for the LAN Equipment Room’s independent cooling system shall include an additional 60,000 BTU/hr. margin. The LAN Equipment Room shall be provided with the following electrical services in addition to electrical receptacles requirements specified herein:
| a) | L14-30R single receptacle (125/250VAC, 30amps) for each computer rack |
| b) | NEMA 5-20A duplex receptacle (125VAC, 20amps) for each computer rack |
401a (continued) Local Area Network (LAN) Equipment Room The Contractor shall install computer racks (Kendall Howard 1940-3-001-41 or equal) with at least a 46 cm (18 inches ) horizontal clearance from bulkheads, furnishings, and installed equipment to the front, back, and one side of each rack within the LAN Equipment Room . Two racks shall be dedicated to the Unclassified LAN, one rack dedicated for the Classified LAN, and one rack dedicated for Wide Area Network (WAN) for external connections . Racks shall be grouped in accordance with security classification with the WAN rack designated as Classified. Each rack shall be provided five shelves (Middle-Atlantic-VSA-7244 or equal). Bulkhead or overhead braces shall be installed to support the upper ends of the computer racks against vertical, transverse, and longitudinal loads due to dynamic craft motions. The braces can be attached to the bulkhead or overhead by either welding or mechanical fasteners. The braces shall not impede the maintenance, insertion, or removal of electronic devices mounted within the computer rack. The estimated weight for a fully loaded, single rack is 404 kg (891 lbs.). All computer racks shall be set level with baseline. All fabrication, welding, mechanical fastening and inspection shall be accomplished in accordance with ABS Rules.
The Classified LAN shall meet DOD security requirements for transmission of data up to the SECRET-Releasable level. The Contractor shall install the network cabling for the Classified LAN in accordance with IA PUB 5239-22 and IA PUB 5239-31. Classified cables routed outside of the LAN Equipment Room shall be designated as a Protective Distribution System in accordance with IA PUB Module 5239-22.
The YRBM craft shall be provided one pierside connectivity, pigtail assembly, fiber optic jam nut mounted receptacle (hermaphroditic) to ST connector (Delphi, P/N 1123790-1H) located in the starboard side recessed Shore Connection Station of the YRBM craft for the Unclassified and Classified LANs.
401b LAN Ethernet Drop Boxes The Contractor shall provide wall-mounted, LAN Ethernet drop boxes (Wiremold P/N 2348 or equal) and 4-port faceplates (Hellermanntyton P/N FPIHQUAD-FW or equal) with Cat 6 modular keystone jacks (Hellermanntyton P/N RJ45FC6-FW or equal) for each Classified and Unclassified LAN termination point identified in Table 401b-1 Unclassified Inter-Compartment Cabling List and Table 401b-2 Classified Inter-Compartment Cabling List.
The LAN Ethernet drop boxes shall provide outlets for the Unclassified, Classified, and telephone cables. The color code of the cabling of the Unclassified network, Classified network, and telephone system shall be green, red, and blue respectively.
401b-1
Unclassified Inter-Compartment Cabling List
401b-2
Classified Inter-Compartment Cabling List
401c Network Cables All inter-compartment cables shall originate from the LAN Equipment Room. The Contractor shall provide, install, and test all CAT 6 cables from the LAN equipment room to Contractor furnished LAN Ethernet drop boxes for the Unclassified and Classified LANs. The Contractor shall seal and coil all non-terminated cable ends upon completion of installation and resealing and coil after completion of testing. Cable wire trays, raceways, hangers, and banding to support the routing of inter-compartment cables shall be provided by the Contractor. All cables shall be of sufficient length to enable termination at the LAN Ethernet drop boxes and reach their respective racks within the LAN Equipment Room plus 2 m (6.6 ft.) at each end .
The network systems shall utilize multi-mode fiber optic backbone between the servers and backbone switches to be furnished and installed by the Government, however, the Contractor shall propose suggested locations for remote switches. The Government will terminate all cables within the LAN Equipment Room and at remote switching devices and the Contractor shall terminate all cables at LAN Ethernet drop boxes after compartment completion.
The Contractor shall install non-metallic cable bands for identification on all network cabling, which meet or exceed the operating and environmental requirements of the cable on which it is used. Cable band material shall be compatible with the cable jacket material on which it is used. The cable bands shall be either black or white. All cable band characters shall be legible, permanently stamped and visible to read without interference. The thickness of cable bands shall be no less than 0.010 inches.
402 Secure Electronic Information Processing Systems Construction of secure spaces and installation of secure inter-compartment cables shall be in accordance with IA PUB Module 5239-22 and Module 5239-31, and exhibit 10a of SECNAV M-5510.36. The physical perimeter barrier of a secure space shall be the deck, overhead, and the bulkheads that bound the space. Secure cables that pass through Uncontrolled Access Area (UAA) spaces shall be installed in a hardened carrier as defined by IA PUB Module 5239 22.
Spaces shall be designated as Secure Room (SR), Restricted Access Area (RAA) or UAA as defined by IA PUB Module 5239-31 as follows:
a) SR:
1. LAN Equipment Room
b) RAA:
| 1. | CO Office |
| 2. | XO Office |
3. SO Office
| 4. | One General Administrative Office in close proximity to the LAN Equipment Room, CO Office, and XO Office |
| c) | UAA: |
| 1. | All other compartments. |
Doors for secure spaces shall be provided with an X-10 Combination Lock.
403 Personnel Safety Personnel shall be warned of potential hazards in accordance with the following:
a) Electrical Shock - A label plate relating to circuit disablement shall be inscribed as follows and shall be affixed, with pertinent information filled in, on all equipment energized from multiple power sources:
WARNING
THIS EQUIPMENT ENERGIZED FROM MULTIPLE SOURCES
TURN OFF THE FOLLOWING TO FULLY DE-ENERGIZE THIS UNIT
| CIRCUIT | SWITCH | SWITCH | ||||
| LOCATION | IDENTIFICATION | |||||
| ________ | _________ | ___________ | ||||
| ________ | _________ | ___________ |
| b) | High Voltage - Warning signs in accordance with IEEE Standard 45 series shall be installed in electronic spaces and other spaces where personnel could come into contact with exposed energized equipment. |
| c) | First Aid Signs - Electronic shock first aid and emergency resuscitation procedures signs shall be posted in all spaces containing electronic equipment. |
405 Grounding and Bonding Shipboard bonding, grounding, and other techniques for electromagnetic compatibility and safety shall be in accordance with Military Standard MIL-STD-1310 unless specified otherwise.
407 Electromagnetic Environment Effects (E3) Cables routed internal to the YRBM craft shall not be routed within 31 cm (12 inches) of weather openings such as doorways, hatchways, and window openings unless the cables have a single or double optimized braid shield or the cables terminate at these openings, such as door alarm cables.
The YRBM crew shall not be exposed to unsafe levels of electromagnetic radiation anywhere on the craft. Equipment arrangement and installation methods shall prevent performance degradation from Electromagnetic Interference.
The YRBM shall be provided lightning protection systems. The lightning protection system shall meet MIL-STD-464 and MIL-STD-1310. A separate 0000 AWG cable connected to the main ground connection point shall be installed for lightning protection. This cable shall be routed in as straight a line as possible and shall be continuous and unspliced from the highest conductive surface to the main ground connection point. Where a metal mast is used, it shall be connected to the ground plates using a size 0000 AWG cable. Equipment on the mast that requires grounding shall be grounded to the mast.
422 Electrical Navigation Aids The YRBM craft shall be provided with navigation lighting in accordance with Department of Homeland Security, USCG Navigation Rules and Regulations Handbook for a moored barge and barge being towed, unmanned, in open-ocean and coastal environments.
Navigation lights and their connected batteries shall be capable of a minimum of eighteen (18) hours of continuous operation without recharging.