MEDIUM VOLTAGE POWERHOUSE – STATEMENT OF WORK SUMMARY
This is a Statement of Work (SOW) for the procurement, design, construction, and delivery of a Medium Voltage (MV) Powerhouse to support the Liquid Nitrogen Air Separation Unit (LNASU) electrical infrastructure at NASA Stennis Space Center in Hancock County, Mississippi. The vendor must provide a fully enclosed, factory-fabricated, transportable steel structure measuring approximately 38 feet in length, 15 feet in width, and 10.5 feet in height, with a total system weight of 66,301 pounds. The structure must be NEMA 3R-rated, built from 16-gauge interlocking galvanized steel panels, with floor insulation of 4 inches spray polyurethane (R-12.0), wall insulation of R-13, and roof insulation of R-19. The powerhouse must be designed for a 10-year service life, be UL/cUL listed, and comply with wind loads of 146 mph (Exposure C), roof and snow loads of 20 psf each, and seismic Category C requirements. The structure must maintain interior temperatures between 65°F and 80°F with a heat load of 13,800 watts and provide lighting at 30 foot-candles at 3 feet above floor at 4000K color temperature.
The major electrical equipment includes: a 45 kVA LV dry-type transformer (480–120/208V), an MVA switchgear (5 kV) with three sections rated at 40 kA and 1,200 amps, a DC load center (100A) with battery rack (120 VDC output, 100AH VRLA batteries), two LV panels (277/480V and 120/208V), and two exterior wall-mounted 4-ton air conditioners. Two soft starters (2,068 KW and 781 KW) are provided by others. The vendor must supply 14 LED 4-foot fixtures (4,000 lumens, 50W), emergency and exit lighting, interior and exterior receptacles, and a complete grounding system with 2-inch by 1/4-inch copper bar around the full perimeter. All equipment must be UL-listed, structural materials must comply with Buy America/BABA/BAA/TAA requirements, and the vendor must deliver comprehensive deliverables including certified structural and HVAC calculations, electrical drawings, as-built documentation with bill of materials, and manufacturer data sheets. Delivery must be completed by April 16, 2027, with two days of customer inspection and factory acceptance testing required. All dimensions referenced in the applicable drawing (EMI XL50-26007-01, E-103) are authoritative, and the vendor is responsible for verifying final dimensions with government-furnished equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Draft MV PWRHS Concept.pdf | ||
| Draft SPECIFICATION - MV Powerhouse.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAFT
National Aeronautics and Space Administration
NASA Shared Services Center (NSSC) Building 1111, Jerry Hlass Road Stennis Space Center, MS 39529
MEDIUM VOLTAGE POWERHOUSE – STATEMENT OF WORK
1. Scope
The vendor will provide equipment indicated in this document. This document directs the procurement, design, construction, equipment delivery, performance, testing, and documentation requirements for the Medium Voltage (MV) Powerhouse supporting the Liquid Nitrogen Air Separation Unit (LNASU) electrical infrastructure at NASA Stennis Space Center, Hancock County, MS. The Powerhouse provides electrical distribution, control, HVAC, grounding, lighting, and ancillary support systems. Dimensions, environmental criteria, and equipment layout default to the latest configuration shown in the MV Powerhouse Plan Layout. Two Soft Starters, explicitly stated in this document, will be provided by others.
2. Applicable Documents
The following documents apply:
• EMI XL50-26007-01, Drawing E-103, “MV Powerhouse – Plan Layout” (authoritative).
• nVent RuggedSpec Equipment Center Specification (for construction methods, materials, insulation, UL requirements).
Codes and Standards:
• NEC (NFPA 70)
• UL 508A, UL 1598 (wet location lighting)
• Applicable International Building Code criteria (structural/wind/seismic)
3. General Requirements
The MV Powerhouse shall be a fully enclosed, factory-fabricated, transportable steel structure designed to house and protect the complete MV electrical distribution system, HVAC equipment, and required support equipment.
• All equipment identified as GFE remains Government-Furnished.
• All dimensions shown in the PDF drawing are authoritative.
• 10-year design life, UL/cUL listed
4. Physical Dimensions (approximate)
• Length: 38 ft
• Width: 15 ft
• Height: 10.5 ft
• Total system weight: 66,301 lbs
5. Environmental & Design Criteria
• Wind Load: 146 mph
• Temperature Range (interior): 65 °F min – 80 °F max
• Interior Heat Load: 13,800 W (engineers to verify)
• Lighting requirement: 30 foot-candles at 3 ft above floor, 4000 K color temperature.
• Structural materials must comply with Buy America, BABA, BAA, or TAA requirements.
Additional structural data:
• Roof Load: 20 psf
• Snow Load: 20 psf
• Wind design: 146 mph Exposure C
• Seismic Category: C
6. Structural Design & Construction
• Structure shall be NEMA 3R, built from 16-gauge interlocking galvanized steel panels.
• Structural steel base engineered for lifting with equipment installed.
• Floor insulation: 4 in spray polyurethane, R-12.0.
• Wall insulation: R-13; Roof insulation: R-19.
• Powerhouse shall have doors for working on back access.
• Doors: Wind-rated CECO personnel doors:
• One single door 3 FT – ASSY - exterior #3070 wind rated 16 ga galvanized personnel door, 70 PSI (165 mph) CECO rated door/frame, stainless steel hinges.
• One double door 6 FT – ASSY - exterior #6080 wind rated galvanized personnel door 70 PSI (165 mph) CECO rated door/frame, stainless steel hinges.
• Paint system: ANSI-70 exterior; interior white polyurethane coating. . (Lead Free)
• Fire resistance (Flame spread rating 25 or less)
• Exterior walls of 16 ga pre-galvanized G90 sheet steel interlocking panels ASTM A653.
• Exterior walls floor channel 12 ga G90 galvanized.
• Exterior wall cap 14 ga G90 galvanized.
• Roof panels 216 ga pre-galvanized G90 sheet steel interlocking panels ASTM A653.
• Ceiling panel of 16 ga pre-galvanized G90 sheet steel interlocking panels ASTM A653.
• Interior walls – 16 ga pre-galvanized G90 sheet steel interlocking panel ASTM A653.
• Insulation ceiling 3” R19 urethane duct board.
• Insulation exterior walls 3” R13 fiberglass batt 16” wide.
• Three 12” x 12” , 90 minutes fire rated window kit (window stich cut in door).
• HVAC controls #18 AWG thermostat wire.
• Roll applied corrosion resistant epoxy primer to minimum DFT of 2.0 mils.
• Polyurethane Enamel paint to minimum DFT of 2.0 mils.
7. Major Electrical Equipment (as shown in EMI XL50-26007-01 E-103-Layout1.pdf)
7.1 MV Soft Staters – Provided by others, two (92” H x 96” W x 30” D)
1. Soft Starter Motor 1 - 2,068 KW (MAC-SS)
2. Soft Starter Motor 2 - 781 KW (RAC-SS)
7.2 Transformers:
• LV Dry-type Transformer: 45 kVA, 480–120/208 V. Dimensions: 24.88 in W × 21.13 in D ×
36.88 in H.
• Additional transformer details (DOCX): 45 kVA, 480V → 208Y/120V, 3-phase.
7.3 Switchgear
• MVA Switchgear (5 kV), standard three sections (96.25 in D × 36 in W × 95 in H for each).
a. Medium Voltage Assemblies, 4160V, 3-Phase, 3-Wire, 60 Hertz
b. 40 kA, 1200 Amps Main Bus Rating
c. Lightning arrester distribution class 9 kV - Set of 3
d. Main Vacuum Breaker - Breaker Compartment 5 VCP-W 40kA 1200A
e. Vacuum Breaker 1 - Breaker Compartment 5 VCP-W 40kA 1200A
f. Vacuum Breaker 2: - Breaker Compartment 5 VCP-W 40kA 1200A
g. Vacuum Breaker 3 - Breaker Compartment 5 VCP-W 40kA 1200A
h. Enclosure: NEMA 1, front and back access.
7.4 Panels & Battery Rack
• DC, Load Center NEMA 1, 100A, 2-poles battery Main, 2-poles charge feed, 12 circuit breakers.
• Battery rack dimension 32 in D x 30 in W x 79 in H, DC output 120 VDC, one 10 battery string, 100AH-Valve-Regulated Lead-Acid (VRLA), DC charge, alarm and communication.
• LV Panel 277/480V: 600A main bus, 400A main breaker, 65 kA rating with all branch breakers, UL listed, approximate dimension: 90” H x 20” W x 6.5” D.
• LV Panel 120/208V: 250A main bus, 150A main breaker, 42 kA rating with all branch breakers, UL listed, approximate dimension: 60” H x 20” W x 6.5” D.
• Cabinet type: NEMA 1, dimension approximate: 30.5 W x 31.5 D x 79 H.
8. Raceway, Cable Tray & Distribution
• Conduit exterior: Exposed rigid galvanized as required by NEC, min ¾” AMSI C80.1
• Conduit interior: Exposed EMT conduit as required by NEC.
• Wire Power wiring – Type: THHN/TNWN, min #12 AWG, 600 V, temperate rating 75 C degree.
• Primary cable tray: 18 in wide, 9” running space, 12 ft sections.
• Copper bar ground loop runs 3 in below ceiling: 2 in × 1/4 in copper bar, around full perimeter.
Supplemental DOCX (non-conflicting):
• Optional 24 in tray for high-amp circuits.
• Aluminum side rail, 9 in rung spacing.
9. HVAC System
• Two 4-ton exterior wall-mounted air conditioners (LV-ACC-1 and LV-ACC-2).
• No cooling redundancy.
DOCX supplemental:
• Bard W36AF-C06BPXXXJ, 480 V, 3-phase, 6 kW heat, 38.2 in W × 17.125 in D × 70.563 in H.
• Low ambient control, alarm relay, internal grills, thermostat, temperate & humidity sensors (remote).
10. Lighting Receptacles
• 14 × LED 4-ft fixtures, 4000 lumens, 50 W, 120/277 V, UL listed.
• Exterior lighting: Wall-pack LED fixtures
• Emergency lights & Exist lights.
• Indoor & Outdoor (GFI) receptacles.
11. Grounding
• Full perimeter copper ground loop: 2 in × 1/4 in bar, 3 in below ceiling.
• 4 × ground pads and 4/0 ground lugs.
• Drops to equipment per drawing.
• Grounding and bonding with materials required per UL 96 A.
12. Communications
• Communication interface: Modbus TCP/IP.
13. Safety & Labeling
• Warning signage required: “DANGER HIGH VOLTAGE / KEEP OUT”.
• Fire protection included
• Fire extinguishers 4A:60B:C / 10 lb. Multipurpose dry chemical.
14. Installation Requirements
• Contractor to verify all final dimensions with GFE and Cosmodyne drawings.
• All customer-supplied equipment must arrive with NRTL labels.
15. Testing & Inspection
• Megger testing of all nVent-furnished circuits.
• Two days of customer inspection and FAT.
16. Deliverables
Structural calculations, electrical drawings, HVAC Calculations, center of gravity calculations (certified design calculations performed by a registered Mississippi Professional Engineer).
• As-built package including BOM and manufacturer data sheets.
• Certification of Structural integrity to meet ASTM and all components to meet requirements.
• Shipping details.
• Powerhouse assembly details at Stennis Space Center – Mississippi.
17. Delivery Timeline
• Delivery receipt of powerhouse to be complete by 4/16/27
18. Notes
• All dimensions are “for reference”; contractor must verify.
• Cooling redundancy: none.
• Temperature control: 65–80 °F.
• All electrical equipment must be UL listed.