This is a draft design refresh drawing package for Fiscal Year 2026 repairs to Unaccompanied Personnel Housing (UPH) Building 581 at Camp Zama, Japan. The project involves comprehensive revitalization of an existing three-story dormitory building (approximately 2,227.5 square meters) used by military personnel, with no individual cooking facilities in bedrooms. The work includes demolition, renovation, modifications, and extensive modifications across all three floors. The project is managed by the U.S. Army Corps of Engineers, Japan Engineer District, and was issued in January 2026 as a 100% backcheck design submittal (not for construction).
The project scope encompasses architectural, civil, mechanical/plumbing, electrical, interior design, environmental, telecom, and fire protection systems. Applicable standards include the 2024 International Building Code (IBC), 2024 NFPA 101 Life Safety Code, 2024 NFPA Fire Code, 2025 NFPA 13R Sprinkler Systems standards, and 2026 National Electrical Code. The building is classified as Type IIB construction with occupancy classification as residential R-2 (dormitory). Building height is 10.48 meters (3 stories), with maximum allowed 18.29 meters, and total building area is 2,227.5 square meters. Total occupant load is 259 persons (103 first floor, 78 second floor, 78 third floor). The project requires a supervised automatic fire sprinkler system throughout, new addressable fire alarm system, mass notification system integration, and hazmat abatement including asbestos remediation, lead/cadmium/chromium abatement, and PCB ballast removal. A new fire water line connection to Waterline B will be installed with associated new fire hydrant to ensure adequate fire flow (3,785 liters per minute at 1.38 bar).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HOKKAIDO
HONSHU
SHIKOKU
OKINAWA
KYUSHU CAMP ZAMA
AR-397 PH-3
RIDGWAY ROAD
PLAY GROUND
174S .T.
S.T.187
(JGSDF)
NON ARMY P
ROPERTY
T-2
-2T-2
-3
S -10
0 -1
S -10
09-1
S-10
-1
S-1
-1
S-1
6-1
S-1005 -1
S-1004-1
S-1 003-1 S-1002-1
S-1001-1
60-H1
GATE
G A
T E
GATE
ELECTRIC
ANTENNA
ANTENNA
TENNIS
S.T.
"L " S
T R
E E
T
"K " S
T R
E E
T
"I " S
TR
E E T
4T H A
VEN
UE
5TH A
VEN
UE
"H " S
T R
E E
T
1ST A
VENUE
H .Q
. R O
A D
4TH A
VEN
UE
5TH AVENUE
2ND A
VE
NUE
S
T A
V E
N U
E
"C " S
T R
E E
T
4TH
A
VEN
UE
RA
N
G E
R O
AD
CLIFF DRIVE
5T H
A V
E N
U E
4T H A
VE
N
U E
NO. 1
N O
. 2
N O
. 3
N O
. 1
N O
. 1
N O
. 4
NO
. 6
N O
. 7
NO. 8
N O
. 1
N O
. 1
NO. 17
NO. 16
NO. 12
NO. 1
E L.195.83B .M.
O.T
A /C
T.B .
A /C
A /C
L.P .G
B O
W M
A N
R O
A D
B O
W M
A N
R O
A D
T.B
O .T
T.B
T.B
A/C
O .T
O.T.
CLAR
K LO
O P
O.T.
T.B .S.T.
S.T.532
O .T
8-
TR
TR
A /C
C H
E S T
N U
T D
R
IV
E
HIGHLAND DRIVE
O.T.9-5
TR
TR
2-5
36-5
PINE TREE ROAD
S.T
35H5
34-5
581-1
MOUNTAIN ROAD
A / C
TR O
T
-5
TR
TR
TR
US ARMY KASTNER AIRFIELD
GATE NO.4
1045-1
TEN
NIS
C
OURT
104-1
70 1
72 1
J-1
J-7
J-3
J-2
P-13
P -9
SHED
P-2
O.T
S-152
S-153
S-1
101H1
S-109
SENTRY B
OX
GATE N
O.6
S-160
S-106
S -69
S-116
S -5
S -99
S -99
S -9
268-1
DUGOUT
DUGOUT
S -28
S -9
S-3 16T-3
16-
S -3
S -3
T-325
C A
R W
A S
H E
R
S-3
332-S
S-333-1
S -337
341-S
S -34
S -40
283-1
S -20
S-3
S-3
-2
S-3
S -37
S -37
S -378
S -376
S-3
S-3
S -383
S -68
T-675
T-684
S -64
S-35
S-
S-34
S-36
1 2
3 4
2 3
S -5
S -50
S-502
S-512
S -2
S-3
S-4
S-15
S-98
S3-2
S-43
55-5 S-55
S-54
S-53
53-5
S-
S-
S
- 5
T-593
S-37
1 4
S-40
S-39
S-8
S-7
S -792
S-99
S -7
S -81
S-809
S-661
S -72
S -724
S-7
S -732
S -731
S -6
S-6
S -625
S-607
S-6 21-1
S-65
M
OTO
R P
OO
L A
REA
400M
RUNNING TRA
CK
S-916
S -99
6T-996-1
T-996-2
S-953
S-82
S
S1008
S100
S1000 S1001
S1002
S1003 S1004
S1005
S100
2 1
T-1020-1
S-1023
1032-1
1032-2
1030-1
1045-2
S-1048
1042-1
1042-2
S-634
-1
T-6
-1 T- 694
-2
S-787
102H2
S-100 S-5
S-6
S -1
T-1
S-312
S-1
S-1
S-1
MO
NUMENT
S-221
S-3 16T-3
16-
T-325
S -337
341-S
S-21
1 2
3 4
2 3
T-571
1 4
S-99
S-8
S-733
P-27
T-6
S -601
989-2
T-608
SUB-S
TATIO
N
S -1
SAGAMIHARA CITY
ZAMA CITY
CITY BOUNDARY
SAGAMIHARA CITY
ZAMA CITY
S-280
S-2
S-5
S-5
T-3
J-6
J-5
1ST AVENUE
S-9
3 9
S -621
OFFIC
ER R
OAD
S-198 FENCE
1ST A
VENUE
S726
S-1027
S-737-1
S-737-2
7 3
H5
T-
JN.C
D
B.M
S-107
S -34
S -723
S-825
S-851
S-1086
WIND SOCK
AUTO MATIC WIND METER
-2
506-1
510-1
2 1
O.T
S-3
-3
S1
S-587
287-2
T-784
FOOTBALL FIELD
PLAY
G R
O U
N D
FISH POND
286-1
BASEBALL F
IE
LD
SOFTBALL F
IE
LD
S-2
33PARADE F
IE
LD
SOCCER F
IE
LD
(S -1
99)
(S-2 95)
GATE NO.1
GATE NO.2
P -3
P -10
P -12
GATE NO.7 852
T-1050-2
FLAG
P
OLE
S
TENNIS COURT
287-1
T E N
N
IS
C O
U R
T
M
IN
I G O
LF
S .T.
S-26
J-4
0-1
S K A
T E R
IN
K
312-1
SWIMM
ING POOL
S318
G A T E N
O .3
SEPARATOR
OIL
WASH RANP
600-1
615BRIDG
E
O.T.
W.T
832-2
W.T
832-1
PLAY GROUND
CARPORT
S-7
1092-1
PLAYGROUND
1094-1
PLAYGROUND
S-1024
M
ECH
x;
B
A
SK
E
TB
AL
L
C O
U R
T
0-1
P
LA
Y G
R O
U N
D
989-1
W.T.
PLAY
GROUND
S-7
S-1024-2
S-1083
S-802
S-1050-1
S-856
T -7
GOLF DRIVING RANGE
T.B
807-1
T-450 -3
S -603
S -64
T-8
GOLF COURSE
PLAY
G
RO
U
ND
1-
201-1
8- 1
C
AR
W
AS
H A
R
EA
S-406-1
S-4 50-2
S -601-1
S-6 21-3
S-69 4-3
S-704 -1
T-7 04-3
1018-1
102H1
1032-5
1043-1
-2
-3
-4
PLAY
GROUND
1065-1
S-5011
S .T
PLAYGROUND18-H3
PLA
Y G
D
P
LA
Y G R
O U N D
"B " S
TR
E
E T
.31
.33
T-1
314-H
M U
LTI P
U
R P
O S
E C
O U
R T
GATE NO.1
T
- 831
9 2 .5
9 5
9 8 .5
9 6 .0
9 6 .2
9 8 .5
9 3 .7
9 8 .5
9 5 .2
9 7 .2
9 5
9 5 .5
9 4 .5
9 7 .5
9 5
9 5 .6
9 6 .9
9 4 .0
9 3 .1
9 3 .0
9 3 .8
.7 0
.9 2
.0 1
.5 5
.8 8
.2 6
.7 0
.6 6
.1 9
.1 7
858 9
.9
.1
.2
.9
.3
.2
.1
1022-1
S-7
W A
TER
ST
O
RA
GE
TAN
K
T -205-H1
A-00-138
T-715-1
T-7
-2
T-53-H6
T-6 45-1
T-234
S -227
1039-1
"D " S
T R
E E
T
581-3
GATE
G A
T E
G A
T E
G A
T E
G A T E
T-58
T-6 42-1
T-6 45-2
T A
Y L O
R R
O A
D
MAC ARTHUR DRIVE
MAC ARTHUR DRIVE
H U
LL
R
O A
D
S-6 x; ST OP x; ST OP T-1095-1
T -5
-1 T
-5
-2
CONC DITH
C O
N C
D
IT
H
CONC DITH
C O
N C
D I T
H
CONC DITH
CONC DITH
C O
N C
D
IT
H
C O
N C
D I T
H
CONC DITH
PLAY GROUND
T-741-10
T-7
-1
T-741-1
J-1
1024-1
910-1
CAR
W
ASH
ER
123H -1
X X
X X
X
X
X X
X
X
X
X
X
X
S-997
XFMR
X F
M R
T -7
1024-5
314 -H
S-795-1
T-795-2
S -5
5-
T-585-2
1042-3
-1
T-694-4 T-694-5
GATE
715H2
T-984-H1
552-H 1
T -1
4-
G A
TE
DO
G
T R
AIN
IN
G A
RE
A
CONC DITH
PLAY GD
GATE
HIGHLAND DRIVE
U.S.T
PGCH1
ANTENA
GATE
GATE
G .T
W
IT
H O
.T
683H
04-H
T- 791
H4 H5
H3
H6 H7
H8 H9
S -998
3-
H3
H3
0-H
-H
341-H
341-H
563-H1
1-H
782-H1
1-
H1
3-
H
EAGLES NEST
CO
O
MER D
RIV
E
3RD A
VEN
UE
E S T R E E
T
E S
T R
E E
T
S -685-1
3R D
A
VE
N U
E
3RD AVENUE
R
D A
V E
N U
E
3RD A
VEN
UE
T-6 25H
T-10 42-4
333H2
704H4
G E
N
X F
M R
T.R
GATE
O.T
UNDER CONSTRUCTION
LAKE 1
LAKE 2
N O
S-8
-H
314- H4
314-H5
314-H6 314-H7
N O
. 1
N O
. 9
GA
TE
621H 4621H
S-3 79-1
.3
.8
.4
.3
OW2.6
OW14
O W
D V5.5
D V .6
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
ARCHITECTURECIVIL
MECHANICAL/PLUMBING
ELECTRICAL
INTERIOR DESIGN
ENVIRONMENTAL
TELECOM
205 N. MICHIGAN AVE.
SUITE 3800
CHICAGO, IL 60601
www.expFederal.com proj. no.: US Army Corps of Engineers ®
CONTRACT NO.:
ISSUE DATE:
SOLICITATION NO.:
JAPAN ENGINEER DISTRICT
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
FIRE PROTECTION
THIS WORK WAS PREPARED BY ME OR
UNDER MY SUPERVISION
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
C O
V E
R S
H E
E T
G-001
B
A C
K C
H E
C K
D E
S
IG
N S
U B
M
IT
T A
L
N O
T F
O R
C O
N S
T R
U C
T
IO
N
B C
A R
IN
O
B C
A R
IN
O
D K
A N
E S
H
IG
E
J A
N U
A R
Y
B R
G
E N
.r v t-
CAMP ZAMA, JAPAN
FY26 REPAIR UPH BLDG 581 DESIGN REFRESH
PAC-25008780-A0
JANUARY 2026
UPH BUILDING 581
MAP OF JAPAN
VICINITY MAP
NORTH
N O
R T H
DR
AF
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SE
A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
S H
E E
T I
N D
E X
G-002
B
A C
K C
H E
C K
D E
S
IG
N S
U B
M
IT
T A
L
N O
T F
O R
C O
N S
T R
U C
T
IO
N
B C
A R
IN
O
B C
A R
IN
O
D K
A N
E S
H
IG
E
J A
N U
A R
Y
B R
G
E N
.r v t-
SHEET
NUMBER
SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX - 1
G-003 SHEET INDEX - 2
GI001 LIFE SAFETY CODE ANALYSIS
GI100 CODE COMPLIANCE SITE PLAN
GI101 FIRST LEVEL LIFE SAFETY PLAN
GI102 SECOND LEVEL LIFE SAFETY PLAN
GI103 THIRD LEVEL LIFE SAFETY PLAN
ENVIRONMENTAL
H-101 HAZMAT ABATEMENT
CIVIL
C-001 ABBREVIATIONS, GENERAL NOTES AND LEGEND
C-002 TEMPORARY CONTRACTOR'S LAYDOWN AREA PLAN
C-003 CONTRACTOR'S HAUL ROUTE
CD101 DEMOLITION PLAN
CU101 UTILITIES PLAN
CU201 FIRE WATER LINE PROFILE AND LAYOUT
C-501 WATER LINE DETAILS
C-502 MISCELLANEOUS DETAILS - 1
C-503 MISCELLANEOUS DETAILS - 2
C-504 MISCELLANEOUS DETAILS - 3
C-505 MISCELLANEOUS DETAILS - 4
C-506 WATER LINE PIPING DIAGRAMS
ARCHITECTURAL
AD001 ARCHITECTURAL REMOVAL SCOPE OF WORK, REMOVAL SCOPE MATRIX
AD100 REMOVAL PLAN OVERVIEW
AD101 FIRST FLOOR REMOVAL PLAN
AD102 SECOND FLOOR REMOVAL PLAN
AD103 THIRD FLOOR REMOVAL PLAN
AD104 FIRST FLOOR REFLECTED CEILING REMOVAL PLAN
AD105 SECOND FLOOR REFLECTED CEILING REMOVAL PLAN
AD106 THIRD FLOOR REFLECTED CEILING REMOVAL PLAN
AD200 REMOVAL ELEVATIONS
AD201 REMOVAL INTERIOR ELEVATION - 1
AD202 REMOVAL INTERIOR ELEVATION - 2
AD203 REMOVAL INTERIOR ELEVATION - 3
AD204 REMOVAL INTERIOR ELEVATION - 4
AD300 BUILDING REMOVAL SECTION
AD400 REMOVAL SECTION DETAIL
AD401 REMOVAL PLAN DETAIL - 1
AD402 REMOVAL PLAN DETAIL - 2
A-001 ARCHITECTURAL NEW SCOPE OF WORK, NEW SCOPE MATRIX
A-100 NEW PLAN OVERVIEW
A-101 FIRST FLOOR NEW PLAN
A-102 SECOND FLOOR NEW PLAN
A-103 THIRD FLOOR NEW PLAN
A-104 FIRST FLOOR REFLECTED CEILING NEW PLAN
A-105 SECOND FLOOR REFLECTED CEILING NEW PLAN
A-106 THIRD FLOOR REFLECTED CEILING NEW PLAN
A-107 NEW DOOR & WINDOW KEY PLAN
A-200 NEW ELEVATIONS
A-201 NEW INTERIOR ELEVATION - 1
A-202 NEW INTERIOR ELEVATION - 2
A-203 NEW INTERIOR ELEVATION - 3
A-204 NEW INTERIOR ELEVATION - 4
A-300 BUILDING NEW SECTIONS
A-400 NEW SECTION DETAIL - 1
A-401 NEW SECTION DETAIL - 2
A-402 NEW PLAN DETAIL - 1
A-403 NEW PLAN DETAIL - 2
A-404 NEW PLAN DETAIL - 3
A-410 FIRE ENTRY ENCLOSURE PLAN AND DETAILS
A-411 FIRE ENTRY ENCLOSURE PLAN AND DETAILS
A-412 FIRE ENTRY ENCLOSURE PLAN AND DETAILS
A-500 DETAILS
A-501 RC WALL MODIFICATION & OTHER WALL DETAILS
A-502 PARTITION TYPES & DETAILS
A-503 CEILING DETAILS
A-504 DOOR DETAILS
A-505 WINDOW DETAILS
A-506 BATHROOM ACCESSORY DETAILS
A-600 DOOR TYPES & HARDWARE SCHEDULE
A-601 DOOR/WINDOW SCHEDULE & WINDOW TYPE
INTERIOR DESIGN
I-101 FIRST FLOOR INTERIOR ELEMENTS PLAN
I-102 SECOND FLOOR INTERIOR ELEMENTS PLAN
I-103 THIRD FLOOR INTERIOR ELEMENTS PLAN
I-401 TYPICAL ENLARGED UNIT PLANS
I-402 TYPICAL ENGLARGED KITCHENETTE PLANS
I-501 MILLWORK ELEVATIONS
I-502 MILLWORK ELEVATIONS
I-601 MILLWORK DETAILS
I-602 MILLWORK DETAILS
IN101 FIRST FLOOR FINISH PLAN
IN102 SECOND FLOOR FINISH PLAN
SHEET
NUMBER
SHEET NAME
IN103 THIRD FLOOR FINISH PLAN
IN601 FIRST FLOOR ROOM FINISH SCHEDULE
IN602 SECOND FLOOR ROOM FINISH SCHEDULE
IN603 THIRD FLOOR ROOM FINISH SCHEDULE
IN604 INTERIOR LEGENDS
IG501 SIGNAGE DETAILS
IG601 ROOM SIGNAGE SCHEDULE
FIRE PROTECTION
FA001 FIRE ALARM/MNS GENERAL NOTES AND LEGEND
FD101 FIRE ALARM DEMOLITION PLAN
FA101 FIRST LEVEL FIRE ALARM/MNS PLAN
FA102 SECOND LEVEL FIRE ALARM/MNS PLAN
FA103 THIRD LEVEL FIRE ALARM/MNS PLAN
FA500 FIRE ALARM/MNS DETAILS
FA700 FIRE ALARM/MNS INPUT/OUTPUT MATRIX
FA701 FIRE ALARM/MNS RISER DIAGRAM
FX001 FIRE SPRINKLER GENERAL NOTES, ABBREVIATIONS, AND LEGEND
FD102 FIRE SPRINKLER DEMOLITION PLAN
FX101 FIRST LEVEL FIRE SPRINKLER PLAN
FX102 SECOND LEVEL FIRE SPRINKLER PLAN
FX103 THIRD LEVEL FIRE SPRINKLER PLAN
FX500 FIRE SPRINKELR DETAILS
FX501 FIRE SPRINKLER RISER DETAILS
PLUMBING
P-001 GENERAL ABREVIATIONS, NOTES AND SYMBOLS
PD100 DEMOLITION PIT FLOOR PLAN - OVERALL
PD101 PIT DEMOLITION PLAN - AREA A
PD102 PIT DEMOLITION PLAN - AREA B
PD103 PIT DEMOLITION PLAN - AREA C
PD110 FIRST FLOOR DEMOLITION PIPING PLAN - OVERALL
PD120 SECOND UNDERFLOOR DEMOLITION PIPING PLAN - OVERALL
PD130 SECOND FLOOR DEMOLITION PIPING PLAN - OVERALL
PD140 THIRD UNDERFLOOR DEMOLITION PIPING PLAN - OVERALL
PD150 THIRD FLOOR DEMOLITION PIPING PLAN - OVERALL
PD160 ROOF DEMOLITION PIPING PLAN - OVERALL
PD401 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 1
PD402 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 2
PD403 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 3
PD404 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 4
PD405 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 5
PD406 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 6
PD407 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 7
PD408 ENLARGED DEMOLITION PLAN - TYPICAL ROOM TYPE 8
PD409 ENLARGED DEMOLITION PLAN - GRID 10 THRU 14
PD410 ENLARGED DEMOLITION PLAN - GRID 10 THRU 14
P-100 PIT PLAN - OVERALL
P-101 PIT PLAN - AREA A
P-102 PIT PLAN - AREA B
P-103 PIT PLAN - AREA C
P-110 FIRST FLOOR PIPING PLAN - OVERALL
P-120 SECOND UNDERFLOOR PIPING PLAN - OVERALL
P-130 SECOND FLOOR PIPING PLAN - OVERALL
P-140 THIRD UNDERFLOOR PIPING PLAN - OVERALL
P-150 THIRD FLOOR PIPING PLAN - OVERALL
P-160 ROOF PIPING PLAN - OVERALL
P-401 ENLARGED PLAN - TYPICAL ROOM TYPE 1
P-402 ENLARGED PLAN - TYPICAL ROOM TYPE 1
P-403 ENLARGED PLAN - TYPICAL ROOM TYPE 2
P-404 ENLARGED PLAN - TYPICAL ROOM TYPE 2
P-405 ENLARGED PLAN - TYPICAL ROOM TYPE 3
P-406 ENLARGED PLAN - TYPICAL ROOM TYPE 3
P-407 ENLARGED PLAN - TYPICAL ROOM TYPE 4
P-408 ENLARGED PLAN - TYPICAL ROOM TYPE 4
P-409 ENLARGED PLAN - TYPICAL ROOM TYPE 5
P-410 ENLARGED PLAN - TYPICAL ROOM TYPE 5
P-411 ENLARGED PLAN - TYPICAL ROOM TYPE 6
P-412 ENLARGED PLAN - TYPICAL ROOM TYPE 6
P-413 ENLARGED PLAN - TYPICAL ROOM TYPE 7
P-414 ENLARGED PLAN - TYPICAL ROOM TYPE 7
P-415 ENLARGED PLAN - TYPICAL ROOM TYPE 7
P-416 ENLARGED PLAN - TYPICAL ROOM TYPE 8
P-417 ENLARGED PLAN - TYPICAL ROOM TYPE 8
P-418 ENLARGED PLAN - TYPICAL ROOM TYPE 8
P-419 ENLARGED PLAN - GRID 10 THRU 14
P-501 DETAILS
P-502 DETAILS
P-503 DETAILS
P-601 SCHEDULES
P-801 LINE RISER DIAGRAM - SANITARY & VENT - OVERALL
P-802 LINE RISER DIAGRAM - DOMESTIC WATER - OVERALL
P-803 LINE RISER DIAGRAM - DOMESTIC WATER - MECHANICAL ROOMS
P-804 ISOMETRIC RISER DIAGRAM - SANITARY & VENT - TYPICAL ROOM TYPE 2
P-805 ISOMETRIC RISER DIAGRAM - DOMESTIC - TYPICAL ROOM TYPE 2
MECHANICAL
M-001 GENERAL ABBREVIATIONS, NOTES AND SYMBOLS
M-002 DESIGN CRITERIA
SHEET
NUMBER
SHEET NAME
MD100 PIT DEMOLITION PIPING PLAN - OVERALL
MD101 PIT DEMOLITION PLAN - AREA A
MD102 PIT DEMOLITION PLAN - AREA B
MD103 PIT DEMOLITION PLAN - AREA C
MD110 FIRST FLOOR DEMOLITION DUCTWORK & PIPING PLAN - OVERALL
MD111 FIRST FLOOR DEMOLITION PLAN - AREA A
MD112 FIRST FLOOR DEMOLITION PLAN - AREA B
MD113 FIRST FLOOR DEMOLITION PLAN - AREA C
MD120 SECOND FLOOR DEMOLITION DUCTWORK & PIPING PLAN - OVERALL
MD121 SECOND FLOOR DEMOLITION PLAN - AREA A
MD122 SECOND FLOOR DEMOLITION PLAN - AREA B
MD123 SECOND FLOOR DEMOLITION PLAN - AREA C
MD130 THIRD FLOOR DEMOLITION DUCTWORK & PIPING PLAN - OVERALL
MD131 THIRD FLOOR DEMOLITION PLAN - AREA A
MD132 THIRD FLOOR DEMOLITION PLAN - AREA B
MD133 THIRD FLOOR DEMOLITION PLAN - AREA C
MD401 ENLARGED DEMOLITION PLAN
M-100 PIT PLAN - OVERALL
M-110 FIRST FLOOR DUCTWORK & PIPING PLAN - OVERALL
M-111 FIRST FLOOR DUCTWORK PLAN - AREA A
M-112 FIRST FLOOR DUCTWORK PLAN - AREA B
M-113 FIRST FLOOR DUCTWORK PLAN - AREA C
M-120 SECOND FLOOR DUCTWORK & PIPING PLAN - OVERALL
M-121 SECOND FLOOR DUCTWORK PLAN - AREA A
M-122 SECOND FLOOR DUCTWORK PLAN - AREA B
M-123 SECOND FLOOR DUCTWORK PLAN - AREA C
M-130 THIRD FLOOR DUCTWORK & PIPING PLAN - OVERALL
M-131 THIRD FLOOR DUCTWORK PLAN - AREA A
M-132 THIRD FLOOR DUCTWORK PLAN - AREA B
M-133 THIRD FLOOR DUCTWORK PLAN - AREA C
M-201 PIT PIPING PLAN - AREA A
M-202 PIT PIPING PLAN - AREA B
M-203 PIT PIPING PLAN - AREA C
M-211 FIRST FLOOR PIPING PLAN - AREA A
M-212 FIRST FLOOR PIPING PLAN - AREA B
M-213 FIRST FLOOR PIPING PLAN - AREA C
M-221 SECOND FLOOR PIPING PLAN - AREA A
M-222 SECOND FLOOR PIPING PLAN - AREA B
M-223 SECOND FLOOR PIPING PLAN - AREA C
M-231 THIRD FLOOR PIPING PLAN - AREA A
M-232 THIRD FLOOR PIPING PLAN - AREA B
M-233 THIRD FLOOR PIPING PLAN - AREA C
M-401 ENLARGED PLANS
M-402 ENLARGED PLANS
M-403 ENLARGED PLANS
M-404 ENLARGED PLANS
M-405 ENLARGED PLANS
M-406 ENLARGED PLANS
M-501 DETAILS
M-502 DETAILS
M-503 DETAILS
M-601 SCHEDULES
M-602 SCHEDULES
M-603 SCHEDULES
M-604 SCHEDULES
M-605 SCHEDULES
M-606 SCHEDULES
M-700 CONTROLS NOTES AND SYMBOLS
M-701 CONTROLS NETWORK ARCHITECTURE
M-702 CHILLED WATER SYSTEM CONTROL DIAGRAM AND SEQEUENCE
M-703 CHILLED WATER SYSTEM CONTROL POINTS LIST
M-704 HOT WATER SYSTEM CONTROL DIAGRAM AND SEQEUENCE
M-705 HOT WATER SYSTEM CONTROL POINTS LIST
M-706 DEDICATED OUTDOOR AIR UNIT CONTROL DIAGRAM & SEQUENCE
M-707 FAN COIL UNIT (4-PIPE) CONTROL DIAGRAM & SEQUENCE
M-708 MISC. CONTROL DIAGRAMS & SEQUENCES
M-709 MISC. CONTROL DIAGRAMS & SEQUENCES
M-710 MISC. CONTROL POINTS LISTS
M-800 HYDRONIC FLOW DIAGRAMS - OVERALL
M-801 HYDRONIC FLOW DIAGRAMS - MECHANICAL ROOMS
M-802 AIR FLOW DIAGRAMS - OVERALLDR
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SE
A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
S H
E E
T I
N D
E X
G-003
B
A C
K C
H E
C K
D E
S
IG
N S
U B
M
IT
T A
L
N O
T F
O R
C O
N S
T R
U C
T
IO
N
B C
A R
IN
O
B C
A R
IN
O
D K
A N
E S
H
IG
E
J A
N U
A R
Y
B R
G
E N
.r v t-
SHEET
NUMBER
SHEET NAME
ELECTRICAL
E-001 LEGEND AND ABBREVIATIONS
E-002 ABBREVIATIONS, GENERAL NOTES AND REFERENCES
ES101 SITE PLAN
E-101 FIRST FLOOR COMPOSITE PLAN
E-102 SECOND FLOOR COMPOSITE PLAN
E-103 THIRD FLOOR COMPOSITE PLAN
ED101 FIRST FLOOR LIGHTING DEMOLITION PLAN - AREA A
ED102 FIRST FLOOR LIGHTING DEMOLITION PLAN - AREA B
ED103 FIRST FLOOR LIGHTING DEMOLITION PLAN - AREA C
ED104 SECOND FLOOR LIGHTING DEMOLITION PLAN - AREA A
ED105 SECOND FLOOR LIGHTING DEMOLITION PLAN - AREA B
ED106 SECOND FLOOR LIGHTING DEMOLITION PLAN - AREA C
ED107 THIRD FLOOR LIGHTING DEMOLITION PLAN - AREA A
ED108 THIRD FLOOR LIGHTING DEMOLITION PLAN - AREA B
ED109 THIRD FLOOR LIGHTING DEMOLITION PLAN - AREA C
ED111 FIRST FLOOR POWER DEMOLITION PLAN - AREA A
ED112 FIRST FLOOR POWER DEMOLITION PLAN - AREA B
ED113 FIRST FLOOR POWER DEMOLITION PLAN - AREA C
ED114 SECOND FLOOR POWER DEMOLITION PLAN - AREA A
ED115 SECOND FLOOR POWER DEMOLITION PLAN - AREA B
ED116 SECOND FLOOR POWER DEMOLITION PLAN - AREA C
ED117 THIRD FLOOR POWER DEMOLITION PLAN - AREA A
ED118 THIRD FLOOR POWER DEMOLITION PLAN - AREA B
ED119 THIRD FLOOR POWER DEMOLITION PLAN - AREA C
ED121 FIRST FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA A
ED122 FIRST FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA B
ED123 FIRST FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA C
ED124 SECOND FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA A
ED125 SECOND FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA B
ED126 SECOND FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA C
ED127 THIRD FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA A
ED128 THIRD FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA B
ED129 THIRD FLOOR EQUIPMENT POWER DEMOLITION PLAN - AREA C
ED601 DEMOLITION ONE LINE DIAGRAM
ED602 DEMOLITION ONE LINE DIAGRAM
ED603 DEMOLITION ONE LINE DIAGRAM
ED604 DEMOLITION ONE LINE DIAGRAM
EL101 FIRST FLOOR LIGHTING PLAN - AREA A
EL102 FIRST FLOOR LIGHTING PLAN - AREA B
EL103 FIRST FLOOR LIGHTING PLAN - AREA C
EL104 SECOND FLOOR LIGHTING PLAN - AREA A
EL105 SECOND FLOOR LIGHTING PLAN - AREA B
EL106 SECOND FLOOR LIGHTING PLAN - AREA C
EL107 THIRD FLOOR LIGHTING PLAN - AREA A
EL108 THIRD FLOOR LIGHTING PLAN - AREA B
EL109 THIRD FLOOR LIGHTING PLAN - AREA C
EL501 DETAILS
EL502 DETAILS
EL511 DETAILS
EL512 DETAILS
EL701 LIGHTING FIXTURE SCHEDULE
EL702 LIGHTING CONTROL SCHEDULE
EP101 FIRST FLOOR POWER PLAN - AREA A
EP102 FIRST FLOOR POWER PLAN - AREA B
EP103 FIRST FLOOR POWER PLAN - AREA C
EP104 SECOND FLOOR POWER PLAN - AREA A
EP105 SECOND FLOOR POWER PLAN - AREA B
EP106 SECOND FLOOR POWER PLAN - AREA C
EP107 THIRD FLOOR POWER PLAN - AREA A
EP108 THIRD FLOOR POWER PLAN - AREA B
EP109 THIRD FLOOR POWER PLAN - AREA C
EP111 FIRST FLOOR EQUIPMENT POWER PLAN - AREA A
EP112 FIRST FLOOR EQUIPMENT POWER PLAN - AREA B
EP113 FIRST FLOOR EQUIPMENT POWER PLAN - AREA C
EP114 SECOND FLOOR EQUIPMENT POWER PLAN - AREA A
EP115 SECOND FLOOR EQUIPMENT POWER PLAN - AREA B
EP116 SECOND FLOOR EQUIPMENT POWER PLAN - AREA C
EP117 THIRD FLOOR EQUIPMENT POWER PLAN - AREA A
EP118 THIRD FLOOR EQUIPMENT POWER PLAN - AREA B
EP119 THIRD FLOOR EQUIPMENT POWER PLAN - AREA C
EP501 DETAILS
EP502 DETAILS
EP601 ONE LINE DIAGRAM
EP602 ONE LINE DIAGRAM
EP603 ONE LINE DIAGRAM
EP604 ONE LINE DIAGRAM
SHEET
NUMBER
SHEET NAME
EP701 SCHEDULES
EP702 SCHEDULES
EP703 SCHEDULES
EP704 SCHEDULES
EP705 SCHEDULES
EP706 SCHEDULES
EP707 SCHEDULES
EP708 SCHEDULES
EP709 SCHEDULES
EP710 SCHEDULES
TELECOMMUNICATIONS
T-001 TELECOM LEGEND AND ABBREVIATIONS
TD101 FIRST FLOOR TELECOM DEMOLITION PLAN
TD102 SECOND FLOOR TELECOM DEMOLITION PLAN
TD103 THIRD FLOOR TELECOM DEMOLITION PLAN
T-101 FIRST FLOOR TELECOM PLAN
T-102 SECOND FLOOR TELECOM PLAN
T-103 THIRD FLOOR TELECOM PLAN
T-501 TELECOM DETAILS
T-601 ONE LINE DIAGRAM
DR
BUILDING USE DESCRIPTION
1. THE EXISTING UNACCOMPANIED PERSONNEL HOUSING (UPH) IS AN EXISTING 3-STORY
BUILDING OF APPROXIMATELY 2,227.5 SQUARE METERS. IT IS A DORMITORY BUILDING (NO
INDIVIDUAL COOKING FACILITY IN BEDROOMS) USED BY MILITARY PERSONNEL. THE PROJECT
INVOLVES REVITALIZATION OF THE EXISTING BUILDING.
APPLICABLE CODES, STANDARDS AND CRITERIA
1. INTERNATIONAL BUILDING CODE (IBC); 2024
2. NFPA 1, FIRE CODE; 2024 EDITION
3. NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS; 2026 EDITION
4. NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS; 2025 EDITION
5. NFPA 13R, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE
RESIDENTIAL OCCUPANCIES; 2025
6. NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR
APPURTENANCES; 2025 EDITION
7. NFPA 70, NATIONAL ELECTRICAL CODE; 2026 EDITION
8. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE; 2025 EDITION
9. NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES; 2025
10. NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING
SYSTEMS; 2024 EDITION
11. NFPA 101, LIFE SAFETY CODE; 2024 EDITION
12. NFPA 291, RECOMMENDED PRACTICE FOR WATER FLOW TESTING AND MARKING OF
HYDRANTS; 2025
13. UFC 1-200-01, DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS); CHANGE 4, 17 DEC
14. UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES; CHANGE 6, 6 MAY 2021
15. UFC 4-010-01, DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, CHANGE 3, 24 MAY
16. UFC 4-021-01 - DESIGN AND O&M: MASS NOTIFICATION SYSTEM: CHANGE 1, JANUARY 2010
17. USACE ECB 2018-17 NEW REQUIREMENTS FOR VISUAL NOTIFICATION FOR MASS NOTIFICATION
SYSTEMS, 26 MARCH 2025
18. JED DESIGN GUIDE V9, APRIL 2025
USE AND OCCUPANCY CLASSIFICATION (UFC 3-600-01)
1. THE IBC SHALL BE UTILIZED TO DETERMINE THE OCCUPANCY CLASSIFICATION AS IT RELATES
TO ALLOWABLE CONSTRUCTION TYPE, BUILDING HEIGHT, BUILDING AREA, BUILDING
SEPARATION DISTANCE, OCCUPANCY SEPARATION AND ASSOCIATED REQUIREMENTS [§
3-2.1.2]
2. NFPA 101 MUST BE UTILIZED TO DETERMINE THE OCCUPANCY CLASSIFICATION AS IT RELATES
TO FIRE/SMOKE RESISTANCE RATING OF INTERIOR NON-LOAD BEARING PARTITIONS, MEANS
OF EGRESS, INTERIOR FINISH, FEATURES OF FIRE PROTECTION AND ASSOCIATED
REQUIREMENTS [§3-3.1.1]
A. COMPLY WITH NFPA 101 FOR ALL COMPONENTS AND FEATURES RELATED TO MEANS
OF EGRESS. IBC MUST NOT BE USED FOR ANY MEANS OF EGRESS FEATURES [§10-1.1]
FIRE PROTECTION SYSTEMS
1. FIRE SPRINKLER SYSTEM - GENERAL
A. SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM PROVIDED THROUGHOUT THE
BUILDING, IN ACCORDANCE WITH UFC 3-600-01 AND NFPA 13R. EXCEPTIONS AS
FOLLOWS:
a. CLOSETS WITHING DWELLING UNITS LESS THAN 2.2 M2
b. BATHROOMS WITHIN DWELLING UNITS LESS THAN 5.1 M2
2. STANDPIPE SYSTEMS - GENERAL
A. STANDPIPE SYSTEM IS NOT REQUIRED AS THE BUILDING IS LESS THAN FOUR STORIES
IN HEIGHT PER UFC 3-600-01, SECTION 9-10.2.1.
3. PORTABLE FIRE EXTINGUISHERS - GENERAL
A. GENERAL PURPOSE PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED WHERE
REQUIRED BY NFPA 101 AND INSTALLED IN ACCORDANCE WITH NFPA 10. [UFC 3-600-01
§9-17].
B. PORTABLE FIRE EXTINGUISHERS ARE NOT REQUIRED IN FULLY SPRINKLERED
APARTMENT OCCUPANCY PER NFPA 101. HOWEVER, CAMP ZAMA FIRE DEPARTMENT
REQUIRES PORTABLE FIRE EXTINGUISHERS PER FIRE REGULATION USAG JAPAN
420-90. ACCORDINGLY, FIRE EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE
WITH NFPA 10.
FIRE ALARM AND MASS NOTIFICATION SYSTEMS
1. EXISTING FIRE ALARM SYSTEM
A. DEMOLITION OF THE EXISTING FIRE ALARM SYSTEM INCLUDING PANELS, DEVICES,
WIRING AND CONDUIT.
2. FIRE DETECTION/ALARM SYSTEMS - GENERAL
A. NEW ADDRESSABLE FIRE ALARM SYSTEM PROVIDED THROUGHOUT THE BUILDING.
3. NOTIFICATION
A. NOTIFICATION DEVICES PROVIDED THROUGHOUT THE BUILDING IN ALL AREAS WHERE
REQUIRED BY NFPA 101 AND UFC 3-600-01 AND NFPA 72.
4. DETECTION
A. PROVIDE AUTOMATIC SMOKE DETECTION ABOVE FIRE ALARM PANELS
B. PROVIDE SMOKE DETECTORS IN ALL SLEEPING AREAS.
5. MANUAL FIRE ALARM ACTIVATION
A. PROVIDE A MANUAL FIRE ALARM PULL STATION AT ALL EXITS REGARDLESS OF
OCCUPANCY PER UFC 3-600-01, 9-18.7.4.1
6. MASS NOTIFICATION SYSTEM
A. MASS NOTIFICATION SYSTEM PROVIDED THROUGHOUT COMBINED WITH THE BUILDING
FIRE ALARM SYSTEM IN ACCORDANCE WITH UFC 4-021-01
WATER SUPPLIES AND FIRE FLOW CALCULATIONS
1. REFER TO FIRE PROTECTION DRAWING FX001 FOR WATER SUPPLY INFORMATION. FIRE FLOW
FOR SPRINKLERED FACILITIES SHALL BE IN ACCORDANCE WITH NFPA 1 OR 3,785 LPM AT 1.38
BAR, WHICHEVER IS GREATER.
A. NFPA 1 FIRE FLOW REQUIREMENTS FOR SPRINKLERED FACILITIES FOR TYPE II (000)
BETWEEN 2,025-2,406 M2 IS 12,301 LPM. THIS IS PERMITTED TO BE REDUCED BY 75%
FOR SPRINKLERED FACILITIES WHICH EQUATES TO 3,075 LPM.
B. BASED ON THE ANALYSIS ABOVE, THE FIRE FLOW REQUIREMENT IS 3,785 LPM AT 1.38
BAR
C. WATERLINE A - AVAILABLE FLOW AT 1.38 BAR IS 2,551 LPM
D. WATERLINE B - AVAILABLE FLOW AT 1.38 BAR IS 4,345 LPM
FIRE DEPARTMENT ACCESS
1. EXISTING FIRE DEPARTMENT ACCESS TO REMAIN.
FIRE HYDRANTS
1. EXISTING FIRE HYDRANTS CONNECTED TO WATERLINE A PROVIDE SUFFICIENT COVERAGE
AROUND THE BUILDING. HOWEVER, ADEQUATE FLOW IS NOT AVAILABLE AT THESE FIRE
HYDRANTS. A NEW FIRE HYDRANT CONNECTED TO WATERLINE B WILL BE PROVIDED SUCH
THAT ALL PARTS OF THE FACILITY EXTERIOR IS WITHIN 106 METERS OF A HYDRANT WITH
CONSIDERATION GIVEN TO ACCESSIBILITY AND OBSTRUCTIONS
2. EXISTING FIRE HYDRANT IS LOCATED WITHING 45 M OF THE FIRE DEPARTMENT CONNECTION.
OCCUPANCY CLASSIFICATION
BUILDING HEIGHT AND AREA SUMMARY
BUILDING CONSTRUCTION TYPE
SPRINKLER SYSTEM
IIB
YES, SM (NFPA 13R SYSTEM)
BUILDING HEIGHT
ACTUAL MAXIMUM ALLOWED
10.48 M 18.29 M*
NUMBER OF STORIES 3 STORIES 4 STORIES*
TABULAR FLOOR AREA PER STORY 1,486 SM
BUILDING AREA ANALYSIS
FRONTAGE AREA FACTOR INCREASE NOT REQUIRED
FLOOR AREA PER STORY W/ FRONTAGE ACTUAL MAXIMUM ALLOWED
1,486 SMFIRST LEVEL
1,486 SMSECOND LEVEL
742.5 SM
TOTAL BUILDING AREA 4,458 SM2,227.5 SM
IBC CODE COMPLIANT YES
STRUCTURAL FIRE RESISTANCE RATING [TABLE 601 AND TABLE 602]
REQUIRED STRUCTURAL FIRE RESISTANCE RATING SUMMARY - TYPE IIB
STRUCTURAL ELEMENT
BEARING WALLS
FIRE RESISTANCE
RATING
EXTERIOR
INTERIOR
NON-LOAD
BEARING WALLS
EXTERIOR: ≥ 9.14 M SEPARATION
INTERIOR
PRIMARY STRUCTURAL MEMBERS
FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS
ROOF CONSTRUCTION AND ASSOCIATED SECONDARY STRUCTURAL
MEMBERS
0-HOUR
0-HOUR
0-HOUR
PER NFPA 101
0-HOUR
0-HOUR
0-HOUR
MAXIMUM AREA OF EXTERIOR WALL OPENINGS (UNPROTECTED / SPRINKLERED) [TABLE 705.9]
1. FIRE SEPARATION DISTANCE GREATER THAN 6 METERS - UNLIMITED
OCCUPANCY CLASSIFICATION BY FLOOR - IBC
FLOOR
FIRST LEVEL
SECOND LEVEL
RESIDENTIAL R-2
OCCUPANCY CLASSIFICATION ACCESSORY OCCUPANCY
TYPE OF CONSTRUCTION
1. TYPE IIB
OCCUPANCY SEPARATION
1. OCCUPANCY SEPARATION IS NOT REQUIRED BETWEEN MAIN OCCUPANCY AND ACCESSORY
OCCUPANCIES
BUILDING HEIGHT AND AREA ANALYSIS [TABLE 504.3, TABLE 504.4, AND TABLE 506.2]
HAZARDOUS AREA PROTECTION
1. ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
OCCUPANCY SHALL BE PROTECTED BY ONE OF THE FOLLOWING MEANS [§8.7.1.1]
A. SEPARATING THE AREA FROM OTHER PARTS OF THE BUILDING WITH A 1-HOUR FIRE
BARRIERS AND WITHOUT WINDOWS.
B. PROTECTING THE AREA WITH AUTOMATIC SPRINKLER SYSTEMS.
C. BOTH 1-HOUR FIRE BARRIER AND SPRINKLER SYSTEM WHERE THE HAZARD IS SEVERE.
D. IN NEW CONSTRUCTION, AUTOMATIC SPRINKLER SYSTEMS WITH SMOKE PARTITIONS.
OPENING PROTECTIVES [TABLE 8.3.3.2.2]
VERTICAL OPENINGS AND EXIT ENCLOSURES REQUIRED FIRE BARRIER
VERTICAL OPENINGS REQUIRED FIRE BARRIER
SHAFTS CONNECTING LESS THAN 3 STORIES 1-HOUR [§8.6.5(2)]
EXIT ENCLOSURES
EXIT ENCLOSURES CONNECTING LESS THAN 4 STORIES 1-HOUR [§7.1.3.2.1(1)]
COMPONENT WALL &
PARTITIONS
FIRE DOOR
ASSEMBLIES
MINIMUM FIRE-RATED WINDOWS RATING
FIRE PROTECTION FIRE RESISTANCE
VERTICAL
SHAFTS
1-HOUR 1-HOUR 1-HOURNOT PERMITTED
INTERIOR FINISH ANALYSIS W/ SPRINKLER PROTECTION [NFPA 101, 28.3.3.2]
OCCUPANCY
NEW DORMITORY
EXIT EXIT ACCESS
CORRIDORS
OTHER SPACES
CLASS A OR B CLASS A,B, OR C CLASS A,B, OR C
MEANS OF EGRESS GENERAL
1. OCCUPANT LOAD FACTOR [TABLE 7.3.1.2 / UFC 3-600-01 TABLE 10-1]
A. ASSEMBLY USE (GENERAL): 1.4 NSM/PERSON
B. BUSINESS USE: 14 SM/PERSON
C. RESIDENTIAL USE: 18.6 SM/PERSON
D. MECH,ELEC, BUILDING EQUIP. USE: 46.5 SM/PERSON
E. STORAGE ROOMS: 46.5 SM/PERSON
2. CAPACITY OF MEANS OF EGRESS
A. EGRESS WIDTH REQUIRED PER PERSON [TABLE 7.3.3.1]
a. HORIZONTAL EGRESS TRAVEL: 5 MM/PERSON
b. VERTICAL EGRESS TRAVEL: 7.6 MM/PERSON
3. MINIMUM EGRESS WIDTH OUTSIDE DWELLING UNIT REQUIRED / PROVIDED
[NFPA 101, 7.3.4]
A. CORRIDORS W/ OCCUPANT LOAD 50 OR MORE: 1120 MM / 1670 MM
B. CLEAR WIDTH DOOR OPENINGS: 810 MM / 900 MM
4. MINIMUM EGRESS WIDTH WITHIN DWELLING UNIT REQUIRED / PROVIDED
[NFPA 101, 28.2.1.2 AND 24.2]
A. DOORS: 710 MM / 750 MM
B. DOORS SERVING ROOM NOT EXCEEDING 6.5 SM: 610 MM / 750 MM
C. BATHROOM DOORS: 610 MM / 700 MM
D. MINIMUM DOOR HEIGHT 1990 MM / 2100 MM
5. TOTAL OCCUPANT LOAD
A. FIRST FLOOR: 103 PERSONS
B. SECOND FLOOR: 78 PERSONS
C. THIRD FLOOR: 78 PERSONS
6. NUMBER OF EXITS REQUIRED / PROVIDED
A. FIRST FLOOR: 2 / 2+
B. SECOND FLOOR: 2 / 2+
C. THIRD FLOOR: 2 / 2+
7. EXIT CAPACITY REQUIRED / PROVIDED
A. FIRST FLOOR: 103 / 856 PERSONS
B. SECOND FLOOR: 78 / 608 PERSONS
C. THIRD FLOOR: 78 / 608 PERSONS
8. ARRANGEMENT OF EXITS
A. WHERE 2 OR MORE EXITS ARE REQUIRED, THEY MUST BE SPACED
APART A MINIMUM OF 1/3 THE LENGTH OF THE MAXIMUM DIAGONAL OF
THE BUILDING OR AREA BEING SERVED [§7.5.1.3.3]
a. WHERE MORE THAN TWO EXITS OR EXIT ACCESS DOORS ARE
REQUIRED, AT LEAST TWO OF THE REQUIRED EXITS OR EXIT
ACCESS DOORS ARE TO BE ARRANGED TO COMPLY WITH THE
MINIMUM SEPARATION DISTANCE REQUIREMENTS DEFINED
ABOVE. THE OTHER EXITS OR EXIT ACCESS DOORS ARE TO BE
LOCATED SO THAT IF ONE BECOMES BLOCKED, THE OTHERS
REMAIN AVAILABLE [§7.5.1.3.1]
b.
EXIT DISCHARGE [NFPA 101, 28.2.7]
1. EXIT DISCHARGE SHALL COMPLY WITH SECTION 7.7 - PROVIDED
ILLUMINATION OF MEANS OF EGRESS [NFPA 101, 28.2.8]
1. MEANS OF EGRESS SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION
7.8 IN DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, AND PASSAGEWAYS
LEADING TO AN EXIT - PRVIDED
EMERGENCY LIGHTING [NFPA 101, 28.2.9]
1. EMERGENCY LIGHTING SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
7.9 - PROVIDED
MARKING OF MEANS OF EGRESS [NFPA 101, 28.2.10]
1. MEANS OF EGRSES SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 -
PROVIDED
OCCUPANCY CLASSIFICATION
OCCUPANCY CLASSIFICATION BY FLOOR - NFPA 101
FLOOR LEVEL
FIRST LEVEL
SECOND LEVEL
OCCUPANCY CLASSIFICATION INCIDENTAL OCCUPANCY
EXISTING DORMITORY ORDINARY HAZARD STORAGE
STORAGE S-1
CODE ANALYSIS GENERAL
CODE ANALYSIS - IBC
CODE ANALYSIS - LIFE SAFETY CODE (NFPA 101)
THIRD LEVEL
THIRD LEVEL
RESIDENTIAL R-2
RESIDENTIAL R-2
STORAGE S-1
STORAGE S-1
1,486 SMTHIRD LEVEL
742.5 SM
742.5 SM
FIRE
BARRIERS
1/2-HOUR 1/3-HOUR 1/3-HOUR1/3-HOUR
FIRE DEPARTMENT CONNECTION AND POST INDICATOR VALVE LOCATION
1. FDC IS LOCATED ON THE EXTERIOR WALL OF THE NEW FIRE RISER ENCLOSURE.
2. PIV IS NOT REQUIRED AS AN INDICATING CONTROL VALVE IS INSTALLED IN A FIRE-RATED
ROOM ACCESSIBLE FROM THE EXTERIOR IN ACCORDANCE WITH NFPA 24, 6.2.9.
* NFPA 13R SPRINKLER SYSTEM LIMITATION
EXISTING DORMITORY
EXISTING DORMITORY
ORDINARY HAZARD STORAGE
ORDINARY HAZARD STORAGE
TABLE 28.3.2.2.2 HAZARDOUS AREA PROTECTION
BOILER ROOM SERVING MORE THAN ONE DWELLING UNIT
LAUNDRIES > 9.3 SM OUTIDE OF DWELLING UNITS
1 HOUR AND SPRINKLERS
STORAGE ROOMS OUTSIDE OF DWELLING UNITS
1 HOUR AND SPRINKLERS
1 HOUR OR SPRINKLERS
• MECHANICAL ROOMS (NO BOILER) AND STORAGE ROOMS SHALL BE PROTECTED BY SMOKE
PARTITION. HOWEVER, DUE TO NFPA 13R REQUIREMENT BELOW, MINIMUM 1/2-HOUR FIRE
BARRIER SHALL BE PROVIDED
• LAUNDRY ROOMS DO NOT REQUIRE ANY FIRE RATING AS THE FLOOR AREA DOES NOT
EXCEED 9.3 SM.
CORRIDOR FIRE RATING REQUIREMENTS [NFPA 101, 28.3.6.1.3]
IN BUILDINGS PROTECTED THROUGHOUT BY SPRINKLER SYSTEMS, CORRIDOR WALLS SHALL HAVE
A MINIMUM 1/2-HOUR FIRE RESISTANCE RATING.
SUBDIVISION OF BUILDING SPACES [NFPA 101, 28.3.7.2]
IN BUILDINGS PROTECTED THROUGHOUT BY SPRINKLER SYSTEMS, DWELLING UNITS SHALL BE
SEPARATED FROM EACH OTHER BY WALLS AND FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING
A MINIMUM 1/2-HOUR FIRE RESISTANCE RATING.
NFPA 13R ORDINARY HAZARD SPACES OUTSIDE DWELLING UNITS [NFPA 13R, 7.2.4.1]
ORDINARY HAZARD SPACES SUCH AS MECHANICAL ROOM, ELECTRICAL ROOM, STORAGE ROOM,
AND SIMILAR SPACES SHALL BE PROTECTED BY MINIMUM 1/2-HOUR FIRE BARRIER.
INTERIOR FLOOR FINISH REQUIREMENT
INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS COMPLYING WITH 28.3.3.3.2 SHALL BE NOT LESS THAN CLASS II.
THE MINIMUM CRITICAL RADIANT FLUX SHALL BE 0.1 W/CM2
EXISTING BUILDING & WORK CLASSIFICATIONS [UFC 3-600-01, 34-1 & NFPA 101 CH. 43
1. DESIGN AND CONSTRUCTION PROJECTS IN EXISTING BUILDINGS SHALL COMPLY WITH NFPA
101 BUILDING REHABILITATION CHAPTER EXCEPT AS SPECIFIED IN UFC 3-600-01. AREAS OF
THE FACILITY WHERE NO WORK IS BEING PERFORMED MUST AT A MINIMUM MEET EXISTING
OCCUPANCY CHAPTER OF NFPA 101.
2. THE SCOPE OF WORK INCLUDES RENOVATIONS, MODIFICATIONS, AND EXTENSIVE
MODIFICATIONS.
3. FLOOR PLAN RECONFIGURATIONS THAT EXCEED 50 PERCENT OF THE AREA OF A FLOOR
REQUIRE THAT THE ENTIRE FLOOR BE BROUGHT UP TO THE RQEUIREMENTS FOR NEW
CONSTRUCTION IN THIS UFC AND NFPA 101. OR IF THE PROJECT COST EXCEEDS 50 PERCENT
OF THE BUILDING REPLACEMENT VALUE, THEN THE ENTIRE BUILDING MUST BE BROUGHT UP
TO THE REQUIREMENTS FOR NEW CONSTRUCTION.
A. FLOOR PLAN RECONFIGURATION EXCEED 50 PERCENT OF THE AREA OF A FLOOR. THE
ENTIRE FLOOR SHALL BE BROUGHT UP TO THE REQUIREMENTS FOR NEW
CONSTRUCTION.
DOORS IN SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS AND SHALL BE SELF OR AUTOMATIC
CLOSING.
DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
TRANSOMS, LOUVERS, OR TRANSFER GRILLES SHALL BE PROHIBITED IN WALLS OR DOORS OF EXIT
ACCESS CORRIDORS. [NFPA 101, 28.3.6.2]
AIR TRANSFER OPENING SHALL BE PERMITTED IN WALLS OR DOORS FROM TOILET ROOMS,
BATHROOMS, SHOWER ROOMS, SINK CLOSETS, AND SIMILAR AUXILIARY SPACES OPENING
DIRECTLY ONTO THE EGRESS CORRIDOR. [NFPA 90A, 5.10.1.3.1]
THROUGH-PENETRATION REQUIREMENTS [NFPA 101, 8.3.4]
1. PIPES, CONDUITS, CABLES, ETC. THAT PENETRATE FIRE-RATED WALLS OR FLOORS SHALL BE
PROTECTED BY UL LISTED FIRESTOPPING WITH RATING EQUAL OR GREATER THAN THE
PENETRATED WALL.
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w
.e xp
F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
S E A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
L
IF
E S
A F
E T
Y C
O D
E A
N A
L Y
S
IS
GI001
B A
C K
C H
E C
K D
E S
IG
N
S U
B M
IT
T
A L
N
O T
F O
R C
O N
S T
R U
C T
IO
N
Y K
IM
B K
IM
Y K
IM
J A
N U
A R
Y
B R
F
P .r v t
DR
M
F W
F W
F W
F W
W
W
W
W
W
W
W
(E) 3
00MM M
AIN W
ATERLINE B
FHY
# 512
FHY
# 511
(E) 3
00MM M
AIN W
ATERLINE A
B581
W
W
W
W
W
W
W
W
(N)
FHY
LEGENDGENERAL NOTES
ALL INFORMATION SHOWN ON THIS SHEET
IS FOR INFORMATION ONLY TO SHOW CODE
COMPLIANCE IN ACCORDANCE WITH UFC
3-600-01. REFER TO CIVIL DRAWING FOR
CIVIL SITE AND UTILITY INFORMATION.
(N) NEW
(E) EXISTING
FHY FIRE HYDRANT
DISTANCE TO FDC
DISTANCE TO BUILDING
(E) VACUUM
PUMP ROOM
(E) TRANSFORMER
STATION
(E) BICYCLE
SHED
(E) STEAM PIT
106M
(N) 150MM FIRE
WATER LINE
(N) GATE VALVE
FW
W
FIRE DEPARTMENT
ENTRANCE TO FACILITY
M
99M
(N) FIRE ENTRY
ENCLOSURE
FW FIRE WATERLINE
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w
.e xp
F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
S E A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
C O
D E
C O
M P
L
IA
N C
E S
IT
E
P L A
N
GI100
B A
C K
C H
E C
K D
E S
IG
N
S U
B M
IT
T
A L
N
O T
F O
R C
O N
S T
R U
C T
IO
N
Y K
IM
B K
IM
Y K
IM
J A
N U
A R
Y
B R
F
P .r v t
SCALE: 1 : 150
A1
CODE COMPLIANCE SITE PLAN
0 7.5 m3
PLAN NORTHDR
P
P
1 2 3 4 5 6 7 8 9 10 11
A
B
C
D
11.8 m² 1
S46.5 m²
STORAGE
8.2 m² 1
R18.6 m²
LAUNDRY
RM
2.7 m² 1
S46.5 m²
LINEN RM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
20.1 m² 2
R18.6 m²
S02
STAIRS
S02
26.0 m² 2
R18.6 m²
C103
CORRIDOR
C103
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
EXIT1W
12.9 m² 1
M46.5 m²
M01
MECHANICAL
RM - 1
M01
FEC
FEC
11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
12.4 m² 1
M46.5 m²
M02
WATER
HEATER
RM
M02
7.6 m² 1
M46.5 m²
E01
ELEC RM
E01
4.2 m² 4
AU1.4 m²
KITCHENETTE
53.6 m² 39
AU1.4 m²
GAME
ROOM
13.4 m² 1
M46.5 m²
M03
MECHANICAL
RM 2
M03 12.5 m² 1
BU14.0 m²
OFFICE
2.1 m² 1
BU14.0 m²
116B
TOILET
116B
9.5 m² 1
S46.5 m²
116A
SUPPLY
116A
11.8 m² 1
S46.5 m²
STORAGE
8.1 m² 1
R18.6 m²
LAUNDRY
RM
2.7 m² 1
S46.5 m²
LINEN RM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
26.0 m² 2
R18.6 m²
C101
CORRIDOR
C101
20.1 m² 2
R18.6 m²
S01
STAIRS
S01
6.9 m² 1
R18.6 m²
TOILET
27.0 m² 2
R18.6 m²
BEDROOM
EXIT1E
358 156
7.6
EXIT
12.9 m² 1
M46.5 m²
M01
MECHANICAL
RM - 1
M01
12.5 m² 9
AU1.4 m²
LOBBY/VENDING
4.0 m² 1
S46.5 m²
JAN
49.4 m² 3
R18.6 m²
C102
CORRIDOR
C102
FIRE ENTRY
ENCLOSURE
3.8 m2 1
46.5 m2 M
FEC
FEC
F01
TRAVEL DISTANCE
COMMON PATH OF TRAVEL
EXIT
DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
DEAD END
LIFE SAFETY ROOM TAG
(A) ROOM AREA (SM)
(B) OCCUPANT LOAD FACTOR (SM/PERSON)
(C) OCCUPANTS (PERSONS)
(D) OCCUPANCY USE
EXIT SIGN WITH DIRECTIONAL ARROWS
STAIR/DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
(4) STAIR CLEAR WIDTH (MM)
(5) STAIR OCCUPANT LOAD FACTOR (MM/PERSONS)
(6) STAIR OCCUPANT LOAD CAPACITY (PERSONS)
DIST.
DIST.
DIST.
(1)
(2)
(3)
EX/DR #
(1)
(2)
(3)
(4)
(5)
(6)
DR #
A C
DB
ROOM
NAME
LIFE SAFETY LEGEND
P P SMOKE PARTITION WALL
1-HR FIRE RATED BARRIER WALL
0.5 HR FIRE RATED BARRIER WALL
FEC SURFACE MOUNTED FIRE EXTINGUISHER CABINET
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w
.e xp
F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
S E A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
F
IR
S T
L E
V E
L L
IF
E
S A
F E
T Y
P L A
N
GI101
B A
C K
C H
E C
K D
E S
IG
N
S U
B M
IT
T
A L
N
O T
F O
R C
O N
S T
R U
C T
IO
N
Y K
IM
B K
IM
Y K
IM
J A
N U
A R
Y
B R
F
P .r v t
OCCUPANT LOAD SCHEDULE - FIRST FLOOR
NUMBER ROOM NAME AREA OCCUPANCY USE
OCCUPANCY
LOAD
FACTOR(PER
PERSON)
OCCUPANT
LOAD
101 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
102 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
103 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
104 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
105 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
106 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
107 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
108 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
109 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
110 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
111 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
112 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
113 LAUNDRY RM 8.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
114 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
115 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
116 OFFICE 12.5 m² BUSINESS - UNCONCENTRATED (NFPA 101) 14.0 m² 1
116A SUPPLY 9.5 m² STORAGE (NFPA 101) 46.5 m² 1
116B TOILET 2.1 m² BUSINESS - UNCONCENTRATED (NFPA 101) 14.0 m² 1
117 GAME ROOM 53.6 m² ASSEMBLY - UNCONCENTRATED (NFPA 101) 1.4 m² 39
118 LOBBY/VENDING 12.5 m² ASSEMBLY - UNCONCENTRATED (NFPA 101) 1.4 m² 9
119 KITCHENETTE 4.2 m² ASSEMBLY - UNCONCENTRATED (NFPA 101) 1.4 m² 4
120 TOILET 6.9 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
121 JAN 4.0 m² STORAGE (NFPA 101) 46.5 m² 1
122 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
123 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
124 LAUNDRY RM 8.2 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
C101 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
C102 CORRIDOR 49.4 m² RESIDENTIAL (NFPA 101) 18.6 m² 3
C103 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
E01 ELEC RM 7.6 m² MECHANICAL, ELECTRICAL, AND OTHER
BUILDING EQUIPMENT SPACES (UFC)
46.5 m² 1
M01 MECHANICAL RM - 1 12.9 m² MECHANICAL, ELECTRICAL, AND OTHER
BUILDING EQUIPMENT SPACES (UFC)
46.5 m² 1
M02 WATER HEATER RM 12.4 m² MECHANICAL, ELECTRICAL, AND OTHER
BUILDING EQUIPMENT SPACES (UFC)
46.5 m² 1
M03 MECHANICAL RM 2 13.4 m² MECHANICAL, ELECTRICAL, AND OTHER
BUILDING EQUIPMENT SPACES (UFC)
46.5 m² 1
S01 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
S02 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
SCALE: 1 : 100
C1
FIRST FLOOR LIFE SAFETY PLAN - AREA A
SCALE: 1 : 100
K1
FIRST FLOOR LIFE SAFETY PLAN - AREA B
358 156
7.6
EXIT
0 5 m2
0 5 m2
GENERAL NOTES
1. REFER TO GI001 FOR LIFE SAFETY CODE ANALYSIS.
2. ALL INFORMATION SHOWN ON THIS SHEET IS FOR
INFORMATION ONLY TO DEMONSTRATE CODE
COMPLIANCE.
3. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR FIRE EXINGUISHER REQUIREMENTS.
4. REFER TO ELECTRICAL DRAWINGS AND SPECIFICATIONS
FOR EXIT SIGN REQUIREMENTS.
MEANS OF EGRESS LIMITATION
OCCUPANCY COMMON PATH (M) TRAVEL DISTANCE (M)
NEW DORMITORY 15 38/61*
* TRAVEL DISTANCE WITHIN A SLEEPING ROOM TO A
CORRIDOR DOOR SHALL NOT EXCEED 38 METERS. TRAVEL
DISTANCE FROM THE CORRIDOR DOOR TO THE NEAREST
EXIT SHALL NOT EXCEED 61 METERS
EXIT CAPACITY SUMMARY
TOTAL EGRESS CAPACITY
TOTAL OCCUPANT LOAD
F01 FIRE ENTRY
ENCLOSURE
3.8 m2 MECHANICAL, ELECTRICAL, AND OTHER
BUILDING EQUIPMENT SPACES (UFC)
46.5 m2 1
PLAN NORTHDR
1 2 3 4 5 6 7 8 9 10 11
A
B
C
D
11.8 m² 1
S46.5 m²
STORAGE
2.7 m² 1
S46.5 m²
LINEN RM
8.1 m² 1
I9.3 m²
LAUNDRY
RM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
20.1 m² 2
R18.6 m²
S02
STAIRS
S02
27.7 m² 2
R18.6 m²
BEDROOM
27.7 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
26.0 m² 2
R18.6 m²
C203
CORRIDOR
C203
276 142
7.6
STAIR2W
540 162
7.6
STAIR 02
27.0 m² 2
R18.6 m²
BEDROOM
FEC
FEC
11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
2.7 m² 1
S46.5 m²
LINEN RM
8.1 m² 1
R18.6 m²
LAUNDRY
RM
36.4 m² 27
AU1.4 m²
LOUNGE
49.4 m² 3
R18.6 m²
C202
CORRIDOR
C202
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
20.1 m² 2
R18.6 m²
S01
STAIRS
S01
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
26.0 m² 2
R18.6 m²
C201
CORRIDOR
C201
6.9 m² 1
R18.6 m²
TOILET
4.0 m² 1
S46.5 m²
JANITOR
540 162
7.6
STAIR 01
276 142
7.6
STAIR2E
11.8 m² 1
S46.5 m²
STORAGE
FEC
FEC
TRAVEL DISTANCE
COMMON PATH OF TRAVEL
EXIT
DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
DEAD END
LIFE SAFETY ROOM TAG
(A) ROOM AREA (SM)
(B) OCCUPANT LOAD FACTOR (SM/PERSON)
(C) OCCUPANTS (PERSONS)
(D) OCCUPANCY USE
EXIT SIGN WITH DIRECTIONAL ARROWS
STAIR/DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
(4) STAIR CLEAR WIDTH (MM)
(5) STAIR OCCUPANT LOAD FACTOR (MM/PERSONS)
(6) STAIR OCCUPANT LOAD CAPACITY (PERSONS)
DIST.
DIST.
DIST.
(1)
(2)
(3)
EX/DR #
(1)
(2)
(3)
(4)
(5)
(6)
DR #
A C
DB
ROOM
NAME
LIFE SAFETY LEGEND
P P SMOKE PARTITION WALL
1-HR FIRE RATED BARRIER WALL
0.5 HR FIRE RATED BARRIER WALL
FEC SURFACE MOUNTED FIRE EXTINGUISHER CABINET
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w
.e xp
F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
S E A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
S E
C O
N D
L E
V E
L L
IF
E
S A
F E
T Y
P L A
N
GI102
B A
C K
C H
E C
K D
E S
IG
N
S U
B M
IT
T
A L
N
O T
F O
R C
O N
S T
R U
C T
IO
N
Y K
IM
B K
IM
Y K
IM
J A
N U
A R
Y
B R
F
P .r v t
SCALE: 1 : 100
B1
SECOND FLOOR LIFE SAFETY PLAN - AREA A
SCALE: 1 : 100
K1
SECOND FLOOR LIFE SAFETY PLAN - AREA B
OCCUPANT LOAD SCHEDULE - SECOND FLOOR
NUMBER ROOM NAME AREA OCCUPANCY USE
OCCUPANCY LOAD
FACTOR(PER PERSON)
OCCUPANT
LOAD
201 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
202 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
203 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
204 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
205 BEDROOM 27.7 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
206 BEDROOM 27.7 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
207 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
208 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
209 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
210 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
211 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
212 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
213 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
214 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
215 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
216 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
217 LAUNDRY RM 8.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
218 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
220 LOUNGE 36.4 m² ASSEMBLY - UNCONCENTRATED (NFPA 101) 1.4 m² 27
221 TOILET 6.9 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
222 JANITOR 4.0 m² STORAGE (NFPA 101) 46.5 m² 1
223 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
224 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
225 LAUNDRY RM 8.1 m² INDUSTRIAL (NFPA 101) 9.3 m² 1
226 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
C201 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
C202 CORRIDOR 49.4 m² RESIDENTIAL (NFPA 101) 18.6 m² 3
C203 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
S01 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
S02 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
0 5 m2
0 5 m2
GENERAL NOTES
1. REFER TO GI001 FOR LIFE SAFETY CODE ANALYSIS.
2. ALL INFORMATION SHOWN ON THIS SHEET IS FOR
INFORMATION ONLY TO DEMONSTRATE CODE
COMPLIANCE.
3. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR FIRE EXINGUISHER REQUIREMENTS.
4. REFER TO ELECTRICAL DRAWINGS AND SPECIFICATIONS
FOR EXIT SIGN REQUIREMENTS.
MEANS OF EGRESS LIMITATION
OCCUPANCY COMMON PATH (M) TRAVEL DISTANCE (M)
NEW DORMITORY 15 38/61*
* TRAVEL DISTANCE WITHIN A SLEEPING ROOM TO A
CORRIDOR DOOR SHALL NOT EXCEED 38 METERS. TRAVEL
DISTANCE FROM THE CORRIDOR DOOR TO THE NEAREST
EXIT SHALL NOT EXCEED 61 METERS
EXIT CAPACITY SUMMARY
TOTAL EGRESS CAPACITY
TOTAL OCCUPANT LOAD
PLAN NORTHDR
1 2 3 4 5 6 7 8 9 10 11
A
B
C
D
36.4 m² 27
AU1.4 m²
LOUNGE
32011.8 m² 1
S46.5 m²
STORAGE
2.7 m² 1
S46.5 m²
LINEN RM
8.1 m² 1
R18.6 m²
LAUNDRY
RM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
20.1 m² 2
R18.6 m²
S02
STAIRS
S02
26.0 m² 2
R18.6 m²
C303
CORRIDOR
C303
276 142
7.6
STAIR3W
540 162
7.6
STAIR 02
26.5 m² 2
R18.6 m²
BEDROOM
11 12 13 14 15 16 17 18 19 20 21 22
A
B
C
D
11.8 m² 1
S46.5 m²
STORAGE
2.7 m² 1
S46.5 m²
LINEN RM
8.1 m² 1
R18.6 m²
LAUNDRY
RM
4.0 m² 1
S46.5 m²
JAN
36.4 m² 27
AU1.4 m²
LOUNGE
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
27.0 m² 2
R18.6 m²
BEDROOM
49.4 m² 3
R18.6 m²
C302
CORRIDOR
C302
20.1 m² 2
R18.6 m²
S01
STAIRS
S01
26.0 m² 2
R18.6 m²
C301
CORRIDOR
C301
6.9 m² 1
R18.6 m²
TOILET
540 162
7.6
STAIR 01
276 142
7.6
STAIR3E
FEC
FEC
TRAVEL DISTANCE
COMMON PATH OF TRAVEL
EXIT
DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
DEAD END
LIFE SAFETY ROOM TAG
(A) ROOM AREA (SM)
(B) OCCUPANT LOAD FACTOR (SM/PERSON)
(C) OCCUPANTS (PERSONS)
(D) OCCUPANCY USE
EXIT SIGN WITH DIRECTIONAL ARROWS
STAIR/DOOR EXIT CAPACITY
(1) DOOR CLEAR WIDTH (MM)
(2) DOOR OCCUPANT LOAD FACTOR (MM/PERSONS)
(3) DOOR OCCUPANT LOAD CAPACITY (PERSONS)
(4) STAIR CLEAR WIDTH (MM)
(5) STAIR OCCUPANT LOAD FACTOR (MM/PERSONS)
(6) STAIR OCCUPANT LOAD CAPACITY (PERSONS)
DIST.
DIST.
DIST.
(1)
(2)
(3)
EX/DR #
(1)
(2)
(3)
(4)
(5)
(6)
DR #
A C
DB
ROOM
NAME
LIFE SAFETY LEGEND
P P SMOKE PARTITION WALL
1-HR FIRE RATED BARRIER WALL
0.5 HR FIRE RATED BARRIER WALL
FEC SURFACE MOUNTED FIRE EXTINGUISHER CABINET
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w
.e xp
F e d e ra l.
c o m p ro j.
n o
P A
C -2
-A
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
S O
L
IC
IT
A
T
IO
N N
O
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
S E A L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
J A
P A
N D
IS
T
R
IC
T
U N
IT
A
P O
A P
-5
C A
M P
Z A
M A
J A
P A
N
F Y
R
E P
A
IR
U P
H B
L D
G
D
E S
IG
N
R E
F R
E S
H
T H
IR
D
L E
V E
L L
IF
E
S A
F E
T Y
P L A
N
GI103
B A
C K
C H
E C
K D
E S
IG
N
S U
B M
IT
T
A L
N
O T
F O
R C
O N
S T
R U
C T
IO
N
Y K
IM
B K
IM
Y K
IM
J A
N U
A R
Y
B R
F
P .r v t
SCALE: 1 : 100
B1
THIRD FLOOR LIFE SAFETY PLAN - AREA A
SCALE: 1 : 100
K1
THIRD FLOOR LIFE SAFETY PLAN - AREA B
OCCUPANT LOAD SCHEDULE - THIRD FLOOR
NUMBER ROOM NAME AREA OCCUPANCY USE
OCCUPANCY LOAD
FACTOR(PER PERSON)
OCCUPANT
LOAD
301 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
302 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
303 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
304 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
305 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
306 BEDROOM 26.5 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
307 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
308 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
309 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
310 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
311 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
312 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
313 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
314 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
315 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
316 BEDROOM 27.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
317 LAUNDRY RM 8.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
318 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
320 LOUNGE 36.4 m² ASSEMBLY - UNCONCENTRATED (NFPA 101) 1.4 m² 27
321 TOILET 6.9 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
322 JAN 4.0 m² STORAGE (NFPA 101) 46.5 m² 1
323 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
324 STORAGE 11.8 m² STORAGE (NFPA 101) 46.5 m² 1
325 LAUNDRY RM 8.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 1
326 LINEN RM 2.7 m² STORAGE (NFPA 101) 46.5 m² 1
C301 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
C302 CORRIDOR 49.4 m² RESIDENTIAL (NFPA 101) 18.6 m² 3
C303 CORRIDOR 26.0 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
S01 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
S02 STAIRS 20.1 m² RESIDENTIAL (NFPA 101) 18.6 m² 2
0 5 m2
0 5 m2
GENERAL NOTES
1. REFER TO GI001 FOR LIFE SAFETY CODE ANALYSIS.
2. ALL INFORMATION SHOWN ON THIS SHEET IS FOR
INFORMATION ONLY TO DEMONSTRATE CODE
COMPLIANCE.
3. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR FIRE EXINGUISHER REQUIREMENTS.
4. REFER TO ELECTRICAL DRAWINGS AND SPECIFICATIONS
FOR EXIT SIGN REQUIREMENTS.
MEANS OF EGRESS LIMITATION
OCCUPANCY COMMON PATH (M) TRAVEL DISTANCE (M)
NEW DORMITORY 15 38/61*
* TRAVEL DISTANCE WITHIN A SLEEPING ROOM TO A
CORRIDOR DOOR SHALL NOT EXCEED 38 METERS. TRAVEL
DISTANCE FROM THE CORRIDOR DOOR TO THE NEAREST
EXIT SHALL NOT EXCEED 61 METERS
EXIT CAPACITY SUMMARY
TOTAL EGRESS CAPACITY
TOTAL OCCUPANT LOAD
PLAN NORTHDR
73455
3620 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3620
73455
3620 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3620
DN
UP
UP UP
DN
1 222 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A
B
C
D
73455
3620 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3485 3620
DN
UP UP
DN
1 222 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
A
B
C
D
DN DN
1 222 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
73455