DOT_Trenching_and_Backfilling.pdf
PDF 512 KB Posted
- Solicitation number
- 39447
- Issued by
- New London County, Connecticut
About this file
Summary
This is a Connecticut Department of Transportation standard specification sheet for trenching and backfilling operations related to electrical conduit installation. The document provides detailed technical guidance for the Town of Waterford Utility Commission's water service replacement project on Rope Ferry Road, a state road in Connecticut. The specifications establish requirements for communication conduit burial, including minimum depth standards of 24 inches, compaction procedures in 6-inch lifts, and identification post placement at approximately 24 inches from rigid metal conduit (RMC) in the vicinity of interconnect handholes. The document specifies materials and methods for various surface conditions, including bituminous pavements, Portland cement concrete, and unpaved earth areas, with detailed diagrams illustrating proper trench configuration, bedding material placement, and warning tape installation. Conduit specifications require 4-inch by 4-inch nominal pressure-treated wood posts with stainless steel identification numbers indicating distances in feet between interconnect handholes when spacing exceeds 1,500 feet.
The standard sheet includes provisions for restoration of disturbed areas to original condition and references Connecticut DOT Standard Specifications, Sections 9.50, 9.21, 9.22, and Article 4.06.03 for concrete work, seeding, and aggregate base material requirements. The specification mandates detectable warning tape in orange with black legend for communication conduits and establishes compaction standards prohibiting hand compaction in favor of power compaction methods. Controlled low-strength material (CLSM) may be used as bedding material when authorized by the engineer, with the top of CLSM required to be at least 20 inches below the surface. The document was submitted by Lisa N. Conroy, P.E., and approved by Matthew C. Blume, P.E., PTOE, on January 23, 2024, and February 21, 2024, respectively.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CT DOT
COMMUNICATION
CONDUIT
BURIED BELOW
CALL BEFORE
YOU DIG
1 - 800
922 - 4455
XX
OW
SAND
BEVELED END
GROUND LINE
CONDUIT
SAND BACKFILL LEVEL
SUITABLE BACKFILL
SIGN FACE DETAIL
INTERCONNECT TYPICAL CURB CROSSING
M
IN
M
IN
NOTES:
1. RESTORE AREAS DISTURBED BY TRENCH TO ORIGINAL CONDITION.
CONDUIT
NOTES:
1. 4" x 4" NOMINAL, PRESSURE TREATED WOOD POST.
NYLON WASHER ON FACE OF SIGN.
IS GREATER THAN 1500' APART.
36" (MIN)
10' (MIN)
36" (MIN)
6"
2" (MIN)
1¼"
1½"
SIGN FACE ON ALL FOUR SIDES
ATTACH NUMBERS TO SIDE OF POST FACING CONDUIT.
TO TRENCH CONTAINING COMMUNICATION CABLE.
2¾" (TYP)
⅜" (TYP)
½" (TYP)
4" MIN
8" MIN
24"
MAX
12"
T
O
SIGN # 41-4669
4" MIN.
SAW CUT EDGE
6" TO 12"
SAW CUT EDGE
CONDUIT
CONCRETE OVERLAY
EXISTING BITUMINOUS
EXISTING BITUMINOUS OR PCC PAVEMENT
EXISTING BITUMINOUS
T
O
CONCRETE OVERLAY
BEDDING MATERIAL OR SAND
1. TOTAL HOT MIX ASPHALT (HMA) THICKNESS TO MATCH EXISTING BITUMINOUS
SAW CUT EDGE, TACK COAT, AND
SEAL JOINT AFTER PAVING. (TYP)
EXISTING GRADE
2. ATTACH SIGN TO POST WITH ¼" x 1¼" STAINLESS STEEL LAG SCREW WITH
4. INSTALL POST APPROX 24" FROM RMC IN VICINITY OF EACH INTERCONNECT HANDHOLE.
5. INSTALL ADDITIONAL POST(S) WHERE SPACING BETWEEN INTERCONNECT HANDHOLES
6. PERMANENTLY ATTACH STAINLESS STEEL NUMBERS INDICATING DISTANCE IN FEET
SEE NOTE 6 3"
UNDER EXISTING UTILITYCROSSING
30" MAX TYP
CAUTION - CABLE BURIED BELOW
NOTE:
EXISTING UTILITY PIPE OR CONDUIT
NOTES:
DETECTABLE WARNING TAPE
8" MIN.
12" MIN.
NOTES:
CONCRETE AND PORTLAND CEMENT CONCRETE (PCC) THICKNESS.
2. WHEN ALLOWED BY ENGINEER, USE CONTROLLED LOW STRENGTH MATERIAL (CLSM)
AS BEDDING MATERIAL. TOP OF CLSM SHALL BE AT LEAST 20" BELOW SURFACE.
SIDEWALK EARTH
NOTES:
1. IN MOWED AREAS: PLACE TOPSOIL, FERTILIZER, SEED, & MULCH.
4" MIN
REFER TO NOTE 1
GENERAL NOTES:
1. TOP OF CONDUIT AT LEAST 24" DEEP.
2. COMPACT BACKFILL IN 6" LIFTS.
1. WHEN ENCOUNTERED AT APPROXIMATELY THE SAME
DEPTH, CROSS BENEATH.
INTERCONNECT CONDUIT
STANDARD SPECIFICATIONS, SECTION 9.50 OR SEEDING TYPE CALLED OUT ON THE PLANS.
DETECTABLE WARNING TAPE
COMMUNICATION - ORANGE BACKGROUND / BLACK LEGEND
STANDARD SPECIFICATIONS, ARTICLE: 1.05.15
1. TAPE COLORS:
2. PROTECT & SUPPORT EXPOSED EXISTING UTILITY.
HAND COMPACTION NOT PERMITTED.
POWER - RED BACKGROUND / BLACK LEGEND
IDENTIFICATION POST
LEGEND - BLACK (OPAQUE).
3. SIGN COLORS: BACKGROUND - ORANGE (RETROREFLECTIVE)
DETECTABLE
WARNING TAPE
OVERLAYED PORTLAND CEMENT CONCRETE
PAVEMENT - BITUMINOUS CONCRETE OR
12" 12"
BE 4"
MINIMUM COMPACTED PAVEMENT THICKNESS SHALL
S0.375 TRAFFIC LEVEL 2 IN MULTIPLE 2"-3" LIFTS
MATCH EXISTING PAVEMENT THICKNESS USING HMA
COMPACTED IN 4" LIFTS
PROCESSED AGGREGATE BASE MATERIAL
TRANSVERSE ENDS OF THE TRENCH
TRAFFIC LEVEL 2, AND SAWCUT
TRAFFIC LEVEL 2, OR 2" HMA S0.5
MILL 2" THEN PLACE 2" HMA S0.375
TACK COAT EDGES (TYP.)
SAND
WARNING TAPE
SUITABLE BACKFILL
CONDUIT
24"
MAX
8" MIN
4" MIN
T
O
12"
SIDEWALK
NOTES:
1. WHERE CONCRETE SIDEWALK IS DAMAGED OR CUT, REPLACE THE
ENTIRE SECTION BETWEEN JOINTS. REPLACEMENT SIDEWALK IS
PAID FOR UNDER THE ITEM "CONCRETE SIDEWALK".
STANDARD SPECIFICATIONS, SECTIONS 9.21 & 9.22
DETECTABLE
COMPACTED IN 4" LIFTS
GRANULAR FILL SHALL BE
8"
STANDARD SPECIFICATION, SECTION 3.04 AND STANDARD SPECIFICATION, ARTICLE 4.06.03
STANDARD SHEET TITLE: STANDARD SHEET NO.:
CONNECTICUT
D E
P A
R T
M E
N T
O F TRANS
P O
R T
A T I
O N
STATE OF CONNECTICUT
TRANSPORTATION
OF
DEPARTMENT
SIGNATURE BLOCK:
TRENCHING & BACKFILLING, ELECTRICAL CONDUIT
TR-1001_01
NOT TO SCALE
NEWINGTON, CT 06111
2800 BERLIN TURNPIKE
OFFICE OF ENGINEERING
STANDARD SHEET
CTDOT
SUBMITTED BY: APPOVED BY:
LEGEND AS SHOWN ON TRAFFIC CONTROL SIGNAL PLAN:
PROPOSED RMC (RIGID METAL CONDUIT)
SAND
EXISTING RMC (RIGID METAL CONDUIT)
CURB OR EDGE OF ROAD
INTERCONNECT
HANDHOLE
UNPAVED EARTH
22.5°- 48" RADIUS
BITUMINOUS SHOULDER
22.5°- 48" RADIUS 22.5°- 48" RADIUS
22.5°- 48" RADIUS
CONDUIT
CONDUIT
CABLE ITEM.
IDENTIFICATION POSTS WITH SIGNS SHALL BE PAID UNDER THE COMMUNICATION 7.
| 2024-01-23T08:17:40-0500 | |
| Lisa N. Conroy, P.E. |
| 2024-02-21T08:25:47-0500 | |
| Matthew C. Blume, P.E., PTOE |
File details come from the government source that posted it. Updated .