DOT_Trenching_and_Backfilling.pdf

PDF 512 KB Posted

Attached to
REPLACEMENT OF EXISTING PLASTIC WATER SERVICES WITH NEW COPPER WATER SERVICES
Solicitation number
39447
Issued by
New London County, Connecticut

About this file

Summary

This is a Connecticut Department of Transportation standard specification sheet for trenching and backfilling operations related to electrical conduit installation. The document provides detailed technical guidance for the Town of Waterford Utility Commission's water service replacement project on Rope Ferry Road, a state road in Connecticut. The specifications establish requirements for communication conduit burial, including minimum depth standards of 24 inches, compaction procedures in 6-inch lifts, and identification post placement at approximately 24 inches from rigid metal conduit (RMC) in the vicinity of interconnect handholes. The document specifies materials and methods for various surface conditions, including bituminous pavements, Portland cement concrete, and unpaved earth areas, with detailed diagrams illustrating proper trench configuration, bedding material placement, and warning tape installation. Conduit specifications require 4-inch by 4-inch nominal pressure-treated wood posts with stainless steel identification numbers indicating distances in feet between interconnect handholes when spacing exceeds 1,500 feet.

The standard sheet includes provisions for restoration of disturbed areas to original condition and references Connecticut DOT Standard Specifications, Sections 9.50, 9.21, 9.22, and Article 4.06.03 for concrete work, seeding, and aggregate base material requirements. The specification mandates detectable warning tape in orange with black legend for communication conduits and establishes compaction standards prohibiting hand compaction in favor of power compaction methods. Controlled low-strength material (CLSM) may be used as bedding material when authorized by the engineer, with the top of CLSM required to be at least 20 inches below the surface. The document was submitted by Lisa N. Conroy, P.E., and approved by Matthew C. Blume, P.E., PTOE, on January 23, 2024, and February 21, 2024, respectively.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CT DOT

COMMUNICATION

CONDUIT

BURIED BELOW

CALL BEFORE

YOU DIG

1 - 800

922 - 4455

XX

OW

SAND

BEVELED END

GROUND LINE

CONDUIT

SAND BACKFILL LEVEL

SUITABLE BACKFILL

SIGN FACE DETAIL

INTERCONNECT TYPICAL CURB CROSSING

M

IN

M

IN

NOTES:

1. RESTORE AREAS DISTURBED BY TRENCH TO ORIGINAL CONDITION.

CONDUIT

NOTES:

1. 4" x 4" NOMINAL, PRESSURE TREATED WOOD POST.

NYLON WASHER ON FACE OF SIGN.

IS GREATER THAN 1500' APART.

36" (MIN)

10' (MIN)

36" (MIN)

6"

2" (MIN)

1¼"

1½"

SIGN FACE ON ALL FOUR SIDES

ATTACH NUMBERS TO SIDE OF POST FACING CONDUIT.

TO TRENCH CONTAINING COMMUNICATION CABLE.

2¾" (TYP)

⅜" (TYP)

½" (TYP)

4" MIN

8" MIN

24"

MAX

12"

T

O

SIGN # 41-4669

4" MIN.

SAW CUT EDGE

6" TO 12"

SAW CUT EDGE

CONDUIT

CONCRETE OVERLAY

EXISTING BITUMINOUS

EXISTING BITUMINOUS OR PCC PAVEMENT

EXISTING BITUMINOUS

T

O

CONCRETE OVERLAY

BEDDING MATERIAL OR SAND

1. TOTAL HOT MIX ASPHALT (HMA) THICKNESS TO MATCH EXISTING BITUMINOUS

SAW CUT EDGE, TACK COAT, AND

SEAL JOINT AFTER PAVING. (TYP)

EXISTING GRADE

2. ATTACH SIGN TO POST WITH ¼" x 1¼" STAINLESS STEEL LAG SCREW WITH

4. INSTALL POST APPROX 24" FROM RMC IN VICINITY OF EACH INTERCONNECT HANDHOLE.

5. INSTALL ADDITIONAL POST(S) WHERE SPACING BETWEEN INTERCONNECT HANDHOLES

6. PERMANENTLY ATTACH STAINLESS STEEL NUMBERS INDICATING DISTANCE IN FEET

SEE NOTE 6 3"

UNDER EXISTING UTILITYCROSSING

30" MAX TYP

CAUTION - CABLE BURIED BELOW

NOTE:

EXISTING UTILITY PIPE OR CONDUIT

NOTES:

DETECTABLE WARNING TAPE

8" MIN.

12" MIN.

NOTES:

CONCRETE AND PORTLAND CEMENT CONCRETE (PCC) THICKNESS.

2. WHEN ALLOWED BY ENGINEER, USE CONTROLLED LOW STRENGTH MATERIAL (CLSM)

AS BEDDING MATERIAL. TOP OF CLSM SHALL BE AT LEAST 20" BELOW SURFACE.

SIDEWALK EARTH

NOTES:

1. IN MOWED AREAS: PLACE TOPSOIL, FERTILIZER, SEED, & MULCH.

4" MIN

REFER TO NOTE 1

GENERAL NOTES:

1. TOP OF CONDUIT AT LEAST 24" DEEP.

2. COMPACT BACKFILL IN 6" LIFTS.

1. WHEN ENCOUNTERED AT APPROXIMATELY THE SAME

DEPTH, CROSS BENEATH.

INTERCONNECT CONDUIT

STANDARD SPECIFICATIONS, SECTION 9.50 OR SEEDING TYPE CALLED OUT ON THE PLANS.

DETECTABLE WARNING TAPE

COMMUNICATION - ORANGE BACKGROUND / BLACK LEGEND

STANDARD SPECIFICATIONS, ARTICLE: 1.05.15

1. TAPE COLORS:

2. PROTECT & SUPPORT EXPOSED EXISTING UTILITY.

HAND COMPACTION NOT PERMITTED.

POWER - RED BACKGROUND / BLACK LEGEND

IDENTIFICATION POST

LEGEND - BLACK (OPAQUE).

3. SIGN COLORS: BACKGROUND - ORANGE (RETROREFLECTIVE)

DETECTABLE

WARNING TAPE

OVERLAYED PORTLAND CEMENT CONCRETE

PAVEMENT - BITUMINOUS CONCRETE OR

12" 12"

BE 4"

MINIMUM COMPACTED PAVEMENT THICKNESS SHALL

S0.375 TRAFFIC LEVEL 2 IN MULTIPLE 2"-3" LIFTS

MATCH EXISTING PAVEMENT THICKNESS USING HMA

COMPACTED IN 4" LIFTS

PROCESSED AGGREGATE BASE MATERIAL

TRANSVERSE ENDS OF THE TRENCH

TRAFFIC LEVEL 2, AND SAWCUT

TRAFFIC LEVEL 2, OR 2" HMA S0.5

MILL 2" THEN PLACE 2" HMA S0.375

TACK COAT EDGES (TYP.)

SAND

WARNING TAPE

SUITABLE BACKFILL

CONDUIT

24"

MAX

8" MIN

4" MIN

T

O

12"

SIDEWALK

NOTES:

1. WHERE CONCRETE SIDEWALK IS DAMAGED OR CUT, REPLACE THE

ENTIRE SECTION BETWEEN JOINTS. REPLACEMENT SIDEWALK IS

PAID FOR UNDER THE ITEM "CONCRETE SIDEWALK".

STANDARD SPECIFICATIONS, SECTIONS 9.21 & 9.22

DETECTABLE

COMPACTED IN 4" LIFTS

GRANULAR FILL SHALL BE

8"

STANDARD SPECIFICATION, SECTION 3.04 AND STANDARD SPECIFICATION, ARTICLE 4.06.03

STANDARD SHEET TITLE: STANDARD SHEET NO.:

CONNECTICUT

D E

P A

R T

M E

N T

O F TRANS

P O

R T

A T I

O N

STATE OF CONNECTICUT

TRANSPORTATION

OF

DEPARTMENT

SIGNATURE BLOCK:

TRENCHING & BACKFILLING, ELECTRICAL CONDUIT

TR-1001_01

NOT TO SCALE

NEWINGTON, CT 06111

2800 BERLIN TURNPIKE

OFFICE OF ENGINEERING

STANDARD SHEET

CTDOT

SUBMITTED BY: APPOVED BY:

LEGEND AS SHOWN ON TRAFFIC CONTROL SIGNAL PLAN:

PROPOSED RMC (RIGID METAL CONDUIT)

SAND

EXISTING RMC (RIGID METAL CONDUIT)

CURB OR EDGE OF ROAD

INTERCONNECT

HANDHOLE

UNPAVED EARTH

22.5°- 48" RADIUS

BITUMINOUS SHOULDER

22.5°- 48" RADIUS 22.5°- 48" RADIUS

22.5°- 48" RADIUS

CONDUIT

CONDUIT

CABLE ITEM.

IDENTIFICATION POSTS WITH SIGNS SHALL BE PAID UNDER THE COMMUNICATION 7.

2024-01-23T08:17:40-0500
Lisa N. Conroy, P.E.
2024-02-21T08:25:47-0500
Matthew C. Blume, P.E., PTOE

File details come from the government source that posted it. Updated .