Dixon Correctional Pump Specifications~1.docx
DOCX document 14 KB Posted
- Attached to
- Dixon CC Recirculating Pump
- Solicitation number
- 20-426DOC-SOURC-B-13583
- Issued by
- Lake County, Illinois
About this file
This document pertains to the specifications for a vertical dry pit non-clog pump required for the Dixon Correctional facility in Illinois. The pump must be a direct replacement for the existing Paco Pump Model #52-61215-358D30, or bid as a modification to the existing system. The bid must include specifications for the proposed pump as well as a detailed list of all required fittings, flange kits, and other parts necessary to ensure the pump will work acceptably with the current system. Submersible pumps or universal wet-dry pumps will not be accepted.
The current pump specifications are provided, including the suction size, discharge size, flow rate, total dynamic head, impeller diameter, horsepower, RPM, and voltage/phase requirements. Bidders must provide a complete solution inclusive of all necessary components within their bid price. This opportunity is part of the Dixon CC Recirculating Pump contract for the state of Illinois.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Roughing Filter B-Pump Motor Nameplate.jpg | JPG image | |
| Dixon Recirculating Pump BOA~1.docx | DOCX document | |
| Roughing Filter B-Pump Curve.jpg | JPG image | |
| Roughing Filter B-Pump Nameplate.jpg | JPG image | |
| Roughing Filter Pump in Basement picture.jpg | JPG image |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Wastewater Roughing Filter Pump required to be Vertical Dry Pit Non-Clog Pump.
· Must either be a DIRECT REPLACEMENT for pump specified below
OR
· Bid as a modification to existing system. Bid must include specifications for pump bid and a detailed list of fittings, flange kits etc. required to make pump work acceptably with existing systems. All required parts must be included in bid price.
NOTE: Submersible pumps or universal wet-dry pumps will not be accepted. See additional pictures attached of current pump and system.
Current Pump Specifications:
· Series 4210 Type NCF Vertical Dry Pit Non - Clog Pump
· Paco Pump Model # 52-61215-358D30
· Paco Pump Serial # UK95R2016401
· Suction Size – 8 inch
· Discharge Size – 6 inch
· 700 GPM
· 24.5 TDH
· Impeller Diameter 10.9 inch
· 7.5 HP
· 875 RPM
· 208 Volts
· 3 Phase
File details come from the government source that posted it. Updated .