Design Radio Upgrades Drawings.pdf
PDF 1 MB Posted
- Solicitation number
- 36C24224B0011
About this file
This notice announces a forthcoming solicitation for radio upgrades at the Canandaigua VA Medical Center in New York. The scope of work includes demolishing existing radio equipment and towers, and installing a new communications antenna system to service subscribers such as the VA Fire and Police Departments. The contractor will be responsible for structural work, electrical work, and ensuring the installed system meets all applicable codes. The solicitation is expected to be posted on February 22, 2024 on SAM.gov in electronic format only. Amendments will also be posted to SAM. The procurement is set aside 100% for Service-Disabled Veteran Owned Small Businesses. The contract value is estimated between $2-5 million. The site visit date will be in the solicitation. Bids must be submitted electronically by the due date in March 2024, and the contract is planned for award that same month. Inquiries should be directed to the named Contracting Officer by email.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
SCALE: NONE
SITE LOCATION
SCALE: NONE
SITE PLAN
35T
BIOMASS
8182 80 107
105109
114 PAVILION COURT 2
124 TRASH HUT - B.6
94 GARAGE (SCHOOL LEASE)
80 S.T.P. CONTROL HOUSE (WASTE WATER TREATMENT)
73 (SCHOOL LEASE)
39 ENGINEERING STORAGE
37 FORMER PATIENT CARE, IS
36 FORMER PATIENT CARE, DAY TREATMENT CENTER
34 SPD, A&MMS, DAYCARES, NETWORK STORAGE
14 VACANT
13 EMERGENCY GENERATOR
5 AUDITORIUM, RECREATION SVC.
NO. BUILDING SCHEDULE 1
4 ADMINISTRATIVE, CANTEEN
18 (SCHOOL LEASE)
1 OUTPATIENT SERVICES, MAIN ADMIN
2 FORMER MAIN KITCHEN, DINING RM., OUTPATIENT PHARMACY
3 GEC OFFICES, PATIENT CARE
6 SUBSTANCE ABUSE OFFICES, EMS
7 NHCU, VOLUNTARY SVC., HRMS
9 PATIENT CARE/DOM, LIBRARY, MAIL RM.
11 WAREHOUSE
12 BOILER PLANT/BIOMASS
16 FIRE STATION, GARAGE, GROUNDS MTN.
24 VALOR HEADQUARTERS
33 PATIENT CARE NHCU, INPATIENT PHARMACY
40 GATE HOUSE
41 OUTDOOR FIREPLACE
42 STONE GRANDSTAND
46 WAREHOUSE POLE BARN
70 MISCELLANEOUS STORAGE
81 SLUDGE DIGESTORS
82 SLUDGE BED
76 STORAGE
8 NHCU, ADULT DAYCARE
10 LAUNDRY
20 VA POLICE STATION
75 OIL HOUSE
77 STORAGE
125 TRASH HUT - B.36/37
123 TRASH HUT - B.8
122 OIL STORAGE TANKS
113 PATIENT'S TOILET, COURT 2
121 SWITCHGEAR
118 ENGINEERING SHOPS & OFFICES
112 PATIENT'S TOILET, COURT 1
111 TRANSFORMERS X-RAY B.1
109 AERATION TANKS
108 PRIMARY TANKS
106 TRICKLING FILTER
107 PUMP HOUSE S.T.P.
110 PAVILION COURT 2
120 FIRE PUMP BLDG., BKFLOW PREVENTOR
115 RECREATION STORAGE, COURT 1
17 CADENCE SQUARE
35 RELOCATED DIETETICS, KITCHEN
43 SALT STORAGE BARN (COVER)
44 GROUNDS AND TRANSPORTATION
45 CHILLER PLANT
50 LOADING DOCK
38 FUTURE TEMPORARY OFFICE
105 SECONDARY TANKS
65 TEMPORARY TRAILERS (OFFICES)
CO URTYARD 2
CO URTYARD 2
2 HR VISITOR
BUSHWOOD LN.
LOOP RD.
LO
O
P R
D
EAST STREET
PARKING
PARKING
PARKING
WATER TOWER
C H
AP
EL
S
TR
EE
T
PARK
EXERCISE
EAST STREET
CAMPUS SITE PLAN
VAMC Canandaigua
RAMP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
DESIGN RADIO
UPGRADES
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Canandaigua VAMC DEPARTMENT OF VETERANS AFFAIRS
PROJECT NO: 528A5-21-502
BUILDINGS 1 & 37
CANANDAIGUA, NY
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:1
PM
T-101
TITLE SHEET
DRAWING INDEX
DRAWING
NUMBER DRAWING NAME
T-101 TITLE SHEET
G-101 GENERAL PROJECT NOTES
G-102 LIFE SAFETY EGRESS PLANS
S-101 BLDG 1 STRUCTURAL REPAIR PLANS (PHASE 1)
ED101 BLDG 1 ELECTRICAL DEMOLITION PLANS (PHASE 2)
ED102 BLDG 37 ATTIC/ROOF ELECTRICAL DEMOLITION PLANS (PHASE 2)
ED901 ELECTRICAL DEMOLITION PHOTOS (PHASE 2)
E-101 BLDG 1 ELECTRICAL NEW WORK PLANS (PHASE 1)
E-102 BLDG 37 BASEMENT ELECTRICAL NEW WORK PLAN (PHASE 1)
E-103 BLDG 37 ATTIC/ROOF ELECTRICAL NEW WORK PLAN (PHASE 1)
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES AND DIAGRAMS
1 & 37
BLDG. 37
BLDG. 1
BLDG. 16
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:0
PM
G-101
GENERAL PROJECT NOTES
1. UNLESS SPECIFICALLY NOTED AS EXISTING, ALL ITEMS, EQUIPMENT, AND WORK SHOW IS NEW AND SHALL BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. DURING THE EXECUTION OF THIS CONTRACT, THE SITE AND BUILDINGS WILL BE OCCUPIED AND IN USE. WORK DONE UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER INSOFAR AS POSSIBLE.
ALL WORK SHALL BE COORDINATED WITH THE CONTRACTING OFFICER’S REPRESENTATIVE AND IS SUBJECT TO HIS
CONTINUOUS APPROVAL.
3. REQUEST APPROVAL FROM THE CONTRACTING OFFICER’S REPRESENTATIVE FOURTEEN (14) DAYS IN ADVANCE FOR
THE SHUTDOWN OF ANY EXISTING SYSTEM.
4. PROVIDE ADEQUATE FIRE PROTECTION IN THE ENTIRE CONSTRUCTION AREA FOR THE DURATION OF THE CONSTRUCTION PERIOD. REFER TO SPECIFICATION DIVISION 1, “GENERAL REQUIREMENTS”, “FIRE SAFETY
REQUIREMENTS”.
5. THE ENTIRE EXISTING FIRE PROTECTION SYSTEM SHALL BE RESTORED TO FULL OPERATION AT THE END OF EACH WORKING DAY. ALL EXISTING FIRE ALARMS AND FIRE EXITS AND ANY OTHER ASPECT OF THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN FULL OPERATION. THE COST OF RESPONSE TO ANY FALSE ALARM AS CHARGED BY ANY
LOCAL FIRE DEPARTMENT SHALL BE PAID BY THE CONTRACTOR.
6. THE GENERAL NOTES ON THIS SHEET APPLY TO ALL THE DRAWING DISCIPLINES.
7. THE WORK INCLUDES ALL ITEMS OF THE SPECIFICATIONS.
8. VISIT THE SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS PRIOR TO SUBMITTING BID. REPORT ANY
DISCREPANCIES TO THE ENGINEER PRIOR TO SUBMITTAL OF BID.
9. DO NOT BEGIN FABRICATION, CUT ANY MEMBERS, OR BEGIN INSTALLATION UNTIL THE SUBMITTALS AND SHOP
DRAWINGS HAVE BEEN APPROVED. ANY WORK CONSTRUCTED OR INSTALLED PRIOR TO THE APPROVAL OF SUBMITTALS AND SHOP DRAWINGS SHALL BE AT THE CONTRACTOR’S RISK AND SHALL BE REMOVED AND REINSTALLED OR RECONSTRUCTED AT THE CONTRACTOR’S EXPENSE AT THE REQUEST OF THE CONTRACTING OFFICER’S REPRESENTATIVE TO THE COMPLETE SATISFACTION OF THE CONTRACTING OFFICER’S REPRESENTATIVE.
10. DO NOT PENETRATE OR CUT ANY STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN ON THE DRAWINGS (E.G., JOISTS, BEAMS, ETC.). IF STRUCTURAL MEMBERS CONFLICT WITH ROUTING, CONTACT THE CONTRACTING OFFICER’S REPRESENTATIVE FOR DIRECTION BEFORE PROCEEDING. EXERCISE CAUTION IN CUTTING CONCRETE FLOORS AND WALLS TO AVOID EXISTING UTILITIES WHICH MAY BE LOCATED IN AND UNDER CONCRETE SURFACES.
11. THE CONTRACTOR SHALL PROVIDE NEW OPENINGS IN WALLS AND FLOORS, AND PATCH EXISTING OPENINGS IN CONJUNCTION WITH THE DEMOLITION AND INSTALLATION OF THE NEW BUILDING COMPONENTS, INCLUDING ELECTRICAL AND GENERAL CONTRACTOR’S ITEMS. ALL NECESSARY FRAMING, COUNTER-FLASHING, ETC. SHALL BE
INCLUDED.
12. FOR ALL FLOOR, WALL, AND ROOF PENETRATION, VERIFY THE LOCATION OF THE (E) STRUCTURAL MEMBERS PRIOR TO DRILLING AND CUTTING, RELOCATE OPENINGS AS REQUIRED AND CONDUIT, ETC. AS APPROPRIATE. REVIEW THE
STRUCTURAL DRAWINGS IN THE ENGINEERING OFFICE.
13. WHERE THERE IS A CONFLICT ON THE PLANS, SPECIFICATIONS, NOTES, GENERAL NOTES, REFERENCES, PUBLICATIONS, CODES, ETC. WITH RESPECT TO MATERIALS, PRODUCTS, METHODS, WORKMANSHIP, PROCEDURE, EXECUTION, ETC. THE MOST STRINGENT OR BENEFICIAL TO THE OWNER AS DETERMINED BY THE CONTRACTING OFFICER’S REPRESENTATIVE SHALL BE UTILIZED OR INSTALLED. NO RELIEF OR EXTRA PAYMENT SHALL BE MADE TO THE CONTRACTOR BECAUSE OF THE INTERPRETATION OF THE CONTRACTING OFFICER’S REPRESENTATIVE.
14. ALL WORK SHALL BE DONE WITH COMPLETE COMPLIANCE WITH THE LATEST EDITIONS OF THE APPLICABLE CODES AND STANDARDS WHETHER STATUTORY OR NOT. ALL WORK SHALL BE INSTALLED TO COMPLY WITH THE UNIFORM BUILDING CODES, FIRE CODES, NATIONAL ELECTRICAL CODE, UNDERWRITER’S LABORATORY, INC., AMERICAN NATIONAL STANDARD INSTITUTE, INC., NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION, BASIC ELECTRICAL REGULATIONS, AND CODES AND STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA). IF ANY PART OF THE INSTALLATION DOES NOT MEET CODE, NOTIFY THE CONTRACTING OFFICER’S REPRESENTATIVE PRIOR TO BEGINNING THE INSTALLATION. IF ANY PART OF THE PROJECT CANNOT BE INSTALLED TO CONFORM WITH THE PLANS AND/OR SPECIFICATIONS, NOTIFY THE CONTRACTING OFFICER’S REPRESENTATIVE PRIOR TO BEGINNING THE
INSTALLATION.
15. ALL EXISTING CONDUIT AND ELECTRICAL EQUIPMENT NOT TO BE REUSED OR REMAIN IN SERVICE SHALL BE REMOVED FROM THE FACILITY, UNLESS NOTED OTHERWISE. THE CONTRACTING OFFICER’S REPRESENTATIVE HAS THE OPTION TO RECLAIM ANY DEMOLISHED MATERIALS OR EQUIPMENT FOR THE GOVERNMENT, IN WHICH CASE IT SHALL BE DELIVERED TO THE LOCATION DESIGNATED BY THE CONTRACTING OFFICER’S REPRESENTATIVE.
16. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, TRANSITIONS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. COORDINATE ALL THE WORK OF ALL THE TRADES TO INSURE ALL CONDUITS, ETC. DO NOT CONFLICT AND CLEAR STRUCTURAL AND ARCHITECTURAL MEMBERS.
17. THE CONTRACTOR SHALL PAY FOR ALL DAMAGE, INCLUDING WATER DAMAGE, TO PROPERTY AND EQUIPMENT
CAUSED BY HIS WORK THROUGHOUT THE CONSTRUCTION AND WARRANTEE PERIOD.
18. REMOVE T-BARS AND 2X4 CEILING PANELS AS REQUIRED FOR THE DEMOLITION AND THE INSTALLATION OF THE NEW WORK. REINSTALL EXISTING OR REPLACE WITH NEW AS REQUIRED TO THE SATISFACTION OF THE CONTRACTING OFFICER’S REPRESENTATIVE. FOR ANY HARD CEILING AREA, CUT AND DEMOLISH ENOUGH OF THE HARD CEILING TO DO THE WORK REQUIRED. REBUILD AND PATCH THE DEMOLISHED. FINISH AND PAINT TO MATCH EXISTING TO THE
SATISFACTION OF THE CONTRACTING OFFICER’S REPRESENTATIVE.
19. ALL UL LISTED EQUIPMENT SHALL BE INSTALLED AS PER LISTING OR LABELING. MAXIMUM FUSE SIZES MEANS FUSE
PROTECTION REQUIRED.
20. PATCH AND PAINT TO MATCH EXISTING, ALL SURFACES DAMAGED BY THE DEMOLITION AND ALL OPENINGS NOT TO
BE REUSED.
21. REPAIR DAMAGE TO CEILING, WALLS, ETC. TO THE SATISFACTION OF THE CONTRACTING OFFICER’S
REPRESENTATIVE.
22. WHEN A DETAIL OR NOTE IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THE DETAIL OR NOTE TO EVERY SIMILAR CONDITION, WHETHER OR NOT THE REFERENCED DETAIL OR NOTE IS REPEATED OR REFERENCED.
23. ALL HOLES, VOIDS, AND DAMAGED OR UNEVEN SURFACES WHICH ARE CAUSED BY THE CONTRACTOR’S WORK AND WHICH REMAIN EXPOSED IN THE WALL, FLOOR, CEILING, OR OTHER SURFACES SHALL BE PATCHED, REPAIRED, AND BROUGHT FLUSH WITH THE ADJACENT CONSTRUCTION. SUCH SURFACES, NOT CONCEALED BY THE NEW CONSTRUCTION, SHALL MATCH IN EVERY RESPECT THE EXISTING NON-DAMAGED CONSTRUCTION. REMOVE EXISTING UTILITIES BACK BEHIND EXISTING SURFACES AND CAP SO AS NOT TO INTERFERE WITH NEW PATCHES.
24. THE DEMOLITION SHALL INCLUDE ALL ASSOCIATED ANCHORAGES, HANGERS, SUPPORTS, BRACES, FASTENERS, MASTIC, MORTAR, LATH, AND RELATED ITEMS. THE EXISTING SUBSTRATE, INCLUDING CONCRETE, MASONRY, METAL
FRAMING AND FURRING SHALL BE REPAIRED WHERE DAMAGE BY THE CONTRACTOR’S WORK.
25. ALL MANUFACTURERS LISTED ON THESE DRAWINGS ARE PROVIDED FOR BASIS OF DESIGN PURPOSES ONLY.
ALTERNATIVE PRODUCTS AND MANUFACTURERS WILL BE CONSIDERED IF THEY ARE DETERMINED TO BE
EQUIVALENT AND MEET ALL DESIGN REQUIREMENTS DURING THE SUBMITTAL REVIEW PHASE.
GENERAL NOTES
1 & 37
CODE NOTES
PRIMARY APPLICABLE CODES AND STANDARDS - EXISTING BUILDING / RECONSTRUCTION
1. THE DEPARTMENT OF VETERANS AFFAIRS HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION
OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURE.
a. NFPA 101 LIFE SAFETY CODE, LATEST EDITION
b. NFPA 1 FIRE CODE, LATEST EDITION
c. NFPA 70 NATIONAL ELECTRIC CODE (NEC), LATEST EDITION
d. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, LATEST EDITION
e. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13), LATEST REVISION
f. ENERGY POLICY ACT (EPAct), LATEST EDITION
g. VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION
GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL)
h. INTERNATIONAL BUILDING CODE (IBC), LATEST EDITION - ONLY WHEN SPECIFICALLY REFERENCED IN VA
DESIGN DOCUMENTS
i. OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
j. VA PHYSICAL SECURITY DESIGN MANUAL (PSDM), LATEST REVISION
2. THE CONSTRUCTION CLASSIFICATION IS TYPE II (222). THE MINIMUM FIRE RATING FOR ALL LOAD BEARING STRUCTURAL ELEMENTS IS 2 HOURS. IF DURING CONSTRUCTION, ANY DAMAGE TO EXISTING FIREPROOFING IS OBSERVED OR IF DISCOVERED THAT ANY FIRE PROTECTION IS MISSING, THE CONTRACTOR SHALL REPAIR TO
MAINTAIN FULL PROTECTION.
NFPA 101 REVIEW
A. CHAPTER 19 EXISTING HEALTH CARE OCCUPANCIES
a. (19.1.1.1) THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY TO EXISTING BUILDINGS OR PORTIONS
THEREOF CURRENTLY OCCUPIED AS HEALTH CARE OCCUPANCIES.
b. (19.1.5) THE CLASSIFICATION OF HAZARD OF CONTENTS SHALL BE AS DEFINED IN SECTION 6.2.
B. MEANS OF EGRESS - CHAPTER 19 AND CHAPTER 7
a. (19.2.1) ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH CHAPTER 7 & THIS CHAPTER.
b. (19.2.3.6) THE MINIMUM CLEAR WIDTH FOR DOORS IN THE MEANS OF EGRESS FROM HOSPITALS, NURSING
HOMES, LIMITED CARE FACILITIES, PSYCHIATRIC HOSPITAL SLEEPING ROOMS, AND DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL THERAPY, SHALL BE NOT LESS THAN 32 IN.
(810 mm) WIDE.
c. (19.2.6.2.1) THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150
FT, UNLESS OTHERWISE PERMITTED BY 19.2.6.2.2.
d. (19.2.6.2.2) THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1 SHALL BE PERMITTED TO BE
INCREASED BY 50 FT IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED,
AUTOMATIC SPRINKLER SYSTEM.
e. (7.1.3.1) EXIT ACCESS CORRIDORS. CORRIDORS USED AS EXIT ACCESS AND SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 SHALL BE SEPARATED FROM OTHER PARTS OF THE BUILDING BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
• THIS REQUIREMENT SHALL NOT APPLY TO EXISTING BUILDINGS, PROVIDED THAT THE OCCUPANCY
CLASSIFICATION DOES NOT CHANGE.
f. (7.1.5.1) MEANS OF EGRESS SHALL BE DESIGNED AND MAINTAINED TO PROVIDE HEADROOM NOT LESS
THAN 7 FT 6 IN, UNLESS OTHERWISE SPECIFIED BY ANY OF THE FOLLOWING:
• IN EXISTING BUILDINGS, THE CEILING HEIGHT SHALL NOT BE LESS THAN 7 FT FROM THE FLOOR, WITH PROJECTIONS FROM THE CEILING NOT LESS THAN 6 FT 8 IN NOMINAL ABOVE THE FLOOR.
g. (7.2.1.2.3.2) DOOR OPENINGS IN MEANS OF EGRESS SHALL NOT BE LESS THAN 32 IN. IN CLEAR WIDTH.
h. (7.2.1.4.3.2) WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS OF EGRESS SHALL NOT PROJECT MORE
THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY OR A LANDING, UNLESS THE DOOR LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT REQUIRED
BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS TRAVEL..
C. FIRE PROTECTION EQUIPMENT - CHAPTER 19 AND CHAPTER 9
a. THE EXISTING BUILDING IS FULLY PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM.
PROJECT PHASING NOTES
1. DURING THE EXECUTION OF THIS CONTRACT, THE PROJECT AREA WILL BE OCCUPIED AND IN USE. WORK DONE
UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER, STAFF, OR OTHER
BUILDING OCCUPANTS. ALL WORK SHALL BE COORDINATED WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE AND IS SUBJECT TO HIS CONTINUOUS APPROVAL.
2. "NORMAL" WORKING HOURS ON THE POST ARE FROM 8:00 AM TO 4:30 PM, MONDAY THROUGH FRIDAY; HOURS OUTSIDE OF "NORMAL" WORKING HOURS ARE DEFINED AS "OFF HOURS". THE CONTRACTOR SHALL DEVELOP A SCHEDULE OF DEMOLITION, NEW INSTALLATION, AND CHANGEOVER OF THE UTILITY SYSTEMS THAT WILL ALLOW FOR MINIMUM DOWNTIME. THE UTILITY CHANGEOVER SHALL BE SCHEDULED WITH THE VA STAFF DURING "OFF HOURS". THE CONTRACTOR SHALL COORDINATE WITH RADIO SYSTEM PROVIDER AND VA STAFF TO PROVIDE A TEMPORARY MEANS OF TWO-WAY COMMUNICATION DURING THE RADIO SYSTEM OUTAGE.
3. THE CONTRACTOR SHALL DEVELOP AND PRESENT A CONSTRUCTION PLAN AND WORK SCHEDULE WITH ALL PHASING, STAGING, AND SEQUENCING OF WORK FOR APPROVAL PRIOR TO THE COMMENCEMENT AND BEGINNING IMPLEMENTATION OF HIS WORK. THE CONTRACTOR SHALL DETERMINE PRIOR TO SUBMITTING HIS WORK SCHEDULE, THE SPECIFIC TIME AVAILABILITY OF ALL AREAS AND SPACES AND DETERMINE WHAT WORK
MUST BE DONE DURING "OFF HOURS".
4. WITH THE EXCEPTION OF THE BLDG. 37 DISPATCH ROOM, ANY WORK REQUIRED IN OCCUPIED SPACES SHALL BE DONE DURING "OFF HOURS". THE WORK REQUIRED IN THE BLDG. 37 DISPATCH ROOM SHALL BE CLOSELY COORDINATED AND SCHEDULED AHEAD OF TIME WITH THE COR, AS THE ROOM WILL BE OCCUPIED AT ALL TIMES AND WORK WILL NEED TO BE PERFORMED WITH OCCUPANTS IN THE SPACE. ALL WORK, AS REQUIRED TO RETURN EXISTING SYSTEMS TO FUNCTIONALITY, REPLACE CEILING TILES, AND CONSTRUCTION CLEANUP SHALL BE FULLY COMPLETE AND APPROVED BY THE COR PRIOR TO THE END-OF-SHIFT AND BEFORE THE
OPENING OF THE AREA TO STAFF AND OTHER BUILDING OCCUPANTS.
5. WITH THE EXCEPTION OF SIGNIFICANT NOISE GENERATING ACTIVITIES SUCH AS CORE DRILLING, ETC., WORK OUTSIDE OF THE OCCUPIED SPACES, SUCH AS ON THE ROOF, ETC., MAY BE PERFORMED DURING NORMAL
WORKING HOURS.
6. THE WORK REQUIRED UNDER THIS PROJECT SHALL BE COMPLETED IN A MANNER THAT REQURIES A MINIMUM AMOUNT OF DOWN TIME OF THE RADIO SYSTEMS. ALL NEW EQUIPMENT AND WIRING SHALL BE INSTALLED AND READY FOR OPERATION PRIOR TO THE DEMOLITION OF ANY EXISTING RADIO EQUIPMENT. CONTRACTOR SHALL COORDINATE WITH THE VA AND PROVIDE A WRITTEN PLAN OF ACTION FOR THE SYSTEM CHANGEOVER TO THE COR AND ALL RADIO SYSTEM SUBSCRIBERS A MINIMUM OF TWO WEEKS PRIOR TO THE PLANNED CHANGEOVER DATE. DURING DEMOLITION AND CONSTRUCTION, THE CONTRACTOR SHALL FOLLOW INFECTION CONTROL MEASURES FOR CLASS II RENOVATION WORK. DO NOT REMOVE ANY EXISTING RADIO EQUIPMENT UNTIL THE
NEW SYSTEM IS FULLY OPERATIONAL AND PASSES ALL TESTS.
EXIST.
F.E.C.
DF
REF.
DN
UP
DN
S2-2 S2-1
OPERATOR SUITE
SERVER ROOM
WHEELCHAIR
STORAGE
86' TO EXIT
8'
T O
E
XI
T
9'
T O
E
XI
T
47' TO EXIT
40' TO EXIT
33' TO
EXIT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:0
PM
G-102
LIFE SAFETY EGRESS PLANS
1/8" = 1'-0"1 B37 BASEMENT LIFE SAFETY PLAN
1/16" = 1'-0"2 B37 ATTIC/ROOF LIFE SAFETY PLAN
1/8" = 1'-0"3 B1 LEVEL 6 LIFE SAFETY PLAN
1/8" = 1'-0"4 B1 LEVEL 7 LIFE SAFETY PLAN
1/8" = 1'-0"5 B1 LEVEL 8 LIFE SAFETY PLAN
1 & 37
MECH
51002
DN
EXST
ELEV MACH
RM
MECH
51001
51005
EXST
TOWER STAIR
ST1-3
MECH
51003
EXIST MECH
51004
REFER PARTIAL FRAMING
PLAN OF BUILDING 1 TOWER
ROOF TOP FRAMING PLAN
(E) WB 901
(E) WB 903 BELOW
(E
W B
BE
LO
W (E
)W B
2A
(E )W
B9
(E
W B
BE
LO
W (E
)W B
2A
(E )W
B9
(E) WB 901
(E) WB 903 BELOW
(E) B 902
(E) B 902
(E) B 901
(E) B 904(E) B 904
(E) B 903
(E) B 903
(E )B
(E )B
(E )B
A
(E )B
A
TYPICAL NOTE: REFER CONCRETE
BEAM/REBAR REPAIR DETAIL FOR
ALL CONCRETE BEAMS UNDER
THE UPPER FLOOR WHICH ARE IN
NEED OF REPAIRS. ALL
CONCRETE BEAMS SHOWN IN
THIS AREA SHALL BE REPAIRED
(APPROX. 260 LF OF BEAM
REPAIR).
NOTES
1. CONTRACTOR SHALL INSPECT ALL WALLS IN THE TOWER
FOR CRACKS AND FILL WITH EPOXY. PLACE SEALER ON THE
STEM WALL TO PROTECT FROM MOISTURE. THE
APPROXIMATE LENGTH OF ALL CRACKS IS 150 LINEAR FEET.
NOTES:
1. CHIP AROUND THE REBAR W/ CHISEL AND MALLET IF THE CONCRETE
IS LOOSE. ALLOW FOR 1" OF CLEARANCE.
2. SANDBLAST THE RUST FROM THE REBAR W/ THE SANDBLASTING
EQUIPMENT. ENSURE TO READ ALL OPERATION AND SAFETY
INSTRUCTIONS FOR THE SANDBLASTER BEFORE USE.
3. APPLY SEALER TO THE REBAR. COVER THE CONCRETE IN THE
BONDING AGENT. PLACE MORTAR GROATS INTO THE OPEN VOIDS IN
THE CONCRETE
CONCRETE BEAM
(V.I.F.)
(E) BOTTOM
REBAR(S)
SEE NOTE 1
SEE NOTES 2 & 3
CONCRETE BEAM/SLAB OPEN
WHERE OCCURS
V.
I.F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:1
PM
S-101
BLDG 1 STRUCTURAL REPAIR
PLANS (PHASE 1) 1
PH
AS
E
1/8" = 1'-0"1 BUILDING 1 - FIFTH FLOOR/ATTIC PLANS
1/8" = 1'-0"2
BUILDING 1 - TOWER ROOF TOP
FRAMING PLAN
NTS3
CONCRETE BEAM/REBAR REPAIR
DETAIL
GFCI
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
PNL PPM
PNL RADIO
ROOM
T
ED901 2
ED901
ED901
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
ED901
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
ED901
BLDG 1 KEY PLAN
A. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ADJACENT FINAL FINISHES. THE REPAIR WORK SHALL BE DONE TO THE OWNER'S SATISFACTION. ANY EXISTING WALL OR ROOF PENETRATIONS ABANDONED BY THE DEMOLITION WORK SHALL BE FILLED IN.
B. DEMOLITION WORK SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO EXTENT REQUIRED TO
PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED.
C. REMOVE ALL EXISTING ELECTRICAL SYSTEM COMPONENTS, MATERIALS , APPARATUS, AND APPLIANCES WITHIN THE DESIGNATED PROJECT AREA, UNLESS OTHERWISE NOTED. COORDINATE WITH ALL CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED. REMOVAL SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL ASSOCIATED ATTACHMENT/MOUNTING ELEMENTS, ENCLOSURES, SWITCHES, AND UTILITY FEEDS. PATCH BUILDING FINISHES WHERE ELECTRICAL ITEMS ARE REMOVED AND ADJACENT EXISTING FINISH IS TO REMAIN.
D. THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK, PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND OTHER DISPOSITION OF MATERIALS SPECIFIED TO BE SALVAGED. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY
DISCONNECTION OF UTILITY SERVICES.
E. EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED, OR TEMPORARILY REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK.
STRUCTURAL MEMBERS OF CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK FOR INSTALLATION OF ELECTRICAL WORK.
F. UNLESS SPECIFIED OTHERWISE, ALL PIPING, WIRING, CONDUIT, AND OTHER DEVICES ASSOCIATED WITH THE EQUIPMENT NOT RE-USED IN THE NEW WORK AREA SHALL BE COMPLETELY DEMOLISHED AND REMOVED FROM THE OWNER'S PROPERTY. THIS INCLUDES ALL CONCRETE PADS, PIPE, VALVES, FITTINGS, INSULATION, AND ALL HANGERS, INCLUDING THE TOP CONNECTION AND ANY FASTENINGS TO BUILDING STRUCTURAL SYSTEMS. ALL OPENINGS SHALL BE SEALED AFTER REMOVAL OF EQUIPMENT, PIPES, DUCTS, AND OTHER PENETRATIONS IN ROOF, WALLS, FLOORS, IN AN APPROVED MANNER. STRUCTURAL INTEGRITY OF THE BUILDING SYSTEM SHALL BE
MAINTAINED.
GENERAL ELECTRICAL DEMOLITION NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:3
PM
ED101
BLDG 1 ELECTRICAL DEMOLITION
PLANS (PHASE 2)
3/16" = 1'-0"1
B1 LEVEL 6 ELECTRICAL DEMOLITION
PLAN
3/16" = 1'-0"2
B1 LEVEL 7/8 ELECTRICAL DEMOLITION
PLAN
3/16" = 1'-0"3
B1 TOWER ELECTRICAL DEMOLITION
PLAN
KEYED NOTES
EXISTING FIBER DISTRIBUTION HUB TO BE
DEMOLISHED.
EXISTING POWER AMPLIFIERS TO BE DEMOLISHED.2
EXISTING NETWORK SWITCHES TO BE DEMOLISHED.3
EXISTING ONTARIO COUNTY RADIO REPEATER TO BE
REMOVED FOR REPLACEMENT.
PATHWAY FOR EXISTING CABLES FROM ANTENNAS TO
FIBER DISTRIBUTION HUB IN THE RADIO ROOM.
PATHWAY CONTINUES DOWN TO GROUND FLOOR OF
BLDG 1 AND IS ROUTED TO BLDG 37 DISPATCH ROOM
FOR DISTRIBUTION. ALL CABLES SHALL BE REMOVED
FROM THE ROOF ANTENNAS TO THE FIBER
DISTRIBUTION HUB IN THE RADIO ROOM
(APPROXIMATELY 75 LINEAL FEET OF CABLE TO BE
REMOVED). ALL CABLE FROM THE RADIO ROOM TO
BLDG 37 DISPATCH ROOM SHALL BE ABANDONED IN
PLACE.
6 EXISTING RADIO ANTENNA TO BE REMOVED FROM
EXTERIOR WALL. REMOVAL SHALL INCLUDE ALL
ANTENNA, MOUNTING BRACKET, AND CABLE. ALL
EXISTING CABLE PENETRATIONS AND DAMAGE TO
EXTERIOR WALLS CAUSED BY THE REMOVAL OF
MOUNTING BRACKETS SHALL BE PATCHED, REPAIRED,
AND PAINTED TO MATCH ADJACENT FINISH
(APPROXIMATELY 4 SQ-FT OF WALL SURFACE TO BE
REPAIRED AT EACH ANTENNA LOCATION).
PH
AS
E
DN
UP
DN
S2-2 S2-1
1 1
ATTIC
FLAT ROOF
FLAT ROOF
A. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ADJACENT FINAL FINISHES. THE REPAIR WORK SHALL BE DONE TO THE OWNER'S SATISFACTION. ANY EXISTING WALL OR ROOF PENETRATIONS ABANDONED BY THE DEMOLITION WORK SHALL BE FILLED IN.
B. DEMOLITION WORK SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO EXTENT REQUIRED TO
PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED.
C. REMOVE ALL EXISTING ELECTRICAL SYSTEM COMPONENTS, MATERIALS , APPARATUS, AND APPLIANCES WITHIN THE DESIGNATED PROJECT AREA, UNLESS OTHERWISE NOTED. COORDINATE WITH ALL CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED. REMOVAL SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL ASSOCIATED ATTACHMENT/MOUNTING ELEMENTS, ENCLOSURES, SWITCHES, AND UTILITY FEEDS. PATCH BUILDING FINISHES WHERE ELECTRICAL ITEMS ARE REMOVED AND ADJACENT EXISTING FINISH IS TO REMAIN.
D. THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK, PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND OTHER DISPOSITION OF MATERIALS SPECIFIED TO BE SALVAGED. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY
DISCONNECTION OF UTILITY SERVICES.
E. EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED, OR TEMPORARILY REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK.
STRUCTURAL MEMBERS OF CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK FOR INSTALLATION OF ELECTRICAL WORK.
F. UNLESS SPECIFIED OTHERWISE, ALL PIPING, WIRING, CONDUIT, AND OTHER DEVICES ASSOCIATED WITH THE EQUIPMENT NOT RE-USED IN THE NEW WORK AREA SHALL BE COMPLETELY DEMOLISHED AND REMOVED FROM THE OWNER'S PROPERTY. THIS INCLUDES ALL CONCRETE PADS, PIPE, VALVES, FITTINGS, INSULATION, AND ALL HANGERS, INCLUDING THE TOP CONNECTION AND ANY FASTENINGS TO BUILDING STRUCTURAL SYSTEMS. ALL OPENINGS SHALL BE SEALED AFTER REMOVAL OF EQUIPMENT, PIPES, DUCTS, AND OTHER PENETRATIONS IN ROOF, WALLS, FLOORS, IN AN APPROVED MANNER. STRUCTURAL INTEGRITY OF THE BUILDING SYSTEM SHALL BE
MAINTAINED.
GENERAL ELECTRICAL DEMOLITION NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:3
PM
ED102
BLDG 37 ATTIC/ROOF ELECTRICAL
DEMOLITION PLANS (PHASE 2)
1/8" = 1'-0"1
B37 ATTIC/ROOF ELECTRICAL
DEMOLITION PLAN
KEYED NOTES
EXISTING ROOF MOUNTED RADIO ANTENNA TO BE
DEMOLISHED.
EXISTING WALL MOUNTED ANTENNA TO BE
DEMOLISHED.
EXISTING CONDUIT TO BE DEMOLISHED BACK TO
FLOOR PENETRATION IDENTIFIED IN KEYED NOTE #4
(APPROXIMATELY 365 LINEAL FEET OF CONDUIT).
EXISTING CONDUIT FLOOR PENETRATION. ALL WIRING
AND CONDUIT BELOW ATTIC SLAB SHALL BE REMOVED
IN ITS ENTIRETY (APPROXIMATELY 135 LINEAL FEET OF
CABLE).
PH
AS
E
CONDUIT PREVIOUSLY INSTALLED DURING PHASE 1
INSTALLATION TO REMAIN. REFER TO DRAWING E-103
FOR INSTALLATION DETAILS.
GFCI
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
PNL PPM
PNL RADIO
ROOM
(PPM) - (19)
1-#10, 1-#10, 1-#10
3/4"ø EMT
RADIO ROOM
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
117 118 119 120 121 122 123 124 125 126 127 128 1K
1L
1M
1N
1P
1Q
1R
1S
1T
1U
1V
BLDG 1 KEY PLAN
A. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK.
B. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO
MATCH ADJACENT FINAL FINISHES AND REQUIRED FIRE RATING. THE REPAIR WORK SHALL BE DONE TO THE
OWNER'S SATISFACTION.
C. COORDINATE WITH ALL CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED. PATCH BUILDING FINISHES WHERE ELECTRICAL ITEMS ARE REMOVED AND ADJACENT EXISTING FINISH IS TO REMAIN.
D. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, COORDINATION WITH OTHER WORK IN PROGRESS, AND
TIMELY DISCONNECTION OF UTILITY SERVICES.
E. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK
FOR INSTALLATION OF ELECTRICAL WORK.
F. ALL EQUIPMENT SHALL BE PROVIDED WITH A LOCAL DISCONNECT SWITCH FOR MAINTENANCE.
GENERAL ELECTRICAL NEW WORK NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:0
PM
E-101
BLDG 1 ELECTRICAL NEW WORK
PLANS (PHASE 1)
3/16" = 1'-0"1
B1 LEVEL 6 ELECTRICAL NEW WORK
PLAN
3/16" = 1'-0"2
B1 LEVEL 7 ELECTRICAL NEW WORK
PLAN
3/16" = 1'-0"3
B1 LEVEL 8 ELECTRICAL NEW WORK
PLAN
KEYED NOTES
PROVIDE FOUR (4) NEW BASE RADIO STATIONS FOR
CAMPUS SUBSCRIBERS. SUBSCRIBERS INCLUDE FIRE
DEPARTMENT, POLICE DEPARTMENT, ENGINEERING/
MAINTENANCE SHOPS, AND GROUNDS AND
TRANSPORTATION OFFICE. REFER TO "RADIO
EQUIPMENT ELECTRICAL COORDINATION SCHEDULE"
ON SHEET E-601 FOR BASIS OF DESIGN EQUIPMENT
SELECTION AND ADDITIONAL INFORMATION.
PROVIDE NEW 2700W UNINTERRUPTIBLE POWER
SUPPLY SIZED FOR 17 MINUTE RUN TIME. REFER TO
"RADIO EQUIPMENT ELECTRICAL COORDINATION
SCHEDULE" ON SHEET E-601 FOR BASIS OF DESIGN
EQUIPMENT SELECTION AND ADDITIONAL
INFORMATION.
PATHWAY FOR NEW CABLES FROM ANTENNAS TO
BASE RADIO STATIONS ON LEVEL 6. ALL CABLES SHALL
BE CONCEALED IN 3/4" CONDUIT FOR THE ENTIRE RUN
AND SHALL FOLLOW THE PATH OF THE EXISTING
CABLING DOWN TO THE RADIO ROOM (APPROXIMATELY
75 LINEAL FEET OF CABLE AND CONDUIT TO BE
INSTALLED).
PROVIDE NEW NEMA L5-30P RECEPTACLE FOR UPS
POWER SUPPLY.
NEW VERY HIGH FREQUENCY (VHF) OMNIDIRECTIONAL
ANTENNA TO BE INSTALLED ON NON-PENETRATING
TRIPOD MOUNT. SEE 5/E-501 FOR MOUNTING DETAIL,
AND REFER TO "RADIO EQUIPMENT ELECTRICAL
COORDINATION SCHEDULE" ON SHEET E-601 FOR BASIS
OF DESIGN EQUIPMENT SELECTION AND ADDITIONAL
INFORMATION.
6 NEW RECEIVER MULTICOUPLER RACK TO BE
INSTALLED. REFER TO "RADIO EQUIPMENT ELECTRICAL
COORDINATION SCHEDULE" ON SHEET E-601 FOR BASIS
OF DESIGN EQUIPMENT SELECTION AND ADDITIONAL
INFORMATION.
PH
AS
E
REF.
BLDG 37 KEY PLAN
PNL RPEM-BB
OPERATOR SUITE
SERVER ROOM
WHEELCHAIR
STORAGE
(RPEM-BB) - (3)
1-#8, 1-#8, 1-#8
3/4"ø EMT
1 1
A. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK.
B. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO
MATCH ADJACENT FINAL FINISHES AND REQUIRED FIRE RATING. THE REPAIR WORK SHALL BE DONE TO THE
OWNER'S SATISFACTION.
C. COORDINATE WITH ALL CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED. PATCH BUILDING FINISHES WHERE ELECTRICAL ITEMS ARE REMOVED AND ADJACENT EXISTING FINISH IS TO REMAIN.
D. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, COORDINATION WITH OTHER WORK IN PROGRESS, AND
TIMELY DISCONNECTION OF UTILITY SERVICES.
E. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK
FOR INSTALLATION OF ELECTRICAL WORK.
F. ALL EQUIPMENT SHALL BE PROVIDED WITH A LOCAL DISCONNECT SWITCH FOR MAINTENANCE.
GENERAL ELECTRICAL NEW WORK NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:1
PM
E-102
BLDG 37 BASEMENT ELECTRICAL
NEW WORK PLAN (PHASE 1)
1/2" = 1'-0"1
B37 BASEMENT ELECTRICAL NEW
WORK PLAN
KEYED NOTES
PROVIDE THREE (3) NEW DISPATCH CONSOLES AT
EXISTING OPERATOR DESK. MONITOR LOCATIONS TO
BE DETERMINED BASED ON AVAILABLE DESK SPACE. A
FOURTH DISPATCH CONSOLE SHALL BE PROVIDED AT
THE CAMPUS FIRE HOUSE IN BUILDING 16.
COORDINATE WITH VA STAFF TO DETERMINE FINAL
LOCATION OF DISPATCH CONSOLE. REFER TO "RADIO
EQUIPMENT ELECTRICAL COORDINATION SCHEDULE"
ON SHEET E-601 FOR BASIS OF DESIGN EQUIPMENT
SELECTION AND ADDITIONAL INFORMATION.
2 PROVIDE NEW MOTOROLA ASTRO 25 K1 CORE (OR
APPROVED EQUIVALENT) IN EXISTING SERVER RACK.
RACK SHALL HOST THE FOLLOWING ITEMS:
• ARCHIVING INTERFACE SERVER
• LOGGING RECORDER
• FREQUENCY SYNCHRONIZING SERVER
• UNIFIED EVENT MANAGER/CONFIGURATION
MANAGER
• DISPATCH CONTROLLER (X6)
• SHORT-HAUL CONTROL STATION COMBINER
• CONVENTIONAL CHANNEL GATEWAY
PH
AS
E
3 PROVIDE NEW ELECTRICAL CIRCUIT FROM PANEL
RPEM-BB TO THE NEW SERVER RACK EQUIPMENT
(APPROXIMATELY 50 LINEAL FEET OF WIRE AND
CONDUIT; SEE PLAN FOR WIRE AND CONDUIT SIZES).
DN
UP
DN
S2-2 S2-1
ATTIC
FLAT ROOF
FLAT ROOF
3/4"ø EMT
5 5
A. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK.
B. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO
MATCH ADJACENT FINAL FINISHES AND REQUIRED FIRE RATING. THE REPAIR WORK SHALL BE DONE TO THE
OWNER'S SATISFACTION.
C. COORDINATE WITH ALL CONTRACT DOCUMENTS FOR ADDITIONAL SCOPE OF WORK FOR SYSTEMS TO BE REMOVED OR RETAINED TO EXTENT REQUIRED TO PERFORM NEW CONSTRUCTION ACTIVITIES INDICATED. PATCH BUILDING FINISHES WHERE ELECTRICAL ITEMS ARE REMOVED AND ADJACENT EXISTING FINISH IS TO REMAIN.
D. PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, COORDINATION WITH OTHER WORK IN PROGRESS, AND
TIMELY DISCONNECTION OF UTILITY SERVICES.
E. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN, WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK
FOR INSTALLATION OF ELECTRICAL WORK.
F. ALL EQUIPMENT SHALL BE PROVIDED WITH A LOCAL DISCONNECT SWITCH FOR MAINTENANCE.
GENERAL ELECTRICAL NEW WORK NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:1
PM
E-103
BLDG 37 ATTIC/ROOF ELECTRICAL
NEW WORK PLAN (PHASE 1)
1/8" = 1'-0"1
B37 ATTIC/ROOF ELECTRICAL NEW
WORK PLAN
KEYED NOTES
1 PROVIDE NEW GPS ANTENNA MOUNTED TO EXTERIOR
WALL OF BUILDING 37. PROVIDE WALL MOUNTING
BRACKET ON WALL FOR INSTALLATION OF GPS
ANTENNA. REFER TO TYPICAL WALL MOUNTING
BRACKET DETAIL ON SHEET E-501 FOR ADDITIONAL
REQUIREMENTS. ANTENNA SHALL BE MOUNTED TO
BRACKET IN ACCORDANCE WITH ANTENNA
MANUFACTURER REQUIREMENTS.
2 PROVIDE NEW VERY HIGH FREQUENCY (VHF)
OMNIDIRECTIONAL ANTENNA TO BE INSTALLED ON
NON-PENETRATING TRIPOD MOUNT. SEE 5/E-501 FOR
MOUNTING DETAIL, AND REFER TO "RADIO EQUIPMENT
ELECTRICAL COORDINATION SCHEDULE" ON SHEET
E-601 FOR BASIS OF DESIGN EQUIPMENT SELECTION
AND ADDITIONAL INFORMATION.
3 PROVIDE NEW 3/4" EMT CONDUIT FOR RADIO
COMMUNICATION CABLING. NEW CONDUIT SHALL BE
RAN ALONGSIDE THE EXISTING COMMUNICATION
CABLE CONDUIT IN THE ATTIC AS SHOWN.
4 PROVIDE NEW FLOOR PENETRATION FOR COAXIAL
COMMUNICATION CABLING. NEW CABLE SHALL BE
CONCEALED IN 3/4" CONDUIT FOR THE ENTIRE RUN AND
SHALL FOLLOW THE PATH OF THE EXISTING CABLING
DOWN TO THE SERVER ROOM EQUIPMENT IN THE
BASEMENT FLOOR OF BUILDING 37. THE APPROXIMATE
LENGTH OF NEW CABLING AND CONDUIT IS 200'.
PH
AS
E
5 EXISTING CONDUIT FOR EXISTING RADIO ANTENNA
EQUIPMENT TO REMAIN THROUGHOUT PHASE 1.
REFER TO DRAWING ED102 FOR PHASE 2 DEMOLITION
WORK.
LENGTH AS REQUIRED
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL LONGER THAN 915mm (36") SHALL BE
INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY
EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER
TO SPECIFICATION SECTION 13 05 41, SEISMIC
RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS.
LOCKING SQUARE
WASHER & LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
CONDUIT, TYP MINERAL WOOL
(FIRMLY PACKED)
FIRESTOP SEALANT
PER SECTION 07 84 00,
FIRESTOPPING
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT, TYP
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, TYP.FLOOR SLAB,
TYP. STEEL EXPANSION
ANCHOR, TYP
(3/8") MAX
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS
FOR QUANTITY & SIZE
OF CONDUITS
LOCKING SQUARE
WASHER &
LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
UV-INHIBITED
POLYCARBONATE OR HIGH-
DENSITY POLYPROPYLENE
PLASTIC BLOCK, LENGTH AS
REQUIRED
2"
4"
1" 1" 1"2"
1 1/2" TYP
1" 5/ 8"
1/4" DIA.
MOUNTING
HOLES TYP.
OF (4)
BASE CLAMP/
BRACKET
3/8" DIA. HOLE
TYP. OF (6)
3/8" x 5/8" HEX
HEAD BOLT
3/8" LOCK WASHER
3/8" FLAT WASHER &
3/8" LOCK WASHER
1/4" THICK
CU BAR
2'-0" MIN
1/4" DIA.
HOLE TYP
OF (8)
GENERAL NOTES:
1. ALL HARDWARE SHALL BE STAINLESS STEEL.
2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
SECTION
STEEL
EXPANSION
ANCHOR
INSULATOR
3/8" FLAT WASHER
INSTALL BALLAST
UNIFORMLY DISTRIBUTED
OVER ALL PANELS
SUPPORT TUBE
SUPPORT ARM (TYP.)
3'-0" 3'-0"
BASE CLAMP/
BRACKET
GENERAL NOTES:
1. ALL HARDWARE SHALL
BE STAINLESS STEEL.
SECTION
STEEL
EXPANSION
ANCHOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:2
PM
E-501
ELECTRICAL DETAILS
NTS1 CONDUIT TRAPEZE MOUNTING DETAIL
NTS2 FLOOR SLAB PENETRATION DETAIL
NTS3 ROOF CONDUIT SUPPORT DETAIL
NTS4 GROUNDING BAR DETAIL
1 & 37
NTS5
NON-PENETRATION ANTENNA ROOF
MOUNT
NTS6
TYPICAL WALL MOUNTING BRACKET
DETAIL
ARCHIVING
INTERFACE
SERVER
LOGGING
RECORDER
FREQUENCY
SYNCHRONIZING
SERVER
GPS ANTENNA
P25 RADIO
SOFTWARE
UNIFIED EVENT MANAGER (UEM)/
CONFIGURATION MANAGER (CM)
WORKSTATION
CONVENTIONAL
CHANNEL
GATEWAY
DISPATCH
CONTROLLER
(ONTARIO COUNTY)
DISPATCH
CONTROLLER
(ROCHESTER PD)
DISPATCH
CONTROLLER
(LOCAL VHF)
DISPATCH
CONTROLLER
(LOCAL VHF)
DISPATCH
CONTROLLER
(LOCAL VHF)
DISPATCH
CONTROLLER
(LOCAL VHF)
BACKHAUL SWITCH
SHORT-HAUL
CONTROL STATION
COMBINER
ALL-BAND
OMNIDIRECTIONAL
ANTENNA
BLDG 37 IT ROOM
DISPATCH
CONSOLE
DISPATCH
CONSOLE
DISPATCH
CONSOLE
BLDG 37 DISPATCH ROOM
RECEIVER
MULTICOUPLER
VHF
OMNIDIRECTIONAL
ANTENNA
VHF
OMNIDIRECTIONAL
ANTENNA
VHF BASE RADIO
(VA FIRE
DEPARTMENT)
VHF BASE RADIO
(VA POLICE
DEPARTMENT)
VHF BASE RADIO
(VA EMS)
VHF BASE RADIO
(VA GROUND
TRANSPORT)
UPS
BLDG 1 PENTHOUSE
DISPATCH
CONSOLE
BLDG 16 FIRE HOUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CD SUBMISSIONOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD MEP Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architect:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
ThinkForm Design Architects LLC 38 East Broad Street Hopewell, NJ 08525
(855) 821-0274
DESIGN RADIO UPGRADES
CANANDAIGUA VA MEDICAL CENTER
528A5-21-502
09/21/2023 EMW MPL
Structural Engineer:
Leake Engineering, LLC 101 W Eagle Rd. #189 Havertown, PA 19083
(215) 645-4437
G sh or tc ut
-ta rg et s-by -id
\1 Am
4f gx
Kh 1N aH Sg
M M
-W y-
Q cI
T2 U
9e tIJ z\ W at so n En gi ne er in g\ 1-
En gi ne er in g\
\V A\
VA
-2
-D es ig n
R ad io U pg ra de s, C an an da ig ua
\W at so n
D ra w in gs \R ev it\
.0
9.
C an an da ig ua
R ad io U pg ra de s.
rv t
9/
/2
1:
:2
PM
E-601
ELECTRICAL SCHEDULES AND
DIAGRAMS
"PANEL TOTALS" REPRESENT ONLY NEW LOADS TO BE ADDED TO THE EXISTING PANEL.
Notes:
Total Est. Demand Current: 10 A Total Conn. Current: 10 A
Total Est. Demand: 3600 VA Total Conn. Load: 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26 23 24 21 22
19 NEMA L5-30P RECEPTACLE FOR UPS 30 A 1 20
17 1 20 A RECEPTACLE (EXIST) 18
15 1 20 A GLYMATIC G-18 (EXIST) 16
5TH FLOOR AIR COMPRESSOR (EXIST) 15 A 3
1 20 A DDC CONTROL PANEL 5TH FLOOR (EXIST) 14
11 12 9 10
P-1 (EXIST) 15 A 3 3 15 A P-2 (EXIST)
5 6 3 4
AHU-1 (EXIST) 20 A 3 3 20 A EF-1 (EXIST)
CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT
EXISTING PANEL TO REMAIN
Notes:
Enclosure: Type 1 MCB Rating: 125 A Mounting: Surface Wires: 4 Mains Rating: 600 A
Supply From: Phases: 3 Mains Type: MLO Location: RADIO ROOM - Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: PPM
NORMAL POWER SWITCHBOARD - CKT 16
NTS1 RADIO SYSTEM SCHEMATIC DIAGRAM
RADIO EQUIPMENT ELECTRICAL COORDINATION SCHEDULE
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NUMBER DESCRIPTION LOCATION
ELECTRICAL PHYSICAL DATA
NOTES
VOLTAGE
[V] PHASE
FREQUENCY
[HZ]
LOAD
[W] L [IN] W [IN] H [IN]
WEIGHT
[LBS]
MOTOROLA SOLUTIONS VOICE PROCESSING MODEL (VPM), Z2 MINI PC ARCHIVING INTERFACE SERVER B37 IT ROOM 120 1 60 240 16 18 - 2 MOTOROLA SOLUTIONS DL360G10 SERVER, Z2 MINI PC, MONITOR LOGGING RECORDER B37 IT ROOM 120 1 60 1244 - 2 SMITHS INTERCONNECT TRAK8835 FREQUENCY SYNCHRONIZING SERVER B37 IT ROOM 120 1 60 23 - 2 MOTOROLA SOLUTIONS ASTRO K1 CORE P25 RADIO SYSTEM SOFTWARE B37 IT ROOM 120 1 60 3100 21 24 90 520 1
TRAK8835 (INCLUDED WITH FREQ. SYNC. SERVER) GPS ANTENNA B37 ROOF - - - - 82 - - - MOTOROLA SOLUTIONS Z2 MINI PC, MONITOR UNIFIED EVENT MANAGER / CONFIGURATION MANAGER B37 IT ROOM 120 1 60 206 - 2 MOTOROLA SOLUTIONS APX ALL BAND CONSOLETTE DISPATCH CONTROLLER B37 IT ROOM 120 1 60 50 16 18 4 20 2
RFI AMERICAS CS0496-0805-31 SHORT-HAUL CONTROL STATION COMBINER B37 IT ROOM 120 1 60 50 - 2 STI-CO IOAK-QB-A/V/U/C ALL-BAND OMNIDIRECTIONAL ANTENNA B37 ROOF - - - - 36 36 35.5 15
MOTOROLA SOLUTIONS MCG 8000 CONVENTIONAL CHANNEL GATEWAY B37 IT ROOM 120 1 60 48 - 2 MOTOROLA SOLUTIONS MCC 7500E DISPATCH CONSOLE B37 DISPATCH ROOM 120 1 60 180 8 5 2 2
RFI WIRELESS COL51-174 VHF OMNIDIRECTIONAL ANTENNA B1 TOWER ROOF - - - - 29 29 82 24 dBSpectra DSRMC0608AAN RECEIVER MULTICOUPLER B1 RADIO ROOM 120 1 60 15 3
MOTOROLA SOLUTIONS GTR 8000 VHF BASE RADIO B1 RADIO ROOM 120 1 60 435 19 18 5 46 3 LIEBERT GXT5-3000 UNINTERRUPTIBLE POWER SUPPLY (2700W) B1 RADIO ROOM 120 1 60 3600 21 17 4 66
1. SUB-SYSTEM INCLUDES ONE (1) LAN SWITCH, ONE (1) BACKHAUL SWITCH, ONE (1) CORE ROUTER, AND ONE (1) SITE CONTROLLER.
2. MOUNTED IN SERVER RACK LOCATED IN BLDG 37 IT ROOM; POWER SUPPLIED FROM SURGE PROTECTIVE DEVICE
3. MOUNTED IN SERVER RACK LOCATED IN BLDG 1 RADIO ROOM (LEVEL 6); POWER SUPPLIED FROM SURGE PROTECTIVE DEVICE IN THE POWER DISTRIBUTION UNIT.
4. IN ADDITION TO THE EQUIPMENT IDENTIFIED IN THIS SCHEDULE, THE FOLLOWING MOBILE EQUIPMENT SHALL BE PROVIDED (ALL MODEL NUMBER INFORMATION IS FOR BASIS OF DESIGN PURPOSES ONLY):
- FORTY (40) MOTOROLA APX 8000 ALL-BAND PORTABLE RADIOS
- SEVEN (7) MOTOROLA APX 8500 ALL-BAND MOBILE RADIOS
- ONE (1) MOTOROLA APX 8500 BASE STATION
- FIFTY (50) MOTOROLA APX N30 SINGLE BAND PORTABLE TWO-WAY RADIO
- SIX (6) MOTOROLA APX 4500 SINGLE BAND MOBILE RADIOS
- ONE (1) MOTOROLA APX 4500 BASE STATION
NOTES
16 18 16 18
16 18
16 18
16 18
-16 18 2
SMITHS INTERCONNECT
1 & 37
"PANEL TOTALS" REPRESENT ONLY NEW LOADS TO BE ADDED TO THE EXISTING PANEL.
Notes:
Total Est. Demand Current: 9 A Total Conn. Current: 9 A
Total Est. Demand: 3100 VA Total…
This is the start of the file's text. The full file is on GovTribe.