STATE SYSTEM OF HIGHER EDUCATION

COMMONWEALTH OF PENNSYLVANIA

BLOOMSBURG CAMPUS

COLUMBIA COUNTY, PENNSYLVANIA

PROJECT/CONTRACT NO.: S.S.H.E. CWU -78- B

SCRANTON COMMONS HOT WATER HEATER REPLACEMENT

CONSTRUCTION DOCUMENTS

SHEET # SHEET NAME

SHEET INDEX

COVER SHEETCS

PROJECT SITE

PRE-FINAL

DOCUMENTS

JOSH SHAPIRO, GOVERNOR

DR. CHRISTOPHER M. FIORENTINO, CHANCELLOR

DR. JEFFERY L. OSGOOD JR, INTERIM PRESIDENT

L&I

SUBMISSION

VICINITY MAP

PROJECT

AREA

ATON

MARCHETTI

CS

COVER SHEET

CONSTRUCTION

SUBMISSION

PROJECT

LOCATION

STATE SYSTEM OF HIGHER EDUCATION

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

BLOOMSBURG CAMPUS

BLOOMSBURG, COLUMBIA COUNTY, PENNSYLVANIA

09/ 9/ 2025

AS NOTED

S.S.H.E. CWU-78-B

COMMONWEALTH UNIVERSITY

SCRANTON COMMONS- HOT WATER HEATER REPLACEMENT

AS-BUILT

SUBMISSION

PLUMBING LEGENDS, NOTES, & ABBREVIATIONSP001

PLUMBING MECHANICAL ROOM PLANP201

PLUMBING MECHANICAL ROOM PHOTOSP202

P203

PLUMBING DETAILSP801

PLUMBING MECHANICAL ROOM PHOTOS

7/28/2025 7/28/2025 7/28/2025 7/28/2025 7/28/2025 7/28/2025

ELECTRICAL LEGENDS, NOTES, & ABBREVIATIONSE001

ELECTRCIAL MECHANICAL ROOM PLANE201

E801 ELECTRCIAL DETAILS

7/28/2025 7/28/2025 7/28/2025

CONTRACTOR

STAGING

LOCATION

CONTRACTOR

PARKING

REGISTERED

PROFESSIONAL

No.PE-051700-E

ENGINEER

LAWRENCE J. MARCHETTI

EWNO

M

M O

C F O

HTLA

P E

N N S Y L V A N

I A

2025-09-09

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text CONTRACTOR LAY-DOWN AREA AND PARKING NOTES NOTES: 1. CONTRACTOR SHALL COORDINATE ALL DELIVERIES WITH THE UNIVERSITY PROVIDING A MINIMUM OF 48-HOURS PRIOR CONTRACTOR SHALL COORDINATE ALL DELIVERIES WITH THE UNIVERSITY PROVIDING A MINIMUM OF 48-HOURS PRIOR NOTICE. 2. CONTRACTOR PARKING WILL BE LIMITED TO THE TRI-LEVEL GARAGE ADJACENT TO ELWELL HALL. COORDINATE SPECIFICS CONTRACTOR PARKING WILL BE LIMITED TO THE TRI-LEVEL GARAGE ADJACENT TO ELWELL HALL. COORDINATE SPECIFICS WITH UNIVERSITY. 3. CONTRACTOR EQUIPMENT LAYDOWN AND STAGING AREA WILL BE THE COURTYARD BETWEEN SCRANTON COMMONS AND CONTRACTOR EQUIPMENT LAYDOWN AND STAGING AREA WILL BE THE COURTYARD BETWEEN SCRANTON COMMONS AND CARVER HALL ADJACENT TO THE ENTRY INTO THE MECHANICAL ROOM AREA.

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

BLOOMSBURG CAMPUS

BLOOMSBURG, COLUMBIA COUNTY, PENNSYLVANIA

2025-09-09

AS NOTED

S.S.H.E. CWU-78-B

COMMONWEALTH UNIVERSITY

SCRANTON COMMONS- HOT WATER HEATER REPLACEMENT

REGISTERED

PROFESSIONAL

No.PE-051700-E

ENGINEER

LAWRENCE J. MARCHETTI

EWNO

M

M O

C F O

HTLA

P E

N N S Y L V A N

I A

2025-09-09

E001-

ELECTRICAL LEGENDS, ABBREVIATIONS, & NOTES

AutoCAD SHX Text 1-800-242-1776

AutoCAD SHX Text

CALL BEFORE YOU DIG

AutoCAD SHX Text

PENNSYLVANIA ONE CALL SYSTEM, INC.

AutoCAD SHX Text

PA ACT 287 (1974) REQUIRES THREE WORKING

AutoCAD SHX Text

DAYS NOTICE TO UTILITIES BEFORE YOU

AutoCAD SHX Text

EXCAVATE, DRILL OR BLAST

AutoCAD SHX Text 1-800-242-1776

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text L

AutoCAD SHX Text V

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text B

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text Y

AutoCAD SHX Text O

AutoCAD SHX Text U

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

NOTE: : ALL SYMBOLS SHOWN MAY NOT BE APPLICABLE TO THIS PROJECT.

AutoCAD SHX Text

DESIGNATIONS

AutoCAD SHX Text

REVISION AREA

AutoCAD SHX Text

REVISION NUMBER

AutoCAD SHX Text

KEYED NOTE

AutoCAD SHX Text

DEMOLITION KEYED NOTE

AutoCAD SHX Text

POINT OF CONNECTION BETWEEN NEW WORK AND EXISTING WORK

AutoCAD SHX Text

POINT BETWEEN EXISTING WORK TO REMAIN AND EXISTING WORK TO BE REMOVED

AutoCAD SHX Text

EQUIPMENT DESIGNATION EQUIP. DESIGNATION (TOP LINE) EQUIP. NUMBER (BOTTOM LINE)

AutoCAD SHX Text

XXX

AutoCAD SHX Text

XXX

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X-X

AutoCAD SHX Text SECTION DESIGNATION SECTION LETTER/NUMBER (TOP LINE) DRAWING SECTION SHOWN (BOTTOM LINE)

AutoCAD SHX Text

DETAIL DESIGNATION DETAIL LETTER/NUMBER

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

FUSE, SIZE AS INDICATED

AutoCAD SHX Text

FUSED SWITCH

AutoCAD SHX Text

CIRCUIT BREAKER

AutoCAD SHX Text

CIRCUIT BREAKER WITH CURRENT LIMITING FUSE

AutoCAD SHX Text

DRAWOUT AIR CIRCUIT BREAKER

AutoCAD SHX Text

SPACE FOR DRAWOUT AIR CIRCUIT BREAKER

AutoCAD SHX Text

POWER TRANSFORMER

AutoCAD SHX Text

CURRENT TRANSFORMER

AutoCAD SHX Text

RELAY COIL

AutoCAD SHX Text

RELAY CONTACT, NORMALLY OPEN (TYPE A)

AutoCAD SHX Text

RELAY CONTACT, NORMALLY CLOSED (TYPE B)

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text

POTENTIAL TRANSFORMER

AutoCAD SHX Text

MEDIUM VOLTAGE CIRCUIT BREAKER

AutoCAD SHX Text

TIME OVERCURRENT RELAY (PHASE)

AutoCAD SHX Text R

AutoCAD SHX Text 50/51

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

XXXX

AutoCAD SHX Text

PANEL BOARD. AMPACITY AND VOLTAGE AS NOTED

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

ONE LINE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

DATA / PHONE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text F

AutoCAD SHX Text w

AutoCAD SHX Text

AutoCAD SHX Text COMBINATION DATA/TELEPHONE OUTLET, 18"AFF, WITH SINGLE-GANG DEVICE BOX AND 3/4" EMT TO THE ACCESSIBLE CEILING SPACE. NUMBER INDICATES QUANTITY OF CABLE PULLS TO BOX.

AutoCAD SHX Text DATA/TELEPHONE OUTLET, IN FLOOR, WITH SINGLE-GANG DEVICE BOX AND 3/4" EMT TO THE ACCESSIBLE CEILING SPACE

AutoCAD SHX Text FLOOR OUTLET BOX AND TELEPHONE OUTLET WITH CARPET FLANGE AND 3/4" C. TO TELEPHONE BACKBOARD

AutoCAD SHX Text WALL OUTLET BOX AND BLANK PLATE WITH MINIMUM 3/4" C. TO ABOVE ACCESSIBLE FINISHED CEILING (PROVIDE PULL CORD). MOUNTED AT 18" AFF, UNLESS OTHERWISE NOTED

AutoCAD SHX Text WALL OUTLET BOX AND BLANK PLATE WITH MINIMUM 3/4" C. TO ABOVE ACCESSIBLE FINISHED CEILING (PROVIDE PULL CORD). MOUNTED AT 48" AFF, UNLESS OTHERWISE NOTED

AutoCAD SHX Text TELEPHONE WALL OUTLET BOX AND BLANK PLATE WITH MINIMUM 1" C. TO ABOVE ACCESSIBLE FINISHED CEILING (PROVIDE PULL CORD). MOUNTED AT 18" AFF, UNLESS OTHERWISE NOTED

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

208/120V BRANCH CIRCUIT PANELBOARD-FLUSH MOUNTED

AutoCAD SHX Text

208/120V BRANCH CIRCUIT PANELBOARD-SURFACE MOUNTED

AutoCAD SHX Text

480/277V BRANCH CIRCUIT PANELBOARD-FLUSH MOUNTED

AutoCAD SHX Text

480/277V BRANCH CIRCUIT PANELBOARD-SURFACE MOUNTED

AutoCAD SHX Text

MOTOR CONTROL CENTER

AutoCAD SHX Text

PULL BOX

AutoCAD SHX Text

MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOADS

AutoCAD SHX Text

20 AMP DUPLEX RECEPTACLE

AutoCAD SHX Text

20 AMP DOUBLE DUPLEX RECEPTACLE

AutoCAD SHX Text

20 AMP SINGLE RECEPTACLE

AutoCAD SHX Text

MOTOR CONNECTION. NUMBER INDICATES HORSEPOWER

AutoCAD SHX Text

UNFUSED DISCONNECT SWITCH. SIZE AS NOTED

AutoCAD SHX Text

MAGNETIC MOTOR STARTER OR CONTACTOR, AS NOTED

AutoCAD SHX Text

FLOOR OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE

AutoCAD SHX Text

FUSED DISCONNECT SWITCH. SIZE AS NOTED

AutoCAD SHX Text

MOTORIZED DAMPER LOCATION

AutoCAD SHX Text

WALL OUTLET BOX AND 15 AMP CLOCK RECEPTACLE

AutoCAD SHX Text

FLUSH WALL JUNCTION BOX OR JUNCTION BOX ABOVE CEILING

AutoCAD SHX Text

20 AMP DUPLEX RECEPTACLE ON DEDICATED CIRCUIT

AutoCAD SHX Text

EMERGENCY POWER "OFF" BUTTON

AutoCAD SHX Text

VARIABLE FREQUENCY DRIVE

AutoCAD SHX Text

SPECIAL PURPOSE OUTLET

AutoCAD SHX Text

WALL OUTLET BOX AND SPECIAL PURPOSE RECEPTACLE

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

MULTI-OUTLET ASSEMBLY WITH OUTLETS AS INDICATED

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text

XX

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text P

AutoCAD SHX Text J

AutoCAD SHX Text

EPO

AutoCAD SHX Text

MCC

AutoCAD SHX Text R

AutoCAD SHX Text

PB

AutoCAD SHX Text FLOOR OUTLET BOX WITH 20 AMP DUPLEX RECEPTACLE AND DATA/COMPUTER OUTLET WITH CARPET FLANGE

AutoCAD SHX Text FLOOR OUTLET BOX WITH 20 AMP DUPLEX RECEPTACLE AND TELEPHONE OUTLET WITH CARPET FLANGE

AutoCAD SHX Text

FLUSH-MOUNTED WALL OUTLET BOX WITH HARDWIRE POWER FEED TO PREWIRED PARTITION

AutoCAD SHX Text FLUSH-MOUNTED WALL OUTLET BOX AND COVER PLATE WITH BUSHED OPENING FOR DATA/VOICE CABLING.

AutoCAD SHX Text THERMOSTAT CONNECTION. PROVIDE AND INSTALL CONTROL WIRING AND RACEWAY AS REQUIRED BY DIVISION 15

AutoCAD SHX Text

COMBINATION DISCONNECT SWITCH AND MAGNETIC MOTOR CONTROLLER SIZE AS NOTED

AutoCAD SHX Text

MANUAL MOTOR STARTER SWITCH WITH PILOT LIGHT AND OVERLOADS

AutoCAD SHX Text

AHU/EXHAUST FAN SHUT DOWN RELAY (24V DC), MOUNTED ADJACENT TO STARTER

AutoCAD SHX Text

TYPICAL OUTLET NOTATIONS

AutoCAD SHX Text SWITCHED OUTLET, "a"-INDICATES SWITCH CONTROL

AutoCAD SHX Text

PEDESTAL MOUNTED ON BENCH TOP

AutoCAD SHX Text "a"

AutoCAD SHX Text "B"

AutoCAD SHX Text

BELOW FLOOR

AutoCAD SHX Text

"BF"

AutoCAD SHX Text "C"

AutoCAD SHX Text

CEILING MOUNTED

AutoCAD SHX Text

"CLG"

AutoCAD SHX Text

DEDICATED DEVICE ON INDIVIDUAL BRANCH CIRCUIT

AutoCAD SHX Text "D"

AutoCAD SHX Text

EMERGENCY

AutoCAD SHX Text "E"

AutoCAD SHX Text

EXISTING DEVICE/EQUIPMENT

AutoCAD SHX Text "[E]"

AutoCAD SHX Text

FLUSH FLOOR BOX WITH FIRE/SMOKE RATED PENETRATION

AutoCAD SHX Text "F"

AutoCAD SHX Text

GROUND FAULT CIRCUIT INTERRUPTER, PERSONAL PROTECTION

AutoCAD SHX Text

"GFI"

AutoCAD SHX Text

GROUND FAULT PROTECTION OF EQUIPMENT

AutoCAD SHX Text

"GFP"

AutoCAD SHX Text

HORIZONTALLY MOUNTED

AutoCAD SHX Text "H"

AutoCAD SHX Text

"IG"

AutoCAD SHX Text "M"

AutoCAD SHX Text

"PED"

AutoCAD SHX Text

POKE THRU WITH TWO HOUR FIRE/SMOKE RATED PENETRATION

AutoCAD SHX Text

"PT"

AutoCAD SHX Text

SURFACE MOUNTED FLOOR BOX

AutoCAD SHX Text "S"

AutoCAD SHX Text

SURGE PROTECTION RECEPTACLE

AutoCAD SHX Text

"SP"

AutoCAD SHX Text

TAMPER RESISTANT SAFETY RECEPTACLE

AutoCAD SHX Text "T"

AutoCAD SHX Text

TWIST-LOCK

AutoCAD SHX Text

"TL"

AutoCAD SHX Text

WALL MOUNTED DEVICE AT 48" AFF UNLESS OTHERWISE NOTED

AutoCAD SHX Text "W"

AutoCAD SHX Text

"WP"

AutoCAD SHX Text

DIMENSIONED HEIGHT

AutoCAD SHX Text

+XX

AutoCAD SHX Text

GENERAL POWER

AutoCAD SHX Text MOUNTED 6" ABOVE COUNTER OR 42" AFF. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS.

AutoCAD SHX Text ISOLATED GROUND RECEPTACLE WITH SEPARATE GREEN GROUND CONDUCTOR TO ISOLATED GROUND BUS IN PANEL

AutoCAD SHX Text MODULAR FURNITURE SERVICE-PROVIDE FLEXIBLE CONNECTION, COORDINATE EXACT LOCATION WITH FURNITURE PLANS

AutoCAD SHX Text

PEDESTAL MOUNTED WITH TWO HOUR FIRE/SMOKE RATED PENETRATION

AutoCAD SHX Text WEATHERPROOF RECEPTACLE WITH "NRTL" LISTED COVERPLATE FOR WET LOCATION WITH PLUG INSTALLED. MTD. 48" AFF UNLESS OTHERWISE NOTED

AutoCAD SHX Text

VFD

AutoCAD SHX Text ELECTRICAL ABBREVIATIONS AC. ALTERNATING CURRENT ALTERNATING CURRENT A/C. AIR CONDITION AIR CONDITION AFF. ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE A.I.C. AMPERES INTERRUPTING AMPERES INTERRUPTING CAPACITY A.I.D. AL. ALUMINUM AL. ALUMINUM ALUMINUM AMP./A. AMPERE AMPERE ARCH. ARCHITECTURAL ARCHITECTURAL A.R.F. ABOVE RAISED FLOOR ABOVE RAISED FLOOR ASY. ASYMMETRICAL ASYMMETRICAL A.T.C. AUTOMATIC TEMPERATURE AUTOMATIC TEMPERATURE CONTROL A.T.S. AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AUX. AUXILIARY AUXILIARY B.F.C. BELOW FINISHED CEILING BELOW FINISHED CEILING BKR. BREAKER BREAKER BLDG. BUILDING BUILDING BSMT. BASEMENT BASEMENT .C. CENTIGRADE DEGREES CENTIGRADE DEGREES C. CONDUIT CONDUIT CB CIRCUIT BREAKER CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CLOSED CIRCUIT TELEVISION CKT. CIRCUIT CIRCUIT CLG. CEILING CEILING COAX. COAXIAL COAXIAL COL. COLUMN COLUMN CONC. CONCRETE CONCRETE CONDR. CONDUCTOR CONDUCTOR CONST. CONSTRUCTION CONSTRUCTION CONTR. CONTRACTOR CONTRACTOR COORD. COORDINATE COORDINATE CONT. CONTINUATION CONTINUATION C.T. CURRENT TRANSFORMER CURRENT TRANSFORMER CU. COPPER COPPER CU. FT. CUBIC FEET CUBIC FEET CW CLOCKWISE CLOCKWISE DISC. DISCONNECT SWITCH DISCONNECT SWITCH DIV. DIVISION DIVISION DN. DOWN DOWN EA. EACH EACH E.C. ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR E.F. EXHAUST FAN EXHAUST FAN ELEC. ELECTRICAL ELECTRICAL ELEC. CL. ELECTRICAL CLOSET ELECTRICAL CLOSET ELEV/EL. ELEVATION/ELEVATOR ELEVATION/ELEVATOR E.M.T. ELECTRICAL METALLIC TUBING ELECTRICAL METALLIC TUBING ENCL. ENCLOSURE ENCLOSURE ENT. ENTRANCE ENTRANCE EQ. EQUAL EQUAL EQUIP. EQUIPMENT EQUIPMENT E.W. EACH WAY EACH WAY EXT. EXTERNAL/EXTERIOR EXTERNAL/EXTERIOR .F. FAHRENHEIT DEGREES FAHRENHEIT DEGREES F.A. FIRE ALARM FIRE ALARM FC FOOTCANDLE FOOTCANDLE FDN. FOUNDATION FOUNDATION F.E. FIRE EXTINGUISHER FIRE EXTINGUISHER FIN. FINISH/FINISHED FINISH/FINISHED FIXT. FIXTURE FIXTURE FL. FLOOR FLOOR FLA FULL LOAD AMPERES FULL LOAD AMPERES FLEX. FLEXIBLE FLEXIBLE FLUOR. FLUORESCENT FLUORESCENT FT. FEET FEET GA. GAGE/GAUGE GAGE/GAUGE GALV. GALVANIZED GALVANIZED G.C. GENERAL CONTRACTOR GENERAL CONTRACTOR GEN. GENERATOR GENERATOR G.F.C. GROUND FAULT INTERRUPTER GROUND FAULT INTERRUPTER GND. GROUND GROUND G.R.S.C. GALVANIZED RIGID STEEL GALVANIZED RIGID STEEL CONDUIT H.I.A. HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE H.O.A. HAND OFF AUTO HAND OFF AUTO HORIZ. HORIZONTAL HORIZONTAL HP. HORSEPOWER HORSEPOWER H.P.S. HIGH PRESSURE SODIUM HIGH PRESSURE SODIUM HT. HEIGHT HEIGHT HZ. HERTZ HERTZ IMC INTERMEDIATE CONDUIT INTERMEDIATE CONDUIT INC. INCANDESCENT INCANDESCENT INSUL. INSULATION/INSULATED INSULATION/INSULATED ISOL. ISOLATED ISOLATED JB JUNCTION BOX JUNCTION BOX KHZ KILOHERTZ KILOHERTZ KV KILOVOLT KILOVOLT KVA KILOVOLT-AMPERE KILOVOLT-AMPERE KVAR KILOVAR KILOVAR KW KILOWATT KILOWATT KWH KILOWATT HOUR KILOWATT HOUR LAN LOCAL AREA NETWORK LOCAL AREA NETWORK LF LINEAR FEET LINEAR FEET LG LONG LONG LG. LENGTH LENGTH LRA LOCKED ROTOR AMPERES LOCKED ROTOR AMPERES LT LIGHT LIGHT LTG LIGHTING LIGHTING MANUF. MANUFACTURER MANUFACTURER MAX. MAXIMUM MAXIMUM MB MAIN BREAKER MAIN BREAKER M.C. MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR M/C MULTI-CONDUCTOR MAIN MULTI-CONDUCTOR MAIN MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCM THOUSAND CIRCULAR MILLS THOUSAND CIRCULAR MILLS MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MDS DISTRIBUTION SWITCHBOARD DISTRIBUTION SWITCHBOARD MECH. MECHANICAL MECHANICAL MF MAINTENANCE FACTOR MAINTENANCE FACTOR MG MOTOR GENERATOR MOTOR GENERATOR M.L.O. MINIMUM MAIN LUGS ONLY MINIMUM MAIN LUGS ONLY MTD. MOUNTED MIN. MOUNTED MIN. N. NEUTRAL NEUTRAL NC NORMAL CLOSED NORMAL CLOSED N.E.C. NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL NATIONAL ELECTRICAL MANUFACTURING ASSO. NIC NOT IN CONTRACT NOT IN CONTRACT NO NORMALLY OPEN NORMALLY OPEN NO./# NUMBER NUMBER NTS NOT TO SCALE NOT TO SCALE % PERCENT PERCENT PHASE PB PULL BOX PULL BOX P.C. PLUMBING CONTRACTOR PLUMBING CONTRACTOR PNL. PANELBOARD PANELBOARD PRI. PRIMARY PRIMARY PVC POLYVINYLCHLORIDE POLYVINYLCHLORIDE R. RADIUS RADIUS R..S.W. REMOTE CONTROL SWITCH REMOTE CONTROL SWITCH REBAR. REINFORCING BAR REINFORCING BAR REC. RECESSED RECESSED RECEPT. RECEPTACLE RECEPTACLE REQ'D REQUIRED REQUIRED REV. REVISE/REVISION REVISE/REVISION RF RADIO FREQUENCY RADIO FREQUENCY RGS RIGID GALVANIZED STEEL RIGID GALVANIZED STEEL CONDUIT 1/C SINGLE CONDUCTOR SINGLE CONDUCTOR SEC. SECONDARY SECONDARY SECT. SECTION SECTION SEP. SEPARATE SEPARATE SERV. SERVICE SERVICE S.F. SQUARE FEET SQUARE FEET SHT. SHEET SHEET SIG. SIGNAL SIGNAL SK. SKETCH SKETCH SN SOLID NEUTRAL SOLID NEUTRAL SPECS. SPECIFICATIONS SPECIFICATIONS SQ. SQUARE SQUARE S.S. STAINLESS STEEL STAINLESS STEEL STA. STATION STATION SURF. SURFACE SURFACE SUSP. SUSPENDED SUSPENDED SW. SWITCH SWITCH SW'BD SWITCHBOARD SWITCHBOARD SYM. SYMMETRICAL SYMMETRICAL TEL. TELEPHONE TELEPHONE THRU THROUGH THROUGH TRANSF./XFMR TRANSFORMER TRANSFORMER TYP. TYPICAL TYPICAL U.O.C. UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED U.R.F. UNDER RAISED FLOOR UNDER RAISED FLOOR V. VOLTAGE/VOLTS VOLTAGE/VOLTS VERT. VERTICAL VERTICAL VD VOLTAGE DROP VOLTAGE DROP VS. VERSUS VERSUS W/ WITH WITH W/O WITHOUT WITHOUT W/I WROUGHT IRON WROUGHT IRON WD. WIDE WIDE WP WEATHERPROOF WEATHERPROOF

AutoCAD SHX Text THE E.C. SHALL PROVIDE A COMPLETE INSTALLATION OF THE ENTIRE LIGHTING SYSTEM THAT IS IN COMPLIANCE WITH 2018 IECC AS ADOPTED BY PENNSYLVANIA. THIS SHALL INCLUDE ALL FUNCTIONAL TESTING, WRITTEN REPORTS, ETC. AS SPECIFIED IN SECTION C407/C408 OF THIS CODE. EC SHALL RETAIN THE SERVICES OF THE LIGHTING CONTROL VENDOR TO PROVIDE A FACTORY SERVICE TECHNICIAN TO COMMISSION AND PROVIDE WRITTEN REPORTS.

AutoCAD SHX Text

ENERGY CODE & COMMISSIONING NOTE

AutoCAD SHX Text ELECTRICAL GENERAL DEMOLITION NOTES 1. THE WORK OF THIS SECTION INCLUDES FURNISHING OF ALL LABOR, TOOLS, MATERIALS, AND EQUIPMENT THE WORK OF THIS SECTION INCLUDES FURNISHING OF ALL LABOR, TOOLS, MATERIALS, AND EQUIPMENT NECESSARY TO COMPLETE ALL THE DEMOLITION REQUIRED FOR THE PROJECT AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. 2. COOPERATION WITH CONTRACTORS UNDER SEPARATE CONTRACTS IS REQUIRED AND THE WORK DESCRIBED COOPERATION WITH CONTRACTORS UNDER SEPARATE CONTRACTS IS REQUIRED AND THE WORK DESCRIBED HEREIN AND SHOWN ON THE DRAWINGS SHALL BE COORDINATED AS REQUIRED TO FULFILL THE INTENT OF THE CONTRACT. 3. THE INTENT OF THE DEMOLITION DRAWINGS IS TO GIVE THE E.C AN OVERALL SCOPE OF WORK REQUIRED TO THE INTENT OF THE DEMOLITION DRAWINGS IS TO GIVE THE E.C AN OVERALL SCOPE OF WORK REQUIRED TO COMPLETE THIS PROJECT. IT IS NOT INTENDED THAT THE SPECIFICATIONS AND DRAWINGS DESCRIBE AND INDICATE EVERY PIECE OF EQUIPMENT REQUIRED TO BE REMOVED. FOR WHERE ITEMS ARE INTENDED TO BE REMOVED, OR AS REQUIRED FOR THE SATISFACTORY COMPLETION OF THE PROJECT, OR IS CONSIDERED TO BE THE ACCEPTED PRACTICE OF THE TRADE, THEY SHALL BE CONSIDERED TO BE SPECIFIED AND INDICATED. 4. PRIOR TO SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL PRIOR TO SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS PERTAINING TO THIS WORK. THE CONTRACTOR SHALL INVESTIGATE ALL RELOCATIONS AND NEW WORK AND MAKE ALLOWANCES IN HIS BID FOR ALL CHANGES TO THE EXISTING ELECTRICAL SYSTEM WHICH ARE NECESSARY. FAILURE TO COMPLY WITH THIS SHALL NOT CONSTITUTE A REASON FOR PAYMENT OF EXTRA MONIES DURING THE CONSTRUCTION PHASE. CONTRACTOR SHALL SUBMIT A CERTIFIED LETTER WITH HIS BID STATING THAT THIS HAS BEEN DONE. 5. THE CONTRACTOR SHALL DISCONNECT AND REMOVE DEVICES, CONDUIT, WIRE, AND RELATED ELECTRICAL THE CONTRACTOR SHALL DISCONNECT AND REMOVE DEVICES, CONDUIT, WIRE, AND RELATED ELECTRICAL ITEMS AS INDICATED ON THE DRAWINGS OR AS REQUIRED BY THE PROJECT. 6. THE CONTRACTOR SHALL SEAL FLOOR, WALL, AND CEILING OPENINGS WITH THERMO SETTING FIRE RESISTIVE THE CONTRACTOR SHALL SEAL FLOOR, WALL, AND CEILING OPENINGS WITH THERMO SETTING FIRE RESISTIVE COMPOUND AFTER REMOVAL OF CONDUITS. 7. THE CONTRACTOR IS CAUTIONED THAT, WHILE PERFORMING DEMOLITION WORK, CIRCUITRY SERVICING AREAS THE CONTRACTOR IS CAUTIONED THAT, WHILE PERFORMING DEMOLITION WORK, CIRCUITRY SERVICING AREAS OF THE BUILDING OUTSIDE THE WORK AREA MUST REMAIN IN OPERATION. THE CONTRACTOR IS RESPONSIBLE, AT HIS OWN EXPENSE, TO REPAIR ANY SERVICES OR DAMAGES CAUSED BY HIS DEMOLITION WORK. 8. WHEN DISCONNECTING EQUIPMENT FROM EXISTING CIRCUITS, IF EQUIPMENT IS CONNECTED TO THE CIRCUIT WHEN DISCONNECTING EQUIPMENT FROM EXISTING CIRCUITS, IF EQUIPMENT IS CONNECTED TO THE CIRCUIT WHICH MUST REMAIN ACTIVE, THE CIRCUIT CONTINUITY SHALL BE MAINTAINED AS REQUIRED. WIRING FROM CIRCUITS BECOMING COMPLETELY INACTIVE SHALL BE REMOVED BACK TO THE SOURCE OF SUPPLY. 9. PRIOR TO START OF DEMOLITION, CHECK TO DETERMINE THAT POWER, COMMUNICATION SERVICES, ETC., PRIOR TO START OF DEMOLITION, CHECK TO DETERMINE THAT POWER, COMMUNICATION SERVICES, ETC., SUCH AS ELECTRICITY AND TELEPHONE, HAVE BEEN DISCONNECTED AT THE SOURCE OF SUPPLY. 10. THE CONTRACTOR SHALL FURNISH AND ERECT BARRIERS AND MAINTAIN APPROVED DANGER, WARNING, AND THE CONTRACTOR SHALL FURNISH AND ERECT BARRIERS AND MAINTAIN APPROVED DANGER, WARNING, AND "KEEP OUT" SIGNS AT LOCATIONS WHERE THE PLACING OF SUCH SIGNS IS WARRANTED FOR SAFETY OF ALL PERSONNEL NOT WORKING IN THE AREA. 11. DEMOLITION SHALL BE PERFORMED IN SUCH A MANNER AS TO AVOID HAZARDS TO WORKING WITHIN THE DEMOLITION SHALL BE PERFORMED IN SUCH A MANNER AS TO AVOID HAZARDS TO WORKING WITHIN THE FACILITY. WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH ALL MUNICIPAL, STATE, AND FEDERAL RULES, REGULATIONS, CODES, AND LAWS WHICH MAY GOVERN AND APPLY TO THIS WORK. 12. DURING THE DEMOLITION WORK IN THE EFFECTED AREAS, THE BUILDING NON-WORK AREAS MUST BE DURING THE DEMOLITION WORK IN THE EFFECTED AREAS, THE BUILDING NON-WORK AREAS MUST BE PROTECTED FROM DUST, DIRT, AND POSSIBLE WATER DAMAGE TO THE OWNER'S SATISFACTION. ALL AREAS SHALL BE CLEANED AND FREE OF ALL DEBRIS RESULTING FROM THE DEMOLITION WORK ON A DAILY BASIS. 13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE TO EXISTING MATERIALS NOT AFFECTED BY THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE TO EXISTING MATERIALS NOT AFFECTED BY THE DEMOLITION WORK. THE CONTRACTOR SHALL REPAIR OR REPLACE DAMAGED MATERIAL OR EQUIPMENT, AS DIRECTED, AT NO ADDITIONAL COST TO THE OWNER. REPAIRING AND PATCHING OF AREAS SHALL BE DONE BY THE RESPECTIVE TRADE INVOLVED WITH THE DEMOLITION, UTILIZING WORKMEN SKILLED IN THE TRADE INVOLVED WITH THE REPAIR OR REPLACEMENT OF THE MATERIAL IN QUESTION. 14. ALL EQUIPMENT REMOVED DURING DEMOLITION SHALL BE DISPOSED OF OFF SITE, UNLESS OTHERWISE ALL EQUIPMENT REMOVED DURING DEMOLITION SHALL BE DISPOSED OF OFF SITE, UNLESS OTHERWISE NOTED. THE OWNER RESERVES ALL RIGHTS TO CLAIMING MATERIAL REMOVED DURING DEMOLITION. THE CONTRACTOR IS RESPONSIBLE TO REMOVE FROM THE SITE ALL MATERIAL NOT CLAIMED BY THE OWNER. 15. ALL WORK REQUIRING SHUTDOWN OF EXISTING SYSTEMS SHALL BE COORDINATED WITH CONSTRUCTION ALL WORK REQUIRING SHUTDOWN OF EXISTING SYSTEMS SHALL BE COORDINATED WITH CONSTRUCTION MANAGER AND OWNER TO MINIMIZE DISRUPTION OF BUILDING OPERATION. SCHEDULE OF SHUTDOWNS DURING THIS PROJECT WILL BE REQUIRED AND ALL WORK NECESSARY WILL BE INCLUDED AT NO COST TO OWNER.

AutoCAD SHX Text ELECTRICAL GENERAL NOTES 1. THE WORK TO BE DONE UNDER THESE SPECIFICATIONS AND THE DRAWINGS CONSISTS OF PROVIDING ALL THE WORK TO BE DONE UNDER THESE SPECIFICATIONS AND THE DRAWINGS CONSISTS OF PROVIDING ALL EQUIPMENT, MATERIALS, LABOR AND SERVICES, AND PERFORMING ALL OPERATIONS TO COMPLETE THE ELECTRICAL CONSTRUCTION WORK FOR THIS PROJECT. 2. THE TERM "FURNISH" SHALL MEAN TO OBTAIN AND SUPPLY TO THE JOB SITE. THE TERM "INSTALL" THE TERM "FURNISH" SHALL MEAN TO OBTAIN AND SUPPLY TO THE JOB SITE. THE TERM "INSTALL" SHALL MEAN TO FIX IN POSITION AND CONNECT FOR USE. THE TERM "PROVIDE" SHALL MEAN TO FURNISH AND INSTALL. THE TERM "ELECTRICAL WORK" OR "WORK" SHALL MEAN ALL LABOR, MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, SUPERVISION, SERVICES AND OTHER INCIDENTALS NECESSARY FOR COMPLETE AND OPERABLE INSTALLATION. 3. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT, MATERIALS AND LABOR TO PROVIDE A THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT, MATERIALS AND LABOR TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM AS INDICATED ON THE CONSTRUCTION DOCUMENTS. 4. ALL MATERIALS, EQUIPMENT AND INSTALLATIONS SHALL BE IN STRICT ACCORDANCE WITH IBC 2018, NEC ALL MATERIALS, EQUIPMENT AND INSTALLATIONS SHALL BE IN STRICT ACCORDANCE WITH IBC 2018, NEC 2017 ELECTRICAL CODES, NEMA, UL, MANUFACTURER'S RECOMMENDATIONS, STATE CODES, LOCAL CODES, AND ALL AUTHORITIES HAVING JURISDICTION. 5. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES IN FIELD PRIOR TO INSTALLATION OF CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES IN FIELD PRIOR TO INSTALLATION OF ANY WORK. REPORT ALL CONFLICTS IMMEDIATELY TO ARCHITECT AND ENGINEER. 6. THE DRAWINGS DIAGRAMMATICALLY INDICATE THE EXTENT, GENERAL CHARACTER, AND LOCATION OF THE THE DRAWINGS DIAGRAMMATICALLY INDICATE THE EXTENT, GENERAL CHARACTER, AND LOCATION OF THE WORK INCLUDED. ADJUSTMENTS TO MOUNTING HEIGHTS OF WIRING DEVICES TO AVOID STRUCTURAL OR OTHER INTERFERENCES, AND WORK INDICATED BUT HAVING MINOR DETAILS OBVIOUSLY OMITTED SHALL BE PROVIDED WITHOUT EXTRA COST. 7. THE CONTRACTOR SHALL COORDINATE THE ACTUAL LOCATIONS OF ALL EQUIPMENT, CASEWORK, DEVICES, THE CONTRACTOR SHALL COORDINATE THE ACTUAL LOCATIONS OF ALL EQUIPMENT, CASEWORK, DEVICES, FIXTURES. SWITCHES, SENSORS, ETC., WITH THE ARCHITECTURAL DRAWINGS PRIOR TO PERFORMING ANY ROUGH-IN WORK FOR THE WORK. 8. ALL DEVICES SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION AND SHOWN FOR GENERAL WIRING ALL DEVICES SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION AND SHOWN FOR GENERAL WIRING PURPOSES ONLY. ALL DEVICES INDICATED TO BE INSTALLED IN THE SAME LOCATIONS WITH DIFFERENT ELEVATIONS SHALL BE ALIGNED VERTICALLY AND HORIZONTALLY FOR MOUNTING DETAILS OF SWITCHES, OUTLETS, FIRE ALARM AUDIBLE & VISUAL DEVICES, FIRE ALARM PULL STATIONS, SECURITY DEVICES, CARD READERS, THERMOSTATS, SENSORS, ETC., REFER TO ARCHITECTURAL DRAWINGS. COORDINATE ALL LOCATIONS BETWEEN TRADES. 9. ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND APPROVED BY THE ENGINEER OR ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND APPROVED BY THE ENGINEER OR OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION. 10. REMOVE ALL TRASH, DEBRIS, AND DEMOLITION MATERIAL FROM PREMISES AT THE END OF EACH WORK REMOVE ALL TRASH, DEBRIS, AND DEMOLITION MATERIAL FROM PREMISES AT THE END OF EACH WORK DAY. 11. ELECTRICAL PANELS AND DISCONNECTS SHALL HAVE ENGRAVED PLASTIC TAGS WITH VOLTAGE AND ELECTRICAL PANELS AND DISCONNECTS SHALL HAVE ENGRAVED PLASTIC TAGS WITH VOLTAGE AND NAMES ON OUTSIDE OF EQUIPMENT. 12. ALL RECEPTACLES SHALL BE LABELED WITH PANEL AND CIRCUIT NUMBER THAT FEEDS THE RECEPTACLE. ALL RECEPTACLES SHALL BE LABELED WITH PANEL AND CIRCUIT NUMBER THAT FEEDS THE RECEPTACLE. 13. LIGHTING CIRCUIT BREAKERS SHALL BE SPECIFIC TO THE AREA. LIGHTING CIRCUITS SHALL USE BUILDING LIGHTING CIRCUIT BREAKERS SHALL BE SPECIFIC TO THE AREA. LIGHTING CIRCUITS SHALL USE BUILDING COLUMNS, ROOM NAMES, ETC. FOR A MORE ACCURATE LOCATION. 14. THE E.C. SHALL PROVIDE ALL PANELBOARD SCHEDULES IN AN EDITABLE ELECTRONIC FORMAT (MS WORD THE E.C. SHALL PROVIDE ALL PANELBOARD SCHEDULES IN AN EDITABLE ELECTRONIC FORMAT (MS WORD OR EXCEL).

AutoCAD SHX Text

PLUMBING/ELECTRICAL EQUIPMENT CONNECTIONS SCHEDULE

AutoCAD SHX Text

EQUIPMENT / TAG

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

STARTER / VFD

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

FURNISHED BY

AutoCAD SHX Text

INSTALLED BY

AutoCAD SHX Text

FURNISHED BY

AutoCAD SHX Text

INSTALLED BY

AutoCAD SHX Text

SWH-1A & SWH-1B

AutoCAD SHX Text

MC

AutoCAD SHX Text

EC

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-1A & P-1B

AutoCAD SHX Text

MC

AutoCAD SHX Text

EC

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RP-1

AutoCAD SHX Text

MC

AutoCAD SHX Text

EC

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NOTES:

AutoCAD SHX Text 1.

AutoCAD SHX Text THE PLUMBING/ELECTRICAL EQUIPMENT CONNECTIONS SCHEDULE AND ACCOMPANYING NOTES ARE INTENDED TO CLEARLY DEFINE WHICH CONTRACTOR FURNISHES AND INSTALLS STARTERS AND DISCONNECTS AND SHALL BECOME PART OF THE SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER WIRING AND FINAL POWER CONNECTIONS. ALL CONTROL WIRING SHALL BE FURNISHED, INSTALLED AND FINAL CONNECTION BY THE TRADE SUPPLYING THE EQUIPMENT.

AutoCAD SHX Text 2.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL WIRE THROUGH DISCONNECT AND STARTER AND MAKE FINAL POWER CONNECTIONS TO MOTOR.

AutoCAD SHX Text 3.

AutoCAD SHX Text CONTROL WIRING 100V AND LESS, RELAYS, CONTACTS, AND TRANSFORMERS SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR.

AutoCAD SHX Text 4.

AutoCAD SHX Text FLOW & TAMPER SWITCH PROVIDED BY F.P.C. INSTALLED BY E.C. E.C. TO WIRE AND COMPLETE TIE IN TO 4. FIRE ALARM SYSTEM.

AutoCAD SHX Text 5.

AutoCAD SHX Text

5. E.C. TO SUPPLY 120V POWER TO P.C. PROVIDED LOW VOLTAGE TRANSFORMER. P.C. SHALL WIRE FROM 5. LOW VOLTAGE TRANSFORMER TO FAUCETS & VALVES.

AutoCAD SHX Text H:\sm Projects Active\25-070 Bu Scranton Commons - Hw Heater Replacement\Drawings\25-070-E001.dwg , 9/10/2025 1:47 PM , 9/10/2025 1:47 PM9/10/2025 1:47 PM

ISSUED FOR BIDDING - 9/09/2025

COMPRESSOR ROOM

CORRIDOR

MECHANICAL ROOM

COMPRESSOR ROOM

CORRIDOR

MECHANICAL ROOM

S S S S

STATE SYSTEM OF HIGHER EDUCATION

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

BLOOMSBURG CAMPUS

BLOOMSBURG, COLUMBIA COUNTY, PENNSYLVANIA

2025-09-09

AS NOTED

S.S.H.E. CWU-78-B

COMMONWEALTH UNIVERSITY

SCRANTON COMMONS- HOT WATER HEATER REPLACEMENT

REGISTERED

PROFESSIONAL

No.PE-051700-E

ENGINEER

LAWRENCE J. MARCHETTI

EWNO

M

M O

C F O

HTLA

P E

N N S Y L V A N

I A

2025-09-09

E201-

ELECTRICAL MECHANICAL ROOM PLAN

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL - DEMOLITION

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL - NEW WORK

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text ELECTRICAL DEMOLITION NOTES: 1. ALL DEMOLITION TO BE COORDINATED WITH OWNER AND PLUMBING ALL DEMOLITION TO BE COORDINATED WITH OWNER AND PLUMBING CONTRACTOR BEFORE START. 2. PLAN AND COORDINATE DEMOLITION ACTIVITIES WITH UNIVERSITY PLAN AND COORDINATE DEMOLITION ACTIVITIES WITH UNIVERSITY SCHEDULED PLANNED SHUTDOWN OF THE FACILITY. 3. CONTRACTOR TO NOTE THAT THE EXISTING ELECTRICAL FEED TO THE CONTRACTOR TO NOTE THAT THE EXISTING ELECTRICAL FEED TO THE UNIT (WITHIN THE FLOOR) IS TO REMAIN. THEREFORE EXERCISE CAUTION TO PROTECT THIS CONDUIT DURING DEMOLITION.

AutoCAD SHX Text

ELECTRICAL KEYED DEMOLITION NOTES

AutoCAD SHX Text ALL POWER FOR CONTROLS AND MOTOR TO BE DEMO'D BACK TO FLOOR, LEAVING THE RIGID CONDUIT AND COUPLING FOR NEW EQUIPMENT INSTALL

AutoCAD SHX Text EXISTING PANEL TO REMAIN, TRACE CIRCUITS FOR WATER HEATERS BACK TO PANEL TO ENSURE CIRCUIT LABELING IS CORRECT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL KEYED NOTES

AutoCAD SHX Text PULL #12 THHN FROM SOURCE AND INSTALL RIGID CONDUIT FROM THE EXISTING COUPLING, REFER TO DETAIL E801-1 FOR MOUNTING INSTRUCTIONS

AutoCAD SHX Text CIRCULATION PUMP POWER AND CONTROL TO BE COORDINATED WITH PLUMBING CONTRACTOR AND MANUFACTURER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

N/E-LL-65

AutoCAD SHX Text

N/E-LL-67

AutoCAD SHX Text ELECTRICAL GENERAL NOTES: 1. THIS DRAWING SHOWS EQUIPMENT LOCATIONS ONLY. COORDINATE CONDUIT THIS DRAWING SHOWS EQUIPMENT LOCATIONS ONLY. COORDINATE CONDUIT ROUTE IN FIELD WITH OTHER TRADES, EQUIPMENT, AND OWNER. VERIFY EXACT LOCATION AND MOUNTING HEIGHTS WITH OWNER & ARCHITECT PRIOR TO INSTALLATION. 2. COORDINATE ELECTRICAL REQUIREMENTS OF ALL OWNER PROVIDED EQUIPMENT COORDINATE ELECTRICAL REQUIREMENTS OF ALL OWNER PROVIDED EQUIPMENT WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION. 3. SEE ARCHITECTURAL AND VENDOR DRAWINGS PRIOR TO START OF ANY WORK SEE ARCHITECTURAL AND VENDOR DRAWINGS PRIOR TO START OF ANY WORK FOR ADDITIONAL INFORMATION AND REQUIREMENTS. 4. ALL CONDUIT AND PULL-STRING/WIRE TO BE PROVIDED AND INSTALLED BY ALL CONDUIT AND PULL-STRING/WIRE TO BE PROVIDED AND INSTALLED BY E.C.

AutoCAD SHX Text

EXISTING PANEL 'N/E-LL'

AutoCAD SHX Text

PANEL 'N/E-LL'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

N/E-LL-10

AutoCAD SHX Text

WHG

AutoCAD SHX Text 1A

AutoCAD SHX Text

WHG

AutoCAD SHX Text 1B

AutoCAD SHX Text

RP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING XFMR

AutoCAD SHX Text

EXISTING XFMR

AutoCAD SHX Text

ELECTRIC CONDUIT FLOOR PENETRATIONS

AutoCAD SHX Text

ELECTRIC CONDUIT FLOOR PENETRATIONS

AutoCAD SHX Text H:\sm Projects Active\25-070 Bu Scranton Commons - Hw Heater Replacement\Drawings\25-070-E201.dwg , 9/10/2025 1:47 PM , 9/10/2025 1:47 PM9/10/2025 1:47 PM

STATE SYSTEM OF HIGHER EDUCATION

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

BLOOMSBURG CAMPUS

BLOOMSBURG, COLUMBIA COUNTY, PENNSYLVANIA

2025-09-09

AS NOTED

S.S.H.E. CWU-78-B

COMMONWEALTH UNIVERSITY

SCRANTON COMMONS- HOT WATER HEATER REPLACEMENT

REGISTERED

PROFESSIONAL

No.PE-051700-E

ENGINEER

LAWRENCE J. MARCHETTI

EWNO

M

M O

C F O

HTLA

P E

N N S Y L V A N

I A

2025-09-09

E801-

ELECTRICAL DETAILS

AutoCAD SHX Text

EXIT SIGNS

AutoCAD SHX Text

HIGHEST CIRCUIT BREAKER IN PANELBOARDS, DISCONNECT SWITCHES, STARTERS.

AutoCAD SHX Text

ELECTRICAL RECEPTACLES IN MECHANICAL/ELECTRICAL ROOMS

AutoCAD SHX Text

LIGHT SWITCHES, DIMMER SWITCHES, MANUAL MOTOR STARTERS, WALL MOUNTED TELEPHONE.

AutoCAD SHX Text

ELECTRIC SWITCHES AT COUNTER

AutoCAD SHX Text ELECTRICAL RECEPTACLES (U.O.N.), COMMUNICATIONS/DATA OUTLETS (U.O.N.), CATV OUTLETS (U.O.N.), TELEPHONE OUTLETS (U.O.N.)

AutoCAD SHX Text

FINISHED FLOOR

AutoCAD SHX Text

2 INCHES ABOVE TOP OF DOOR TO BOTTOM

AutoCAD SHX Text 6'-0"

AutoCAD SHX Text

6" ABOVE BACKSPLASH ON COUNTER

AutoCAD SHX Text 4'-6"

AutoCAD SHX Text 4'-0"

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text 0'-0"

AutoCAD SHX Text NOTES THE MOUNTING HEIGHTS SHOWN SHALL GENERALLY BE DIMENSIONED TO THE MID-LINE OF A GIVEN DEVICE. EXACT DEVICE MOUNTING HEIGHTS SHALL BE WITHIN THE SPECIFIC REACH/MOUNTING HEIGHT LIMITS SPECIFIED IN THE LATEST REVISION OF THE ADA GUIDELINES AND THE LATEST ADOPTED REVISION OF ICC/ANSI A117.1, SPECIFICALLY FIRE ALARM DEVICES, CONTROLS, OPERATING MECHANISMS AND HARDWARE, INCLUDING ELECTRICAL OUTLETS AND SWITCHES THAT CONTROL LIGHTING, VENTILATION, ETC.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

MOUNTING HEIGHT DETAIL

AutoCAD SHX Text

NONE

AutoCAD SHX Text

PP1-1

AutoCAD SHX Text

PP1-2

AutoCAD SHX Text

PP1-4

AutoCAD SHX Text LABEL ALL RECEPTACLES AND SWITCHES WITH PANEL DESIGNATION AND CIRCUIT NUMBER. LABEL SHALL BE BRADY- B483 OR APPROVED EQUAL

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

TYPICAL RECEPTACLE LABELING REQUIREMENTS

AutoCAD SHX Text

NONE

AutoCAD SHX Text

RIGID CONDUIT (EMT OR GRSC)

AutoCAD SHX Text

PROVIDE RIGID CONDUIT (EMT OR GRSC) OUT OF PANELBOARD IN ELECTRICAL ROOMS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

TYPICAL BRANCH CIRCUIT CONDUIT & WIRING

AutoCAD SHX Text

NONE

AutoCAD SHX Text

TYPICAL JUNCTION BOX ABOVE ACCESSIBLE CEILING

AutoCAD SHX Text USE EMT OR GRSC WHEN RUNNING SURFACE MOUNTED ON WALLS OR NEW CONSTRUCTION LIFE SAFETY / CRITICAL BRANCH POWER CIRCUIT

AutoCAD SHX Text

TYPICAL OUTLET IN STUDDED PARTITION

AutoCAD SHX Text

PANELBOARD

AutoCAD SHX Text TYPICAL SURFACE MOUNTED OUTLET OR SURFACE / CONCEALED LIFE SAFETY / CRITICAL BRANCH OUTLET

AutoCAD SHX Text

TYPICAL MC CABLE RUN CONCEALED IN STUDDED PARTITION

AutoCAD SHX Text MC CABLE RUN ABOVE ACCESSIBLE CEILINGS AND IN STUDDED PARTITIONS. RUN PARALLEL AND PERPENDICULAR TO BUILDING LINES AND SUPPORT PER SPECIFICATIONS.

AutoCAD SHX Text NOTES: ALL CONDUITS SHALL BE CONCEALED ABOVE CEILINGS OR IN WALLS AND FLOORS. CONDUIT RUNS IN FLOORS SHALL BE GRSC. HOME RUNS SHALL BE IN RIGID CONDUIT (EMT OR GRSC) EXCEPTION: PROVIDE GRSC RIGID CONDUIT IN ALL UNFINISHED ROOMS, MECHANICAL SPACES, LOADING DOCKS, GARAGE AREAS, ETC. EMT= ELECTRICAL MATALLIC TUBING GRSC= GALVANIZED RIGID STEEL CONDUIT SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. THIS DETAIL APPLIES TO ALL BRANCH CIRCUITS IN COMMON AREAS. LIFE SAFETY CIRCUITS SHALL BE INSTALLED IN CONDUIT AND BE KEPT ENTIRETY SEPARATED AND WIRED IN ACCORDANCE WITH NEC 700.

AutoCAD SHX Text

NEW DISCONNECT SWITCH

AutoCAD SHX Text

UNISTRUT TO CEILING

AutoCAD SHX Text

EXISTING 3/4" CONDUIT

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

DISCONNECT SWITCH FOR WATER HEATER

AutoCAD SHX Text

NONE

AutoCAD SHX Text NOTES: 1. COORDINATE WITH PLUMBING CONTRACTOR BEFORE INSTALLATION FOR EXACT COORDINATE WITH PLUMBING CONTRACTOR BEFORE INSTALLATION FOR EXACT LOCATION AND REQUIREMENTS

AutoCAD SHX Text

MC CABLE TO CIRC PUMP AND CONTROLS

AutoCAD SHX Text

EXISTING 3/4" CONDUIT

AutoCAD SHX Text

NEW DISCONNECT SWITCH

AutoCAD SHX Text

UNISTRUT TO CEILING

AutoCAD SHX Text

MC CABLES TO CIRC PUMP AND CONTROLS

AutoCAD SHX Text

EXISTING 3/4" CONDUIT

AutoCAD SHX Text H:\sm Projects Active\25-070 Bu Scranton Commons - Hw Heater Replacement\Drawings\25-070-E801.dwg , 9/10/2025 1:47 PM , 9/10/2025 1:47 PM9/10/2025 1:47 PM

STATE SYSTEM OF HIGHER EDUCATION

Scale:

Date:

Project/Contract No.

Drawn By:

Checked By:

Drawing No.

Title:

Submitted:

Authorized By:

Reviewed By:

Submitted:

Description DescriptionDateDate

System Representative:

Construction Manager:

Consultant:

Professional:

BLOOMSBURG CAMPUS

BLOOMSBURG, COLUMBIA COUNTY, PENNSYLVANIA

2025-09-09

AS NOTED

S.S.H.E. CWU-78-B

COMMONWEALTH UNIVERSITY

SCRANTON COMMONS- HOT WATER HEATER REPLACEMENT

REGISTERED

PROFESSIONAL

No.PE-051700-E

ENGINEER

LAWRENCE J. MARCHETTI

EWNO

M

M O

C F O

HTLA

P E

N N S Y L V A N

I A

2025-09-09

P001SA

LM

PLUMBING LEGENDS, ABBREVIATIONS, & NOTES

AutoCAD SHX Text PLUMBING ABBREVIATIONS AFF ABOVE FINISH FLOOR ABOVE FINISH FLOOR AP ACCESS PANEL ACCESS PANEL AWD ACID WASTE DRAINAGE ACID WASTE DRAINAGE BFF BELOW FINISHED FLOOR BELOW FINISHED FLOOR BFP BACKFLOW PREVENTER BACKFLOW PREVENTER CAP CAPACITY CAPACITY CI CAST IRON CAST IRON CLG CEILING CEILING CO CLEAN OUT CLEAN OUT CONC CONCRETE CONCRETE CONN CONNECTION CONNECTION CORR CORRIDOR CORRIDOR COTG CLEAN OUT TO GRADE CLEAN OUT TO GRADE CTR CONTRACTOR CONTRACTOR CW DOMESTIC COLD WATER DOMESTIC COLD WATER DEG F DEGREES FAHRENHEIT DEGREES FAHRENHEIT DIA DIAMETER DIAMETER DN DOWN DOWN DS DOWN SPOUT DOWN SPOUT DWG DRAWING DRAWING [E] EXISTING TO REMAIN EXISTING TO REMAIN EA EACH EACH [ED] EXISTING TO BE DEMOLISHED EXISTING TO BE DEMOLISHED ELEC ELECTRIC ELECTRIC [ER] EXISTING TO BE RELOCATED EXISTING TO BE RELOCATED EST ESTUCHEON ESTUCHEON EWC LECTRIC WATER COOLER LECTRIC WATER COOLER FAI FRESH AIR INLET FRESH AIR INLET FD FLOOR DRAIN FLOOR DRAIN FIN FINISH FINISH FHC FIRE HOSE CABINET FIRE HOSE CABINET FL FLOOR FT FEET FLOOR FT FEET GC GENERAL CONTRACTOR GENERAL CONTRACTOR GEN GENERAL GENERAL GPH GALLONS PER HOUR GALLONS PER HOUR GPM GALLONS PER MINUTE GALLONS PER MINUTE GV GATE VALVE GATE VALVE GLV GLOBE VALVE GLOBE VALVE HB HOSE BIBB HOSE BIBB HW DOMESTIC HOT WATER DOMESTIC HOT WATER HWR DOMESTIC HOT WATER RECIRC DOMESTIC HOT WATER RECIRC IE INVERT ELEVATION INVERT ELEVATION ID INDIRECT WASTE INV INVERT INDIRECT WASTE INV INVERT LAV LAVATORY LAVATORY MAX MAXIMUM MAXIMUM MECH MECHANICAL MECHANICAL MFR MANUFACTURER MANUFACTURER MH MANHOLE MIN MINIMUM MANHOLE MIN MINIMUM MR MOP RECEPTOR NO NUMBER MOP RECEPTOR NO NUMBER NTS NOT TO SCALE NOT TO SCALE OPG OPENING OPENING PIV POST INDICATOR VALVE POST INDICATOR VALVE PLB PLUMBING PLUMBING PRV PRESSURE REDUCING VALVE PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH RD ROOF DRAIN ROOF DRAIN RET RETURN RETURN RV PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE RWC RAINWATER CONDUCTOR RAINWATER CONDUCTOR SAN SANITARY SANITARY SCV SWING CHECK VALVE SWING CHECK VALVE SPKR SPRINKLER SPRINKLER SQ FT SQUARE FEET FT SQUARE FEET SS STAINLESS STEEL STAINLESS STEEL STL STEEL STEEL STR STRAINER ST STORM STRAINER ST STORM TYP TYPICAL TYPICAL TW DOMESTIC TEMPERED WATER DOMESTIC TEMPERED WATER UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED UR URINAL URINAL VA VALVE VALVE VOL VOLUME VOLUME VS VENT STACK VENT STACK VTR VENT THRU FOOF VENT THRU FOOF WC WATER CLOSET WATER CLOSET WH WALL HYDRANT WALL HYDRANT W WASTEWASTE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

PLUMBING SYMBOLS - GENERAL

AutoCAD SHX Text

NEW CONNECTION

AutoCAD SHX Text C.O.

AutoCAD SHX Text

CLEAN-OUT (EXPOSED)

AutoCAD SHX Text G

AutoCAD SHX Text T.W.

AutoCAD SHX Text

FLOW IN DIRECTION OF ARROW

AutoCAD SHX Text H.W.R.

AutoCAD SHX Text

RISE OUT OF TEE

AutoCAD SHX Text H.W.

AutoCAD SHX Text

DROP OUT OF TEE

AutoCAD SHX Text C.W.

AutoCAD SHX Text

RISER UP (ELBOW)

AutoCAD SHX Text I.D.

AutoCAD SHX Text

RISER DOWN (ELBOW)

AutoCAD SHX Text V.P.

AutoCAD SHX Text

CONNECTION OUT OF SIDE

AutoCAD SHX Text R.W.C.

AutoCAD SHX Text

CONNECTION OUT OF BOTTOM

AutoCAD SHX Text S.W.

AutoCAD SHX Text

CONNECTION OUT OF TOP

AutoCAD SHX Text

SAN.

AutoCAD SHX Text

DROP OR RISE

AutoCAD SHX Text

HIGH

AutoCAD SHX Text

LOW

AutoCAD SHX Text

CLEAN-OUT (IN FLOOR)

AutoCAD SHX Text C.O.

AutoCAD SHX Text

RUNNING TRAP

AutoCAD SHX Text R.T.

AutoCAD SHX Text

PIPE ANCHOR

AutoCAD SHX Text

PIPE GUIDE

AutoCAD SHX Text

EXPANSION JOINT

AutoCAD SHX Text

EXPANSION LOOP

AutoCAD SHX Text S.A.

AutoCAD SHX Text

"P" TRAP

AutoCAD SHX Text

FRESH AIR INLET

AutoCAD SHX Text F.A.I.

AutoCAD SHX Text

ACCESS PANEL

AutoCAD SHX Text A.P.

AutoCAD SHX Text

WALL HYDRANT NON-FREEZE

AutoCAD SHX Text W.H.

AutoCAD SHX Text

FLOOR DRAIN TRAPPED

AutoCAD SHX Text F.D.

AutoCAD SHX Text

ROOF DRAIN/OVERFLOW DRAIN

AutoCAD SHX Text R.D.

AutoCAD SHX Text

ABBREVIATION

AutoCAD SHX Text

AP

AutoCAD SHX Text

SA(A)

AutoCAD SHX Text C.O.

AutoCAD SHX Text C.O.

AutoCAD SHX Text

PITCH DOWN - IN DIRECTION OF ARROW

AutoCAD SHX Text

SHOCK ABSORBER- (A) INDICATES SIZE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

ABBREVIATION

AutoCAD SHX Text

SAN.

AutoCAD SHX Text

STORMWATER DRAIN PIPE

AutoCAD SHX Text S.W.

AutoCAD SHX Text R.W.C.

AutoCAD SHX Text

VENT PIPE

AutoCAD SHX Text V.P.

AutoCAD SHX Text

LOW PRESSURE STEAM

AutoCAD SHX Text

LPS

AutoCAD SHX Text

COLD WATER

AutoCAD SHX Text C.W.

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text H.W.

AutoCAD SHX Text

HOT WATER RETURN

AutoCAD SHX Text H.W.R.

AutoCAD SHX Text

TEMPERED WATER

AutoCAD SHX Text T.W.

AutoCAD SHX Text

GAS

AutoCAD SHX Text G

AutoCAD SHX Text

AIR

AutoCAD SHX Text A

AutoCAD SHX Text

SW

AutoCAD SHX Text

RWC

AutoCAD SHX Text

LPS

AutoCAD SHX Text

TW

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

PLUMBING SYMBOLS - PIPING

AutoCAD SHX Text

GREASE/OIL WASTE

AutoCAD SHX Text

GOW.

AutoCAD SHX Text

SAN

AutoCAD SHX Text

GOW

AutoCAD SHX Text

LOW PRESSURE CONDENSATE

AutoCAD SHX Text

LPC

AutoCAD SHX Text

LPC

AutoCAD SHX Text

SOIL OR WASTE PIPE - SANITARY

AutoCAD SHX Text

RAIN WATER CONDUCTOR AT CEILING

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

ABBREVIATION

AutoCAD SHX Text

GATE VALVE

AutoCAD SHX Text G.V.

AutoCAD SHX Text

GLOBE VALVE

AutoCAD SHX Text G.B.

AutoCAD SHX Text

SWING CHECK VALVE

AutoCAD SHX Text S.C.V.

AutoCAD SHX Text

NON-SLAM CHECK VALVE

AutoCAD SHX Text N.C.V.

AutoCAD SHX Text

PRESSURE REDUCING VALVE

AutoCAD SHX Text P.R.V.

AutoCAD SHX Text

PRESSURE RELIEF VALVE

AutoCAD SHX Text R.V.

AutoCAD SHX Text

VALVE ON RISER

AutoCAD SHX Text

GAS COCK

AutoCAD SHX Text G.C.

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

STR.

AutoCAD SHX Text

THERMOMETER WELL

AutoCAD SHX Text

TH.W.

AutoCAD SHX Text

BACKWATER VALVE

AutoCAD SHX Text B.W.V.

AutoCAD SHX Text

PLUMBING SYMBOLS - VALVES

AutoCAD SHX Text

BALL VALVE

AutoCAD SHX Text B.V.

AutoCAD SHX Text

MAXIMUM HANGER SPACING PER IPC

AutoCAD SHX Text

ITEM

AutoCAD SHX Text

MAXIMUM HORIZONTAL SPACING (FT.)

AutoCAD SHX Text

MAXIMUM VERTICAL SPACING (FT.)

AutoCAD SHX Text

ABS PIPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ALUMINUM TUBING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BRASS PIPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CAST IRON

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

COPPER OR COPPER-ALLOY PIPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

COPPER OR COPPER-ALLOY TUBING 1 1/4" DIAMETER OR SMALLER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

COPPER OR COPPER-ALLOY TUBING 1 1/2" DIAMETER OR LARGER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CROSS-LINKED POLYETHYLENE (PEX) PIPE

AutoCAD SHX Text

2.67 (32 INCHES)

AutoCAD SHX Text

AutoCAD SHX Text CROSS-LINKED POLYETHYLENE/ALUMINU,M/CORSS-LINKED POLYETHYLENE (PEX-AL-PEX) PIPE (PEX) PIPE

AutoCAD SHX Text

2.67 (32 INCHES)

AutoCAD SHX Text

AutoCAD SHX Text

CPVC PIPE OR TUBING, 1" OR SMALLER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CPVC PIPE OR TUBING, 1 1/4" OR LARGER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

STEEL PIPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PB PIPE OR TUBING

AutoCAD SHX Text 2.67

AutoCAD SHX Text

AutoCAD SHX Text

POLYETHYLENE/ALUMINUM/POLYETHYKENE (PE-AL-PE) PIPE

AutoCAD SHX Text 2.67

AutoCAD SHX Text

AutoCAD SHX Text

POLYPROPYLENE (PP) PIPE OR TUBING 1" OR SMALLER

AutoCAD SHX Text 2.67

AutoCAD SHX Text

AutoCAD SHX Text

POLYPROPYLENE (PP) PIPE OR TUBING 1 1/4" OR LARGER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PVC PIPE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

STAINLESS STEEL DRAINAGE SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NOTES: :

AutoCAD SHX Text 1.

AutoCAD SHX Text

PIPE HANGERS SHALL ENCIRCLE PIPE INSULATION.

AutoCAD SHX Text 2.

AutoCAD SHX Text PROVIDE MAXIMUM HANGER SPACING AS PER THE SCHEDULE ABOVE OF PER SPECIFICATIONS WHICH EVER IS MORE STRINGENT.

AutoCAD SHX Text

DESIGNATIONS

AutoCAD SHX Text

REVISION AREA

AutoCAD SHX Text

REVISION NUMBER

AutoCAD SHX Text

KEYED NOTE

AutoCAD SHX Text

DEMOLITION KEYED NOTE

AutoCAD SHX Text

POINT OF CONNECTION BETWEEN NEW WORK AND EXISTING WORK

AutoCAD SHX Text

POINT BETWEEN EXISTING WORK TO REMAIN AND EXISTING WORK TO BE REMOVED

AutoCAD SHX Text

EQUIPMENT DESIGNATION EQUIP. DESIGNATION (TOP LINE) EQUIP. NUMBER (BOTTOM LINE)

AutoCAD SHX Text

XXX

AutoCAD SHX Text

XXX

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X-X

AutoCAD SHX Text SECTION DESIGNATION SECTION LETTER/NUMBER (TOP LINE) DRAWING SECTION SHOWN (BOTTOM LINE)

AutoCAD SHX Text

DETAIL DESIGNATION DETAIL LETTER/NUMBER

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

NOTE: : ALL SYMBOLS SHOWN MAY NOT BE APPLICABLE TO THIS PROJECT.

AutoCAD SHX Text PLUMBING GENERAL REQUIREMENTS THESE NOTES SHALL APPLY TO ALL DRAWINGS: A. GENERAL PLUMBING NOTES GENERAL PLUMBING NOTES 1. PROVIDE ALL LABOR AND MATERIALS NEEDED FOR A COMPLETE AND PROVIDE ALL LABOR AND MATERIALS NEEDED FOR A COMPLETE AND PROPERLY OPERATIONAL PLUMBING SYSTEM. 2. THE DRAWINGS AS PREPARED ARE DIAGRAMMATIC BUT SHALL BE THE DRAWINGS AS PREPARED ARE DIAGRAMMATIC BUT SHALL BE FOLLOWED AS CLOSELY AS CONSTRUCTION OF THE PROJECT AND THE WORK OF THE TRADES WILL PERMIT. EQUIPMENT LOCATIONS INDICATED ARE APPROXIMATE. COORDINATE EXACT LOCATIONS AND REQUIRED CLEARANCES WITH EQUIPMENT SUPPLIER AND ALL TRADES PRIOR TO INSTALLATION. DO NOT SCALE LOCATION DIMENSIONS FROM THESE DRAWINGS. 3. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING AND VERIFYING ALL THE CONTRACTOR IS RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS AND DIMENSIONS AND FOR COORDINATION OF HIS WORK WITH THAT OF OTHER TRADES. PERFORM WORK IN AN ORDERLY MANNER AND WITH THE LEAST POSSIBLE INTERFERENCE. 4. ALL CONTRACTORS SHALL EXAMINE THE SITE AND REVIEW THE DRAWINGS ALL CONTRACTORS SHALL EXAMINE THE SITE AND REVIEW THE DRAWINGS AND SPECIFICATIONS PRIOR TO SUBMITTING A PROPOSAL. 5. CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING UTILITIES IN FIELD PRIOR TO STARTING WORK. 6. WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND OWNER. 7. PERFORM ALL WORK IN ACCORDANCE WITH THE PENNSYLVANIA UNIFORM PERFORM ALL WORK IN ACCORDANCE WITH THE PENNSYLVANIA UNIFORM CONSTRUCTION CODE, THE OWNERS INSURANCE UNDERWRITERS, THE INTERNATIONAL PLUMBING CODE, THE PENNSYLVANIA DEPARTMENT OF LABOR & INDUSTRY CODES, LOCAL CODES, THE NFPA CODE AND ANY OTHER AUTHORITIES HAVING JURISDICTION. PROVIDE OWNER WITH CERTIFICATES OF INSPECTION. 8. ALL FITTINGS, VALVES, PIPING, FIXTURES, SOLDERS, AND FLUXES USED ALL FITTINGS, VALVES, PIPING, FIXTURES, SOLDERS, AND FLUXES USED IN POTABLE WATER SYSTEMS SHALL MEET THE REQUIREMENTS OF SECTION 1147 OF THE EPA SAFE DRINKING WATER ACT, EFFECTIVE IN 2014, WITH A WEIGHTED AVERAGE OF 0.25% LEAD ACROSS THE WETTED SURFACES OF PIPES, FITTINGS, AND FIXTURES AND 0.2% LEAD FOR SOLDER AND FLUX. PLUMBING PRODUCTS SHALL BE PROVIDED WITH THIRD PARTY CERTIFICATION TO NSF 372, NSF 61 ANNEX G FOR "LEAD FREE" DESIGNATION. 9. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN. CONTRACTOR SHALL PROTECT THE IN-SLAB PIPING FROM CORROSION AND STRESS AND STRAIN TO CONFORM. 10. ALL MATERIALS, EQUIPMENT, AND DEVICES SHALL, AS A MINIMUM, MEET ALL MATERIALS, EQUIPMENT, AND DEVICES SHALL, AS A MINIMUM, MEET THE REQUIREMENTS OF UL WHERE UL REQUIREMENTS ARE ESTABLISHED FOR THOSE ITEMS. ALL ITEMS SHALL BE LISTED AND LABELED BY UL AS SUITABLE FOR THE PURPOSE USED. 11. ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE NEW UNLESS NOTED OTHERWISE AND SHALL BE CURRENT PRODUCTS BY MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. 12. ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED WITHOUT RUST, SCRATCHES, OR DENTS. 13. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTIONS AND PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTIONS AND ACCEPTANCE FROM THE AUTHORITY HAVING JURISDICTION. B. COORDINATION REQUIREMENTS COORDINATION REQUIREMENTS 1. COORDINATE LOCATION AND INSTALLATION OF PLUMBING WORK WITH COORDINATE LOCATION AND INSTALLATION OF PLUMBING WORK WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE COMPLETELY RESOLVED BY CONTRACTOR IN ACCORDANCE WITH RECOMMENDATIONS OF THE CONSTRUCTION MANAGER. 2. COORDINATE FINAL LOCATIONS OF PLUMBING EQUIPMENT WITH COORDINATE FINAL LOCATIONS OF PLUMBING EQUIPMENT WITH ARCHITECTURAL PLANS. 3. PROVIDE TO THE CONSTRUCTION MAMAGER DIMENSIONED LOCATIONS AND PROVIDE TO THE CONSTRUCTION MAMAGER DIMENSIONED LOCATIONS AND SIZE OF ALL REQUIRED FLOOR, WALL, AND ROOF OPENINGS. PROVIDE FOR INSTALLATION OF SLEEVES AND FRAMING AS REQUIRED. 4. ALL PLUMBING PIPING SHALL BE RUN TIGHT TO STEEL TRUSSES AND ALL PLUMBING PIPING SHALL BE RUN TIGHT TO STEEL TRUSSES AND RACKED ALONG STEEL AND WALLS WITH A STANDARD PIPE HANGING / RACKING SYSTEM. PIPING SHALL BE RUN CLEAR OF ALL DOORS AND WINDOWS. C. PLUMBING INSTALLATION REQUIREMENTS PLUMBING INSTALLATION REQUIREMENTS 1.