Dayton VA Generator Specs.xlsx
XLSX spreadsheet 20 KB Posted
- Attached to
- J028--Generator Preventative Maintenance and Load Bank Testing Federal contract opportunity
- Solicitation number
- 36C25025Q0565
About this file
The file is a detailed Excel spreadsheet documenting generator specifications for the Dayton VA Medical Center. The spreadsheet contains comprehensive technical details for multiple generators across various buildings, including specifications such as total facility fixed generator capacity, storage capacity, building location, kilowatt ratings, engine manufacturers, model numbers, serial numbers, voltage, and phase information. Generators are from manufacturers like Caterpiller, Kohler, Detroit, Volvo Penta, Cummings, and Perkins, with capacities ranging from 30 kW to 2000 kW.
The related federal contract opportunity is a presolicitation for Generator Preventative Maintenance and Load Bank Testing, solicitation number 36C25025Q0565, issued by the Department of Veterans Affairs Network Contracting Office. The procurement is classified under NAICS code 811310 with a small business size standard of $12.5 Million, and Product Service Code J028. The solicitation is for maintenance services at the Dayton VA Medical Center, with a response deadline of 05-23-2025 at 4 PM Eastern Time. Vendors must be registered in the System for Award Management (SAM) database, and the opportunity is located at 4100 West Third Street, Dayton, OH 45428-9000.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25025Q0565 0001.docx | DOCX document | |
| 36C25025Q0565.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| VA MEDICAL CENTER | 5c. Total Facility Fixed Generator Capacity (kW): | YES | ||||||||||||||||
| DAYTON, OHIO 45428 | ||||||||||||||||||
| EMERGENCY GENERATOR | 7b. Total Storage Capacity (In Gallons): | |||||||||||||||||
| SCHEDULE | ||||||||||||||||||
| Main Tank | 7a. Estimated Maximum Usage (Gallons/ Hours): | |||||||||||||||||
| Building | Location | K.W. | Day Tank | Reserve | Gal. used | Run Hrs. | Generator | K.V.A. | Volts | Phase | Current | Engine | Engine | Engine | Driven Unit | Driven Unit | Driven Unit | |
| Capacity | Capacity | Per. Hour | Per. Tank | H.P. | Mfgr. | Model# | Serial# | Mfgr. | Model# | Serial# | ||||||||
| Load at 100% | ||||||||||||||||||
| Bldg.147 | Boiler Plant | 210 | 300 Gal. | 550 Gal. | 10 Gal. | 82.5 | 305 | 283 | 480 | 30.8PF | 316 Amp. | Caterpiller | CAT 3406 | 075Z00528 | Caterpiller | SR4 | 5HA3431 | x |
| Bldg.302 | Outside N. 302 | 300 | 2,500 Gal. |
Don Brown: Don Brown:
6-15-06 150 gal.
8-25-06 500 gal.
| 10-20-06 1134.8 gal. | N/A | 14 Gal. | 107 | 474 | 375 | 208 | 30.8PF | 1042Amp. | Detroit | Det 6V92 | 6VF213140 | Kohler | 300ROZD1 | 369082 | x |
| Bldg.310/315/340 Gen. #1 |
Don Brown: Don Brown:
1-800-544-2444 Kohler option #2 Gen. Rm. 310 510 275 Gal. 6,000 Gal. 37.3 Gal Don Brown: Don Brown:
100% = 37.3 gal 75% = 27 gal 50% = 18.6 gal 25% = 10.8 gal 80 757 638 480 30.8PF 752Amp. Kohler D500 16.1b65 D16*024656*C3A Kohler Don Brown: Don Brown:
| Volvo Penta Engine Model # TAD1641GE | 500REOVB 5M4028 | 2186770 | x | |||||||||||||
| Bldg.310/315/340 Gen. #2 | Gen. Rm. 310 | 510 | 1 Tank for both Gens | 1 Tank for both Gens | 37.3 Gal | 80 | 757 | 638 | 480 | 30.8PF | 752 Amp. | Kohler | D500 16.1b65 | D16*024658*C3A | Kohler |
Don Brown: Don Brown:
| Volvo Penta Engine Model # TAD1641GE | 500REOVB 5M4028 | 2186769 | x | ||||||||||||||||
| Bldg.320 | Bsmt 320 | 350 | 100 Gal. | 1,650 Gal. | 15 Gal | 116.6 | 530 | 437.5 | 480 | 30.8PF | 527 Amp. | Caterpiller | Cat 3508 | 078Z01983 | Caterpiller | SR4 | 6CA0076 | x | |
| Bldg.320 | Outside N. 320 | 450 | 3650 | N/A | 30 Gal. | 113.7 | 755 | 562.5 | 480 | 0.8PF | 676.6 | Cummings | QSX15-G9 | 79675433 | Onan | DFEJ-1333290 | G130537268 | x | |
| Bldg.330-1 | Rm. BB-105a | 600 | 100 Gal. | 20,000 Gal. | 28 Gal. | 179 | 885 | 750 | 480 | 30.8PF | 902 Amp | Caterpiller | Cat.3508 | 023Z02488 | Caterpiller | SR4 | 5UA01255 | x | |
| Bldg.330-2 | Rm. BB-105a | 600 | 100 Gal. | Total | 28 Gal. | 179 | 885 | 750 | 480 | 30.8PF | 902 Amp | Caterpiller | Cat.3508 | 023Z02486 | Caterpiller | SR4 | 5UA01257 | x | |
| Bldg.330-3 | Rm. BB-105a | 600 | 100 Gal. | For all 4 | 28 Gal. | 179 | 885 | 750 | 480 | 30.8PF | 902 Amp | Caterpiller | Cat.3508 | 023Z02487 | Caterpiller | SR4 | 5UA01254 | x | |
| Bldg.330-4 | Rm. BB-105a | 600 | 100 Gal. | Generators | 28 Gal. | 179 | 885 | 750 | 480 | 30.8PF | 902 Amp | Caterpiller | Cat.3508 | 023Z02483 | Caterpiller | SR4 | 5UA01253 | x | |
| Bldg.330-6 | Bldg.330-6 | 2000 | 4000 Gal. | Generators are tied into the 2 10,000 gal. tanks | 147 Gal. |
vhadaybrowd: vhadaybrowd:
Full Load + 147 Gals per Hr.
3/4 Load=112 gals. Per hr.
1/2 Load=78gals. Per hr. 27.2 3058 2500 480 3 / 0.8PF 3007 Mult-DD Diesel Engine
DB: DB:
Onsite Energy www.mtu-online.com Model: 2000RXC6DT2 Serial: 307408-1-1-0509 Rating: Standby Engine: 16V-4000-Detroit RPM: 1800 Hz: 60
KW: 2000 KVA: 2500
Volts: 480/277 Amp: 3007 3-phase 4-wire PF: 0.8
| USA. Phone: +1 800 325 5450. +1 507 625 7973. Fax: +1 507 625 2968 | T1638A36 | 5272003506 | Magnamax DVR | 744RSL4054 | WA-569528-0409 | x | |
| Bldg.330-7 | Bldg.330-7 | 2000 | 4000 Gal. | 147 Gal. |
vhadaybrowd: vhadaybrowd:
Full Load + 147 Gals per Hr.
3/4 Load=112 gals. Per hr.
1/2 Load=78gals. Per hr. 27.2 3058 2500 480 3 / 0.8PF 3007 Mult-DD Diesel Engine
DB: DB:
DB:
Onsite Energy www.mtu-online.com Model: 2000RXC6DT2 Serial: 307408-1-2-0509 Rating: Standby Engine: 16V-4000-Detroit RPM: 1800 Hz: 60
KW: 2000 KVA: 2500
Volts: 480/277 Amp: 3007
| 3-phase 4-wire PF: 0.8 | T1638A36 | 5272003506 | Magnamax DVR | 744RSL4054 | WA-569528-0409 | x | ||||||||||||
| Bldg.408 13/3/2000 | Outside N. 408 | 50 | 155.Gal | N/A | 6 Gal. | 24 | 63 | 208 | 30.8PF | 173 Amp | Perkins | Perk T4.236 | 3777E06B12B | Olympian | D50P1 | F0990A/001 | x | |
| Bldg.409 | Rm. 27 | 375 |
Don Brown: Don Brown:
you can run the generator at 290 KW at 800amps before it will start to over heat.
vhadaybrowd: vhadaybrowd:
Full Load + 147 Gals per Hr.
3/4 Load=112 gals. Per hr.
1/2 Load=78gals. Per hr.
Don Brown: Don Brown:
Volvo Penta Engine Model # TAD1641GE Don Brown: Don Brown:
1-800-544-2444 Kohler option #2
Don Brown: Don Brown:
Volvo Penta Engine Model # TAD1641GE Don Brown: Don Brown:
6-15-06 150 gal.
8-25-06 500 gal.
10-20-06 1134.8 gal.
DB: DB:
Onsite Energy www.mtu-online.com Model: 2000RXC6DT2 Serial: 307408-1-1-0509 Rating: Standby Engine: 16V-4000-Detroit RPM: 1800 Hz: 60
KW: 2000 KVA: 2500
Volts: 480/277 Amp: 3007 3-phase 4-wire PF: 0.8 USA. Phone: +1 800 325 5450. +1 507 625 7973. Fax: +1 507 625 2968 Don Brown: Don Brown:
100% = 37.3 gal 75% = 27 gal 50% = 18.6 gal 25% = 10.8 gal
DB: DB:
DB:
Onsite Energy www.mtu-online.com Model: 2000RXC6DT2 Serial: 307408-1-2-0509 Rating: Standby Engine: 16V-4000-Detroit RPM: 1800 Hz: 60
KW: 2000 KVA: 2500
Volts: 480/277 Amp: 3007
| 3-phase 4-wire PF: 0.8 | 50 Gal. | 1,000 Gal. | 18.5 Gal. | 56.7 | 600 | 468.75 | 208 | 30.8PF | 1290 Amp | Caterpiller | Cat 3412 | 038S07003 | Caterpiller | SR4 | x | |||||
| Bldg.411/410 | Gen. Rm. 411 | 725 | 100 Gal. | 2,500 Gal. | 32 Gal. | 78.4 | 1232 | 906 | 208 | 30.8PF | 2515 Amp | Detroit | Det 6V92 | 16VF010587 | Kohler | 75OROZD81 | 302612 | x | ||
| Bldg.120 5/8/2003 | Outside S.120 | 30 | 152.2 Gal. | N/A | 3.3 Gal. | 40 | 48 | 37.5 | 208 | 30.8PF | 104 Amp | Perkins | 2320/1500 | AG51040*U572511 | Olympian | D30P3 | 147581/02 | x | ||
| Bldg.127 1-17-2006 | Outside E. 127 | 30 | 200 Gal. | N/A | 2.5 Gal. | 80 | 48 | 43.7 | 208 | .8PF | 121 Amp | Cummings | 4B3.3G1 | B3368042373 | NEWAGE | M-Spec#:M10335 UCN224D | M05J086020-02 | x | ||
| Bldg.350 | Outside S.350 | 562.5 | 112 GAL | 755 | 536 | 480 | 3PHASE | 676.6 | cummings | DFEJ-A063M044 | J190655962 | STAMFORD | N19H346524 | HC1534D1 | x | |||||
| Bldg.425 | Outside n.425 | 80 | 1023481BTU/Hr | 100 | 120/208 | 3phase | 277.6 | cummings | c80 n6 | A240308857 | natural gas feed | x |