Datasheet 80A to 500A 120VDC ProUPS Rectifier.pdf

PDF 251 KB Posted

Attached to
LTI Power Systems brand name Battery Chargers and Inverter
Solicitation number
W9127N26QA083
Issued by

About this file

This is a product specification document for the ProUPS 120VDC industrial rectifier system manufactured by LTI Power Systems. The document describes a professional series industrial 120VDC rectifier available in seven power ratings: 10kva, 15kva, 20kva, 30kva, 40kva, 50kva, and 60kva. The system features three-phase input capability ranging from 208VAC to 600VAC with both 50Hz and 60Hz input options, and output current ratings from 80A to 500A. Key technical specifications include a 20-year design life, four-quadrant IGBT solid-state design, power factor correction, high DC filtering with less than 2% RMS ripple, RFI/EMI filtration, and full isolation copper wound transformers. The rectifier meets UL1778, NEMA, NEC, ANSI, and FCC requirements.

Seven specific models are detailed with technical specifications: the LT1048H through LT6048H, ranging from 83.3A to 500A maximum recharge capacity with corresponding AC input requirements at 480V and 208V. Cabinet dimensions vary from 31.5"x34"x65" for smaller models to 49.5"x34"x65" for the larger units, with weights ranging from 900 to 2,110 pounds. Heat loss ranges from 3,855 to 12,822 BTU/hour depending on model. Environmental operating parameters include 0°C to 40°C ambient temperature capability, up to 95% relative humidity non-condensing, and operation at altitudes up to 5,000 feet without de-rating. The unit features NEMA 1 (IP20) cabinet construction with 14-gauge steel rated for seismic zone 4, with optional configurations including drip shields, air filters, gasketing, conformal coating, key lockable doors, and customizable designs for unique applications. Contact information is provided for custom requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ProUPS 120VDC 80A to 500A Rectifier

Professional Series Industrial

120VDC Rectifier

• Available in 10kva, 15kva, 20kva, 30kva, 40kva, 50kva, and 60kva Power Ratings

• Three Phase Input (208VAC thru 600VAC*)

• Output (80A thru 500A*)

• 3-Phase 50Hz or 60Hz Input

• 20-Year Design Life

• Four Quadrant IGBT Solid State Design

• Power Factor Correction For Lower Power Consumption Charges

• High DC Filtering/Extremely Low Ripple

• RFI/EMI Filtration and Surge Suppression

• Full Isolation Copper Wound Transformers

• LCD Monitoring Panel

• LED Power Flow Diagram

• Form “C” Alarm Interface Contacts

• Built to Meet UL1778, NEMA, NEC, ANSI and FCC requirements

*Contact Factory for any custom requirements

80A – 350A Model

OPTIONS

⇒ Multiple Voltage Inputs Available ⇒ 65kAIC Breakers ⇒ Air Filtration and Gasketing ⇒ Conformal Coating ⇒ Key Lockable Doors ⇒ Drip Shield ⇒ Wall Anchor Brackets ⇒ Multiple Output Terminal Blocks/Breakers ⇒ Emergency Power Off / Shunt Trip ⇒ Pad Lockable Breakers ⇒ Customizable Designs for Unique Applications

Industrial 120VDC 80A to 500A Rectifier

Note:

1. Specifications shown reflect standard 60Hz Rectifier models. Models of 50Hz, 400Hz, or other input/output/battery voltage configurations are available by contacting the factory.

2. All data is subject to change without notice.

LTI Power Systems • 10800 Middle Ave., Bldg. B • Elyria, OH 44035

Phone 888 327 5050 • Fax 440 458 8140 • www.ltipowersystems.com

Technical Specifications Model LT1048H LT1548H LT2048H LT3048H LT4048H LT5048H LT6048H Max Recharge 83.3A 125A 166A 250A 333A 416A 500A Max AC Input (480V) 16A 24A 32A 48A 65A 80A 97A Max AC Input (208V) 37A 56A 75A 112A 149A 186A 224A Mechanical Size W x D x H (in) 31.5x34x65 31.5x34x65 31.5x34x65 31.5x34x65 31.5x34x65 49.5x34x65 49.5x34x65 Weight (lbs) 900 1,100 1,280 1,410 1,550 1,870 2,110 Heat Loss

BTU/Hr 3855 5294 5868 9169 9952 10,257 12,822

Electrical

AC Input: 3-Phase 208, 380, 480,600 (+-10%) DC Output: 110/120/220/240/360/480VDC Ripple: <2% RMS Input THD: <4% RMS

Environmental

Ambient Temperature: 0°C to 40°C (45°C capable) Relative Humidity: Up to 95% non-condensing Acoustical Noise: <65dB (A) scale @ 1 meter Altitude: 5,000 Ft without de-rating Storage Temperature: -20°C to 70°C

General Information

Cable Entry: Top or Bottom

(Side Entry Optional) Ventilation: Forced Air N+1 Exterior Finish: Light Gray Powder Coat

(316 Stainless Steel Optional) Cabinet: NEMA 1 (IP20), 14ga (2mm)

Steel Seismic Zone 4 Rated (Drip Shield , Air Filters and Gasketing Optional) http://www.ltipowersystems.com/

File details come from the government source that posted it. Updated .