The Professional Series (ProUPS) is available in eight models ranging from 10 to 60 kilowatt-ampere (KVA) capacity with three-phase input voltages of either 208 or 480 volts. Key technical specifications include true on-line technology with full load rated dual solid-state static switching, input power factor correction typically achieving 1.0 P.F. at full load, and input total harmonic distortion (THD) less than 4%. The system features full input and output isolation with copper wound transformers, a nominal 120VDC link with 60 cells, AC-to-AC efficiency of 80 percent, and DC-to-AC efficiency of 90 percent. Output configurations support three-phase or single-phase delivery at 60Hz with voltage regulation of ±2 percent from 0 to 100 percent load. Physical specifications range from 31.5 inches by 34 inches by 65 inches for smaller models to 81 inches by 34 inches by 65 inches for the 50 and 60 KVA models, with weights ranging from 1,280 to 3,380 pounds. The system is built to meet UL1778, NEMA, NEC, ANSI, and FCC requirements and includes a redundant cooling system, LCD monitoring panel with power flow diagram, Ethernet RJ45 communications port, and optional features including external maintenance bypass switches, air filtration, emergency power off functions, and customizable designs. The cabinet is NEMA1 rated for Seismic Zone 4 and available in light gray or optional 316 stainless steel.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Industrial 120VDC 10 to 60KVA UPS
Professional Series (ProUPS) Uninterruptible Power Supply
• True On-line Technology for Maximum Power Protection
• Input Power Factor Correction Reduces Power Consumption Conserving Energy
• Input THD Less Than 4%
• Full Load Rated No-Break Dual Solid-State Static Switch
• Reliable and Robust Design
• 20+ year Design Life
• Full Input/Output Isolation, Copper Wound Transformers
• LCD Monitoring Panel with Power Flow Diagram
• Dual Input for Optimal Load Protection
• Redundant Cooling System
• Ethernet RJ45 Communications Port
• Form “C” Interface Contacts
• Generator Compatible Rectifier Input
• Built to Meet UL1778, NEMA, NEC, ANSI and FCC requirements
20KVA Model Shown
OPTIONS
Multiple Voltage Inputs/Outputs Available
50Hz/60Hz Models
External Maintenance Bypass Switch
Air Filtration and Conformal Coating
Emergency Power Off / Shunt Trip
Redundant Configurations Available
Customizable Designs for Unique Applications
Industrial 120VDC 10 to 60KVA UPS
LTI Power Systems • 10800 Middle Ave., Bldg. B • Elyria, OH 44035
Phone 888 327-5050 • Fax 440 458-8140 • www.ltipowersystems.com
Note:
1. Specifications shown reflect standard 60Hz UPS models. Models of 50Hz, 400Hz, or other frequencies available
2. Other input/output/DC link voltage configurations are available by contacting the factory.
3. All models are available as stand alone DC to AC inverters and frequency converters.
4. All data is subject to change without notice.
Technical Specifications
Model 10kva 15kva 20kva 25kva 30kva 40kva 50kva 60kva
Input Voltage² (3 Ph) 208 480 208 480 208 480 208 480 208 480 208 480 208 480 208 480
Nom. Current (Amps) 31.1 13.5 46.7 20.2 62.3 27 77.8 33.7 93.4 40.5 124.5 53.9 155.6 67.4 186.75 80.9
Max Current (Amps) 33.3 14.4 50 21.6 66.7 28.9 83.4 36.1 100 43.3 133.4 57.8 166.7 72.2 200.1 86.7
Input Power Factor Typically 1.0 P.F. @ full load
Input Frequency¹ 50/60Hz ±-6%
AC Output Three-Phase
Output Voltage VAC² 208 480 208 480 208 480 208 480 208 480 208 480 208 480 208 480
Frequency¹ (Hz) 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
Full Load (Amps) 28.7 12.0 41.7 18.1 55.6 24.1 69.5 30.1 83.4 36.1 111.2 48.2 139 60.2 166.8 72.3
AC Output Single-Phase
Output Voltage² VAC 120 240 120 240 120 240 120 240 120 240 120 240 120 240 120 240
Frequency¹ (Hz) 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
Full Load (Amps) 83.4 41.7 126 63 166 83 208 104 250 125 334 167 416 208 500 250
DC Link
Nominal DC Voltage² 120 120 120 120 120 120 120 120
DC Watts (Full Load) 9,600 14,400 19,200 24,000 28,800 38,400 48,000 57,600
DC Amps (Full Load) 80 120 160 200 240 320 400 480
Max DC Amps 100 150 200 250 300 400 500 600
End of Discharge 105VDC 105VDC 105VDC 105VDC 105VDC 105VDC 105VDC 105VDC
Number of Cells 60 60 60 60 60 60 60 60
VDC Flt/Eq. Range 105 to 150 105 to 150 105 to 150 105 to 150 105 to 150 105 to 150 105 to 150 105 to 150
Efficiency
AC to AC (%) 80 80 80 80 80 80 80 80
DC to AC (%) 90 90 90 90 90 90 90 90
BTU/Hr. 5,459 8,189 10,918 13,648 16,378 21,837 27,296 32,755
Mechanical
Size W x D x H (in) 31.5x34x65 31.5x34x65 49.25x34x65 63x34x65 63x34x65 63x34x65 81x34x65 81x34x65
Weight (lbs) 1,280 1,350 1,560 1,750 2,010 2,700 3,020 3,380
Input Voltage: 3 Phase, 3-wire plus ground Range: +10%, -20% Regulation: ±1% from 0 to 100% load Power Factor: .99 P.F. at full rated load Walk-In: 10 seconds to full load Input THD: Typically less than 4% Frequency: 50Hz or 60Hz ±6% Surge Protection: ANSI C62.41
Environmental Ambient Temperature: 0°C to 40°C (45°C capable) Relative Humidity: Up to 95% non-condensing Acoustical Noise: <65dB (A) scale @ 1 meter Altitude: 5,000 Ft without de-rating Storage Temperature: -20°C to 70°C
Output Voltage: 3/1 Ph, 2, 3 or 4-wire + ground Regulation: ±2% from 0 to 100% load Unbalanced: ±3% for 100% unbalanced load Output THD: <3% linear, <5% nonlinear load Overload: 120% for 15 min, 150% for 1 min, Bypass- 1000% for 1 sec Slew Rate: 1Hz per second (adjustable) Frequency: ± 0.01% free running
General Information Cable Entry: Top or Bottom Ventilation: Forced Air N+1 Paint: Light Gray (316 Stainless Steel Optional) Cabinet: NEMA1, Seismic Zone 4 Rated http://www.ltipowersystems.com/