M0026321Q1026
Section B - Supplies or Services and Prices
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Job |
Site Wiring Infrastructure Upgrade
FFP
See Section C, Performance Work Statement.
FOB: Destination
MILSTRIP: M8100121SURSNAS
PURCHASE REQUEST NUMBER: M8100121SURSNAS
PSC CD: DG01
NET AMT
Section C - Descriptions and Specifications
PERFORMANCE WORK STATEMENT
1. Title. United States Marine Corps Recruiting Command, Recruiting Station Nashville Unified Communications Infrastructure (RS NAS Wiring)
2. Background. Recruiting Station Nashville (RS NAS) has an aging cabling infrastructure of CAT3, CAT5, CAT6 and Coax. The current communications area is a small closet enclosure that is not appropriately sized to accommodate a modern infrastructure. The primary objectives of this scope are to move the communications space to a larger location, install a complete CAT6 infrastructure, extend or re-run existing circuits as necessary to the new location, remove old infrastructure and insure system uptime between by using a phased approach. The new location must be wired to meet the requirements of Voice over Internet Protocol (VOIP) with a Unified Communications (UC) infrastructure. This change will require installation of Category 6 (CAT6) cable, the installation of a conduit to the building demarcation point, establishment of pathways throughout the suite, and associated installation hardware.
3. Objectives. The primary objective is to provide the location with a flexible, modern and robust unified communication infrastructure, which meets or exceeds industry standards and best practices and provides a low maintenance and long lasting solution. The contractor shall provide all management, personnel, equipment, tools, materials, supervision, transportation, and other items and services necessary to provide a professional and error free Unified Communications infrastructure install. All new equipment for the infrastructure install shall be Contractor Furnished Equipment (CFE) and accomplished as necessary. Components chosen must be of professional/commercial quality and all BISCI (Building Industry Consulting Service International) standards must be met. BICSI, TIA (Telecommunication Industry Association) and EIA (Electronic Industries Alliance) standards are incorporated into the UBC (Universal Building Code), various DOD Directives and MARADMINS as well. All referenced standards are from these bodies. The installation must adhere to all UC standards as set forth by the Certified Technology Specialists (CTS) Code of Ethics and Conduct and International Communications Industries Association (ICIA). All equipment necessary to complete the tasks herein shall be CFE. The contractor shall deliver, install, label, and test the Unified Communication Infrastructure. See attached plan for reference. The top edge of the attached image is to be considered NORTH for this statement of work.
4. Scope.
· Task Area 1 – Complete install of Horizontal Unified Communications (UC) Infrastructure
· Task Area 2 – Installation of Pathways
· Task Area 3 – Installation of Conduits
· Task Area 4 – Communications Room
· Task Area 5 – Demarcation Point Extension
· Task Area 6 – In floor install in Conference Room
· Task Area 7 – Testing, Certification and Knowledge Transfer
5. Specific Tasks. The contractor shall provide the services to accomplish all capabilities as outlined in this Performance Work Statement (PWS). The contractor shall provide all management, personnel, equipment, tools, materials, supervision, transportation, and other items and services necessary to provide a professional and error free Unified Communications infrastructure install. All new equipment for the infrastructure install shall be Contractor Furnished Equipment (CFE) and accomplished as necessary. Components chosen must be of professional/commercial quality and all BISCI standards must be met. The installation must adhere to all UC standards as set forth by the Certified Technology Specialists (CTS) Code of Ethics and Conduct and International Communications Industries Association (ICIA). All equipment necessary to complete the tasks herein shall be CFE. The contractor is responsible for all electrical wiring and HVAC work required to complete the project. The contractor must coordinate all electrical work with the facility manager and 4th District Information Technology department and Logistics sections. The contractor shall deliver, install, label, and test the Unified Communication Infrastructure. The contractor may view the subject areas and is encouraged to perform a site-survey of the facility prior to the start of the project to validate the tasks covered in this SOW and determine the completeness of the task list. The approximate locations of drops and equipment locations are described in the appropriate sections. For the purpose of this SOW consider the top of the page to be NORTH for all images. Images are illustrative and may have variation from the site.
0. Complete installation of Unified Communications (UC) Infrastructure (68 Quad, 23 Duo)
1. Install horizontal UC infrastructure at Recruiting Station Nashville located at 2519 Perimeter Drive, Nashville, TN 37214 with a sufficient number of drops of sufficient size to accommodate existing voice and data equipment, with additional capacity to meet reasonable changes in manning and associated equipment without the need for additional distribution equipment, hubs and switches, at the edge user location.
0. Install uniformly colored plenum CAT6 cable to identified locations in identified quantities. The uniform color for all cables at all locations must be selected from one of the following: Blue, Black, Grey or Green.
0. Utilize surface mount raceway and surface mount boxes for on-wall termination, in uniform color, only in locations where in wall single gang low voltage boxes cannot be used.
0. Utilize sloped quad keystone faceplates for wall terminations in uniform color.
2. All user locations will be populated with single gang quad drops
2. All TV height locations will be single gang quad faceplates with 2 terminated RJ-45 and blanks in the same color as the faceplate.
0. Label all ports with uniformly in accordance with BISCI standards, with printed labels.
0. Secure all cables with BLACK hook and pile fasteners in every location where a fastener is utilized.
1. Remove decommissioned copper and fiber cabling once the site has migrated users onto the new infrastructure.
1. Replace any orphaned single/double gang outlets with blank faceplates matching the installed plates in color and style.
5.2 Installation of Pathways
1. Install pathways with J-hooks or cable tray as appropriate for all horizontal infrastructure.
0. Insure that pathways are not are both parallel to and closer than 12 inches to any high voltage cabling.
0. Any penetrations for pathways shall be above the ceiling and shall be sealed with fire retardant phone.
0. Utilize sloped faceplates for wall terminations in uniform color.
0. Label all ports with uniformly in accordance with BISCI standards, with printed labels.
0. Installation of Conduits
1. Install 2 quantity 2” rigid metal conduit from building demarcation point to Communications Room.
0. CONDUIT A - Terminate 1 conduit against EAST wall and above ladder rack to RACK 1 (4 post rack) in Communications Room.
0. Locate demarc end of Conduit B as designated by local representative.
0. CONDUIT B - Terminate 1 conduit against EAST wall and with an unobstructed path to the room facing surface of the wall mounted plywood with and unobstructed direct path between ladder rack for RACK 1 and RACK 2 to the wall mounted plywood.
1. Locate demarc end of Conduit B as designated by local representative.
0. Label each conduit per BISCI Standards.
0. Leave a pull string in each conduit with no less than 2 feet of slack at each end and secured in a fashion to prevent accidental retreat into conduit.
1. Install appropriately sized rigid metal conduit in any place cables pass outside of Marine Corps controlled spaces, such as public areas, shared spaces, entry ways, ect.
1. Install appropriately sized rigid metal sleeves in any place cables penetrate the drop ceiling.
1. Any penetrations for pathways shall be above the ceiling and be sealed with fire retardant foam that meets or exceeds local ordinances and industry best practices.
0. Communications Room
1. EAST Wall
0. Install no less than one sheet of 8’ by 4’ TIA/EIA-569 compliant 1 hour fire-rated, painted ¾” or thicker plywood on designated wall suitable for the wall mounting of gear centered behind racks. (RACK 1, RACK 2 and RACK 3)
0. Wall will house a bus bar bonded to building ground.
0. Ladder rack installed from wall to Rack 1, 2 and 3.
0. Ladder rack will be bonded to bus bar and to Rack 1, 2 and 3.
0. All wall mounted low voltage control equipment (security, alarm, environmental control, ect.) shall be mounted on this wall. All ISP equipment shall be mounted on this wall.
1. WEST Wall
1. A laminated copy of the as-built drawing of ports and pathways will be mounted on this wall in a size no less than 24” in width, with the top edge matching the top edge of the attached image. Image shall be to scale.
1. Rack 3
2. Install a 45U 2-post equipment rack equivalent to Panduit R2P Standard Rack approximately 36” from SOUTH with front face no less than 36” from WEST wall, separated from Rack 2 by vertical cable management equivalent to Panduit WMPVHC45E.
0. Flanked by vertical cable management equivalent to Panduit WMPVHC45E on both left and right.
0. EAST side of rack will be considered rear, WEST side front, SOUTH side right, and NORTH side left.
2. Rack 1 will be bonded to Rack 2 and ladder rack.
2. Rack will have the top 1U left open.
2. U44 and U17 will be populated with 1U Dual Sided Horizontal cable management, equivalent to Panduit WMPSE.
2. Rack will be populated with alternating 2U Dual Sided Horizontal cable management, equivalent to Panduit WMPH2E and 48 port patch panels, equivalent to Panduit NKFPL48.
2. Every patch panel will have a horizontal manager above and below it.
2. Rack will be flanked by vertical cable manager equivalent to Panduit WMPVHC45E on each side.
2. Terminate and label copper in sequential order, per labeling starting in the top left when viewed from the front. Label all ports with uniformly in accordance with BICSI standards, with printed labels, and match the termination at the edge user side.
7. Patch Panel in U18/U19 will be left unpopulated by horizontal distribution cables.
When viewed from the WEST the front of the rack appear as follows:
RACK 3
| WMPVHC45E Panduit - Vertical Dual Sided Manager |
| U45 |
| EMPTY |
| WMPVHC45E Panduit - Vertical Dual Sided Manager |
| U44 |
| WMPSE 1U Dual Sided Horizontal Cable Manager |
| U43 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U42
| U41 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U40
| U39 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U38
| U37 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U36
| U35 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U34
| U33 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U32
| U31 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U30
| U29 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U28
| U27 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U26
| U25 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U24
| U23 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U22
| U21 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U20
| U19 |
| NKFPL48 48 Port CAT6 PATCH PANEL - BLACK |
U18
| U17 |
| WMPSE 1U Dual Sided Horizontal Cable Manager |
| U16 |
| EMPTY |
U15
U14
U13
U12
U11
U10
U9
U8
U7
U6
U5
U4
U3
U2
U1
Referenced equipment:
WMPSE 1U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/WMPSE.html This requirement is for a 1U dual sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 40 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 70 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a wide slotted enter on top and bottom of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPH2E 2U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/wmph2e.html This requirement is for a 2U dual sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 80 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 120 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a wide slotted enter on top and bottom of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPVHC45E Panduit - Vertical Dual Sided Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/vertical-cable-managers/wmpvhc45e.html This requirement is for a dual sided vertical cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must accommodate 45U of rack space.
Must be mountable on both left and right sides concurrently.
50% fill capacity of no less than 350 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 350 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on left and right to front cable trough.
Must have a wide slotted enter on left and right of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
NKFPL48 48 Port Keystone Patch Panel - Black PANDUIT https://www.panduit.com/en/products/copper-systems/patch-panels-accessories/modular-patch-panels/nkfpl48.html This requirement is for a 48 port keystone patch panel.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must be made of steel.
Must accept all standard keystone terminators.
Must have labels and clear label covers to identify each port.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must be uniform in color with all cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
R2P 84” Black Standard Rack - Black PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/racks-accessories/racks/r2p.html This requirement is for a 2 Post rack.
Must be an EIA compliant 19” wide 2 post rack.
Must be 84” tall with 45U of equipment space.
Each U must be numbered from bottom to top.
Must have a load capacity of at least 1000Lbs Must accommodate 12-24 x .5" screws for mounting hardware and equipment.
Must be made of aluminum or steel.
Must have powder coat finish over all exposed metal surfaces.
Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
Must meet UL 2416, EIA/ECA-310-E, RoHS Compliant
1. Rack 2
3. Install a 45U 2-post equipment rack equivalent to Panduit R2P Standard Rack bolted to floor with front lined up with Rack 3 and Rack 1, separated from Rack 3 by vertical cable management equivalent to Panduit WMPVHC45E, and separated from Rack 1 by vertical cable management equivalent to Panduit WMPVHC45E.
0. Flanked by vertical cable management equivalent to Panduit WMPVHC45E on both left and right.
0. EAST side of rack will be considered rear, WEST side front, SOUTH side right, and NORTH side left.
3. Rack 2 will be bonded to Rack 1, Rack 3 and ladder rack. Rack will be flanked by vertical cable managers on each side.
3. U44 and U30 will be populated with 1U Dual Sided Horizontal cable management equivalent to Panduit WMPSE.
3. U41/U42, U38/U39, U35/U36 and U32/U33 will be populated with 2U Dual Sided Horizontal cable management equivalent to Panduit WMPH2E.
3. Provide 3 quantity 2U shelves equivalent to Panduit SRM19FM2.
4. Shelves shall be installed so they do not extend past the front of the rack.
4. Shelves shall be installed in U2, U6 and U10
RACK 2
| WMPVHC45E Panduit - Vertical Dual Sided Manager |
| U45 |
| EMPTY |
| WMPVHC45E Panduit - Vertical Dual Sided Manager |
| U44 |
| WMPSE 1U Dual Sided Horizontal Cable Manager |
| U43 |
| EMPTY |
| U42 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U41
| U40 |
| EMPTY |
| U39 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U38
| U37 |
| EMPTY |
| U36 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U35
| U34 |
| EMPTY |
| U33 |
| WMPH2E 2U Dual Sided Horizontal Cable Manager |
U32
| U31 |
| EMPTY |
| U30 |
| WMPSE 1U Dual Sided Horizontal Cable Manager |
| U29 |
| EMPTY |
U28
U27
U26
U25
U24
U23
U22
U21
U20
U19
U18
U17
U16
U15
U14
U13
U12
| U11 |
| 2U Shelf Panduit SRM19FM2 |
U10
| U9 |
| EMPTY |
U8
| U7 |
| 2U Shelf Panduit SRM19FM2 |
U6
| U5 |
| EMPTY |
U4
| U3 |
| 2U Shelf Panduit SRM19FM2 |
U2
| U1 |
| EMPTY |
WMPSE 1U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/WMPSE.html This requirement is for a 1U dual sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 40 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 70 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a wide slotted enter on top and bottom of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPH2E 2U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/wmph2e.html This requirement is for a 2U dual sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 80 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 120 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a wide slotted enter on top and bottom of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPVHC45E Panduit - Vertical Dual Sided Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/vertical-cable-managers/wmpvhc45e.html This requirement is for a dual sided vertical cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must accommodate 45U of rack space.
Must be mountable on both left and right sides concurrently.
50% fill capacity of no less than 350 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 350 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on left and right to front cable trough.
Must have a wide slotted enter on left and right of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
SRM19FM2 Panduit 2U Shelf PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/racks-accessories/rack-accessories/srm19fm2.html This requirement is for a 2U shelf.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must be made of folded steel.
Must support a minimum of 65lbs of load.
Must have lip on front and back to prevent equipment from sliding off.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must be uniform in color with all cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
R2P 84” Black Standard Rack - Black PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/racks-accessories/racks/r2p.html This requirement is for a 2 Post rack.
Must be an EIA compliant 19” wide 2 post rack.
Must be 84” tall with 45U of equipment space.
Each U must be numbered from bottom to top.
Must have a load capacity of at least 1000Lbs Must accommodate 12-24 x .5" screws for mounting hardware and equipment.
Must be made of aluminum or steel.
Must have powder coat finish over all exposed metal surfaces.
Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
Must meet UL 2416, EIA/ECA-310-E, RoHS Compliant
NKFPL48 48 Port Keystone Patch Panel - Black PANDUIT https://www.panduit.com/en/products/copper-systems/patch-panels-accessories/modular-patch-panels/nkfpl48.html This requirement is for a 48 port keystone patch panel.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must be made of steel.
Must accept all standard keystone terminators.
Must have labels and clear label covers to identify each port.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must be uniform in color with all cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
1. Rack 1
4. Install a 45U 4-post equipment rack equivalent to Panduit R4P Standard Rack bolted to floor no less than 2’ from SOUTH wall with front lined up with Rack 3, no less than 6” from EAST wall, no less than 30” from the NORTH wall, separated from Rack 2 by vertical cable management equivalent to Panduit WMPVHC45E.
0. Flanked by vertical cable management equivalent to Panduit WMPVHC45E on both left and right.
0. EAST side of rack will be considered rear, WEST side front, SOUTH side right, and NORTH side left.
4. Rack 3 will be bonded to Rack 2 and ladder rack. Rack will be flanked by vertical cable managers on each side.
4. U44 will be populated with 1U Dual Sided Horizontal Cable Management equivalent to Panduit WMPSE.
4. U43 will be populated with a 1U fiber optic distribution frame.
4. U39/U40 will be populated with one 48 port patch panel equivalent to Panduit NKFPL48.
4. U37 and U41 will be populated with 2U Dual Sided Horizontal Cable Management equivalent to Panduit WMPSE.
R4P 4 Post Rack PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/racks-accessories/racks/r4p.html This requirement is for a 4 Post rack.
Must be an EIA compliant 19” wide 2 post rack.
Must be 84” tall with 45U of equipment space.
Must be at least 30”deep Each U must be numbered from bottom to top.
Must have a load capacity of at least 2500Lbs Must accommodate 12-24 x .5" screws for mounting hardware and equipment.
Must be made of aluminum or steel.
Must have powder coat finish over all exposed metal surfaces.
Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
Must meet UL 2416, EIA/ECA-310-E, RoHS Compliant Item required must be a brand name, product, or feature of a product, particular to one manufacturer.
WMPSE 1U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/WMPSE.html This requirement is for a 1U single sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 40 CAT6 24 AWG cables for front cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a physical barrier separating front cable trough from rear of the rack with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted.
Must have a front cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPH2E 2U Dual Sided Horizontal Cable Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/horizontal-cable-managers/wmph2e.html This requirement is for a 2U dual sided horizontal cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
50% fill capacity of no less than 80 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 120 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on top and bottom to front cable trough.
Must have a wide slotted enter on top and bottom of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
WMPVHC45E Panduit - Vertical Dual Sided Manager PANDUIT https://www.panduit.com/en/products/cabinets-thermal-management-racks-enclosures/cable-managers-accessories/vertical-cable-managers/wmpvhc45e.html This requirement is for a dual sided vertical cable manager.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must accommodate 45U of rack space.
Must be mountable on both left and right sides concurrently.
50% fill capacity of no less than 350 CAT6 24 AWG cables for front cable trough.
50% fill capacity of no less than 350 CAT6 24 AWG cables for back cable trough.
Must have a wide slotted entry on left and right to front cable trough.
Must have a wide slotted enter on left and right of back cable trough.
Must have a physical barrier separating front cable trough from rear cable trough with openings allowing cables to be routed from one to the other.
All areas exposed to cables must be non-ferrous and non-conductive.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must allow all cables to enter above minimum bend radius at described fill levels.
Must have a front and rear cover.
Covers must be dual-hinging and easily removable and interchangeable with all similarly sized cable managers Must be uniform in color with all other cable managers and racks in black.
NKFPL48 48 Port Keystone Patch Panel - Black PANDUIT https://www.panduit.com/en/products/copper-systems/patch-panels-accessories/modular-patch-panels/nkfpl48.html This requirement is for a 48 port keystone patch panel.
Must be compatible with any EIA compliant 19” rack or cabinet.
Must be made of steel.
Must accept all standard keystone terminators.
Must have labels and clear label covers to identify each port.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must be uniform in color with all cable managers and racks in black.
5.5 Demarcation Point and COMM ROOM Extension
1. Install a 12 strand single mode and 12 strand multimode cable between the building demarcation point (demarc) and fiber tray in Rack 1 room via Conduit A and ladder rack.
0. Install any required mounting hardware to insure fiber is secured above minimum bend radius and protected from strain or incidental damage.
0. Secure cable with BLACK hook and pile fasteners against the edge of the ladder rack.
0. Terminate fiber on Rack 3 such that there are female LC connectors available for cross connections
0. At demarc install fiber at designated location, and terminate in identical fashion.
0. Label all ports with uniformly in accordance with BISCI standards, with printed labels.
1. Install 24 CAT6 in CONDUIT B between the building demarcation point (demarc) and the plywood on the wall between the ladder rack of RACK 2 and RACK 3.
1. Install any required mounting hardware to insure copper is secured and protected from strain, incidental damage, crosstalk or electromagnetic interference.
1. Secure bundle with BLACK hook and pile fasteners against the edge of the ladder rack.
1. On both Demarc and Communications Room locations terminate CAT6 to wall mounted CAT6 female keystone panels (2 per location) equivalent to Panduit NKFP12W on 89D mounting brackets at designated locations.
1. Label all ports uniformly in accordance with BISCI standards, with printed labels
1. Install 12 CAT6 in a bundle, separated from horizontal distribution cables, between OLD COMM ROOM and plywood on the wall between RACK 1 and RACK 2.
2. Install any required mounting hardware to insure copper is secured and protected from strain, incidental damage, crosstalk or electromagnetic interference.
2. Secure bundle with BLACK hook and pile fasteners against the edge of the ladder rack.
2. On both Demarc and Communications Room locations terminate CAT6 to wall mounted CAT6 female keystone panels (1 per location) equivalent to Panduit NKFP12W on 89D mounting brackets at designated locations.
2. Label all ports uniformly in accordance with BISCI standards, with printed labels
Referenced equipment:
NKFP12W Keystone 12-port modular patch panel PANDUIT https://www.panduit.com/en/products/copper-systems/patch-panels-accessories/modular-patch-panels/nkfp12w.html This requirement is for a 12 port keystone patch panel.
Must be oriented for vertical mounting.
Must be paired with appropriate wall mounting hardware.
Must accept all standard keystone terminators.
Must have labels for each port.
All edges exposed to cables must be rounded or blunted to prevent damage to cables.
Must be uniform in color with all cable managers and racks in black.
Must be compatible and interoperable with all other items in this request where applicable.
5.6 In Floor Install in Conference Room
1. Vendor shall trench between power outlet location and floor location in conference room on plan.
0. Install 2 conduits, Conduit C and Conduit D, between terminal location and above wall in plenum space as designated by local representative.
0. Label each conduit per BISCI Standards.
0. Leave a pull string in each conduit with no less than 2 feet of slack at each end and secured in a fashion to prevent accidental retreat into conduit.
0. Conduit C shall be populated by CAT6
0. Conduit D shall be left unpopulated by the vendor, but must be installed meeting local guidelines for power.
0. On terminal end conduits shall connect to dual gang or larger receptacle with a flush mounted floor box that permits the pass-through of cables and access to the conduits
0. Restore trenched surface smooth and level with surrounding concrete floor.
0. Carpet tiles to be restored by Recruiting Station Nashville.
5.7 Testing, Certification and Knowledge Transfer
| 1. | Test each installed CAT6 cable from MDF to terminal equipment location to insure it meets industry standards for continuity, data rate and connectivity. |
| 2. | The contractor will supply a Portable Document Format (.pdf) copy of test results for each port. |
| 3. | The contractor will provide as built drawings showing pathways and port numbers. |
| 4. | Government shall, at its digression, test all, some or none of the installed cables to verify the accuracy of the provided testing and as-built. |
6. Government-Furnished Equipment (GFE) The Government will furnish or make available to the contractor the following equipment.
Equipment List:
1. No GFE provided.
7. Materials and Equipment (CFE)
1. Materials. The contractor shall provide all materials, other than GFE provided, essential to making the integrated system operational. All products and materials developed, prepared and/or purchased by the contractor for the use or ownership of the Federal Government becomes the property of the Federal Government. The contractor shall document the transfer of all materials.
2. Equipment. The contractor shall ensure all components are compatible with all equipment in the Unified Communications Infrastructure. The equipment shall have the characteristics and functionality to perform as a Unified Communications Infrastructure.
3. Incidental Equipment/Materials. The contractor shall furnish all wiring, cables, connectors, fixtures, woodwork, hardware, and hardware necessary to connect and mount the various components of the Unified Communications Infrastructure as required for a professional, complete, and operable system.
4. Government material removed by the contractor shall be turned over to the 4MCD for disposition. The contractor shall not dispose of any government property being removed.
8. Client- Responsibilities
1. Provide access to necessary areas to complete the project during normal business hours. 8:00 AM – 5:00 PM, M-F.
Section E - Inspection and Acceptance
INSPECTION AND ACCEPTANCE TERMS
Supplies/services will be inspected/accepted at:
| CLIN |
| INSPECT AT |
| INSPECT BY |
| ACCEPT AT |
| ACCEPT BY |
| 0001 |
| Destination |
| Government |
| Destination |
| Government |
Section F - Deliveries or Performance
DELIVERY INFORMATION
| CLIN |
| DELIVERY DATE |
| QUANTITY |
| SHIP TO ADDRESS |
| DODAAC / CAGE |
| 0001 |
| 2 mths. ADC |
| 1 |
| 4TH MARINE CORPS DISTRICT |
GYSGT ERIC NELSON
RS NASHVILLE
2519 PERIMETER PL DR
NASHVILLE TN 37214
(717) 836-0997 FOB: Destination M93933
Section G - Contract Administration Data
MANPOWER REPORTING
Enterprise-wide Contractor Manpower Reporting Application (ECMRA) The contractor shall report contractor labor hours (including subcontractor labor hours) required for performance of services provided under this contract wiring installation via a secure data collection site. Contracted services excluded from reporting are based on Product Service Codes (PSCs). The excluded PSCs are:
(1) W, Lease/Rental of Equipment;
(2) X, Lease/Rental of Facilities;
(3) Y, Construction of Structures and Facilities;
(4) S, Utilities ONLY;
(5) V, Freight and Shipping ONLY.
The contractor is required to completely fill in all required data fields using the following web address https://doncmra.nmci.navy.mil.
Reporting inputs will be for the labor executed during the period of performance during each Government fiscal year (FY), which runs October 1 through September 30. While inputs may be reported any time during the FY, all data shall be reported no later than October 31 of each calendar year. Contractors may direct questions to the help desk, linked at https://doncmra.nmci.navy.mil.
CLAUSES INCORPORATED BY REFERENCE
| 52.204-18 |
| Commercial and Government Entity Code Maintenance |
| AUG 2020 |
| 52.247-34 |
| F.O.B. Destination |
| NOV 1991 |
| 252.232-7003 |
| Electronic Submission of Payment Requests and Receiving Reports |
| DEC 2018 |
CLAUSES INCORPORATED BY FULL TEXT
252.232-7006 WIDE AREA WORKFLOW PAYMENT INSTRUCTIONS (DEC 2018)
(a) Definitions. As used in this clause—
“Department of Defense Activity Address Code (DoDAAC)” is a six position code that uniquely identifies a unit, activity, or organization.
“Document type” means the type of payment request or receiving report available for creation in Wide Area WorkFlow (WAWF).
“Local processing office (LPO)” is the office responsible for payment certification when payment certification is done external to the entitlement system.
“Payment request” and “receiving report” are defined in the clause at 252.232-7003, Electronic Submission of Payment Requests and Receiving Reports.
(b) Electronic invoicing. The WAWF system provides the method to electronically process vendor payment requests and receiving reports, as authorized by Defense Federal Acquisition Regulation Supplement (DFARS) 252.232-7003, Electronic Submission of Payment Requests and Receiving Reports.
(c) WAWF access. To access WAWF, the Contractor shall—
(1) Have a designated electronic business point of contact in the System for Award Management at https://www.sam.gov; and
(2) Be registered to use WAWF at https://wawf.eb.mil/ following the step-by-step procedures for self-registration available at this web site.
(d) WAWF training. The Contractor should follow the training instructions of the WAWF Web-Based Training Course and use the Practice Training Site before submitting payment requests through WAWF. Both can be accessed by selecting the “Web Based Training” link on the WAWF home page at https://wawf.eb.mil/.
(e) WAWF methods of document submission. Document submissions may be via web entry, Electronic Data Interchange, or File Transfer Protocol.
(f) WAWF payment instructions. The Contractor shall use the following information when submitting payment requests and receiving reports in WAWF for this contract or task or delivery order:
(1) Document type. The Contractor shall submit payment requests using the following document type(s):
(i) For cost-type line items, including labor-hour or time-and-materials, submit a cost voucher.
(ii) For fixed price line items—
(A) That require shipment of a deliverable, submit the invoice and receiving report specified by the Contracting Officer.
N/A
(B) For services that do not require shipment of a deliverable, submit either the Invoice 2in1, which meets the requirements for the invoice and receiving report, or the applicable invoice and receiving report, as specified by the Contracting Officer.
Invoice 2 in 1
(iii) For customary progress payments based on costs incurred, submit a progress payment request.
(iv) For performance based payments, submit a performance based payment request.
(v) For commercial item financing, submit a commercial item financing request.
(2) Fast Pay requests are only permitted when Federal Acquisition Regulation (FAR) 52.213-1 is included in the contract.
[Note: The Contractor may use a WAWF “combo” document type to create some combinations of invoice and receiving report in one step.]
(3) Document routing. The Contractor shall use the information in the Routing Data Table below only to fill in applicable fields in WAWF when creating payment requests and receiving reports in the system.
Routing Data Table*
| Field Name in WAWF |
| Data to be entered in WAWF |
| Pay Official DoDAAC |
| M67443 |
| Issue By DoDAAC |
| M00263 |
| Admin DoDAAC** |
| M00263 |
| Inspect By DoDAAC |
| M81001 |
| Ship To Code |
| ____ |
| Ship From Code |
| ____ |
| Mark For Code |
| ____ |
| Service Approver (DoDAAC) |
| M81001 |
| Service Acceptor (DoDAAC) |
| M81001 |
| Accept at Other DoDAAC |
| ____ |
| LPO DoDAAC |
| ____ |
| DCAA Auditor DoDAAC |
| ____ |
| Other DoDAAC(s) |
| ____ |
(4) Payment request. The Contractor shall ensure a payment request includes documentation appropriate to the type of payment request in accordance with the payment clause, contract financing clause, or Federal Acquisition Regulation 52.216-7, Allowable Cost and Payment, as applicable.
(5) Receiving report. The Contractor shall ensure a receiving report meets the requirements of DFARS Appendix F.
(g) WAWF point of contact.
Daniel.Feigley@marines.usmc.mil Donna.lloyd@usmc.mil
(1) The Contractor may obtain clarification regarding invoicing in WAWF from the following contracting activity’s WAWF point of contact.
Donna.lloyd@usmc.mil
(2) Contact the WAWF helpdesk at 866-618-5988, if assistance is needed.
(End of clause)
Section H - Special Contract Requirements
DOL WAGE DETERMINATION
WD 2015-4647 (Rev.-15)
U.S. Department of Labor Wage Determination Number 2015-4647, Revision Number 15 dated 12 December 2020 is hereby incorporated into this contract and any subsequent order.
This Wage Determination can be found at http://www.dol.gov
Section I - Contract Clauses
| 52.204-13 |
| System for Award Management Maintenance |
| OCT 2018 |
| 52.204-19 |
| Incorporation by Reference of Representations and Certifications. |
| DEC 2014 |
| 52.222-41 |
| Service Contract Labor Standards |
| AUG 2018 |
| 52.222-42 |
| Statement Of Equivalent Rates For Federal Hires |
| MAY 2014 |
| 52.232-39 |
| Unenforceability of Unauthorized Obligations |
| JUN 2013 |
| 52.232-40 |
| Providing Accelerated Payments to Small Business Subcontractors |
| DEC 2013 |
| 252.203-7000 |
| Requirements Relating to Compensation of Former DoD Officials |
| SEP 2011 |
| 252.203-7002 |
| Requirement to Inform Employees of Whistleblower Rights |
| SEP 2013 |
| 252.204-7012 |
| Safeguarding Covered Defense Information and Cyber Incident Reporting |
| DEC 2019 |
| 252.204-7018 |
| Prohibition on the Acquisition of Covered Defense Telecommunications Equipment or Services |
| JAN 2021 |
| 252.223-7006 |
| Prohibition On Storage, Treatment, and Disposal of Toxic or Hazardous Materials |
| SEP 2014 |
| 252.223-7008 |
| Prohibition of Hexavalent Chromium |
| JUN 2013 |
| 252.225-7048 |
| Export-Controlled Items |
| JUN 2013 |
| 252.232-7010 |
| Levies on Contract Payments |
| DEC 2006 |
| 252.243-7001 |
| Pricing Of Contract Modifications |
| DEC 1991 |
| 252.244-7000 |
| Subcontracts for Commercial Items |
| JAN 2021 |
| 252.247-7023 |
| Transportation of Supplies by Sea |
| FEB 2019 |
52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS--COMMERCIAL ITEMS (JAN 2021)
(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial items:
(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L. 113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).
(2) 52.204-23, Prohibition on Contracting for Hardware, Software, and Services Developed or Provided by Kaspersky Lab and Other Covered Entities (Jul 2018) (Section 1634 of Pub. L. 115-91).
(3) 52.204-25, Prohibition on Contracting for Certain Telecommunications and Video Surveillance Services or Equipment. (AUG 2020) (Section 889(a)(1)(A) of Pub. L. 115-232).
(4) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (Nov 2015).
(5) 52.233-3, Protest After Award (AUG 1996) (31 U.S.C. 3553).
(6) 52.233-4, Applicable Law for Breach of Contract Claim (OCT 2004) (Public Laws 108-77 and 108-78 (19 U.S.C. 3805 note)).
(b) The Contractor shall comply with the FAR clauses in this paragraph (b) that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)
___ (1) 52.203-6, Restrictions on Subcontractor Sales to the Government (JUN 2020), with Alternate I (Oct 1995) (41 U.S.C. 4704 and 10 U.S.C. 2402).
____ (2) 52.203-13, Contractor Code of Business Ethics and Conduct (JUN 2020) (41 U.S.C. 3509).
____ (3) 52.203-15, Whistleblower Protections under the American Recovery and Reinvestment Act of 2009 (JUN 2010) (Section 1553 of Pub. L. 111-5). (Applies to contracts funded by the American Recovery and Reinvestment Act of 2009.)
X (4) 52.204-10, Reporting Executive Compensation and First-Tier Subcontract Awards (JUN 2020) (Pub. L. 109-282) (31 U.S.C. 6101 note).
___ (5) [Reserved]
___ (6) 52.204-14, Service Contract Reporting Requirements (Oct 2016) (Pub. L. 111-117, section 743 of Div. C).
___ (7) 52.204-15, Service Contract Reporting Requirements for Indefinite-Delivery Contracts (Oct 2016) (Pub. L. 111-117, section 743 of Div. C).
X (8) 52.209-6, Protecting the Government's Interest When Subcontracting with Contractors Debarred, Suspended, or Proposed for Debarment. (JUN 2020) (31 U.S.C. 6101 note).
____ (9) 52.209-9, Updates of Publicly Available Information Regarding Responsibility Matters (OCT 2018) (41 U.S.C. 2313).
____ (10) [Reserved]
____ (11)(i) 52.219-3, Notice of HUBZone Set-Aside or Sole-Source Award (MAR 2020) (15 U.S.C. 657a).
____ (ii) Alternate I (MAR 2020) of 52.219-3.
____ (12) (i) 52.219-4, Notice of Price Evaluation Preference for HUBZone Small Business Concerns (MAR 2020) (if the offeror elects to waive the preference, it shall so indicate in its offer) (15 U.S.C. 657a).
____ (ii) Alternate I (MAR 2020) of 52.219-4.
____ (13) [Reserved]
X (14)(i) 52.219-6, Notice of Total Small Business Set-Aside (NOV 2020) (15 U.S.C. 644).
____ (ii) Alternate I (MAR 2020) of 52.219-6.
____ (15)(i) 52.219-7, Notice of Partial Small Business Set-Aside (NOV 2020) (15 U.S.C. 644).
____ (ii) Alternate I (MAR 2020) of 52.219-7.
____ (16) 52.219-8, Utilization of Small Business Concerns (OCT 2018) (15 U.S.C. 637(d)(2) and (3)).
____ (17)(i) 52.219-9, Small Business Subcontracting Plan (JUN 2020) (15 U.S.C. 637(d)(4)).
____ (ii) Alternate I (NOV 2016) of 52.219-9.
____ (iii) Alternate II (NOV 2016) of 52.219-9.
____ (iv) Alternate III (JUN 2020) of 52.219-9.
____ (v) Alternate IV (JUN 2020) of 52.219-9.
____ (18) (i) 52.219-13, Notice of Set-Aside of Orders (MAR 2020) (15 U.S.C. 644(r)).
____ (ii) Alternate I (MAR 2020) of 52.219-13.
____ (19) 52.219-14, Limitations on Subcontracting (MAR 2020) (15 U.S.C. 637(a)(14)).
____ (20) 52.219-16, Liquidated Damages—Subcontracting Plan (Jan 1999) (15 U.S.C. 637(d)(4)(F)(i)).
____ (21) 52.219-27, Notice of Service-Disabled Veteran-Owned Small Business Set-Aside (MAR 2020) (15 U.S.C. 657f).
X (22) (i) 52.219-28, Post Award Small Business Program Rerepresentation (NOV 2020) (15 U.S.C. 632(a)(2)).
____ (ii) Alternate I (MAR 2020) of 52.219-28.
____ (23) 52.219-29, Notice of Set-Aside for, or Sole Source Award to, Economically Disadvantaged Women-Owned Small Business (EDWOSB) Concerns (MAR 2020) (15 U.S.C. 637(m)).
____ (24) 52.219-30, Notice of Set-Aside for, or Sole Source Award to, Women-Owned Small Business Concerns Eligible Under the Women-Owned Small Business Program (MAR 2020) (15 U.S.C. 637(m)).
____ (25) 52.219-32, Orders Issued Directly Under Small Business Reserves (MAR 2020) (15 U.S.C. 644(r)).
____ (26) 52.219-33, Nonmanufacturer Rule (MAR 2020) (15 U.S.C. 637(a)(17)).
X (27) 52.222-3, Convict Labor (JUN 2003) (E.O. 11755).
X (28) 52.222-19, Child Labor--Cooperation with Authorities and Remedies (JAN 2020) (E.O. 13126).
X (29) 52.222-21, Prohibition of Segregated Facilities (APR 2015).
X (30)(i) 52.222-26, Equal Opportunity (SEPT 2016) (E.O. 11246).
____ (ii) Alternate I (FEB 1999) of 52.222-26.
____ (31)(i) 52.222-35, Equal Opportunity for Veterans (JUN 2020) (38 U.S.C. 4212).
____ (ii) Alternate I (JUL 2014) of 52.222-35.
X (32)(i) 52.222-36, Equal Opportunity for Workers with Disabilities (JUN 2020) (29 U.S.C. 793).
____ (ii) Alternate I (JUL 2014) of 52.222-36.
____ (33) 52.222-37, Employment Reports on Veterans (JUN 2020) (38 U.S.C. 4212).
____ (34) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (DEC 2010) (E.O. 13496).
X (35)(i) 52.222-50, Combating Trafficking in Persons (OCT 2020) (22 U.S.C. chapter 78 and E.O.
This is the start of the file's text. The full file is on GovTribe.