VA Medical Center - Long Beach, CA
ANSI/ASME A17.1 Safety & Inspection Code for Elevators & Escalators is used as standard for testing of elevator systems.
Building Name & Number
VA Medical Center – Long Beach
Elevator Number
Acceptance Test
Five-Year Test
Test Date
Address
5901 East 7th Street
Manufacturer
Speed in fpm
City
Long Beach
State
CA
Zip
90822
Alteration Date
Capacity
Passenger duty Service duty Freight duty
FIVE (5) YEAR FULL LOAD INSPECTION & TEST
GOVERNOR
Section: 2.18
Manufacturer:
Hollister-Whitney
Governor Type: Flyball Centrifugal Other
Governor Jaw Condition: ok
Fastening Condition: ok
SAFETIES
Section: 2.17
Manufacturer:
Montgomery
Safeties Type: Type “C”
Instantaneous Flexible guide
Wedge clamp Other
Safeties Condition: ok
Car stops level Record safeties rope pull-out:
If not, record distance car is out-of-level: Record # turns on drum:
BUFFERS
Section: 2.22
CAR - Buffer Type: Spring Oil Oil level: ok
Satisfactory condition after test
CWT - Buffer Type: Spring Oil Oil level: ok
Satisfactory condition after test
Stroke measurements:
Plunger return time:
Stroke measurements:
Plunger return time: _
SAFETY
SWITCHES
Section: 2.26
In-car: ok Top-of-car: ok Pit: ok Overhead: ok
Directional Limits: up down
Final Limits: up down
SOS: Comp: Buffer
Selector cable:
Slack rope:
Other: _____________________
EMERGENCY
ITEMS
Section: 2.27
Emergency Firefighters Service Mode
Phase I recall is operating: Passed Test:
Phase II recall is operating: Passed Test:
List remarks on back:
Lobby fire sign is present: ok
DOORS
Section: 2.14
Record door closing
Force:
Safety edge and other door protective devices installed and operation:
DOB: Safety edge: Detector edge: Photocell/Lightrays:
STANDBY POWER
OPERATION
Test with no load in car: Inspected: Test passed:
MAINTENANCE
AND
PERFORMANCE
Leveling: Documentation: Door operation:
Housekeeping: Car speed: Communications:
Signals: Dispatching: Lighting:
Good Maintenance disciplines are present.
VA Medical Center - Long Beach, CA
FIVE (5) YEAR FULL LOAD ELEVATOR
INSPECTION & TEST RESULTS
GOVERNOR
Section: 2.18
Gov. tripping speed: Data tag: vs Actual:
Electrical overspeed tripping speed:
Pull through set at: Gov. is sealed? Y
Calibration needed? Y N
Gov. tripped w/full load: Y
Test tags are installed: Y
SAFETIES
Section: 2.17
Test weights added
To Cab must equal
Rated Capacity
Record length of test marks on Record Gov. rope releasing carrier
Rails caused by safeties: Pull-through setting:
Safety test tags are installed: Y
OIL
BUFFERS
Section: 2.22
CAR - Test weight added to Cab Stroke measurement:
Must equal rated capacity Oil level:
Car/CWT Condition after test: ok
CWT – Test is conducted with Stroke measurement:
NO weight in the Cab Oil level:
Buffer test tags installed:
Buffer test tags installed:
BRAKE
Rule 1002.3d
Drive machine safely lowered, stopped, and held the car at the lowest landing, with 125% of rated capacity. Yes
Comments:
Lubricate Brake Assembly
EMERGENCY
ITEMS
Section: 2.25
Test Emergency Terminal
Speed limiting devices.
ok
Static Control Elevators with speeds over 500 fpm
Test Emergency Terminal stopping devices. ok
DOORS
Section: 2.14
Power opening of doors occurs in landing zone: ok
STANDBY POWER
OPERATION
Test weight is 125% of Inspected
Rated capacity Test passed
COMMENTS/RECOMMENDATIONS