Cutler PP one-line 4-2014.pdf
PDF 73 KB Posted
- Attached to
- CUTLER 480 SUB SERVICE Federal contract opportunity
- Solicitation number
- N7027223Q0005
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bustienameplate.jpg | JPG image | |
| typical AK-2-50 nameplate.jpg | JPG image | |
| typical AK-2-25nameplate.jpg | JPG image | |
| 480sublayout.jpg | JPG image | |
| Station service (SE-5-1) disconnector cabinet.jpg | JPG image | |
| 23Q0005 RFQ.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AA
BB
A1
B1
A4
B4
A5
B5
A6
B6
A8 A7
B8 B7
A13A14 A9
B14 B13 B9
A12 A10
B12 B10
"A" Bus 4,160V Unregulated
"B" Bus 4,160V Unregulated
A3
B3
Gen
Gen
Gen
Gen
Gen
750 kVA 3 0 750 kVA
3 O
Aux.
Gen #1 750 kW
Main Sta.
Serv. #1
Main Sta.
Serv. #2
G M
B15B16B17B19 B20
Unregulated Bus 4,160V B21B22
B23
Station Lighting
150 kVA 3 O 208/120V
B25
Regulated Bus 4,160V
POWER PLANT
Fuel Oil Pump House
6250 kVA 3 O
6250 kVA 3 O
T2 T14,160V
43,800V
MM M M
S2 S1S3S4
NC 480V
NCTAMSLANT DET Cutler Revision Date:
Original Drawing Date:
5 April, 2013
Original Drawing #:
Bldg. 103, Power Plant
One-line Diagram Power Distribution Systems
VLF
Transmitter Bldg.
VLF
Transmitter Bldg.
North & South Helix Houses
North & South Helix Houses
NOTES:
Deicing Transformers T1 & T2 have a Load Tap Changer (LTC) mounted on each transformer on the 4160V side.
Generator #1 has been out of service for approximately 8 years.
Engine coolant is not connected to the radiator cooling system.
Information for Generators 2, 3, 4, & 5:
kVA 3750 kW 3000 RPM 360 Amp 520 pF .8 Hz. 60 Volts 4160
Average generator load readings taken late March:
Volts 4160 kW 2,600 kVAR 1,200 Amps 413 - 509
Circuit Breaker information:
I-T-E, Type 5HV-150, Model C6, 1200 amp 4160 volt, Air Circuit Breaker, Closing volts - 125 DC Opening volts - 125 DC, Date - 10/1959
Fire Protection Pump House
MCC
6 & 7
MCC
1 & 2
MCC
3 & 4
MCC
8 & 9
Sea Water & Stripper Pump House Feeds
MCC
Westinghouse Ground Resistor:
Volts 2400 Ohms 2.67 Amps 900
General Electric, Type "CFD" High Speed Differential Relay Model # 12CFD12B2A (Generator Differential Relay)
PROTECTIVE RELAY INFORMATION:
A General Electric, Type "ICW" Power Relay Model # 12ICW51A2A (Generator Reverse Power Relay)
B
General Electric, Type "JCV" Over Current Relay w/ Voltage Restraint Model # 12JCV51A1A (Generator Over Current Relay)
General Electric, Type "DS-63" Polyphase Watt-hour Meter Cat # 700X63G108 (Watt-hour Meter)
C D
General Electric, Type "PVD" Differential Voltage Relay Model # 12PVD11C1A (High Speed Bus Differential Relay)
General Electric, Type "IAC" Time Over Current Relay Model # 12IAC51_ _ _ (Over Current Relay)
E F
General Electric, Type "TMC" Thermal Overload Relay Model # 12TMC11B42A (Motor Overload Relay)
G General Electric, Type "IAV" Voltage Relay Model # 12IAV54E1A (Under Voltage Relay)
H
Generator Relays= A A A B C
Breaker AA, BB, A1, B1, A3, B3, A10, B10, A12, B12 Relays = D D E
"A" Bus Relay = F F"B" Bus Relay =
F F
F F
Breaker A4, B4, A5, B5, A6, B6, A7, B7, A8, B8, A9, B9, A13, B13, A14, B14, B19, B20, B21, B22 Relays= EE E Breaker B17 Relays = G H
Drawn By:
SWS
5 May, 2013
Revision Date: 22 Jan, 2014
MG Set 4,160V
Revision Date: 23 Oct, 2013
FOR OFFICIAL USE ONLY
Model