Architect of Record:
IBI Group of Virginia, Inc.
1505 Prince Street, Suite 200 Alexandria Va, 22314 703-836-9600 POC: Valeri Vanchieri, Associate - Lead Designer
Sanda Iliescu, Project Architect Peter Boccia, Associate, Technical Director
Client:
The District of Columbia Courts Capital Projects and Facilities Management Division 616 H Street, NW, Suite 622 Washington, DC 20001 202-879-2801 POC: Judith Hill, Project Manager Judith.Hill@dcsc.gov | Office: 202 879-2871
Partition Type
Furnishing References
Keynote Reference
Finish Reference
Revision Reference
Detail Reference
Room Number Reference
Partition Reference Column Grid Reference
Elevation Reference
Top of Steel El: 10'-0" AFF
Column Grid Reference Number
Drawing Number
Sheet Number
Finish Type
Keynote Reference Number (Prefix may vary) x-1
Revision Number
Room Number
Description of Mark
Elevation Reference Dimension
Item Reference for Millwork, Furniture, Equipment, etc.
Elevation Reference
Drawing Number
Sheet Number
Section Reference
Drawing Number
Sheet Number
Door Number Reference
Door Number
Blocking Reference
Note: Where multiple suites are part of the Scope, refer to Door Schedule for full Door Number.
Indicates side(s) of partition to receive wood blocking for wall mounted eqpt. or furniture. If no dimension is given, blocking extends full width of indicated partition.
Not in Contract (NIC)
Hidden Lines or Items Above
Centerlines, Projected Lines
Partition Reference
Existing Partition to Remain
Existing Partition to be Demolished
New Ceilng-High Partition
Slab High Partition
Hatching Reference
Linetype Reference
AK-01
A.101
B
Millwork
Signage Note: See Sign Plan x X
NAT
NRC
NOM
N
NIC
NTS
natural noise reduction coefficient nominal north not in contract not to scale
OC
OPG
OPP
OA
OH
on center(s) opening opposite overall overhead
PNT
PNL
PAR
PBD
PTN
PED
PLAM
PWD
PT
POL
P/D/T
PFAB
PFIN
PREP
paint(ed) panel parallel particle board partition pedestal plastic laminate plywood point polished power/data/telephone prefabricate(d) prefinished preparation
QT quarry tile angle at centerline number plate round/phase (elec.)
AFF
ACT
ADJ
A/C
ALT
above finished floor acoustical tile adjacent air conditioning alternate
BLK
BLKG
block blocking
CPT
CLG
CT
CLR
COL
CONC
CMU
CONS
T
CONT
carpet(ed) ceiling ceramic tile clear(ance) column concrete concrete masonry unit construction continuous or continue
DTL
DIAG
DIAM
DIM
DIV
DBL
DN
DWR
DWG
detail diagonal diameter dimension division double down drawer drawing
EA
E
ELEC
EL
ELEV
EMER
ENCL
EQ
EQPT
EST
EXH
EXIST.
EXP
EXT
each east electric(al) elevation elevator emergency enclose(ure) equal equipment estimate exhaust existing exposed exterior
HDW
HWD
HDR
HTG
HVAC
HT
HC
hardware hardwood header heating heating/ventilating/ air conditioning height hollow core
JC
JT
JB
janitor's closet joint junction box
KD
KO
knock down knock out
LBS
LAM
LAV
L
LT
LF
LG
pounds laminate(d) lavatory length light linear feet long
IN
INCL
INFO
ID
INST
INT
inch include(d), (ing) information inside diameter install(ed), (ation) interior
HM
HO
R hollow metal horizontal
MFR
MAS
MAX
MED
MET
MEZZ
MWK
MIN
MISC
MOD
MLDG
MTD
manufacture(r) masonry maximum medium metal mezzanine millwork minimum miscellaneous modular molding, moulding mount(ed), (ing)
RAD
REC
REF
REQ
RES
RA
REV
RH
RM
RO
R radius recessed reference require(d) resilient return air revision(s), revised right hand room rough opening riser
SCH
SEC
SEP CIR
SHT
SIM
SC
STC
S
SPKR
SPEC
SQ
SF
SS
STD
STL
SUS
SYS
schedule section separate circuit sheet similar solid core sound transmission class south speaker specification(s) square square feet stainless steel standard steel suspended system
TKBD
TEL
THK
T
TOS
TYP
tackboard telephone thick(ness) tread top of slab typical
UNF
UNO
VFY
VIF
VERT
VWC
VT
V unfinished unless noted otherwise verify verify in field vertical vinyl wall covering vinyl tile volt wainscoat wall to wall wall hung water closet watt weight west width, wide with without wood
WSCT
WTW
WH
WC
W
WT
W W W/ W/O
WD
ɸ
GA
GC
GL
GFI
GYP
BD
gage, gauge general contract(or) glass, glazing ground fault interrupter gypsum wall board
FAB
FT
FIN
FFE
FFL
FA
FE
FEC
FHS
FLR
FLUOR
FH
FS
FW
FBO
FBT
FUT
fabric feet, foot finish(ed) finished floor elevation finished floor line fire alarm fire extinguisher fire extinguisher cab.
fire hose station/ fire standpipe floor(ing) fluorescent full height full size full width furnished by others furnished by tenant future
NO
RT
H
F Street
National Building Museum
E Street
5t h
St re et
4t h
St re et
Judiciary Square
National Law Enforcement
Officer's Memorial 515 5th Street
510 4th Street
MJudiciary Square Metro Station
Probate Division 3rd Floor
Probate
131 SF
OFFICE 316C: 2
125 SF
316B: 3 1590 SF
OPEN OFFICE 316
A: 1
462 SF
WAITING 315: 4 1496 SF
OPEN OFFICE
314A: 5
148 SF
PUBBLIC
CORRIDOR 318a:
6 1735 SF
Area: 7
157 SF
Area: 8
OPEN OFFICE
304A
OFFICE
304G
A
17' - 6"
53' - 0"
9'
STAIR #3
3_3
STAIR #5
3_5
STAIR #4
3_4
B
18' - 6"
9' - 6"
13' - 0"
8'
C
35' - 4"
7' - 8"
D
20' - 6"
51' - 0"
9'
2013 DCMR 12
2012 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL MECHANICAL CODE
2012 INTERNATIONAL PLUMBING CODE
2012 INTERNATIONAL FIRE CODE
2012 INTERNATIONAL ENERGY CONSERVATION CODE
2012 INTERNATIONAL EXISTING BUILDING CODE
PROJECT AREA = 5,824 SF
SCOPE OF WORK: RENOVATE 5,824 SF OFFICE SPACE INSIDE AT THE THIRD FLOOR OF AN EXISTING BUILDING LOCATED AT 515 5TH STREET NW, WASHINGTON DC. THE RENOVATION INCLUDES REORGANIZING EXISTING SYSTEM FURNITURE AND NEW FINISHES.
EXISTING BUILDING TYPE IB CONSTRUCTION
EXISTING BUILDING 3 STORIES + BASEMENT.
YEAR OF CONSTRUCTION: 1938
BUILDING'S STRUCTURAL FRAME: PROTECTED STEEL/ POSSIBLY CLASS 2 FIRE PROTECTED STRUCTURE 1938 BUILDING CODE
BUILDING IS SPRINKLERED.
BUILDING OCCUPANCY: MIXED USE B, A-3, S-2
AREA OF RENOVATION OCCUPANCY: B
TOTAL OCCUPANCY LOAD = 58 OCCUPANTS
REQUIRED NUMBER OF EXITS : 2 (SECTION 1015 IBC)
NUMBER OF EXITS PROVIDED : 3
EXIT ACCESS TRAVEL DISTANCE MAXIMUM ALLOWED = 300FT FOR FULLY SPRINKLERED BUILDINGS
EXIT ACCESS TRAVEL DISTANCE MAXIMUM PROVIDED = 121FT
SYMBOL KEY
FE FIRE EXTINGUISHER
1. THIS DRAWING IS FOR FIRE AND LIFE SAFETY PURPOSES ONLY.
2. MAXIMUM TRAVEL DISTANCE NOT TO EXCEED 300'
3. SEE REFLECTED CEILING PLAN FOR EXIT LIGHT LOCATIONS.
PATH OF TRAVEL
NOTES
1 HR PARTITION
2 HR PARTITION
XX
XXX
ACTUAL NUMBER OF OCCUPANTS USING THE DOOR
MAXIMUM EGRESS CAPACITY OF THE DOOR
XX OCC OCCUPANCY LOAD
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Design Intent Documents for Interior Improvement to:
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
De sig n I nt en t D oc um en ts for In ter ior
Im pr ov em en t t o:
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
08/18/2017
A000115.2153
Cover Sheet
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318
515 5th Street (Building A) Washington DC, NW 20001
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird F loo r, Ro om s 3
, 3
, 3
, 3
, 3
Sheet: Revision:
No. Title 1 2 3 4 5 6 7 8
A0001 Cover Sheet A0002 General Notes A0003 Schedules/ Standard Details A0004 Door Schedule, Details A0005 Phasing Plans A0006 Phasing Plans A0007 Demolition Plans A0008 Floor Plans A0009 Finish Plan A0010 Power and Data Plan A0011 Details A0012 Details A0013 Intake Counter Details A0014 Existing Furniture Plan A0015 Furniture Plan
Project Team
Index of DrawingsStandard Drawing Symbols
Abbreviations
Start Path of Travel EXIT
A 117' - 0" Stair #3 B 95' - 8" Stair #3 C 108' - 0" Stair #5 D 121' - 0" Stair #4
Key Plan - Judiciary Square
Life Safety Plan
DESIGN INTENT (50%) REVIEW AND PRICING 08/18/2017
Life Safety Symbols
1. ALL FINISHES SHALL BE APPLIED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. A COPY OF THE RECOMMENDATIONS AND INSTRUCTIONS SHALL BE SUBMITTED TO THE DESIGNER PRIOR TO THE INSTALLATION OF MATERIALS.
2. UNLESS OTHERWISE NOTED, ALL PAINT IS TO BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
3. ALL CHANGES IN FLOOR MATERIAL AND COLORS SHALL OCCUR AT THE CENTERLINE OF DOORWAYS UNLESS NOTED OTHERWISE.
4. PAINT ALL UNFINISHED MATERIALS, GRILLES, REGISTERS, ETC, TO MATCH ADJACENT WALLS. MATERIALS WITH A NATURAL FINISH, SUCH AS ANODIZED ALUMINUM, SHALL BE LEFT IN THEIR NATURAL FINISH UNLESS OTHERWISE NOTED BY THE CONSTRUCTION DOCUMENTS.
5. SEE REFLECTED CEILING PLANS FOR CEILING FINISHES.
6. PROVIDE LEVEL 4 FINISH FOR ALL GYPSUM BOARD SURFACES IN PREPARATION FOR APPLICATION OF NEW FINISHES, INCLUDING EXISTING
SURFACES THAT ARE TO BE PAINTED.
7. APPLY ONE PRIMER COAT AND TWO FINISH COATS ON SURFACES TO BE PAINTED.
8. PREPARE FLOOR FOR INSTALLATION OF FINISHES IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
REMOVE ALL FOREIGN MATTER, GREASE, WAX, PAINT, OIL, ADHESIVES, DIRT, ETC. CRACKS, HOLES AND DEPRESSIONS SHOULD BE FILLED WITH FLASHING COMPOUND OR LATEX PATCH MATERIAL. CUT OFF ANY PROTRUDING OBJECTS AND GRIND SMOOTH TO LEVEL WITH THE FLOOR
SURFACE.
9. INSPECT FLOOR CONSTRUCTION AND SURFACES TO RECEIVE NEW FINISHES AND PROMPTLY NOTIFY THE ARCHITECT OF ANY DEFECTS IN THE SUBSTRATE THAT AFFECT THE WORK SO THAT THEY MAY BE CORRECTED BEFORE THE START OF THE WORK. PROCEEDING WITH THE WORK SHALL BE DEEMED AS ACCEPTANCE BY THE CONTRACTOR OF THE FLOOR AREAS AND HE SHALL BE RESPONSIBLE THEREAFTER FOR THE
INSTALLATION OF THE WORK.
10. INSTALL FLOORING MATERIALS WITHIN THE ALLOWABLE TEMPERATURE RANGE AS STATED BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL FLOORING MATERIAL SHALL BE DELIVERED TO THE SITE IN TIME TO ACCLIMATE TO CONDITIONS PRIOR TO INSTALLATION.
SUBMIT A COPY OF THE INSTALLATION INSTRUCTIONS SHALL BE SUBMITTED TO THE ARCHITECT AND THE OWNER.
11. COORDINATE THE SCHEDULED RESILIENT FLOOR LAYOUT FITTING AND SEAM LOCATION WITH ARCHITECT PRIOR TO INSTALLATION.
12. PROVIDE AND INSTALL THE SCHEDULED RESILIENT WALL BASE AS STYLE COVE BASE WITH TOP-SET TOE IN AREAS SCHEDULED TO RECEIVE
RESILIENT FLOORING. BASE SHALL HAVE PREMOLDED INSIDE AND OUTSIDE CORNERS.
13. REFER TO DOOR AND HARDWARE SCHEDULE FOR DESIGNATED FINISHES OF DOORS AND FRAMES.
14. ALL ELECTRICAL SWITCHES, OUTLETS AND COVER PLATES SHALL BE A PAINTABLE FINISH. COORDINATE THE COLOR/FINISH OF ALL ELECTRICAL
SWITCHES, OUTLETS AND COVER PLATES WITH ARCHITECT. SUBMIT SAMPLES FOR APPROVAL.
15. INSTALL SCHEDULED CARPET TILE AS INDICATED IN FLOOR PLANS. CONTRACTOR TO PROVIDE A DRY LAY FOR REVIEW IN FIELD BY ARCHITECT.
1. SEE THE REFLECTED CEILING PLAN FOR CEILING HEIGHTS.
2. UNLESS INDICATED OTHERWISE BY THE DRAWINGS, CENTER ALL SUSPENDED CEILINGS IN THE SPACE OR SPACES IN WHICH THEY OCCUR SUCH THAT THE WIDTH OF THE PERIMETER TILES IS GREATER THAN ONE-HALF OF THE WIDTH OF A STANDARD TILE.
3. UNLESS NOTED OTHERWISE, LOCATE ALL NEW SWITCHES AT 45" A.F.F. TO CENTER LINE OF SWITCH(IS) IN ACCORDANCE WITH THE
ADA ACCESSIBILITY GUIDELINES.
4. INSTALL ALL FIXTURES AND WIRE THOSE REQUIRED TO BE CONNECTED TO EMERGENCY CIRCUITS AND EXIT LIGHTS, BASED ON APPLICABLE CODES AND REVISE FINAL LOCATION, SUBJECT TO THE FINAL REVIEW OF THE ARCHITECT.
5. FURNISH AND INSTALL IN QUANTITY AND TYPE ALL LIGHT BULBS TOGETHER WITH ALL MATERIALS INCIDENTAL THERETO, AS SHOWN ON THE REFLECTED CEILING PLAN, UNO. LOCATIONS OF ANY ITEM NOT SHOWN OR SPECIFICALLY LOCATED ON THE REFLECTED CEILING PLANS SHALL BE FIELD COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION.
6. COORDINATE THE INSTALLATION AND VERIFY THE REQUIRED LOCATION OF ANY/ALL SUPPLEMENTAL MECHANICAL, ELECTRICAL, OR PLUMBING EQUIPMENT. FURNISH AND INSTALL ANY REQUIRED SUPPLEMENTAL STRUCTURE WHICH MAY BE REQUIRED FOR THE
SUPPORT OF SAID EQUIPMENT WHETHER SPECIFICALLY NOTED IN PLAN OR NOT.
7. SUPPLY FINISH TRIM WHERE REQUIRED FOR ALL CEILING MOUNTED LUMINARIES WHICH IS DESIGNED FOR USE IN THE CEILING
WHERE IT OCCURS.
8. FIXTURES ON SUSPENDED CEILING SHALL BE SUPPORTED FROM THE FLOOR ABOVE BY MEANS OF A MINIMUM OF TWO CHAINS PER
FIXTURE; EACH CHAIN CAPABLE OF SUPPORTING 100 LBS.
9. PERFORM SELECTIVE DEMOLITION AS REQUIRED FOR THE MODIFICATION/INSTALLATION OF EQUIPMENT AND DEVICES WHETHER SPECIFICALLY NOTED IN PLAN OR NOT. RETURN THE SURROUNDING SURFACES AND SUBSTRUCTURE TO "LIKE-NEW" CONDITION OR
REPLACE AS REQUIRED TO PROVIDE A SUITABLE SUBSTRATE FOR NEW FINISHES.
1. FIXTURES, LAMPS AND RELATED DEVICES FURNISHED UNDER THIS CONTRACT SHALL CARRY THE APPROVAL LABEL OF UL OR ETL FOR THE
SPECIFIC APPLICATION IN WHICH THEY ARE USED.
2. UNLESS OTHERWISE INDICATED, ALL FLUORESCENT LAMP BALLASTS SHALL BE ELECTRONIC TYPE. DIMMING BALLASTS AND BALLASTS FOR USE WITH DAYLIGHT-HARVESTING SHALL BE COMPATIBLE WITH THE CONTROL SYSTEM THAT WILL BE OPERATING THEM, PER THE ELECTRICAL
ENGINEER.
3. LED DIMMING DRIVERS SHALL BE COMPATIBLE WITH THE CONTROL SYSTEM THAT WILL BE OPERATING THEM, AS SPECIFIED BY THE
ELECTRICAL ENGINEER.
4. UNLESS OTHERWISE NOTED, FLUORESCENT LAMP DESIGNATIONS ARE FOR LAMPS BY OSRAM/SYLVANIA. LAMPS OF EQUIVALENT CHARACTERISTICS WITH EQUAL OR BETTER PERFORMANCE CHARACTERISTICS FROM PHILIPS LIGHTING AND GENERAL ELECTRIC ARE
ACCEPTABLE ALTERNATIVES.
5. CONFIRM THAT FIXTURE VOLTAGES AND FIXTURE CEILING TRIMS ARE COMPATIBLE WITH THEIR APPLICATION PRIOR TO ORDERING FIXTURES.
6. CONTRACTOR SHALL SUPPLY, FOR REVIEW BY THE ARCHITECT AND/OR LIGHTING CONSULTANT, ONE WORKING SAMPLE (120V), WITH CORD AND PLUG, OF EACH LED FIXTURE VARIETY IN THE FINAL SPECIFICATIONS. IF THE FIXTURE IS TO BE DIMMED, A FUNCTIONAL DIMMER OF THE SAME TYPE AS THE INTENDED CONTROL SYSTEM SHALL BE SUPPLIED WITH THE FIXTURE SAMPLE, SO THE DIMMING RESPONSE CAN BE TESTED AND DEMONSTRATED. CONTRACTOR TO PROVIDE UPDATED LIGHTING "FACTS SHEET" FOR EACH LED PRODUCT.
7. FURNISH AND INSTALL THE CORRECT SIZE OF SECONDARY WIRING FROM REMOTE TRANSFORMERS, DRIVERS, AND/OR REMOTE BALLASTS AS
REQUIRED TO KEEP VOLTAGE DROP IN THE SECONDARY WIRING BELOW 3% OF RATED VOLTAGE.
8. PROVIDE LABOR AND EQUIPMENT FOR FOCUSING OF ADJUSTABLE FIXTURES AND PRESETTING OF LIGHTING CONTROL SYSTEMS. FOCUSING AND PRESETTING SHALL BE DONE IN THE PRESENCE OF THE DESIGN PROFESSIONAL. FOCUS LIGHTING AFTER DARK IF DIRECTED BY THE OWNER'S REPRESENTATIVE. PROVIDE AT LEAST ONE DAY OF A FACTORY-TRAINED AND CERTIFIED TECHNICIAN TO PROVIDE WARRANTY START UP AND PROGRAMMING FOR ALL LIGHTING CONTROL SYSTEMS AND PROGRAMMABLE LIGHTING FIXTURES.
9. PROVIDE THE FOLLOWING WITH BID:
A. THE TOTAL QUANTITY OF EACH LIGHT BULB TYPE WITH THE PRICE EXTENSION FOR THAT QUANTITY.
10. WITHIN 21 DAYS OF CONTRACT AWARD, FURNISH SUBMITTALS FOR ALL SPECIFIED LIGHTING FIXTURES FOR REVIEW BY THE DESIGN PROFESSIONAL. THE SUBMITTALS SHALL INCLUDE LUMINAIRE CATALOG CUTS INDICATING THE FOLLOWING:
A. MANUFACTURER'S NAME AND COMPLETE CATALOG NUMBER
B. FIXTURE TYPE, DIMENSIONS AND FINISH
C. FIXTURE PHOTOMETRIC TEST DATA FROM AN INDEPENDENT TEST LABORATORY
D. FIXTURE ACCESSORIES, WHEN SPECIFIED
E. LAMP TYPE, QUANTITY, WATTAGE, LUMEN OUTPUT, RATED LIFE, COLOR TEMPERATURE, COLOR RENDERING INDEX AND BEAM SPREAD
AS APPLICABLE
F. BALLAST TYPE AND FIXTURE VOLTAGE
11. SUBMITTALS FOR LIGHTING FIXTURES MOUNTED WITHIN ARCHITECTURAL COVES OR CASEWORK, AND FOR NON-STANDARD OR CUSTOM FIXTURES, SHALL ALSO INCLUDE SCALED DRAWINGS SHOWING THE LAYOUT AND DIMENSIONS OF ALL FIXTURE COMPONENTS AND
ACCESSORIES, THE METHOD OF INSTALLATION, AND A COMPLETE BILL OF MATERIALS.
1. INSTALLATION OF ALL COURTS TELECOMMUNICATIONS/CABLING SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, AND IS THE RESPONSIBILITY OF THE CONTRACTOR TO COMPLY WITH THE LATEST VERSION.
• ANSI/NFPA 70; NATIONAL ELECTRICAL CODE
• ANSI/TIA 455-78-B OPTICAL FIBERS-PART 1-40: MEASUREMENT METHODS AND TEST PROCEDURES
• ANSI/TIA-598-C OPTICAL FIBER CABLE COLOR CODING
• ANSI/TIA 526-7 OPTICAL POWER LOSS MEASUREMENTS OF INSTALLED SINGLE-MODE FIBER CABLE PLANT
• ANSI/TIA 526-14-A OPTICAL POWER LOSS MEASUREMENTS OF THE INSTALLED MULTIMODE FIBER CABLE PLANT
• ANSI/TIA 606-A ADMINISTRATION STANDARDS FOR THE TELECOMMUNICATIONS INFRASTRUCTURE OF COMMERCIAL BUILDINGS
• ANSI/J-STD 607-A COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS
• ANSI/TIA 569-B ANSI/TIA 568-B COMMERCIAL BUILDING STANDARDS FOR TELECOMMUNICATIONS PATHWAYS AND SPACES TIA/TSB 140
ADDITIONAL GUIDELINES FOR FIELD-TESTING LENGTH, LOSS AND POLARITY OF OPTICAL FIBER CABLING SYSTEMS.
a. INSTALLERS SHOULD ALWAYS FOLLOW THE NESC, NEC, APPLICABLE STATE AND LOCAL REGULATORY CODES, MANUFACTURER'S INSTRUCTION, AND THE DISTRICT OF COLUMBIA COURTS CABLE & WIRE MANAGEMENT PROCEDURES MANUAL WHEN INSTALLING
TELECOMMUNICATION CABLING PRODUCTS AND SYSTEMS.
2. PRIOR TO BEGINNING ANY WORK, SECURE NECESSARY PERMITS OR CLEARANCES FROM THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL LABOR AND MATERIALS FOR A COMPLETE INSTALLATION. WORK SHALL BE ONLY EXECUTED BY EXPERIENCED AND QUALIFIED PERSONS WHO ARE
CERTIFIED IN THE JURISDICTION WHERE THE PROJECT IS LOCATED.
3. THE CONTINUITY OF ALL EXISTING CABLING IDENTIFIED AND INDICATED TO REMAIN SHALL BE MAINTAINED U.O.N. ALL CABLE, WIRE CONDUIT, OR OTHER COMPONENTS THAT ARE DESIGNATED TO BE DECOMMISSIONED SHOULD BE REMOVED. COORDINATE FULL SCOPE OF WORK WITH CM/PM CPFMD AND COURT'S IT AND/OR TELECOMMUNICATION REPRESENTATIVES PRIOR TO COMMENCING ANY WORK.
4. THE POWER DATA & TELEPHONE PLANS ARE DIAGRAMMATIC ONLY. COORDINATE ALL TELECOMMUNICATIONS EQUIPMENT, CABLING REQUIREMENTS, TELECOMMUNICATION CLOSET LOCATIONS AND INSTALLATION WITH CM/PM CPFMD AND COURT'S IT AND/OR
TELECOMMUNICATION REPRESENTATIVES.
5. ALL EQUIPMENT SHALL BE "UL" LABELED U.O.N.
6. CONTRACTOR SHALL COORDINATE THE SCHEDULING OF ALL WORK WITH CM/PM AND ALLOW SUFFICIENT TIME FOR COORDINATION OF EXISTING
BUILDING ACTIVITIES WITH THE CONSTRUCTION SCOPE OF WORK.
7. TELECOMMUNICATION CABLING SHALL BE TAGGED AT EACH END AND TERMINATED IN ACCORDANCE WITH THE COURTS CABLE & WIRE
MANAGEMENT PROCEDURES MANUAL
8. QUAINTLY OF DROPS MAY NOT BE INDICATED FOR ALL LOCATIONS, NOTE IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL CABLING NECESSARY FOR THE PROPER FUNCTION OF EQUIPMENT, DEVICES, ETC. REFER TO ARCHITECTURAL / ENGINEERING DRAWINGS FOR RECEPTACLE LOCATIONS. ALL WORK THAT CONNECTS/TERMINATES TO AN EXISTING BUILDING SYSTEM SHALL BE COORDINATED WITH CM/PM, CPFMD AND COURT'S IT AND OR TELECOMMUNICATION REPRESENTATIVES.
9. CONTRACTOR SHALL NOTE FOR ALL CABLE TRAY PLANNING AND INSTALLATION OF CABLE TRAY SHALL BE INSTALLED IN ACCORDANCE WITH GUIDELINES AND RECOMMENDATIONS CONTAINED WITHIN NECA/BICSI 568-2006 (STANDARD FOR INSTALLING COMMERCIAL BUILDING TELECOMMUNICATION CABLE-ANSI). CONTRACTOR TO CONSULT THE DISTRICT OF COLUMBIA COURTS CABLE & WIRE MANAGEMENT PROCEDURES
MANUAL FOR FLEXTRAY SYSTEM CUT SHEETS AND TECHNICAL SPECIFICATION.
10. EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION DURING CONSTRUCTION IN EXISTING BUILDING. WITH WRITTEN APPROVAL FROM THE FIRE MARSHALL AND THE OWNER, EXISTING FIRE ALARM DEVICES IN THE AREA OF CONSTRUCTION MAY BE DISCONNECTED FROM SERVICES DURING CONTRACTOR'S WORKING HOURS. WHEN THE CONTRACTOR IS FINISHED FOR THE DAY, THE FIRE ALARM DEVICES SHALL BE RECONNECTED AND BACK IN OPERATION. FIRE ALARM DEVICES MUST BE COVERED OR OTHERWISE PROTECTED FROM DUST AND DEBRIS DURING CONSTRUCTION.
11. ALL FIRE ALARM WORK SHALL BE PERFORMED BY THE BASE BUILDING FIRE ALARM CONTRACTOR. GENERAL CONTRACTOR SHALL OBTAIN THE
SERVICES OF THE BASE BUILDING FIRE ALARM CONTRACTOR.
12. PROVIDE EMPTY CONDUIT WITH PULL STRING FOR ALL SECURITY DEVICES UP TO THE SECURITY JUNCTION BOXES/TROUGHS. COORDINATE CONDUIT SIZE AND EXACT LOCATION OF ALL SECURITY DEVICES WITH SECURITY VENDOR/TYCO, CM/PM & ARCHITECT PRIOR TO INSTALL.
1. UNLESS OTHERWISE INDICATED BY THE CONSTRUCTION DOCUMENTS,ALL ITEMS OF CONSTRUCTION ARE TO BE FURNISHED AND INSTALLED BY THE CONTRACTOR
AND/ OR HIS SUBCONTRACTORS.
2. WHEN REFERRED TO IN THE CONSTRUCTION DOCUMENTS THE TERM "DC COURTS" AND/ OR "OWNER" SHALL REFER THE DISTRICT OF COLUMBIA COURTS CAPITAL PROJECTS AND FACILITIES MANAGEMENT DIVISION (CPFMD) AND/ OR THEIR APPROUVED REPRESENTATIVES, UNLESS NOTED OTHERWISE.
3. WHEN REFERRED TO IN THE CONSTRUCTION DOCUMENTS THE TERM "WORK" SHALL REFER TO THE PERFORMANCE AND/ OR COORDINATION OF WORK RELATED TO INTERIOR FIT-OUT OF THE PROJECT INCLUDING ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND AUDIO-VISUAL DISCIPLINES.
4. WHEN REFERRED TO IN THE CONSTRUCTION DOCUMENTS THE TERM "FURNISH", "INSTALL", "PROVIDE" AND ANY FORM OF DIRECTION THEREOF USED IN THE CONSTRUCTION DOCUMENTS, ARE DIRECTING THE CONTRACTOR TO BOTH FURNISH AND INSTALL ANY GIVEN ITEM AND ITS INCIDENTAL MATERIALS, UNLESS NOTED
OTHERWISE.
5. THE WORK INCLUDES BUT IS NOT NECESARELY LIMITED TO THE FOLLOWING. THIS LIST IS SOLELY FOR THE GENERAL INDICATION OF ITEMS INVOLVED IN THE WORK. IT IS IN NO PARTICULAR ORDER AND IT IS NOT MEANT TO BE A SUGGESTED SEQUENCING.
6. THE REMOVAL OF EXISTING LIGHTFIXTURES AS INDICATED BY THE CONSTRUCTION DOCUMENTS.
7. THE DEMOLITION AND DISPOSAL OF ALL EXISTING MATERIALS AND CONSTRUCTS, TOGETHER WITH ALL MATERIALS INCIDENTAL THERETO, AS INDICATED BY THE CONSTRUCTION DOCUMENTS. SAID MATERIALS AND CONSTRUCTS INCLUDE, BUT ARE NOT NECESSARILY LIMITED TO:
A. PARTITIONS,
B. ACOUSTICAL CEILING TILES, SUSPENSION GRID, AND HANGER WIRE,
C. EXIT SIGNAGE AND OTHER CEILING MOUNTED DEVICES,
D. CARPET AND BASE MATERIALS,
E. SELECTIVE CONCRETE FLOOR SLAB DEMOLITION,
F. LIMITED DEMOLITION OUTSIDE OF THE PROJECT AREA AS MAY BE NECESSARY FOR THE COMPLETION OF THE WORK.
G. DOOR + FRAME ASSEMBLIES UNLESS NOTED TO BE REUSED,
8. THE CLEANING AND PREPARATION OF SURFACES TO RECEIVE NEW FINISHES OR CONSTRUCTS AS INDICATED BY THE CONSTRUCTION DOCUMENTS. PREPARATION SHALL BE IN ACCORDANCE WITH THE RECOMMENDATIONS AND SPECIFICATIONS OF THE RESPECTIVE MANUFACTURER.
9. THE INSTALLATION OF NEW WORK AS INDICATED BY THE CONSTRUCTION DOCUMENTS.
10. THE INSTALLATION OF CEILING BULKHEADS AND SUPPORT FRAMING.
11. THE ERECTION OF NEW GYPSUM BOARD PARTITIONS AND CEILING ASSEMBLIES.
12. THE INSTALLATION OF ALL STOREFRONT, DOORS AND HARDWARE.
13. THE INSTALLATION OF ALL FINISHES AND ACCESSORIES AS INDICATED BY THE CONSTRUCTION DOCUMENTS.
14. THE INSTALLATION OF ALL MILLWORK AS INDICATED BY THE CONSTRUCTION DOCUMENTS TOGEATHER WITH NECESSARY BLOCKING FOR SUPPORT.
15. THE INSTALLATION OF SUSPENDED ACOUSTICAL ASSEMBLIES.
16. THE INSTALLATION OR REINSTALLATION OF ALL LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES INDICATED BY THE CONSTRUCTION DOCUMENTS
TOGETHER WITH ALL MATERIALS INCIDENTAL THERETO.
17. THE RECONFIGURATION OF THE EXISTING AUTOMATIC SPRINKLER SYSTEM TO ACCOMMODATE THE PROPOSED LAYOUT.
18. THE INSTALLATION OF ALL FIRE AND LIFE SAFETY DEVICES AS INDICATED BY THE CONSTRUCTION DOCUMENTS AS REQUIRED BY CODE.
19. COORDINATION OF WORK WITH THE DC COURTS SECURITY VENDOR AND THE PROVISION OF ROUGH-IN WORK THAT THEY MAY REQUIRE, WHETHER SPECIFICALLY
NOTED IN PLAN OR NOT.
20. THE REPAIR AND/OR REPLACEMENT OF EXISTING CONSTRUCTION TO REMAIN THAT WAS REMOVED FOR THE INSTALLATION OF WORK OR WHICH WAS DAMAGED AS A
RESULT OF THE WORK.
21. FURNISH AND INSTALL AUDIO/VISUAL EQUIPMENT AS SPECIFIED, WITH PROVISION OF ANY ELECTRICAL, DATA CONNECTION SERVICES THAT MAY BE REQUIRED TO
FACILITATE A COMPLETE AND PROPER FUNCTION OF EQUIPMENT, DEVICES, ETC.
22. COORDINATION OF WORK WITH CM/PM PROVISION OF ANY EXISTING FF&E TIEMS AS SPECIFIED IN DOCUMENTS FOR RELOCATION OR DESPOSAL .
23. COORDINATION OF WORK REQUIRED TO FURNISH AND INSTALL FF&E ITEMS, IN QUANTITY AND TYPE, TOGETHER WITH ALL MATERIALS INCIDENTAL THERETO, WITH VENDORS, INSTALLERS, AND THE PROVISION OF ANY ELECTRICAL, DATA OR TELEPHONE CONNECTION SERVICES THAT MAY BE REQUIRED TO FACILITATE A COMPLETE SCOPE OF WORK WHETHER INDICATED IN DOCUMENTS OR NOT. NOTE PROVISION FOR ANY ITEM NOT SHOWN OR SPECIFICALLY INDICATED IN
DOCUMENTS SHALL BE COORDINATED WITH CM/PM AND ARCHITECT PRIOR TO INSTALLATION.
1. THE INTENT OF THESE DRAWINGS IS TO PROVIDE GENERAL GUIDELINES FOR THE SELECTIVE DEMOLITION OF PORTIONS OF ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PIPING SYSTEMS SERVING THE BUILDING. NOTE THAT THE CONTRACTOR IS OBLIGATED TO EXAMINE THE PLANS. ANY OBSERVED
DISCREPANCIES BETWEEN THE DRAWINGS AND FIELD CONDITIONS SHALL BE CALLED TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY, REQUESTING CLARIFICATION SO THAT THE MATTER MAY BE RESOLVED PRIOR TO SUBMISSION OF BIDS. NOTE THAT BY SUBMISSION OF BID THE CONTRACTOR SHALL ACKNOWLEDGE ACCEPTANCE OF THESE DOCUMENTS AS ADEQUATE DEFINITION OF THE SCOPE OF WORK AND EXTRA COST CLAIMS ON INADEQUACY OF THE
DOCUMENTS WILL NOT BE CONSIDERED.
2. BEFORE SUBMITTING A PROPOSAL, ALL CONTRACTORS SHALL VISIT THE PREMISES, FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS, AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF THE WORK AND THE DIFFICULTIES THAT ATTEND ITS SUCCESSFUL EXECUTION AND COMPLETION OF THE WORK
AS INDICATED IN THE DOCUMENTS.
3. ALL WORK ON THIS PROJECT SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST APPLICABLE CODES AND REGULATIONS.
4. CODES AND REGULATIONS: CONFORM TO CODES AND REGULATIONS CURRENTLY IN FORCE BY THE DISTRICT OF COLUMBIA. SAID DOCUMENTS INCLUDE, BUT
ARE NOT LIMITED TO, THE FOLLOWING:
A. 2012 INTERNATIONAL BUILDING CODE
B. 2012 INTERNATIONAL FIRE PREVENTION CODE
C. 2013 DCMR 12 BUILDING CODE REGULATIONS
D. 2015 ARCHITECTURAL BARRIERS ACT STANDARDS
5. THE WORK DETAILED ON THESE PLANS IS BASED ON PREVIOUSLY PREPARED BASE BUILDING DRAWINGS WHERE EXISTING FIELD CONDITIONS MAY BE DIFFERENT THAN SHOWN. ADVISE THE ARCHITECT OF DISCREPANCIES WHICH WILL AFFECT THE PROPOSED WORK PRIOR TO BEGINNING ANY WORK.
6. SYMBOLS SHOWN ON LEGEND DEFINE TYPE OF ITEMS ONLY. CONTRACTOR IS RESPONSIBLE FOR RESEARCHING DRAWINGS FOR EXACT CONSTRUCTION
MATERIALS OR QUANTITIES OF EACH.
7. ALL WORK DEMOLISHED SHALL BE REMOVED FROM THE PREMISES EVERY DAY, EXCEPT ITEMS INDICATED TO BE REUSED OR RETURNED TO THE OWNER. REFER TO SPECIFICATION SECTION 02 4119 SELECTIVE DEMOLITION - SELECTIVE DEMOLITION SCHEDULE.
8. VERIFY ALL POINTS OF DISCONNECT BEFORE COMMENCING ANY ELECTRICAL AND TELECOM DEMOLITION WORK, AND COORDINATE WITH THE BUILDING
SECURITY DATA, TELEPHONE AND COMMUNICATIONS SYSTEMS PROVIDER.
9. WHERE OPENINGS OCCUR IN EXISTING FIRE-RATED AREAS OR PARTITIONS DUE TO REMOVAL OF CONDUIT, DUCTWORK, PIPING, ETC, AND/OR WHERE EXISTING
FIRE STOPPING HAS BEEN REMOVED, PROVIDE TEMPORARY CLOSURE AS REQUIRED.
10. WHERE A CONFLICT OCCURS IN OR BETWEEN THE AFOREMENTIONED CODES AND REGULATIONS, THE STRICTER SHALL APPLY UNLESS OTHERWISE INDICATED OR
AGREED UPON.
11. DUE TO THE SMALL SCALE OF THE DRAWINGS AND THE INSTABILITY OF THE REPRODUCTION PROCESS, DO NOT SCALE THESE DRAWINGS. FIELD VERIFY ANY
DIMENSIONS DEEMED, OR NOTED AS BEING, CRITICAL.
12. VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT JOB SITE AND ADVISE THE ARCHITECT OF ANY DISCREPANCIES, ADDITIONS, DELETIONS AND/OR ALTERATIONS IN ANY OR ALL CONDITIONS BEFORE PROCEEDING WITH ANY PHASE OF THE WORK.
13. UNLESS NOTED OTHERWISE, ALL DIMENSIONS ARE FROM FINISH FACE TO FINISH FACE.
14. FURNISH AND INSTALL FIRE RETARDANT TREATED WOOD BLOCKING AS REQUIRED AT ALL LOCATIONS FOR THE PROPER AND SECURE INSTALLATION OF ALL WALL
MOUNTED EQUIPMENT OR MILLWORK WHETHER SPECIFICALLY NOTED IN THE DRAWINGS OR NOT.
15. WHERE ELECTRICAL AND PLUMBING FIXTURES, OR OTHER RELATED EQUIPMENT, OCCUR IN MILLWORK, PROVIDE CUT-OUTS, ROUGH-INS AND STUB-INS FOR
THESE ITEMS AND COORDINATE THE WORK TO ASSURE PROPER LOCATION AND INSTALLATION.
16. PROVIDE FIRESTOPPING/SAFING MATERIAL AS REQUIRED TO MAINTAIN THE FIRE-RATING OF FLOOR, WALL AND CEILING ASSEMBLIES WHETHER SPECIFICALLY NOTED IN PLAN OR NOT. THIS APPLIES TO EXISTING AS WELL AS NEW PENETRATIONS. REFER TO SPECIFICATION SECTION 07 8413 PENETRATION
FIRESTOPPING.
17. PROVIDE DEMOLITION TO THE MINIMUM EXTENT REQUIRED FOR THE INSTALLATION OF FIRE ALARM, SPRINKLER, MEP AND TELECOMMUNICATIONS WORK.
COORDINATE WITH EACH OF THE RESPECTIVE TRADES AND CONSULTANTS AND VERIFY THE EXTENT OF THE WORK REQUIRED. UNLESS NOTED OTHERWISE, EXISTING FINISHES AND EQUIPMENT IN THE DESIGNATED AREAS ARE TO REMAIN AND SHOULD BE DISTURBED ONLY TO THE MINIMUM EXTENT TO PERFORM THE WORK. REPAIR OR REPLACE FINISHES THAT ARE DAMAGED AS A RESULT OF WORK TO MATCH SURROUNDING CONDITIONS.
18. WHERE CORE DRILLING IS REQUIRED, ANALYZE THE CONCRETE SLAB USING EITHER XRAY OR GPR METHODS IN ORDER TO VERIFY THAT THE LOCATION TO BE DRILLED IS FREE OF OBSTRUCTIONS. REPORT FINDINGS TO THE OWNER PRIOR TO COMMENCING THE WORK.
19. MILLWORK:
A. FABRICATE AND INSTALL ALL MILLWORK INDICATED IN THE CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH THE SPECIFICATIONS AND PROVISIONS OF THE "ARCHITECTURAL WOODWORK QUALITY STANDARDS", LATEST EDITION, AS PUBLISHED BY THE ARCHITECTURAL WOODWORK
INSTITUTE, FOR CUSTOM CABINETS.
B. REFER TO THE FINISH SCHEDULE FOR THE COLOR SELECTION OF PLASTIC LAMINATES (PLAM) AND SOLID SURFACE MATERIALS.
20. PROVIDE SAMPLES, SPECIFICATION SHEETS AND/OR PRODUCT DATA FOR ALL SCHEDULED ITEMS. PREPARE COMPREHENSIVE LIST OF ALL SUBMITTALS AT THE
START OF THE PROJECT FOR REVIEW BY ARCHITECT.
21. PROVIDE AND INSTALL NEW SPRAY-ON FIREPROOFING TO MATCH COLUMNS, ETC. AT LOCATIONS WHERE EXISTING FIREPROOFING WAS REMOVED DUE TO DEMOLITION OR NEW CONSTRUCTION. COORDINATE WITH ARCHITECT AND OWNER'S REPRESENTATIVE PRIOR TO COMMENCEMENT OF ANY WORK. PROVIDE AN ALLOWANCE FOR REPLACEMENT OF 2000SF OF FIREPROOFING AND A UNIT PRICE FOR ADJUSTMENTS.
22. WHERE NEW GYPSUM BOARD CONSTRUCTION ABUTS EXISTING CONSTRUCTION, COLUMNS, PARTITIONS, ETC., ALIGN NEW TRACK WITH EXISTING ADJACENT SURFACE AND CONTINUE A NEW LAYER OF THE SCHEDULED GYPSUM WALL BOARD ACROSS EXISTING SURFACE FOR A SMOOTH CONTINUOUS SURFACE.
23. ARCHITECT TO REVIEW CHALK LINES OF ALL NEW SCHEDULED PARTITIONS IN WRITING PRIOR TO THE SECURING OF ANY METAL TRACK RUNNER OR SETTING
OF ANY NON-BEARING CONCRETE MASONRY UNITS.
24. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION.
25. PREPARE ALL EXISTING PARTITIONS WITHIN PROJECT SCOPE TO RECEIVE THE NEW SCHEDULED FINISH IN ACCORDANCE WITH MANUFACTURERS'
SPECIFICATIONS.
26. PROVIDE AND INSTALL NEW SPRAY-ON FIREPROOFING TO MATCH COLUMNS, ETC. AT LOCATIONS WHERE EXISTING FIREPROOFING WAS REMOVED DUE TO DEMOLITION OR NEW CONSTRUCTION. COORDINATE WITH ARCHITECT AND OWNER'S REPRESENTATIVE PRIOR TO COMMENCEMENT OF ANY WORK. PROVIDE AN ALLOWANCE FOR REPLACEMENT OF 2000SF OF FIREPROOFING AND A UNIT PRICE FOR ADJUSTMENTS.
27. WHERE NEW GYPSUM BOARD CONSTRUCTION ABUTS EXISTING CONSTRUCTION, COLUMNS, PARTITIONS, ETC., ALIGN NEW TRACK WITH EXISTING ADJACENT SURFACE AND CONTINUE A NEW LAYER OF THE SCHEDULED GYPSUM WALL BOARD ACROSS EXISTING SURFACE FOR A SMOOTH CONTINUOUS SURFACE.
1. INSTALL ALL WALL MOUNTED P/D/T DEVICES VERTICALLY AT 18" A.F.F. TO CENTERLINE UNLESS NOTED OTHERWISE ON THE PLANS.
2. ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE AND ALL OTHER RELATED CODES IN USE BY THE GOVERNING GOVERNMENT AGENCY(IES) AT THE TIME OF CONSTRUCTION. IN THE EVENT OF A CONFLICT BETWEEN THE AFOREMENTIONED REQUIREMENTS, THE
MORE RESTRICTIVE SHALL APPLY.
3. ALL MOUNTING HEIGHTS INDICATED ARE TO THE CENTERLINE(S) OF OUTLET(S), DEVICE(S) OR EQUIPMENT UNLESS NOTED OTHERWISE.
4. OUTLETS, OR OTHER DEVICES, WHICH ARE MOUNTED ON OPPOSITE SIDES OF PARTITIONS SHALL NOT BE MOUNTED BACK TO BACK.
5. INSTALL MULTIPLE SWITCH GROUPINGS IN COMMON GANG BOXES WITH BARRIERS AND COMMON COVERPLATES.
6. COORDINATE WITH DC COURTS FOR THE PROVISION AND INSTALLATION REQUIREMENTS FOR SECURITY EQUIPMENT.
Probate
1. HAZARDOUS MATERIALS ARE NOT PART OF THE SCOPE OF THESE DRAWINGS. CONTRACTOR AGREES TO INDEMNIFY, HOLD HARMLESS AND DEFEND OWNER AND ARCHITECT FROM CLAIMS, DAMAGES, LOSSES, COSTS, EXPENSES, AND LIABILITIES ARISING OUT OF OR RESULTING FROM THE PRESENCE, UNCOVERING OR RELEASE OF SUSPECTED OR CONFIRMED HAZARDOUS MATERIALS TO THE EXTENT CAUSED BY THE NEGLIGENCE OF, OR FAILURE TO COMPLY WITH, THE TERMS AND CONDITIONS OF THE CONTRACT DOCUMENTS BY THE CONTRACTOR OR ANYONE FOR WHOM THE CONTRACTOR IS RESPONSIBLE.
2. IF HAZARDOUS MATERIALS ARE ENCOUNTERED AT THE SITE OF THE WORK OR IN THE PERFORMANCE OF THE WORK, CONTRACTOR SHALL STOP WORK IN THE AREA OF HAZARDOUS MATERIALS AND IMMEDIATELY NOTIFY THE OWNER. CONTRACTOR SHALL BAR ALL PERSONS FROM ENTERING THE AFFECTED AREA AND TAKE ALL NECESSARY STEPS TO MINIMIZE THE RISKS TO EMPLOYEES AND OTHERS FROM SUCH HAZARDOUS MATERIALS. CONTRACTOR AND OWNER SHALL MEET TO IDENTIFY THE ENTIRETY OF THE AFFECTED AREA AND REVIEW CONTAINMENT AND REMEDIAL ACTION. IT IS UNDERSTOOD THAT OWNER MAY EMPLOY CONTRACTOR OR SEPARATE CONTRACTOR(S) TO REMOVE, REMEDIATE OR RENDER HARMLESS HAZARDOUS MATERIALS ENCOUNTERED AT THE SITE OR IN THE PERFORMANCE OF THE
WORK.
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Scale:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
As indicated
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
08/18/2017
A000215.2153
General Notes
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird Fl oo r, Ro om s 3
, 3
, 3
6, General Notes
General Reflected Ceiling Plan Notes
General Lighting Notes
General Telecommunication Cabling Notes
General Description of Work
General Architectural Notes
General Power, Data and Telephone Notes
Hazardous Materials
SCALE:SCALE:SCALE:SCALE:SCALE:
3 5/8", 18 GA. STEEL STUDS @
16" O.C. MAX.
LINE OF SCHEDULED CEILING
SEE REFLECTED CEILING PLAN
SOUND ATTENUATION BLANKET
SCHEDULED FLOOR
FINISH
ACOUSTICAL SEALANT - BOTH SIDES
CONTINUOUS FLOOR TRACK,
FASTENERS @ 24" O.C. MIN.
SCHEDULED BASE
3E Partition Type
Fire Rating/Test #: N/A
STC Rating: 49-51
Partition Thickness: 4 7/8"
Stud Thickness: 3 5/8"
SAFB Insulation Thickness: 3 1/2"
BA
SE
PL
AN
CE
IL
IN
G
DE
CK
Description: Slab High with SAFB
BOTTOM OF STRUCTURE
TOP OF STEEL STUD
CONTINUOUS SLOTTED STEEL
TRACK (SEE TYPICAL TOP
RUNNER DETAILS)
0' - 4 7/8"
1 LAYER OF 5/8" FIRE RATED GWB -
TYPE X (EACH SIDE)
3 1/2" SOUND ATTENUATION FIRE
BLANKETS
Pa rt iti on
N ot es
3 5/8", 18 GA. STEEL STUDS @
16" O.C. MAX.
BOTTOM OF STRUCTURE
CONTINUOUS SLOTTED STEEL
TRACK (SEE TYPICAL TOP RUNNER
DETAILS)
LINE OF SCHEDULED CEILING
SEE REFLECTED CEILING PLAN
SOUND ATTENUATION BLANKET
SCHEDULED FLOOR
FINISH
BACKER ROD & ACOUSTICAL
SEALANT
CONTINUOUS FLOOR TRACK,
FASTENERS @ 24" O.C. MIN.
SCHEDULED BASE
1K Partition Type
Fire Rating/Test #: N/A
STC Rating: TBD
Partition Thickness: 4 1/4"
Stud Thickness: 3 5/8" SAFB Insulation Thickness: 3 1/2"
BA
SE
PL
AN
CE
IL
IN
G
DE
CK
Pa rt iti on
N ot es
Description: Slab High with SAFB - 1 Layer of GWB, One Side Only
TOP OF STEEL STUD
0' - 4 1/4"
1 LAYER OF 5/8" FIRE RATED GWB -
TYPE X
3 1/2" SOUND ATTENUATION FIRE
BLANKETS
NOTES:
1. ALL STUDS ARE SPACED 16" O.C. MAX.
2. ALL STUDS SHALL BE "C" STUDS W/ 1/4" FLANGE MIN.
3. DENOTES SHELVING OR CABINETRY
4 IN NO CASE SHALL DOUBLE STUDS @ SIDES OF OPENINGS BE CUT FOR DUCTWORK OR OTHER MECHANICAL SYSTEMS
UNDERSIDE OF SLAB,
FLOOR, OR ROOF DECK
CEILING LINE
2" WIDE 22 GA. MTL. STRAP
22 GA. MTL. TOP
TRACK (TYP
U.N.O.)
22 GA. BOTTOM
TRACK (TYP)
FLOOR LINE
MOUNTING DETAIL
ABOVE CEILING OPENING LARGE ABOVE CEILING OPENING
LARGE BELOW
CEILING OPENING
BELOW
CEILING OPENING
DOUBLE DOOR
OPENING
DOOR
OPENING
DOUBLE STUDS DOUBLE STUDS
AT WALL MOUNTED
ARCHITECTURAL CABINETS/
MILLWORK/ ATTACHED
SHELVING
D
C
D
A
E
E
E A
A
B
20 GA. STUDS 4' - 6" MAX 8' - 6" MAX 4' - 6" MAX 4' - 6" MAX 8' - 6" MAX 8' - 6" MAX
3'
2"
7'
3"
DOUBLE 20 GA.
MTL. STUDS
22 GA. MTL.
TRACK AT FLOOR
1" X 22 GA. MTL.
STRAP PLATES AT
3'-6" O.C. EA. SIDE
22 GA. MTL. SILL
BELOW TRACK
DOUBLE 20
GA. MTL. STUDS
20 GA. MTL.
TRACK AT FLOOR
1" X 22 GA.
MTL. STRAP
PLATES AT
3'-6" O.C. EA.
SIDE
20 GA. MTL.
TRACK
CLIP ANGLE -
20 GA. X 1 1/2"
X 1 1/2"" X 3"
FOR 3 5/8"
STUDS AND 5"
FOR 6" STUDS
EA. SIDE
20 GA. MTL.
TRACK
A Double Door/Large Opening HeaderB Large Opening Jamb StudsC Door Opening HeaderD Door Opening Jamb StudsE Opening Header
CLIP ANGLE -
20 GA. X 1 1/2"
X 1 1/2"" X 3"
FOR 3 5/8"
STUDS AND 5"
FOR 6" STUDS
EA. SIDE
CLIP ANGLE -
20 GA. X 1 1/2"
X 1 1/2"" X 3"
FOR 3 5/8"
STUDS AND 5"
FOR 6" STUDS
EA. SIDE
CLIP ANGLE -
20 GA. X 1 1/2"
X 1 1/2"" X 3"
FOR 3 5/8"
STUDS AND 5"
FOR 6" STUDS
EA. SIDE
6A Partition Type
Fire Rating/Test #: N/A
STC Rating: TBD
Partition Thickness: 7 1/4"
Stud Thickness: 6"
SAFB Insulation Thickness: 6"
Description: Slab High with SAFB
SCHEDULED FLOOR
FINISH
ACOUSTICAL SEALANT -
BOTH SIDES
CONTINUOUS FLOOR TRACK,
FASTENERS @ 24" O.C. MIN.
SCHEDULED BASE
LINE OF SCHEDULED CEILING
SEE REFLECTED CEILING PLAN
6", 18 GA. STEEL STUDS
16" O.C. MAX.
BOTTOM OF STRUCTURE
DE
CK
CE
IL
IN
G
PL
AN
BA
SE
TOP OF STEEL STUD
CONTINUOUS SLOTTED STEEL
TRACK (SEE TYPICAL TOP
RUNNER DETAILS)
1 LAYER OF 5/8" FIRE RATED GWB -
TYPE X (EACH SIDE)
6" SOUND ATTENUATION FIRE
BLANKETS
0' - 7 1/4"
Pa rt iti on
N ot es
1. REFER TO ARCHITECTURAL PLAN FOR THE LOCATIONS OF PARTITION TYPES HEREIN
INDICATED.
2. PROVIDE 5/8" CEMENTITIOUS BACKER BOARD IN LIEU OF 5/8" GWB AT ALL PARTITIONS
INDICATED TO RECEIVE WITH CERAMIC OR STONE TILES.
PROVIDE SEALANT AROUND ALL WALL PENETRATIONS, SUCH AS ELECTRICAL BOXES, ETC.,
WITH SOUND ATTENUATION TO PREVENT NOISE TRANSFER. PROVIDE FIRE-RATED
ACOUSTICAL SEALANT AT ALL FIRE-RATED PARTITIONS. CROSS-BRACE ALL CHASE WALLS
SHALL TO ADJACENT WALL AND PROVIDE A MINIMUM OF 1 1/2" OF SOUND ATTENUATION
BLANKETS.
3. PROVIDE STEEL STUD BRACING AS REQUIRED AT STUDS ABOVE CEILING TO MEET
DEFLECTION REQUIREMENT - L/240 FOR STANDARD GWB WALLS, L/360 FOR WALLS WITH
TILE OR STONE FINISH.
REINFORCE BRACE AND PROVIDE BLOCKING IN WALLS AS REQUIRED TO SUPPORT THE
INSTALLATION OF WALL MOUNTED TOILET AND KITCHEN EQUIPMENT, CABINETRY, AND
SHELVING WHETHER SPECIFICALLY INDICATED BY THE DRAWINGS
OR NOT.
4. CONFIRM THE GAUGES REQUIRED FOR COLD ROLLED STEEL FRAMING MEMBERS IN
RELATION TO THEIR APPLICATION AND/OR FUNCTION AND INCREASE THE GAUGES
INDICATED BY THE PARTITION TYPES IF REQUIRED. THE CONTRACTOR SHALL NOT
DECREASE THE GAUGES OF MEMBERS WITHOUT THE PRIOR WRITTEN CONSENT OF THE
ARCHITECT AND THE OWNER.
5. ALL FIRE RATED PARTITIONS SHALL FIT TIGHT AGAINST OVERHEAD STRUCTURE.
6. PROVIDE NONCOMBUSTIBLE FIRE STOPPING MATERIAL AND SEAL AROUND PENETRATIONS
IN FLOOR AND PARTITIONS IN ORDER TO PROVIDE REQUIRED FIRE SEPARATION.
7. FUR AND FINISH ALL VERTICAL PIPES AND DUCTS IN THE SAME MATERIAL AS THE
ADJACENT WALL OR COLUMN WHETHER INDICATED OR NOT ON THE ARCHITECTURAL
DRAWINGS.
8. UNLESS NOTED OTHERWISE, ALL GYPSUM BOARD USED IN THIS PROJECT SHALL BE FIRE
RESISTANT.
Probate
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Scale:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
As indicated
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
08/18/17
A000315.2153
Schedules/ Standard Details
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird Fl oo r, Ro om s 3
, 3
, 3
6, Scale : 1/4" = 1'-0" 3 Partitions Framing Elevations
Partition Types
Scale : 3" = 1'-0" 4 Partitions Framing Details
Partition Notes
3' - 9"
7'
5"
1/
2"
4 1/2"
1/
2"
5' - 0"
1' - 8" 3' - 4"
7'
0"
3' - 0"
7'
0"
6'
3' - 0"
FRAME TYPE A FRAME TYPE B DOOR TYPE 1 DOOR TYPE 2
A0004
A0004
A0004
A0004
A0004
VI
F
1/
4"
0' - 4 5/8"
EXISTING WOOD TRIM TO
BE REUSED FROM
RELOCATED DOOR
EXISTING WOOD DOOR
FRAME TO BE REUSED
FROM RELOCATED DOOR
EXISTING WOOD DOOR TO
BE REUSED
WOOD TRIM PROFILE AND
SIZE TO MATCH EXISTING
WOOD BLOCKING
EXISTING WOOD TRIM TO BE
REUSED FROM RELOCATED
DOOR
EXISTING WOOD DOOR
FRAME TO BE REUSED
FROM RELOCATED DOOR
EXISTING WOOD DOOR TO
BE REUSED
WOOD TRIM TO MATCH
EXISTING
WOOD BLOCKING
5/8" TYPE "X" GYPSUM
BOARD ON BOTH SIDES OF
6" X 18 GA METAL STUDS
5 1/2" SOUND
ATTENUATION BATT
INSULATION
0'
1/
4" 0'
5"
PARTITION TYPE 6A, SEE PARTITIONS SCHEDULE.
EXISTING RELOCATED STOREFRONT SYSTEM.
SEALANT AND BACKER ROD
WOOD SHIM
WOOD BLOCKING
Probate
PARTITION TYPE 6A, SEE PARTITIONS SCHEDULE.
EXISTING RELOCATED STOREFRONT SYSTEM.
SEALANT AND BACKER ROD
WOOD SHIM
0'
1/
2"
WOOD BLOCKING
RELOCATED STOREFRONT SYSTEM/ SIDELIGHT JAMB
RELOCATED STOREFRONT DOOR
0'
5"
0' - 2 1/2"
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Scale:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
As indicated
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
07/27/17
A000415.2153
Door Schedule, Details
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird Fl oo r, Ro om s 3
, 3
, 3
6, DOOR NO.
Actual Model Door Size & Type DOOR FRAME HARDWARE
REMARKSWidth Height Thickness
DESCRIPTION
TYPE MAT'L FIN. SET # MODIFIERTYPE MAT'L FIN.
314 3' - 0" 7' - 0" 1 3/4" TYPE 1 WOOD STAIN A WOOD STAIN
315 3' - 0" 7' - 0" 1 3/4" TYPE 1 WOOD STAIN A WOOD STAIN
316D 3' - 0" 7' - 0" 1 3/4" TYPE 1 WOOD STAIN A WOOD STAIN
318A 3' - 0" 6' - 9 1/2" TYPE 2 ALUM/ GLASS P-2 B ALUM P-2
318B 3' - 0" 7' - 0" 1 3/4" TYPE 1 WOOD STAIN A WOOD STAIN
Scale : 1/2" = 1'-0" 1 Door and Frame Types
Scale : 3" = 1'-0" 2 Door Jamb Detail - Wood Trim
Scale : 3" = 1'-0" 3 Door Head Detail - Wood Trim
Scale : 3" = 1'-0" 6 Storefront Jamb
Scale : 3" = 1'-0" 5 Storefront Head
Scale : 3" = 1'-0" 4 Door Jamb Detail at Sidelight
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
PHASE 4 SELF HELP CENTER AND WAITING ROOM PHASE 5 OPERATIONS
SWING SPACE SUITE 319
A0006
A0006
A0006
A0006
A0006
A0006 5A
ELEV. #1
3_10
ELEV. #3
3_11
ELEV. #2
3_12
ELEV. #4
3_13
STAIR #5
3_5
PROBATE
HEARING
319C
ELEV. #6
3_9
STAIR #3
3_3
STAIR #4
3_4
ELEV. #5
3_8
ELEC. CLOSET
CLOSET
NORTH
Probate
Not in Contract (NIC)
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Scale:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
As indicated
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
08/18/17
A000515.2153
Phasing Plans
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird Fl oo r, Ro om s 3
, 3
, 3
6, Scale : 1/8" = 1'-0" 1 Level 3 - Probate Renovations Floor Plan Phasing Mapping
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
2H
E
E.1
F
109.1 9.2 9.5 9.6
TEMPORARY
PARTITION
E
E.1
F
11 12 13 14
SUBPHASE 5B
SUBPHASE 5A
TEMPORARY
PARTITION
PROBATE
HEARING
319C
PUBLIC CORR.
319A
ROBING
319E
E
E.1
F
11 12 13 14
SUBPHASE 5B
SUBPHASE 5A
Probate
PR
O
JE
CT
TI
TL
E
SH
EE
T
Date:
Scale:
Checked by:
Planned By:
Drawn by:
Do Not Scale this Drawing Contractors to Verify Dimensions on Site c G
R U
Z E
N S
A M
T O
N a rc hi te ct s llp
Pl ot te d:
515 5th Street NW Washington DC Building A
DESIGN INTENT ONLY
NOT FOR
CONSTRUCTION
This drawing and the design shown hereon are the property of IBI Group. The reproduction, copying, or other use of the drawing without their written consent is prohibited and any infringement will be subject and any infringement will be subject to legal action.
Accepted By:
Capital Projects and Facilities Management Officer Contracting Officer District of Columbia Courts
SU
BM
IS
SI
O N
RE
V
IS
IO
N S
ISSUED FOR DATE
NO. DESCRIPTION DATE BY
K
EY
PL
A
N A
RC
H
IT
EC
T
E N
G
IN
EE
R
N A
M E
L
O G
O
APPROVALS DATE
Location:
CL
IE
N T
N A
M E
L
O G
O A
PP
RO
V A
L
ST
A M
P
IBI GROUP
Architects, Planners & Interior Designers 1505 Prince Street - Suite 200 Alexandria VA 22314-2852 USA tel 703 836 9600 fax 703.836.2484 ibigroup.com
Pr oje ct Ti tle
Cl ien t N am e
Bu ild ing A dd res s
As indicated
8/
/2
:1 3:
A
M
BIM 360://2153 - DC Courts/515 5th St_3_Probate.rvt
08/18/17
A000615.2153
Phasing Plans
Probate Division, Third Floor, Rooms 304, 314, 315, 316, 318 515 5th Street (Building A) Washington DC, NW 20001
Di str ict of
C olu m bia
C ou rts Ca pi ta l P ro jec ts an d F ac ilit ies M an ag em en t D ivi sio n
5 5 th St re et
(B uil din g A
W as hin gto n D
C, N
W
Pr ob ate D ivi sio n, Th ird Fl oo r, Ro om s 3
, 3
, 3
6, Scale : 1/8" = 1'-0" 1 Partial Floor Plan Phase 1 Temporary Intake / Room 314A
Scale : 1/8" = 1'-0" 2 Partial Floor Plan Phase 2 Intake/ Room 315
Scale : 1/8" = 1'-0" 3 Partial Floor Plan Phase 3 Operations/ 314A
Scale : 1/8" = 1'-0" 4 Partial Floor Plan Phase 4 Self Help Center and Waiting Room/ Room 316A
Scale : 1/8" = 1'-0" 5A Partial Floor Plan Phase 5A Operations/ Room 304
Scale : 1/8" = 1'-0" 6 Partial Floor Plan -Swing Space 319
1) Temporary Intake in Room 314: Install temporary partition to screen off area of construction. Build new drywall surround and move entry door from Public Corridor in Operations Room 314. Install power poles and power, data and telephone connections for stations, staff copier and public copier. Install wiremold for power, data and telephone connections at public computer stations in existing marble vestibules. Install blocking, power and data in two locations for digital messaging system on corridor wall. Provide power for and install existing digital number display on temporary partition. Existing lighting, ceiling and finishes to remain in place.
2) Intake Room 315: Existing systems furniture computer stations to remain in place and to be protected during renovation. Existing carpet tile to remain in place and to be protected during renovation. Demolish partition, windows and counter in Intake Room 315 and ceiling high partition in Room 314. Remove glass door and sidelight and store for reuse. Wall off opening into Self Help Center 316 and paint. Install new finishes and power, data and telephone connections for millwork counter .
Re-lamp light fixtures and replace ceiling tiles as necessary using existing ceiling tiles in Rooms 316B and 316C as necessary (Replace with like kind). Extend ceiling pattern at area of demolished walls to match ceiling pattern at entry. Install blocking, power and data for digital messaging system.
3) Operations Room 314: Remove existing linoleum and install new carpet tile, paint and power, data and telephone connections. Re-lamp light fixtures and replace ceiling tiles as necessary.
This is the start of the file's text. The full file is on GovTribe.