Amend_002_Attach_B_-_Equipment_Cut_Sheets_-__Encelium_LMS082_Ceiling-MountedOS.pdf

PDF 513 KB Posted

Attached to
Probate Division Interior Improvements, 515 5th Street, NW Third Floor
Solicitation number
CPFMD-17-0825
Issued by

About this file

Amendment 0002 - Attachment B (Part 1) - Equipment Cut Sheets - Encelium LMS082 Ceiling MountedOS

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Key Features & Benefits

— State of the Art Sensors: Passive Infra-Red (PIR) sensor and optional Ultrasonic (U/S) sensor afford a wide variety of space coverage while providing options for fine motion sensitivity. (450 to 2000 sq.

ft., see Ordering Information table.)

— Simple Installation: Easy ceiling mount with low-voltage connection and twist-lock attachment for 360° directional flexibility.

— Flexible Timer Settings:

Automatic – 30 seconds – 30 minutes. Includes installer test mode with 6 seconds auto exit programming.

— Adaptive Learning with Local Protected Memory: Sensor self-calibrates to optimize performance and retains settings during power interruptions.

— Low Voltage Operation: Uses ENCELIUM PPK Series Power Pack with Class 2, 24 volt wiring.

Multiple sensors can control single or multiple power packs.

— Convenient AC Power Base Option: Make any ENCELIUM low-voltage ceiling sensor a line-voltage sensor and avoid bulky external power-packs. (see PBA-015)

— Integrated Daylight Hold-OFF Light Sensor: Avoid wasting energy when there is enough natural light.

— Auto-Adapting Mode: Sensor’s digital system continually analyzes and adjusts the sensitivity and time delay.

— Walk-Through Mode: Provides increased energy savings by decreasing the time delay to

2.5 minutes when someone momentarily walks through the monitored space.

Modern occupancy sensors use digital technology to ensure that the occupants in a room have light when they are present and that lighting energy is saved when the room is unoccupied.

Depending on the application, either single technology or multi-tech-nology sensors are appropriate to maximize occupant and energy manager satisfaction.

ENCELIUM single-technology Passive Infra-Red (PIR) sensors are a cost-effective option for small and large spaces when major motion is available. The multi-technology option adds an active Ultrasonic (U/S) sensor to the PIR sensor to increase minor motion sensitivity in critical applications like single-occupant offices and restrooms.

For Greater Savings

Combine with the ENCELIUM Energy Management System to gain considerable energy savings in addition to occupancy sensing:

— Polaris 3D® Software enables the addition of Daylight-Harvesting, Time Scheduling, Task Tuning, Variable Load Shedding and Personal Control for significantly greater energy savings.

— Software Remapping: any sensor to any zone

— Software Adjustable: Extended time-out

— Connects directly to ENCELIUM Sensor Interface Module

— BACnet Interface (optional): Occupancy sensing for building automation, HVAC, security, traffic data, etc.

For more information on the ENCELIUM Energy Management System, refer to LMS075 – ENCELIUM BROCHURE.

ENCELIUM® Ceiling-Mounted Occupancy Sensors www.osram-americas.com/ENCELIUM

LMS082R2 3-14

Application Information

Applications

— Cafeterias

— Classrooms

— Computer rooms

— Conference rooms

— Day care centers

— Executive and private offices (U/S models)

— Filing rooms

— Hallways

— Loading docks

— Offices with cubicles

— Open areas

— Open warehouses

— Parking garages

— Restrooms (U/S models)

— Stairwells

— Storage rooms

— Warehouses

— Workspaces

Ordering Information

Sensing Current Item Ordering Sensing Angle Coverage Required Number Description Technology(ies) (degrees) (ft2) (mA)

45363 SCP-0450 PIR 360 450 20

45364 SCP-1500 PIR 360 1500 20

45365 SCM-0500 PIR + U/S 180 500 25

45366 SCM-1000 PIR + U/S 360 1000 35

45367 SCM-2000 PIR + U/S 360 2000 30

45376 PBA-015

Power Base Adapter, 120-277Vac, 15A

DIP Switch Settings

Switch Switch Functions Switch Settings Switch Settings Factory Settings

BANK A OFF ON —

A1 (U/S Only) Mode Multi-Tech Single-Tech Multi-Tech A2 (U/S Only)* PIR or U/S Select PIR Only (if in single-tech mode, see A1) U/S Only (if in single-tech mode, see A1) — A3 Manual Mode Auto Adapting Enabled Auto Adapting Disabled Auto Adapting Disabled A4 Walk-Thru Disable Walk-Thru Enabled Walk-Thru Disabled Walk-Thru Disabled Bank B B1 Override to ON Auto Mode Lights forced ON Auto Mode B2 Override to OFF Auto Mode Lights forced OFF Auto Mode B3 Test Mode OFF}ON}OFF to start Test Mode. Auto-exits after 15 min. — — B4 LEDs Disabled LEDs Enabled LEDs Disabled LEDs Enabled

* Applicable only when in Single Tech mode (A1 ON)

Sensor Specifications (SCM and SCP Models)

Sensor Electrical Specifications:

— Power Requirements: 24Vdc, works with ENCELIUM® PPK Power Pack or ENCELIUM PBA Power Base Adaptor

— Power Consumption: See Current Required (mA) in Ordering Information

— Output: 24Vdc active high logic control signal with short circuit protection

Control Specifications:

— U/S Sensitivity: 0 to 100%; green knob (U/S models only)

— PIR Sensitivity: 0 to 100%; red knob

— Light Sensor: 20 to 3,000 Lux.; blue knob (Connect gray wire to blue PPK wire for Light Sensor function)

— Time Delay: 30 seconds – 30 minutes; black knob (Factory setting: 10 minutes)

Indicator Specifications:

— Red LED: Motion detected with PIR sensor

— Green LED: Motion detected with U/S sensor (U/S models only)

Environmental Specifications:

— Operating Temperature Range: 32°F to 104°F (0°C to 40°C)

— Relative Humidity: 0% to 95% non-condensing, for indoor use only

Physical Specifications:

— Size: Base Diameter: 4.2" (107mm); Height: 1.57" (40mm)

— Weight: 5oz (142g)

— Wire Length: 6" (160mm)

— Color: White

— Housing: Rugged, high-impact, UV inhibitors

Other Specifications:

— Mounting Height: 8-12 feet

— Listings: CUL/US Certified, meets ASHRAE Standard 90.1 and CEC Title 24 requirements

Adaptive Learning Scenarios

Real-World Scenario Adaptive Learning Reaction

An installer accidentally leaves the sensor in the 6 sec. timer test mode and the lights may go OFF or ON every 6 sec.

The sensor automatically resets the timer to 10 min. after 15 min. of test mode.

The sensor detects movement in a nearby corridor or hallway and the room lights turn ON.

After an initial movement is sensed, if another movement is not sensed within the timer setting then the delayed OFF time setting is automatically reduced.

The sensor does not detect movement because an occupant sits virtually motionless at a desk and the lights turn OFF.

If motion is sensed within a short period after the lights go OFF, then the current delayed OFF-time setting is increased.

Field-of-View

11.5

11.5

8.5

8.5

TOP VIEW

TOP VIEW

TOP VIEW

SIDE VIEWSIDE VIEW

SIDE VIEW

TOP VIEW

TOP VIEW

SIDE VIEWSIDE VIEW

2323 1717

111115 1520 2099 33 0 5.65.6

11.5

11.5

03 35.5 5.59 911 1115 1520 2032 3222.5 22.5

11.5

11.5

8.5

8.5

0 20 2317 11 155.6 93

0 77 1212 5 95 Feet

Feet Feet

Fe et

Fe et

Fe et

Fe et

Fe et

Feet Feet

201111 1515 5.65.6 99 3320

SCM-2000, 2000 sq. ft.

SCM-1000, 1000 sq. ft.SCM-0500, 500 sq. ft.

Major Motion, PIR

Minor Motion, PIR

Minor Motion, U/S

Major Motion, U/S

Mounting Height = 8–12 ft.

SCP-0450, 450 sq. ft.

SCP-1500, 1500 sq. ft.

Dimensions

1.571” (39.9mm)

4.200” (106.68mm)

Ultrasonic Ports for U/S models only

Weight: 5 oz.

Color coded leads: 6" (152.4mm)

Power Base Adapter Specifications (PBA-015)

Electrical Specifications:

— Input Voltage: 120-277Vac @ 50/60Hz

— Output Voltage: 24Vdc, 40mA nominal

— Load Rating: 15A Incandescent, Electronic or Magnetic Fluorescent Ballast; 3/4 HP at 120V

— Wire Designation: Line-Black, Load-Blue, White-Neutral

— Power Consumption (base only):

Lights ON: 120V – 1.58W, 277V – 2.34W Lights OFF: 120V – .27W, 277V – 1.04W

Environmental Specifications:

— Operating Temperature Range: 32°F to 104°F (0°C to 40°C)

— Relative Humidity: 0% to 90% non-condensing, for indoor use only

Physical Specifications:

— Case: High impact plastic

— Relay: Class B (130°C) insulating material. Silver alloy contacts switching power supply – 120/230/277 Vac

— Wire: 6" (152.4mm) leads 14 AWG input, two-part terminal block output

— Size: 4.5" (114.3mm) dia. x 1.75" (44.45mm) deep

— Color: White

Other Specifications:

— Agency Standards and Compliance: UL and cUL Listed, CEC Title-24

Wiring Diagram

Load

SensorOSPxx Series Power Pack

Black W hite

Neutral (White)

Hot Black Blue

Blue Black

W hite

Red Black Blue* (occupancy)

Red Black

Blue* (occupancy)

Gray* (photocell + occupancy)

Gray* (photocell + occupancy)

Red (24VDC)

Black Blue

(control)

NC-Brown Common-Green NO-Brown/White To HVAC System

120/277/347 VAC60Hz

Line

© 2014 OSRAM

Americas Headquarters

100 Endicott Street

Danvers, MA 01923 USA

Phone 1-800-LIGHTBULB www.osram-americas.com

Warranty

ENCELIUM® Occupancy Sensors and Power Packs are covered by the ENCELIUM Energy Management System Limited warranty. For the full text of the limited warranty, or to download the warranty registration form, refer to the limited warranty which is available in the Tools & Resources section of www.osram-americas.com.

OSRAM is a registered trademark of OSRAM GmbH.

ENCELIUM and Polaris 3D are registered trademarks.

Specifications subject to change without notice.

Installation and Wiring

Connect and mount the PBA-015 to the electrical box. Using the terminal block, connect the low voltage sensor. Match the arrows on the sensor to the base and twist to lock. Test the sensor for correct operation.

ENCELIUM Low Voltage Ceiling or Wall Sensor

Hot (Black) 120-277V

PBA-015

Power Base Adaptor

LoadNeutral (White)

Load (Blue)

File details come from the government source that posted it. Updated .