Key Features & Benefits
— State of the Art Sensors: Passive Infra-Red (PIR) sensor and optional Ultrasonic (U/S) sensor afford a wide variety of space coverage while providing options for fine motion sensitivity. (450 to 2000 sq.
ft., see Ordering Information table.)
— Simple Installation: Easy ceiling mount with low-voltage connection and twist-lock attachment for 360° directional flexibility.
— Flexible Timer Settings:
Automatic – 30 seconds – 30 minutes. Includes installer test mode with 6 seconds auto exit programming.
— Adaptive Learning with Local Protected Memory: Sensor self-calibrates to optimize performance and retains settings during power interruptions.
— Low Voltage Operation: Uses ENCELIUM PPK Series Power Pack with Class 2, 24 volt wiring.
Multiple sensors can control single or multiple power packs.
— Convenient AC Power Base Option: Make any ENCELIUM low-voltage ceiling sensor a line-voltage sensor and avoid bulky external power-packs. (see PBA-015)
— Integrated Daylight Hold-OFF Light Sensor: Avoid wasting energy when there is enough natural light.
— Auto-Adapting Mode: Sensor’s digital system continually analyzes and adjusts the sensitivity and time delay.
— Walk-Through Mode: Provides increased energy savings by decreasing the time delay to
2.5 minutes when someone momentarily walks through the monitored space.
Modern occupancy sensors use digital technology to ensure that the occupants in a room have light when they are present and that lighting energy is saved when the room is unoccupied.
Depending on the application, either single technology or multi-tech-nology sensors are appropriate to maximize occupant and energy manager satisfaction.
ENCELIUM single-technology Passive Infra-Red (PIR) sensors are a cost-effective option for small and large spaces when major motion is available. The multi-technology option adds an active Ultrasonic (U/S) sensor to the PIR sensor to increase minor motion sensitivity in critical applications like single-occupant offices and restrooms.
For Greater Savings
Combine with the ENCELIUM Energy Management System to gain considerable energy savings in addition to occupancy sensing:
— Polaris 3D® Software enables the addition of Daylight-Harvesting, Time Scheduling, Task Tuning, Variable Load Shedding and Personal Control for significantly greater energy savings.
— Software Remapping: any sensor to any zone
— Software Adjustable: Extended time-out
— Connects directly to ENCELIUM Sensor Interface Module
— BACnet Interface (optional): Occupancy sensing for building automation, HVAC, security, traffic data, etc.
For more information on the ENCELIUM Energy Management System, refer to LMS075 – ENCELIUM BROCHURE.
ENCELIUM® Ceiling-Mounted Occupancy Sensors www.osram-americas.com/ENCELIUM
LMS082R2 3-14
Application Information
Applications
— Cafeterias
— Classrooms
— Computer rooms
— Conference rooms
— Day care centers
— Executive and private offices (U/S models)
— Filing rooms
— Hallways
— Loading docks
— Offices with cubicles
— Open areas
— Open warehouses
— Parking garages
— Restrooms (U/S models)
— Stairwells
— Storage rooms
— Warehouses
— Workspaces
Ordering Information
Sensing Current Item Ordering Sensing Angle Coverage Required Number Description Technology(ies) (degrees) (ft2) (mA)
45363 SCP-0450 PIR 360 450 20
45364 SCP-1500 PIR 360 1500 20
45365 SCM-0500 PIR + U/S 180 500 25
45366 SCM-1000 PIR + U/S 360 1000 35
45367 SCM-2000 PIR + U/S 360 2000 30
45376 PBA-015
Power Base Adapter, 120-277Vac, 15A
DIP Switch Settings
Switch Switch Functions Switch Settings Switch Settings Factory Settings
BANK A OFF ON —
A1 (U/S Only) Mode Multi-Tech Single-Tech Multi-Tech A2 (U/S Only)* PIR or U/S Select PIR Only (if in single-tech mode, see A1) U/S Only (if in single-tech mode, see A1) — A3 Manual Mode Auto Adapting Enabled Auto Adapting Disabled Auto Adapting Disabled A4 Walk-Thru Disable Walk-Thru Enabled Walk-Thru Disabled Walk-Thru Disabled Bank B B1 Override to ON Auto Mode Lights forced ON Auto Mode B2 Override to OFF Auto Mode Lights forced OFF Auto Mode B3 Test Mode OFF}ON}OFF to start Test Mode. Auto-exits after 15 min. — — B4 LEDs Disabled LEDs Enabled LEDs Disabled LEDs Enabled
* Applicable only when in Single Tech mode (A1 ON)
Sensor Specifications (SCM and SCP Models)
Sensor Electrical Specifications:
— Power Requirements: 24Vdc, works with ENCELIUM® PPK Power Pack or ENCELIUM PBA Power Base Adaptor
— Power Consumption: See Current Required (mA) in Ordering Information
— Output: 24Vdc active high logic control signal with short circuit protection
Control Specifications:
— U/S Sensitivity: 0 to 100%; green knob (U/S models only)
— PIR Sensitivity: 0 to 100%; red knob
— Light Sensor: 20 to 3,000 Lux.; blue knob (Connect gray wire to blue PPK wire for Light Sensor function)
— Time Delay: 30 seconds – 30 minutes; black knob (Factory setting: 10 minutes)
Indicator Specifications:
— Red LED: Motion detected with PIR sensor
— Green LED: Motion detected with U/S sensor (U/S models only)
Environmental Specifications:
— Operating Temperature Range: 32°F to 104°F (0°C to 40°C)
— Relative Humidity: 0% to 95% non-condensing, for indoor use only
Physical Specifications:
— Size: Base Diameter: 4.2" (107mm); Height: 1.57" (40mm)
— Weight: 5oz (142g)
— Wire Length: 6" (160mm)
— Color: White
— Housing: Rugged, high-impact, UV inhibitors
Other Specifications:
— Mounting Height: 8-12 feet
— Listings: CUL/US Certified, meets ASHRAE Standard 90.1 and CEC Title 24 requirements
Adaptive Learning Scenarios
Real-World Scenario Adaptive Learning Reaction
An installer accidentally leaves the sensor in the 6 sec. timer test mode and the lights may go OFF or ON every 6 sec.
The sensor automatically resets the timer to 10 min. after 15 min. of test mode.
The sensor detects movement in a nearby corridor or hallway and the room lights turn ON.
After an initial movement is sensed, if another movement is not sensed within the timer setting then the delayed OFF time setting is automatically reduced.
The sensor does not detect movement because an occupant sits virtually motionless at a desk and the lights turn OFF.
If motion is sensed within a short period after the lights go OFF, then the current delayed OFF-time setting is increased.
Field-of-View
11.5
11.5
8.5
8.5
TOP VIEW
TOP VIEW
TOP VIEW
SIDE VIEWSIDE VIEW
SIDE VIEW
TOP VIEW
TOP VIEW
SIDE VIEWSIDE VIEW
2323 1717
111115 1520 2099 33 0 5.65.6
11.5
11.5
03 35.5 5.59 911 1115 1520 2032 3222.5 22.5
11.5
11.5
8.5
8.5
0 20 2317 11 155.6 93
0 77 1212 5 95 Feet
Feet Feet
Fe et
Fe et
Fe et
Fe et
Fe et
Feet Feet
201111 1515 5.65.6 99 3320
SCM-2000, 2000 sq. ft.
SCM-1000, 1000 sq. ft.SCM-0500, 500 sq. ft.
Major Motion, PIR
Minor Motion, PIR
Minor Motion, U/S
Major Motion, U/S
Mounting Height = 8–12 ft.
SCP-0450, 450 sq. ft.
SCP-1500, 1500 sq. ft.
Dimensions
1.571” (39.9mm)
4.200” (106.68mm)
Ultrasonic Ports for U/S models only
Weight: 5 oz.
Color coded leads: 6" (152.4mm)
Power Base Adapter Specifications (PBA-015)
Electrical Specifications:
— Input Voltage: 120-277Vac @ 50/60Hz
— Output Voltage: 24Vdc, 40mA nominal
— Load Rating: 15A Incandescent, Electronic or Magnetic Fluorescent Ballast; 3/4 HP at 120V
— Wire Designation: Line-Black, Load-Blue, White-Neutral
— Power Consumption (base only):
Lights ON: 120V – 1.58W, 277V – 2.34W Lights OFF: 120V – .27W, 277V – 1.04W
Environmental Specifications:
— Operating Temperature Range: 32°F to 104°F (0°C to 40°C)
— Relative Humidity: 0% to 90% non-condensing, for indoor use only
Physical Specifications:
— Case: High impact plastic
— Relay: Class B (130°C) insulating material. Silver alloy contacts switching power supply – 120/230/277 Vac
— Wire: 6" (152.4mm) leads 14 AWG input, two-part terminal block output
— Size: 4.5" (114.3mm) dia. x 1.75" (44.45mm) deep
— Color: White
Other Specifications:
— Agency Standards and Compliance: UL and cUL Listed, CEC Title-24
Wiring Diagram
Load
SensorOSPxx Series Power Pack
Black W hite
Neutral (White)
Hot Black Blue
Blue Black
W hite
Red Black Blue* (occupancy)
Red Black
Blue* (occupancy)
Gray* (photocell + occupancy)
Gray* (photocell + occupancy)
Red (24VDC)
Black Blue
(control)
NC-Brown Common-Green NO-Brown/White To HVAC System
120/277/347 VAC60Hz
Line
© 2014 OSRAM
Americas Headquarters
100 Endicott Street
Danvers, MA 01923 USA
Phone 1-800-LIGHTBULB www.osram-americas.com
Warranty
ENCELIUM® Occupancy Sensors and Power Packs are covered by the ENCELIUM Energy Management System Limited warranty. For the full text of the limited warranty, or to download the warranty registration form, refer to the limited warranty which is available in the Tools & Resources section of www.osram-americas.com.
OSRAM is a registered trademark of OSRAM GmbH.
ENCELIUM and Polaris 3D are registered trademarks.
Specifications subject to change without notice.
Installation and Wiring
Connect and mount the PBA-015 to the electrical box. Using the terminal block, connect the low voltage sensor. Match the arrows on the sensor to the base and twist to lock. Test the sensor for correct operation.
ENCELIUM Low Voltage Ceiling or Wall Sensor
Hot (Black) 120-277V
PBA-015
Power Base Adaptor
LoadNeutral (White)
Load (Blue)