City_of_Royal_Oak_Library_Solar_PV_-_Permits.pdf
PDF 9 MB Posted
- Attached to
- 2025 Library Solar Installation
- Solicitation number
- 2024-27
- Issued by
- Macomb County, Michigan
About this file
This document is a comprehensive solar photovoltaic (PV) system design and engineering set of drawings for the Royal Oak Public Library, prepared by NOVA Consultants, Inc. for a 150 kW AC, 190 kW DC rooftop solar array project located at 222 E. 11 Mile Road in Royal Oak, Michigan. The project involves installing a ballasted roof mount solar PV system using Jinko Eagle 585-600 watt solar modules and three SMA Sunny Tripower CORE1-US inverters, with a total of 325 solar modules across 21 strings. The design includes detailed electrical plans, one-line diagrams, grounding schemes, equipment elevations, and system specifications, with design reviews conducted on 7-3-2025 and permit drawings issued on 7-16-2025.
The system will be integrated with the library's existing electrical infrastructure, connecting to a 500 kVA transformer and main distribution panel. The solar array will be mounted on both the upper and lower roofs with a 10-degree tilt and 178-degree azimuth, utilizing K2 Systems' South Face mounting system with concrete block ballasting. The project adheres to the 2023 National Electrical Code, Michigan Electrical Code, and all applicable local standards. The solar modules have a 25-year linear power warranty, and the system includes rapid shutdown devices, grounding equipment, and comprehensive labeling to meet safety and electrical code requirements. The overall design aims to provide a sustainable energy solution for the Royal Oak Public Library, with a DC to AC ratio of 1.27 and a focus on efficient, code-compliant installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ONE LINE DIAGRAM SYMBOLS
DISCONNECT SWITCH
TRANSFORMER
FUSE
GROUND
EV CHARGING STATION
INVERTER
DISCONNECT
METER
COMBINER
MOD
MODULE (ONE - LINE DIAGRAM)
ELECTRICAL ABBREVIATION LIST
DESCRIPTION
ABOVE FINISH FLOOR
ELECTRICAL DETAIL SYMBOLS
PB
M
D
INVERTER
PANEL BOARD
DISCONNECT
METER
T
TRANSFORMER
COPPER CLAD GROUND ROD
C
COMBINER
SWITCHGEAR
MODULE (PV WIRING PLAN)
SITE, ROOF & FLOOR PLAN SYMBOLS
EV CHARGING STATION
PB
M
D
INVERTER
PANEL BOARD
DISCONNECT
METER
T
TRANSFORMER
AC WIRING
DC WIRING
COPPER CLAD GROUND ROD
GROUND WIRE
C
COMBINER
STRING WIRING
EV CHARGING ONLY (PARKING SPACE)
NORTH
SWITCHGEAR
CHAIN LINK FENCE
X X
NORTH ARROW
SILT FENCE
GRAPHIC SCALE
STANDARD METHODS OF NOTATION
SHEET KEY NOTES (TAGS)
REVISION / ADDENDUM TAG
ABBREVIATION
AMPERESA
A.F.F.
NOTE: SOME SYMBOLS AND ABBREVIATIONS
SHOWN MAY NOT APPLY TO THIS PROJECT.
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
OPTIMIZER
DISCONNECT
FUSED DISCONNECT
EV CHARGING STATION
EV CHARGING ONLY (PARKING SPACE)
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
MODULE (SITE & ROOF PLAN)
RAPID SHUTDOWN
CIRCUIT BREAKER
BUS BAR
WYE TRANSFORMER CIRCUIT CONNECTION
DELTA TRANSFORMER CIRCUIT CONNECTION
CURRENT TRANSFORMER (CTs)
POTENTIAL TRANSFORMER (PTs)
OUTDOOR RATED WEATHER RESISTANT
GFCI WITH IN USE COVER
SURGE PROTECTIVE DEVICE (SPD)
UTILITY POLE TO GRID
PANELBOARD (PB) W/ MAIN BREAKER
STANDARD MOUNTING HEIGHTS
HEIGHT
16" A.F.F. TO BOTTOM OF BOX. (MIN.)
DESCRIPTION
6'-0" A.F.F. TO TOP OF BOXPANELBOARD
RECEPTACLE OUTLET
48" A.F.F. TO TOP OF BOX (MAX.)
18" BELOW GRADE - TO TOP OF CONDIUT (MIN.)CONDUIT IN TRENCH
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
M
E103
SCALE: N.T.S.
DET.
E104
10'-0"
A.F.F.
SHEET C102
SHEET C103
SPOT ELEVATION
MATCH LINE
(DRAWING TITLE & IDENTIFICATION)
SHEET WHERE FOUND
DETAIL NUMBER
ENLARGEMENT AREA
E402
E201
(SECTION CUT TAG)
(ELEVATION TAG)
SHEET WHERE FOUND
DETAIL NUMBER
SHEET WHERE FOUND
DETAIL NUMBER
(BUBBLE DETAIL)
SHEET WHERE FOUND / SCALE
DETAIL NUMBER / NAME
HEAVY LINE INDICATES NEW WORK
DASHED LINE INDICATES DEMOLITION
CENTER LINE
LIGHT LINE INDICATES EXISTING WORK
UNDERGROUND CONDUIT AND WIRING
CIRCUIT HOMERUN W/ STRING IDENTIFIER
CIRCUIT BREAKER
BREAKERBKR
CB
CURRENT TRANSFORMER
CIRCUITCKT
CT
DIMENSION
DEMOLITIONDEMO
DIM
DISTRIBUTION PANEL
DISCONNECTDISC
DP
ELECTRICAL
DRAWINGDWG
ELEC
ELECTRICAL METALLIC TUBING
EMERGENCYEM / EMER
EMT
EXISTINGEX / EXIST
GROUND
FLOORFLR
G / GRD / EG
HORSEPOWER
GROUND FAULT CIRCUIT INTERRUPTERGFCI / GFI
HP
AUXILIARYAUX
HIGH VOLTAGEHV
ISOLATED GROUND
HERTZHZ
IG
JUNCTION BOXJB
KILOVOLTkV
KILOVOLT- AMPERESkVA
KILOWATT - HOURS
KILOWATTkW kWH
LINES & WIRES
MAXIMUMMAX
MOUNTED
MISCELLANEOUSMISC
MTD
NATIONAL ELECTRICAL CODENEC
MAIN DISTRIBUTION PANELMDP
MINIMUMMIN
POLE
ON CENTEROC
P
PHASEPH
NOT IN CONTRACTNIC
NOT TO SCALENTS
NOT APPLICABLEN/A
RECEPTACLERECEPT
SWITCH BOARD
SWITCHSW
SWBD
SWITCH GEARSWGR
POWER DISTRIBUTION PANELPDP
RIGID STEEL CONDUITRSC
POTENTIAL TRANSFORMERPT
AMERICAN WIRE GAUGEAWG
MAXIMUM POWER POINT TRACKINGMPPT
PHOTOVOLTAICPV
ELECTRIC VEHICLE CHARGING STATIONEVCS
TYPICAL
TAMPERPROOFTP
TYP
UNLESS OTHERWISE NOTEDU.O.N.
TELECOMMUNICATIONSTELCOM
WEATHERPROOF
WIREW
WP
TRANSFORMERXFMR
VERIFY IN FIELDV.I.F.
INVERTERINV
REQUIREDREQ'D
VOLTSV
PANELPNL
INV-1
RAPID SHUTDOWN DEVICERSD
GASGAS
GAS LINE
A
ITEM DESIGNATION
(E601 WIRE AND CONDUIT SCHEDULE)
GFCI DUPLEX RECEPTACLE
- (NEG.)
- (POS.)
STRING 1-1
STRING 1-1
CONDUIT DOWN
CONDUIT UP AREA DIVIDER LINE (E601 ONE-LINE DIAGRAM)
ROOF
ELEC ROOM
(SHEET E601)
OVER CURRENT PROTECTION DEVICE OCPD
PV ARRAY ANNOTATION PLAN
INVERTER ANNOTATION - EXAMPLE
DC
AC
INV-1
SOLAR EDGE
SE80KUS
UL1741/1EEE 1547
80 kW INVERTER
277 / 480 V, 96.5A
BOUNDARY AREA OF STRING
PV STRING DESIGNATION
SOLAR PV MODULE
INTRAROW SPACING
MANUFACTURER / MODEL
INVERTER DESIGNATION
MODEL NUMBER
SIZE
1-1
AC VOLTAGE / CURRENT
STANDARD
CT
CT CABINET
CT
CT CABINET
AC WIRING UNDERGROUND
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-G002.dwg Date: Jul 16 2025; 10:38AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
GENERAL NOTATION
G002
6-27-2025 60% REVIEW JE
7-16-2025 PERMITS JE
AutoCAD SHX Text
AutoCAD SHX Text
SHEET GENERAL NOTES
LEGEND
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-C101.dwg Date: Jul 16 2025; 9:24AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
SITE PLAN
RGM
JE
C101
AS NOTED
GAK
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT MICHIGAN
ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE (NEC), 2021
MICHIGAN BUILDING CODE, CURRENT INTERNATIONAL FIRE CODE,
AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. FIELD ADJUST THE ARRAY LAYOUT BASED ON ROOF OBSTRUCTIONS
IF NECESSARY.
4. LEGAL DESCRIPTION: ON FILE WITH CITY'S ASSESSOR'S OFFICE.
5. ZONING: "CENTRAL BUSINESS"
6. PARCEL NUMBER: 72-25-22-103-005
OWNER:
CITY OF ROYAL OAK
203 S TROY
Royal Oak, MI 48067
* INFORMATION FROM THE INTERNET AT BSAONLINE.COM
7. SCOPE OF WORK: EXISTING BUILDING, NO ADDITIONS TO BUILDING,
PV SOLAR ON ROOF WITH BALLASTED ROOF MOUNT
PV SYSTEM DESCRIPTION
NTS
SITE PLAN
NORTH
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
PB
M
D
INVERTER
PANEL BOARD
DISCONNECT
METER
T
TRANSFORMER - EXISTING
7-3-2025 JE60% REVIEW
SOLAR PV ARRAY
ON UPPER ROOF
(TYPICAL)
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
BALLASTED ROOF MOUNT RACKING: THE SOUTH FACE SYSTEM BY
K2 SYSTEMS. SEE RACKING LAYOUT AND BALLAST PLAN
(ATTACHED TO DRAWING SET)
0 15' 30' 60'
SCALE: 1" = 30'
EXISTING UTILITY METER
EXISTING MAIN BUILDING
DISCONNECT (SEE E601)
SOLAR PV ARRAY
ON LOWER ROOF
(TYPICAL)
EXISTING ELECTRICAL
EQUIPMENT
EXISTING XFMR FOR
OTHER BUILDING
EXISTING TRANSFORMER
IN SERVICE COURT
EXISTING MECHANICAL
EQUIPMENT (COOLER) IN
SERVICE COURT
EXISTING ELECTRICAL
ROOM IN BUILDING
ARRAY TYPE BALLASTED ROOF MOUNT
TILT 10°
AZIMUTH 178.0°
INTRAROW SPACING 12"
S
M
A I N
S
T R
E E
T
52'-6
" 6'-6
82'-7
T
105'-2
"6'-5
8'-10
176'-7
5'-10
M
I
N
M
I
N
9'-4
SHEET GENERAL NOTES
LEGEND
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-C102.dwg Date: Jul 16 2025; 10:18AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
CONSTRUCTION
PLAN
RGM
JE
C102
AS NOTED
RGM, GAK
CONSTRUCTION PLAN
INVERTER
T
TRANSFORMER
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
PB-A
PANEL BOARD
SHEET KEY NOTES
PV SYSTEM DESCRIPTION
1. 190 KW DC SOLAR ARRAY
2. 50 KW AC INVERTER SMA SUNNY TRIPOWER CORE1-US
3. SERVICE RACK WITH PB-A
ARRAY TYPE BALLASTED ROOF MOUNT
TILT 10°
AZIMUTH 178.0°
INTRAROW SPACING 12"
EXISTING TRANSFORMER AT
GRADE IN WALLED COURT
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT MICHIGAN
ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE (NEC), 2021
MICHIGAN BUILDING CODE, CURRENT INTERNATIONAL FIRE CODE,
AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. FIELD ADJUST THE ARRAY LAYOUT BASED ON ROOF OBSTRUCTIONS
IF NECESSARY.
4. EXISTING BUILDING: TO REMAIN, NO ALTERATIONS TO BUILDING
INTERIOR PATHWAY TO
ROOF HATCH PER IFC
1205.3.2 ITEM #3
7-3-2025 60% REVIEW JE
7-16-2025 PERMITS JE
DISTANCE INTERVAL
NOT GREATER THAN
150-FEET, THEREFORE
PER IFC CH-12
ADDITIONAL INTERIOR
PATHWAYS ARE NOT
REQUIRED (TYPICAL)
MAIN ROOF: LOW SLOPE
MEMBRANE ROOF (TYP)
OSHA 1910 SUBPART D: WALKING-WORKING SURFACES;
(ADDITIONAL FALL PROTECTION) PER OSHA 1910.28(b)(13)(ii).
EMPLOYER MAY USE DESIGNATED AREA WHEN PERFORMING
WORK THAT IS BOTH INFREQUENT AND TEMPORARY (TYPICAL)
BALLASTED ROOF MOUNT, SEE RACKING
DATA SHEET AND STRUCTURAL DRAWINGS
BY RACKING MANUFACTURER (TYPICAL)
PERIMETER PATHWAYS PER 2021 IFC 1205.3.1; EITHER AXIS
LESS THAN 250 FEET. THEREFORE 4-FOOT PATHWAY SETBACK
IS ALLOWED IN LIEU OF 6-FOOT SETBACK SHOWN, PER
EXCEPTION #1 (TYPICAL)
ROOF
HATCH
UPPER ROOF: LOW SLOPE
MEMBRANE ROOF (TYP)
S E
T
B A
C K
EXISTING COOLING TOWER BELOW
EXISTING PLUMBING
STACK VENT (TYPICAL)
INTERIOR PATHWAY TO
VENTILATION HATCH COMPLIES
WITH IFC 1205.3.2 ITEM #2
VENTILATION STACK (NOT
VENTILATION HATCH) TYPICAL
EXISTING ROOF
DRAIN / SUMP (TYP.)
DISTANCE INTERVAL NOT GREATER
THAN 150-FEET, THEREFORE PER IFC
CH-12 ADDITIONAL INTERIOR PATHWAYS
ARE NOT REQUIRED (TYPICAL)
DISTANCE INTERVAL GREATER THAN
150-FEET, THEREFORE PER IFC CH-12
INTERIOR PATHWAY PROVIDED
(TYPICAL)
INTERIOR
PATHWAY
SHADED AREA SHOWS 6-FOOT PERIMETER
PATHWAY SETBACK PROVIDED (TYPICAL)
RM. 104
EXISTING ELECTRICAL
EQUIPMENT (TYPICAL)
EXISTING COLUMN
RM. 103
MECH / ELEC
BOOK STORAGE
RM. 109
CORRIDOR
J
T
EXISTING PRIMARY
TRANSFORMER 500 KVA
T-1
CONDUIT ON WALL FROM PB-A ON
ROOF, GOES THRU WALL W/
DUCT-SEAL ALL AROUND (TYP.)
M D
P
P P
C
POINT OF CONNECTION
(P.O.C.)
DISCONNECT-A (DISC-A)
SOLAR SERVICE
DISCONNECT
ROOM
ELEC
1-1
1-2
1-5
1-6
2-21-7
2-6
3-5
1-3
1-4
2-7
3-4
3-3
3-2
3-1
3-7
3-6
2-1
2-3
2-5 2-4
PB-A
INV-1
INV-2
INV-3
T
SHEET GENERAL NOTES
LEGEND
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT
MICHIGAN ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE
(NEC), AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. CONDUIT FILL TO BE LESS THAN 40%.
SHEET KEY NOTES
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E101.dwg Date: Jul 17 2025; 10:20AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
ELECTRICAL
SITE PLAN
RGM
JE
E101
AS NOTED
GAK
PV SYSTEM DESCRIPTION
ELECTRICAL SITE PLAN
SCALE: NONE
ELECTRICAL ROOM - PLAN DETAIL
E101
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
M
D
INVERTER
DISCONNECT
METER - EXISTING
T
TRANSFORMER
AC WIRING CONDUIT
DC WIRING CONDUIT
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
1. 150 KW AC SOLAR ARRAY (190 KW DC)
2. INVERTER
3. SOLAR PV DISCONNECT (DISC-A) IN ELEC RM
4. EXISTING TRANSFORMER
5. POINT OF CONNECTION (POC) MDP IN ELECTRICAL ROOM
6. SERVICE RACK WITH PANELBOARD (PB-A)
STRING BOUNDARY LINE
PB-A
PANEL BOARD
7-3-2025 60% REVIEW JE
ARRAY TYPE BALLASTED ROOF MOUNT
TILT 10°
AZIMUTH 178.0°
INTRAROW SPACING 12"
7-16-2025 PERMITS JE
EX. COOLING TOWER
PB-A
INV-1
INV-2
INV-3
PB-A
T
RM. 104
EXISTING ELECTRICAL
EQUIPMENT (TYPICAL)
EXISTING COLUMN
RM. 103
MECH / ELEC
BOOK STORAGE
RM. 109
CORRIDOR
J
T
EXISTING PRIMARY
TRANSFORMER 500 KVA
T-1
CONDUIT ON WALL FROM PB-A ON
ROOF, GOES THRU WALL W/
DUCT-SEAL ALL AROUND (TYP.)
M D
P
P P
C
POINT OF CONNECTION
(P.O.C.)
DISCONNECT-A (DISC-A)
SOLAR SERVICE
DISCONNECT
ROOM
ELEC
SHEET GENERAL NOTES
LEGEND
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT
MICHIGAN ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE
(NEC), AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. CONDUIT FILL TO BE LESS THAN 40%.
SHEET KEY NOTES
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E102.dwg Date: Jul 16 2025; 10:22AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
AC POWER
PLAN
RGM
JE
E102
AS NOTED
GAK
PV SYSTEM DESCRIPTION
D
INVERTER
DISCONNECT
T
TRANSFORMER
AC WIRING CONDUIT
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
PB-A
PANEL BOARD
1. 150 KW AC SOLAR ARRAY (190 KW DC)
2. INVERTER
3. SOLAR SERVICE DISCONNECT (DISC-A) IN ELEC RM
4. EXISTING TRANSFORMER
5. POINT OF CONNECTION (POC) MDP IN ELECTRICAL ROOM
6. SERVICE RACK WITH PANELBOARD (PB-A)
7-3-2025 60% REVIEW JE
ARRAY TYPE BALLASTED ROOF MOUNT
TILT 10°
AZIMUTH 178.0°
INTRAROW SPACING 12"
AC POWER PLAN
ELECTRICAL ROOM - PLAN DETAIL
E101
INV-1
INV-2
INV-31-1
1-2
1-5
1-6
2-21-7
2-6
3-5
1-3
1-4
2-7
3-4
3-3
3-2
3-1
3-7
3-6
2-1
2-3
2-5 2-4
SHEET GENERAL NOTES
LEGEND
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT
MICHIGAN ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE
(NEC), AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. CONDUIT FILL TO BE LESS THAN 40%.
SHEET KEY NOTES
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E103.dwg Date: Jul 17 2025; 10:18AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
DC POWER
PLAN
RGM
JE
E103
AS NOTED
GAK
PV SYSTEM DESCRIPTION
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
M
D
INVERTER
DISCONNECT
METER - EXISTING
T
TRANSFORMER
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
PB-A
PANEL BOARD
7-3-2025 60% REVIEW JE
DC WIRING CONDUIT
STRING BOUNDARY LINE
ARRAY TYPE BALLASTED ROOF MOUNT
TILT 10°
AZIMUTH 178.0°
INTRAROW SPACING 12"
1. SOLAR ARRAY (190 KW DC)
2. INVERTER
1 1
DC POWER PLAN
INV-1
INV-2
INV-3
T
1-1
1-2
1-5
1-6
2-21-7
2-6
3-5
1-3
1-4
2-7
3-4
3-3
3-2
3-1
3-7
3-6
2-1
2-3
2-5 2-4
RM. 104
EXISTING ELECTRICAL
EQUIPMENT (TYPICAL)
EXISTING COLUMN
RM. 103
MECH / ELEC
BOOK STORAGE
RM. 109
CORRIDOR
J
T
EXISTING PRIMARY
TRANSFORMER 500 KVA
T-1
CONDUIT ON WALL FROM PB-A ON
ROOF, GOES THRU WALL W/
DUCT-SEAL ALL AROUND (TYP.)
M D
P
P P
C
POINT OF CONNECTION
(P.O.C.)
DISCONNECT-A (DISC-A)
SOLAR SERVICE
DISCONNECT
ROOM
ELEC
SHEET GENERAL NOTES
LEGEND
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT
MICHIGAN ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE
(NEC), AND ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. REFER TO SHEET E601 FOR ONE-LINE DIAGRAM FOR
INTERCONNECTION BETWEEN EQUIPMENT.
3. CONDUIT FILL TO BE LESS THAN 40%.
4. K2 SYSTEMS RACKING IS UL 2703 RATED, AND MEETS NEC 690.43
REQUIREMENTS.
5. INSTALL BONDING IN ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS. WHEN SO INSTALLED ALL CONNECTIONS MEET THE
REQUIREMENTS OF NEC 690.43.
6. BOND ANY METAL RACEWAY TO THE K2 CHASSIS WITH ILSCO LUG.
SHEET KEY NOTES
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E104.dwg Date: Jul 17 2025; 10:17AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
GROUNDING
PLAN
RGM
JE
E104
AS NOTED
GAK
INVERTER #
1-1
STRING #
PV STRING DESIGNATION
D
INVERTER
DISCONNECT
T
TRANSFORMER
GROUNDING WIRE
3 WORKING DAYS
FOR FREE LOCATION OF PUBLIC UTILITY LINES
IN MICHIGAN CALL: 811
BEFORE YOU DIG
CALL MISS DIG
1-800-482-7171
1. 150 kW AC SOLAR ARRAY (190 KW DC)
2. INVERTER
3. SOLAR PV DISCONNECT (DISC-A) IN ELEC RM
4. RACK TO RACK GROUNDING USE GREEN. USE-2 #6 COPPER.
5. POINT OF INTERCONNECTION (POI) SOURCE SIDE OF MDP
6. INSTALL GROUNDING LUG PER MANUFACTURER SPECIFICATIONS.
7. AC GROUNDING CONNECTION TO EXISTING GROUNDING
ELECTRODE SYSTEM.
8. SERVICE RACK WITH PANELBOARD (PB-A)
STRING BOUNDARY LINE
PB-A
PANEL BOARD
EX. COOLING TOWER
GROUNDING LUG
7-3-2025 60% REVIEW JE
GROUNDING PLAN
ELECTRICAL ROOM - PLAN DETAIL
E104
(TYP)
(TYP)
(TYP)
UNISTRUT P1001
PGSL RACK FRAMING
8" x 16" x4" SOLID
CONCRETE BLOCK
BALLAST
5'-0"
1'-0"
2'-0"
RUBBERFORM ROOF
WALKWAY MATS
INSTALLED UNDER
UNISTRUT BASE (TYP.)
UNISTRUT P1001
PGSL RACK
FRAMING
8" x 16" x 4" SOLID
CONCRETE BLOCK
BALLAST (TYP.)
7'-0" X 2'-0" X 5/16" THICK
RUBBERFORM ROOF WALKWAY MATS
INSTALLED BELOW UNISTRUT BASE,
(TYPICAL)
8" x 16" x 4" SOLID
CONCRETE BLOCK
BALLAST (TYP.)
PANEL
BOARD - A
8" x 16" x 4" SOLID
CONCRETE BLOCK
BALLAST (TYP.)
1'-0"3'-0"
5/16" THICK
RUBBERFORM ROOF
WALKWAY MATS
INSTALLED BELOW
UNISTRUT BASE, (TYP.)
2'-0"
CONDUIT TO BLDG.
ELEC. TIE-IN
E401
E401
CONDUIT TO BLDG. ELEC.
TIE-IN
N
T S
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E401.dwg Date: Jul 16 2025; 10:25AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
EQUIPMENT
ELEVATIONS
RGM
JE
E401
AS NOTED
RGM, GAK
N.T.S.
FRONT ELEVATION - EQUIPMENT RACK
E401
SIDE ELEVATION - EQUIPMENT RACK
PLAN - EQUIPMENT RACK
SHEET GENERAL NOTES
LEGEND
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT MICHIGAN
ELECTRICAL CODE, 2023 NATIONAL ELECTRICAL CODE (NEC), 2021
MICHIGAN BUILDING CODE, CURRENT INTERNATIONAL FIRE CODE, AND
ALL APPLICABLE LOCAL CODES AND STANDARDS.
2. FIELD ADJUST THE ARRAY LAYOUT BASED SITE OBSTRUCTIONS
IF NECESSARY.
3. SITE PLAN BASED ON INFORMATION PROVIDED BY OWNER.
SHEET KEY NOTES
7-3-2025 JE60% REVIEW
GALVANIZED
SLOTTED STRUT
1-5/8" MINIMUM
M
A X
REFER TO SHEET
E601 FOR CONDUIT
SIZE (TYPICAL)
NOTE:
SUPPORT CONDUIT PER NEC 2023
MINIMUM EVERY 10'-0"
SECURING ANCHOR
WALL / SURFACE
MASONRY WALL:
ANCHOR WITH MINIMUM
1/4" LEAD ANCHORS
FRAMED WALL:
ANCHOR TO STUDS
PIPE TUBE / RIGID STEEL
CONDUIT CLAMP
M
I N
P E
R
C
O D
E
PLAN VIEW
SECTION
REFER TO SHT. E601
FOR CONDUIT SIZE
CONDUIT SUPPORT
M
I N
P E
R
C
O D
E
N T
S
REFER TO SHT. E601
FOR CONDUIT SIZE
CONDUIT SUPPORT
M
I N
P E
R
C
O D
E
N T
S
GROUND WIRE, FROM
ARRAY TO INVERTER
SUPPORT STRUCTURESTAR WASHER
LAY-IN LUG RATED
FOR DIRECT BURIAL
BOLT & NUT
RACK LUG HARDWARE
GALVANIZED STEEL COPPER GALVANIZED STEEL
ALUMINUM STAINLESS OR TIN-PLATED
COPPER
STAINLESS STEEL
STAINLESS STEEL COPPER, STAINLESS OR
TIN-PLATED COPPER
STAINLESS STEEL
CONDUIT SUPPORT
REFER TO SHT. E601
FOR CONDUIT SIZE
M
I N
P E
R
C
O D
E
N T
S
GROUND LUG, ILSCO SGB-4:
TORQUE THE MOUNTING BOLT TO 6.2 FT-LBS.
TORQUE THE TERMINAL BOLT TO 2.9 FT-LBS.
NOTE:
CONNECT ONE GROUNDING
CONDUCTOR PER SUB ARRAY.
MC4 CONNECTOR
(TYPICAL)
RAPID SYSTEM SHUTDOWN
MOUNTED TO RACKING PER
MANUFACTURERS SPECIFICATIONS
MC4 CONNECTOR
(TYPICAL)
RAPID SYSTEM SHUTDOWN
MOUNTED TO RACKING PER
MANUFACTURERS SPECIFICATIONS
MC4 CONNECTOR
(TYPICAL)
RAPID SYSTEM SHUTDOWN
MOUNTED TO RACKING PER
MANUFACTURERS SPECIFICATIONS
GENERAL BONDING/GROUNDING NOTES:
A SAMPLE BONDING PATH DIAGRAM IS SHOWN. YOUR SPECIFIC INSTALLATION MAY VARY, BASED UPON
SITE CONDITIONS AND REQUIREMENTS.
INSTALLATION SHOULD BE PERIODICALLY REINSPECTED FOR LOOSE COMPONENTS OF FASTENERS AND
ANY CORROSION. PLEASE NOTE THAT REMOVING A PV MODULE FROM A SYSTEM IS NOT CONSIDERED TO
BE ROUTINE MAINTENANCE.
CAUTION: MODULE REMOVAL MAY DISRUPT THE BONDING PATH AND INTRODUCE THE RISKS OF ELECTRIC
SHOCK. ADDITIONAL STEPS MAY BE REQUIRED TO MAINTAIN THE BONDING PATH. MODULES SHOULD ONLY
BE REMOVED BE QUALIFIED PERSONS IN COMPLIANCE WITH MANUFACTURERS INSTRUCTIONS.
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E501.dwg Date: Jul 16 2025; 10:27AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
ELECTRICAL
DETAILS
RGM
JE
E501
AS NOTED
GAK, RGM
DETAIL - CONDUIT SUPPORT - ROOF
E501
DETAIL - CONDUIT MASONRY WALL
SCALE: NONE
GROUNDING DETAIL - MECH. / ELEC.
E501
ARRAY GROUNDING LUG DETAIL
7-3-2025 JE60% REVIEW
DETAIL - STRING MODULE WIRING
#6 COPPER GROUND WIRE
INSTALL ILSCO GROUNDING LUG PER
MANUFACTURERS SPECIFICATIONS
(TYPICAL)
MANUFACTURERS CONDUIT GROUNDING CLAMP
MANUFACTURERS ARRAY GROUNDING
MANUFACTURERS CONTINUNITY
7-16-2025 PERMITS JE
NONE
BONDING / GROUNDING PLAN (TYPICAL)
E501
E501
BALLASTED ROOF MOUNT RACKING: THE SOUTH FACE SYSTEM BY K2 SYSTEMS.
SEE RACKING LAYOUT AND BALLAST PLAN (TO BE ATTACHED TO DRAWING SET)
DC
AC
#10 AWG (TYP.)
#10 AWG PV WIRE
HOME RUN, (TYP.)
DC
AC
FIRST AND LAST STRINGS
ARE SHOWN (TYPICAL)
18 CKT, 277 / 480 V, 250 A, 3Ø, 4W
W/ 250 A MAIN BREAKER
PANELBOARD
IN NEMA 3R ENCLOSURE
480 V, 250 A, 3Ø W /250 A
MAIN
BREAKER
ELECTRICAL ROOM
ROOF
UL1741/1EEE 1547
50kW INVERTER
277 / 480 V, 64 A
192A
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
64 A
64 A
80 A
AP SMART RSD-S-PLC RAPID SYSTEM
SHUTDOWN (TYPICAL)
MOD
STRINGS 1-1 THRU 1-5
80 A
SPARE SPARE
SPARE
80A
FROM UTILITY
750 kVA 4800V PRI.
277 / 480 V 3Ø 4W SEC.
MOD
MOD
STRINGS 2-2 THRU 2-3
DC
AC
MOD
MOD
64 A
STRINGS 3-1 THRU 3-5
STRINGS 2-4 AND 2-5
MOD
MOD
STRINGS 2-6 AND 2-7
MOD
MOD
STRINGS 3-6 AND 3-7
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
MOD
CONDUIT AND WIRE SIZE CHART
H
SMA Sunny Tripower
CORE1-US (STP 50-US-41)
D
PB-A
MAIN PV AC DISCONNECT SWITCH
400A, 277/480V, 3Ø, 4W
WITH 250A RK-5 FUSES
NEMA 1
E
DISC-A
(EXISTING)
MAIN DISTRIBUTION PANEL
277/480 V, W/ BUS BAR
F
BUS BAR
TO BUILDING LOADS
(TYPICAL)
(P.O.C.) POINT OF CONNECTION
(SUPPLY SOURCE SIDE
CONNECTION)
A
800A MAIN
BREAKER
LOAD SIDESOURCE
MDP
GROUND AND NEUTRAL ARE
BONDED, TO BE CONNECTED
TO THE FACILITY GROUND
ELECTRODE SYSTEM
M
(EXISTING)
UTILITY
METER
MEDIUM VOLTAGE
DISCONNECT SWITCH
MAIN BUILDING
DISCONNECT
(EXISTING)
INVERTER 1
A
UL1741/1EEE 1547
50kW INVERTER
277 / 480 V, 64 A
SMA Sunny Tripower
CORE1-US (STP 50-US-41)
INVERTER 2
B
UL1741/1EEE 1547
50kW INVERTER
277 / 480 V, 64 A
SMA Sunny Tripower
CORE1-US (STP 50-US-41)
INVERTER 3
C
TRANSFORMER
(EXISTING)
ELECTRICAL ROOM
OUTSIDE - OFF S. TROY ST.
SERVICE COURTYARD
SERVICE COURTYARD
INTEGRATED
DC SAFETY
SWITCH UL
1699B
INTEGRATED
DC SAFETY
SWITCH UL
1699B
INTEGRATED
DC SAFETY
SWITCH UL
1699B
MOD
MOD
MOD
MOD
MOD
MOD
STRING 2-1
I
G
WHEN CONNECTING A SINGLE MODULE TO AP SMART
RSD-D-20 RAPID SYSTEM SHUTDOWN. CONNECT THE
MODULE TO INPUT ONE ON THE RSD-D-20. INPUT TWO
CONNECT THE TWO LEADS TOGETHER TO SHORT OUT
INPUT NUMBER TWO PER MANUFACTURERS
REQUIREMENTS (TYPICAL).
STRINGS 1-6 AND 1-7
NO SCALE
ONE LINE DIAGRAM
A1
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E601.dwg Date: Jul 21 2025; 8:47AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ONE LINE DIAGRAM
E601
GAK
SHEET GENERAL NOTES
SHEET KEY NOTES
PV SYSTEM DESCRIPTION
LEGEND
INVERTER #
1-1
STRING #
DISCONNECT SWITCH
GROUND
PV STRING DESIGNATION
FOR TOTAL SYSTEM:
PV MODULE MODEL: JINKO SOLAR (EAGLE), JKM585N-72HL4-BDV
PV MODULE SIZE: 44.65" W X 89.69" L X 1.18" H
PV MODULE PMAX: 585 W
RAPID SYSTEM SHUTDOWN: AP SMART RSD-D-20
INVERTER: SMA SUNNY TRIPOWER
CORE 1-US (STP 50-US-41)
NO OF STRINGS PER INVERTER: 7
DC TO AC RATIO: 1.27
NUMBER OF INVERTERS: 3
NUMBER OF STRINGS: 21
NUMBER OF MODULES: 325
NUMBER OF RAPID SYSTEM SHUTDOWN: 167
TOTAL NAMEPLATE SIZE: 190.125 kW DC
150 kW AC
NOTE: PV SYSTEM IS 1000 V DC
7-3-2025 JE60% REVIEW
41 92
5 94
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
7-16-2025 JEPERMITS
4 10
WARNING
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
LABEL 2
THE UTILITY METERING CABINET, EACH INVERTER, EACH DC AND
AC DISCONNECTING MEANS (SWITCHES AND BREAKERS) MUST
BE LABELED WITH THIS PLACARD
PHOTOVOLTAIC
SYSTEM
DISCONNECT
LABEL 1
EACH PV STSTEM DISCONNECTING MEANS MUST BE
LABELED WITH THIS PLACARD
LABEL 4
INVERTER DC DISCONNECT MUST BE
LABELED WITH THIS PLACARD
WARNING
IF GROUND FAULT IS INDICATED ALL
NORMALLY GROUNDED CONDUCTORS
MAY BE UNGROUNDED AND ENERGIZED
LABEL 3
LABEL 6
INSTALL MAP PLACARD AS PER UTILITY REQUIREMENTS, SIGNAGE SHALL BE RED BACKGROUND
WITH WHITE ENGRAVED LETTERS: (CAUTION
", POWER TO...(
"), CALL OUTS (
THIS LABEL TO BE INSTALLED IN ELECTRICAL ROOM ON MAIN PV AC DISCONNECT.
CAUTION
POWER TO THIS FACILITY IS ALSO SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS AS SHOWN:
NORTH
LABEL 5
INTERACTIVE SYSTEM POINT OF INTERCONNECTION
MUST BE LABELED WITH THIS PLACARD
PHOTOVOLTAIC SYSTEM
AC POINT OF INTERCONNECTION
THIS EQUIPMENT FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICE SHALL NOT EXCEED
AMPACITY OF BUSSBAR
WARNING
MAX SYSTEM DC VOLTAGE
SHORT CIRCUIT DC CURRENT 50kW
1000 V
64 A
RATED AC OUTPUT CURRENT
NOMINAL OPERATING AC VOLTAGE
192 A
480 VAC
ELECTRIC SHOCK HAZARD ELECTRIC SHOCK HAZARD
PHOTOVOLTAIC SYSTEM
DC DISCONNECT
WARNING
SOURCES UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
DUAL POWER SUPPLY
LABEL 8
PHOTOVOLTAIC
SOLAR BREAKER
LABEL 10
LABEL 9
DO NOT RELOCATETHIS
OVERCURRENT DEVICE
LABEL 7
EQUIPMENT BACK FED FROM PHOTOVOLTAIC SYSTEMS
MUST BE LABELED WITH THIS PLACARD INCLUDING BOTH 480 V.
DISCONNECTS AND PRIMARY SWITCH AT SUBSTATION
PHOTOVOLTAIC
SYSTEM
kWH METER
LABEL 11
AC
DISCONNECT
LABEL 12
EACH AC DISCONNECTING MEANS MUST BE
LABELED WITH THIS PLACARD
DC
DISCONNECT
LABEL 13
EACH DC DISCONNECTING MEANS MUST BE
LABELED WITH THIS PLACARD
TOP OF LABEL IS WHITE ON BLACK, BOTTOM IS BLACK ON WHITE
TOP OF LABEL IS WHITE ON BLACK, BOTTOM IS BLACK ON WHITE
LABEL 14
CAUTION
PV OUTPUT CIRCUIT
LABEL 15
CAUTION
INVERTER OUTPUT CIRCUIT
PHOTOVOLTAIC
SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
LABEL 16
DC
PHOTOVOLTAIC
SOURCE CIRCUIT
LABEL 17
LABEL 18
CAUTION SOLAR CIRCUIT
INVERTER AND P.O.I.
LOCATION OF ROOF HATCH
TRANSFORMER AT GRADE
SERVICE RACK WITH PB-A
LOCATED ON ROOF
INVERTERS ON ROOF
SERVICE COURTYARD
PV ARRAY ON LOWER ROOF
PV ARRAY ON UPPER ROOF
MAIN PV AC DISCONNECT AND
MDP W/ P.O.C. IN ELECTRICAL
ROOM BELOW
MAIN BUILDING DISCONNECT
WITH UTILITY METER AT GRADE
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E701.dwg Date: Jul 16 2025; 10:30AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
LABELS AND
PLACARDS
RGM
JE
E701
NONE
7-3-2025 60% REVIEW JE
7-16-2025 REVIEW JE
NOVA Consultants, Inc.
21580 Novi Road
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E801.dwg Date: Jul 16 2025; 10:31AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
DATA SHEETS
E801
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E802.dwg Date: Jul 16 2025; 10:35AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
DATA SHEETS
E802
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E803.dwg Date: Jul 16 2025; 10:36AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
DATA SHEETS
E803
Suite 300
Novi, MI 48375
Phone: (248) 347-3512
Fax: (248) 347-4152 www.novaconsultants.com
NO. DATE DESCRIPTION APPVD.
REVISED
SHEET NUMBER
DRAWN BY
SHEET SIZE
SCALE
CERTIFICATION
DATE DESCRIPTION APPVD.
ISSUED
PROJECT NUMBER
25-03-1206
22x34
DESIGNED BY CHECKED BY
1 2 3 4 5
1 2 3 4 5
A
B
C
D
Dwg: J:\PROJECTS\25 projs\25-03-1206 City of Royal Oak Library Solar PV Engineering\Drawings\25031206-E804.dwg Date: Jul 16 2025; 10:37AM User: george kachadoorian
222 E. 11 MILE ROAD
ROYAL OAK, MI 48067
150 kW AC SOLAR ARRAY
190 kW DC SOLAR ARRAY
ROYAL OAK
PUBLIC LIBRARY
DATA SHEETS
E804
| doc02178420250722113945 |
| 25031206-G002 |
| Sheets and Views |
| G002 |
| 25031206-C101 |
| Sheets and Views |
| C101 |
| 25031206-C102 |
| Sheets and Views |
| C102 |
| 25031206-E101 |
| Sheets and Views |
| E101 |
| 25031206-E102 |
| Sheets and Views |
| E102 |
| 25031206-E103 |
| Sheets and Views |
| E103 |
| 25031206-E104 |
| Sheets and Views |
| E104 |
| 25031206-E105 |
| Sheets and Views |
| E105 |
| 25031206-E401 |
| Sheets and Views |
| E401 |
| 25031206-E501 |
| Sheets and Views |
| E501 |
| 25031206-E601 |
| Sheets and Views |
| E601 |
| 25031206-E701 |
| Sheets and Views |
| E701 |
| 25031206-E801 |
| Sheets and Views |
| E801 |
| 25031206-E802 |
| Sheets and Views |
| E802 |
| 25031206-E803 |
| Sheets and Views |
| E803 |
| 25031206-E804 |
| Sheets and Views |
| E804 |
File details come from the government source that posted it. Updated .