City of DeSoto 2026 Inspection.pdf

PDF 10 MB Posted

Attached to
DeSoto Westmoreland PS Recoating Two 5 MG Ground Storage Tanks
Solicitation number
146699
Issued by
Dallas County, Texas

About this file

This is a Remotely Operated Vehicle (ROV) inspection report prepared by US Underwater, LLC for the City of DeSoto, Texas, documenting underwater inspections of seven potable water storage facilities conducted in July 2026. The inspection report certifies that all work was completed in accordance with American Water Works Association (AWWA) standards, specifically ANSI/AWWA C652-92 disinfection procedures. The facilities inspected include two 1,500,000-gallon elevated tanks (Parks EST and Parkerville), one 2,000,000-gallon elevated tank (Biarwood Hydropillar), two 5,000,000-gallon ground tanks (North and South), one 3,000,000-gallon clearwell (N Hampton), and one 30,000-gallon pressure tank (30K PT). Inspections were conducted between June 7 and July 7, 2026, with comprehensive external and internal assessments of each facility including structural condition, coating integrity, safety systems, and water quality parameters.

The report identifies multiple maintenance recommendations across all facilities, with critical deficiencies requiring immediate attention. Priority maintenance items include sediment removal from floor plates across all tanks (ranging from 20% to 100% coverage with depths between 1/8 inch and 2 inches), repair of the water access ladder at the North tank showing heavy corrosion and missing rungs, repair of the cathodic protection system at the North tank where anode plates have shifted, removal of the fall protection system at Parkerville tank, installation of a new 16-gauge fine mesh screen on the South tank roof ventilation structure, and installation of confined space entry placards at three facilities. Coating condition ratings range from SSPC rating 3 to 9, with several tanks showing moderate rust development and staining. All facilities are equipped with proper locking mechanisms on water access hatches and compliant overflow systems, though some roof access hatches require lock installation. The inspection serves as a baseline for required maintenance and capital improvement planning for the City of DeSoto's water storage infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

City of DeSoto

2026 ROV Inspections

July 2026

US UNDERWATER

123 Sentry Drive • Mansfield, TX 76063 800.860.2178 www.usunderwaterservices.com http://www.usunderwaterservices.com/

US Underwater, LLC | 123 Sentry Drive, Mansfield, TX 76063 P: 817-447-7321, F: 817-447-0021, Toll: 800-860-2178

Statement of Certification

City of DeSoto

Location: DeSoto, TX

July 2026

This form certifies the inspections were completed on the above date for the facilities listed below:

[2] 1,500,000 Gallon Elevated [1] 2,000,000 Gallon Elevated [2] 5,000,000 Gallon Ground

[1] 3,000,000 Gallon Clearwell [1] 30,000 Gallon Pressure

U.S. Underwater certifies the work was completed in accordance with the American Water Works Association’s [AWWA] current standards [ANSI/AWWA c652-92] regarding disinfection procedures when conducting underwater activities in potable water storage facilities. All equipment used is designated for potable water use only.

Ryan Enos Director of Sales & Marketing US Underwater, LLC

Report Proposal July 15, 2026

City of DeSoto U.S. Underwater Brandon Lacy Ryan Enos blacy@desototexas.gov renos@usunderwaterservices.com

These recommendations are based on the results of the inspection and are suggested to comply with OSHA and/or AWWA standards. Please contact your U.S. Underwater Account Manager for a customized proposal.

Inspection Capacity Type Name #1 1,500,000 Elevated Parks EST

Remove the 1/8 in-1 1/2 in, 100% coverage of sediment from the floor plates

#2 1,500,000 Elevated Parkerville

Remove the fall protection system from water access ladder Remove the 1/16 in-1/4 in, 70% coverage of sediment from the floor plates

#3 2,000,000 Elevated Biarwood Hydropillar

Remove the 1/16 in-1/4 in, 60% coverage of sediment from the floor plates

#4 5,000,000 Ground North

Repair water access ladder Repair cathodic protection Remove the 1/4 in-2 in, 90% coverage of sediment from the floor plates

#5 5,000,000 Ground South

Install a new 16-gauge fine mesh screen on the roof ventilation structure Remove the 1/4 in-2 in, 100% coverage of sediment from the floor plates

#6 3,000,000 Clearwell N Hampton

Remove the 1/4 in-2 in, 100% coverage of sediment from the floor plates

#7 30,000 Pressure 30K PT

Remove the 1/8 in-1 in, 20% coverage of sediment from the floor plates mailto:blacy@desototexas.gov mailto:renos@usunderwaterservices.com

Rust

Grades A

Description

Graphical Representation

No rusting or less than 0.01% of surface rusted

Unnecessary

Minute rusting less than 0.03% of

8B

Few isolated rust spots less than

0.1% of surface rusted

Less than 0.3% of surface rusted

6C

Extensive rust spots but less than

Rusting to the extent of 3% of

4D

Rusting to the extent of 10% of

3E

Approximately on sixth of the surface rusted 16%

Approximately one third of the surface rusted 33%

Approximately one half of the surface rusted 50%

References

Standard Method of Evaluating Degree of Rusting on

Painted Steel Surfaces – SSPC-Vis 2-82 & ASTM D 610-85 The graphical representations show examples of area percentages, which may be helpful in rust grading. The use of photographical reference standards requires the following precautions:

Some finishes are stained by rust. This staining must not be confused with the actual rusting involved.

Accumulated dirt or other material may make accurate determination of the degree of rusting difficult.

Certain types of deposited dirt that contain iron or iron compounds may cause surface discoloration that should not be mistaken for corrosion.

It must be realized that failure may vary over a given area and discretion must therefore be used in applying these reference standards.

In evaluating surfaces, consideration shall be given to the color of the finish coating, since failures will be more apparent on a finish that shows color contrast with rust, such as white, than on a similar color, such as iron oxide finish.

The photographic reference standards are not required for use of the rust-grade scale since the scale is based upon the percent of the area rusted and any method of assessing area rusted may be used to determine the rust grade.

1% of surface rusted

Elevated Inspection - ROV

City of DeSoto Inspection #1 / Parks EST Complete

Flagged items 1

Inspection Title City of DeSoto Inspection #1

Client Specific Tank Name Parks EST

Client City of DeSoto

Job Number U269501YX.00

Prepared by Rov One

Conducted on 06.07.2026 08:11 CDT

Recommended Maintenance 1 flagged

Internal Inspection

Is Facility Free of Sediment/Debris? No

Recommend the 1/8 in-1 1/2 in, 100% coverage, of sandy silt sediment be removed from the floor plates

External Inspection

Reference photo of facility

Photo 1

Facility Type Multi-Leg

Facility Construction Metal-Welded

Capacity 1.5MG

Height 172ft

Diameter 80ft

Tank ID Plate Yes

Tank ID Plate Photo

Photo 2

Tank Builder Horton Elevated Tank

Year Built 1979

Serial/ID Number 91539

Lower Level

Condition of Intruder Protection Fence Good

Condition of Foundation Good

Photo of Foundation

Photo 3

Photo 4 Photo 5

Photo 6 Photo 7

Photo 8

Photo 9

Photo 10 Photo 11

Photo 12 Photo 13

Photo 14

Photo 15

Lower Level Manway/Facility Access Door Yes

Photo of Lower Level Manway

Photo 16

Photo 17 Photo 18

Photo 19

Size 36.75in x 80.5in

Was Manway Labeled 'Confined Space?' Yes

Water Level Indicator Type(s)

Pressure Gauge Electronic

Photo of Water Level Indicator(s)

Photo 20

Photo 21

Condition of Water Level Indicator(s) Good

Condition of Overflow Good

Photo of Overflow

Photo 22

Photo 23 Photo 24

Does Overflow Extend to Ground/Accessible? Compliant

Does Overflow Flapper Seal? Compliant

Photo of Flapper

Photo 25

Photo 26

Overflow Diameter 12in

Photo of External Plumbing

Photo 27

Photo 28

Condition of External Plumbing Good

Condition of External Lower Ladder Good

Photo of External Lower Ladder

Photo 29

Photo 30 Photo 31

Photo 32 Photo 33

Width of External Lower Ladder 16.75in

Diameter of Rung .75in

Length of External Lower Ladder 110ft

Length of Standoff 6in

Condition of Intruder Protection Door Good

Photo of Intruder Protection Door

Photo 34

Does External Ladder Have Cage? Yes

Diameter of Cage 28in

Cage Material Mild Steel

Photo of Cage

Photo 35

Photo 36

Condition of Fall Protection System Good

Photo of Fall Protection System

Photo 37

Upper Level

Condition of Catwalk Good

Condition of Sidewall Plates Good

Photo of Sidewall Plates

Photo 38

Photo 39 Photo 40

Photo 41

Condition of Sidewall Protective Coating (SSPC Rating) 8

Condition of Center Access Tube Good

Condition of Side Manway Access Hatch Good

Condition of External Upper Ladder Good

Photo of External Ladder

Photo 42

Photo 43 Photo 44

Photo 45

Width of External Ladder 17 in

Diameter of Rung 7/8 in

Length of External Ladder 50 ft

Length of Standoff 9 in

Photo 46

Condition of Roof Access Hatch Good

Photo of Roof Access Hatch

Photo 47

Photo 48 Photo 49

Size of Roof Access Hatch 24 in

Was Roof Access Hatch Locked? No, Needs Lock Installed

Photo of Roof Plates

Photo 50

Photo 51 Photo 52

Photo 53 Photo 54

Condition of Roof Plates Good

Condition of Roof Coating (SSPC Rating) 6

Condition of Anode Plates Compliant

Photo of Water Access Hatch

Photo 55

Photo 56 Photo 57

Photo 58 Photo 59

Condition of Water Access Hatch Good

Size of Water Access Hatch 31 in

Was Water Access Hatch Labeled 'Confined Space?' Yes

Was Water Access Hatch Locked? Yes, Lock in Good Condition

Type of Roof Vent Mushroom Shape

Photo of Roof Vent

Photo 60

Photo 61 Photo 62

Photo 63 Photo 64

Photo 65

Photo 66

Condition of Roof Vent Good

Vent Circumference 76 in

Vent Screen opening Height 12 in

Condition of Vent Screen Compliant

Condition of Aircraft Warning Lights Not-Working

Photo 67

RF Antennas Present? Yes

Photo of Antennas

Photo 68

Photo 69

RF Hazard Warning Signs Posted? Yes

Internal Inspection 1 flagged

Condition of Water Access Ladder Good

Photo of Water Access Ladder

Photo 70

Photo 71 Photo 72

Photo 73 Photo 74

Photo 75

Photo 76

Photo 77

Width of Water Access Ladder 23 in

Length of Ladder 45 ft

Length of Standoff N/A

Condition of Fall Protection System Fair

Condition of Roof Supports N/A

Photo 78

Photo 79 Photo 80

Photo 81

Condition of Roof Plates (SSPC Rating) 9

Condition of Water Level Indicator System N/A

Photo 82

Photo 83 Photo 84

Photo 85 Photo 86

Photo 87

Condition of Cathodic Protection N/A

Photo 88

Photo 89 Photo 90

Photo 91 Photo 92

Photo 93

Photo 94

Photo 95

Condition of Sidewall Plates (SSPC Rating) 8

Condition of Side Manway Access Good

Photo of Side Manway Access

Photo 96

Condition of Internal Plumbing Good

Photo of Internal Plumbing

Photo 97

Photo 98 Photo 99

Photo 100 Photo 101

Photo 102

Photo 103

Photo 104

Does Facility Have a Mixer? No

Condition of Floor Plates Floor not visible due to sediment

Recommend the 1/8 in-1 1/2 in, 100% coverage, of sandy silt sediment be removed from the floor plates

Sediment/Debris Type

Sand Sandy Silt

Photo of Sediment/Debris

Photo 105

Photo 106 Photo 107

Photo 108 Photo 109

Photo 110

Photo 111

Photo 112

Sediment Depth .125-1.5in

Percentage of Sediment Coverage 100%

Level of Staining Inside Facility Moderate

Photo of Staining

Photo 113

Photo 114 Photo 115

Photo 116 Photo 117

Photo 118

Photo 119

Photo 120

Clarity of Water Good

Quality of Water Good

Water Temperature Warm

Water Depth (Maximum) 59ft

Water Depth (Actual) 20ft

Inspector

A. Nowacki

15.07.2026 14:55 CDT

City of DeSoto Inspection #2 / Parkerville Complete

Flagged items 2

Inspection Title City of DeSoto Inspection #2

Client Specific Tank Name Parkerville

Job Number U269501TX.00

Conducted on 06.07.2026 09:25 CDT

Recommended Maintenance 2 flagged

Condition of Fall Protection System Poor

Recommend fall protection system be removed

Recommend the 1/16 in-1/4 in, 70% coverage, of sandy silt sediment be removed from the floor plates

Facility Type Multi-Leg

Capacity 1.5MG

Height 149ft

Diameter 94ft

Tank ID Plate Yes

Tank Builder Hydrostorage

Year Built 1985

Serial/ID Number H4588

Photo 5

Photo 6

Photo 11

Photo 12

Size Standard Door

Was Manway Labeled 'Confined Space?' Yes

Electronic Pressure Gauge

Overflow Diameter 12in

Photo 29

Photo 31

Width of External Lower Ladder 17in

Length of External Lower Ladder 100ft

Length of Standoff 14in

Diameter of Cage 34in

Cage Material Mild Steel

Length of External Ladder 45 ft

Length of Standoff 11 in

Size of Roof Access Hatch 30 in

Photo 50

Photo 51 Photo 52

Photo 57

Condition of Anode Plates N/A

Size of Water Access Hatch 30 in

Photo 62

Photo 63 Photo 64

Photo 65 Photo 66

Vent Circumference 73 in

Vent Screen opening Height 12 in

Condition of Aircraft Warning Lights Working

RF Antennas Present? Yes

Photo of Antennas

RF Hazard Warning Signs Posted? Yes

Photo 72 Photo 73

Photo 74

Width of Water Access Ladder 17 in

Length of Ladder 45 ft

Condition of Fall Protection System Poor

Recommend fall protection system be removed

Photo 82

Photo 84

Photo 85

Photo 87

Photo 90

Photo 91 Photo 92

Photo 93

Condition of Sidewall Plates (SSPC Rating) 9

Photo 99

Photo 100

Does Facility Have a Mixer? No

Condition of Floor Plates Good

Photo of Floor Plates

Photo 104

Photo 105

Photo 107

Condition of Floor Plates (SSPC Rating) 9

Recommend the 1/16 in-1/4 in, 70% coverage, of sandy silt sediment be removed from the floor plates

Sediment/Debris Type Sandy Silt

Photo 108

Sediment Depth Dusting-.25in

Percentage of Sediment Coverage 70%

Photo 113

Photo 115

Water Temperature Hot (88 degrees or greater)

Water Depth (Maximum) 59ft

Water Depth (Actual) 33ft

15.07.2026 15:08 CDT

City of DeSoto Inspection #3 / Biarwood Hydropillar Complete

Inspection Title City of DeSoto Inspection #3

Client Specific Tank Name Biarwood Hydropillar

Conducted on 06.07.2026 10:47 CDT

Recommend the 1/16 in-1/4 in, 60% coverage, of sandy silt sediment be removed from the floor plates

Facility Type Composite

Capacity 2MG

Height 100ft

Diameter 100ft

Tank ID Plate No

Photo 4

Photo 5 Photo 6

Size Standard Door

Was Manway Labeled 'Confined Space?' No

Recommend a 'confined space entry' placard be installed

Photo 11

Overflow Diameter 18in

Photo 20

Photo 25

Width of External Lower Ladder 16.75in

Length of External Lower Ladder 52ft

Length of Standoff 8in

Diameter of Cage 33.75in

Cage Material Stainless Steel

Condition of Sidewall Protective Coating (SSPC Rating) 9

Length of External Ladder 7/8 in

Length of Standoff 9 in

Size of Roof Access Hatch 30 x30 in

Photo 45

Photo 46

Condition of Roof Coating (SSPC Rating) 7

Photo 53

Size of Water Access Hatch 37 x 37 in

Type of Roof Vent Box

Photo 58

Photo 59

Vent Circumference 26 x 26 inn

Vent Screen opening Height 26 x17 in

Condition of Aircraft Warning Lights Working

RF Antennas Present? No

Photo 65

Photo 66

Width of Water Access Ladder 17 in

Length of Ladder 50 ft

Photo 73 Photo 74

Photo 75

Condition of Overflow Fair

Deficiency Some corrosion starting at the lower section

Photo of Deficiency

Photo 83

Photo 88

Photo 89

Photo 94

Does Facility Have a Mixer? Yes

Visual Condition of Mixer Good

Photo of Mixer

Condition of Floor Plates Good

Photo 105 Photo 106

Photo 107

Condition of Floor Plates (SSPC Rating) 8

Recommend the 1/16 in-1/4 in, 60% coverage, of sandy silt sediment be removed from the floor plates

Sediment/Debris Type Sandy Silt

Photo 113

Photo 114

Photo 116

Sediment Depth Dusting-.250in

Percentage of Sediment Coverage 60%

Photo 121

Photo 122 Photo 123

Photo 124 Photo 125

Photo 126

Water Temperature Hot (88 degrees or greater)

Water Depth (Maximum) 50ft

Water Depth (Actual) 33ft

15.07.2026 15:20 CDT

Ground Tank Inspection - ROV

City of DeSoto Inspection #4 / North Complete

Flagged items 3

Inspection Title City of DeSoto Inspection #4

Client Specific Tank Name North

Conducted on 06.07.2026 12:29 CDT

Recommended Maintenance 3 flagged

Condition of Water Access Ladder Poor

Recommend water access ladder be repaired

Condition of Cathodic Protection Poor

Recommend cathodic protection be repaired

Recommend the 1/4 in-2 in, 90% coverage, of sandy silt sediment be removed from the floor plates

Reference Photo of Facility

Facility Type Ground

Facility Construction Metal- Welded

Capacity 5MG

Height 20ft

Diameter 210ft

Does Facility Extend Underground? No

Tank ID Plate? Yes

Tank Builder Pitts Des Moines

Year Built 2000

Serial/ID Number 50519

Photo 5

Photo 6

Photo 11

Photo 12

Pressure Gauge SCADA

Overflow Diameter 25in

Condition of External Plumbing NA

Condition of Sidewall Protective Coating (SSPC Rating) 6

Photo 22

Photo 23

Photo of Side Manway Access Hatch

Photo 32

Photo 33

Size of Manway Access Hatch 38in and 37in for 3

Was Manway Access Hatch Labeled 'Confined Space?' Yes

Condition of External Ladder Good

Photo 40

Width of External Ladder 16.75in

Length of External Ladder 20ft

Length of Standoff 16in

Does External Ladder Have Cage? No

Photo 46

Photo 47

Photo 52

Condition of Roof Coating (SSPC Rating) 3

Deficiency

Photo 57

Photo 58

Photo 66

Size of Water Access Hatch 36 x 36 in

Was Water Access Hatch Labeled 'Confined Space?' No

Photo 71

Photo 72

Vent Circumference 114 in

Vent Screen Opening Height 11 in

Internal Inspection 2 flagged

Condition of Water Access Ladder Poor

Recommend water access ladder be repaired

Deficiency Heavy corrosion missing rungs

Photo 78

Photo 79

Width of Water Access Ladder 16 in

Length of Ladder 25 ft

Length of Standoff 18 in

Condition of Fall Protection System Fair

Condition of Roof Supports Good

Photo of Roof Supports

Photo 84

Photo 85

Photo 90

Photo 91

Photo 99

Photo 100

Photo 105

Photo 106

Condition of Roof Plates (SSPC Rating) 4

Deficiency

Condition of Water Level Indicator System NA

Condition of Overflow Fair

Mild/Moderate Corrosion

Photo 116

Condition of Cathodic Protection Poor

Recommend cathodic protection be repaired

Deficiency Almost the entire system has fallen, anode plates have shifted

Photo of Cathodic Protection

Photo 120

Photo 121 Photo 122

Photo 123

Photo 124

Photo 127

Photo 128 Photo 129

Photo 130 Photo 131

Photo 132

Condition of Sidewall Plates (SSPC Rating) 6

Photo 133

Photo 134 Photo 135

Photo 136

Photo 137 Photo 138

Photo 139 Photo 140

Photo 141

Photo 142

Photo 143

Photo 144

Photo 145 Photo 146

Condition of Floor Plates Floor unable to inspect due to sediment

90% sediment coverage

Photo 147

Photo 148

Condition of Floor Plates (SSPC Rating) N/A

Does Tank Have Baffles? No

Recommend the 1/4 in-2 in, 90% coverage, of sandy silt sediment be removed from the floor plates

Photo 149

Photo 150 Photo 151

Photo 152 Photo 153

Photo 154

Photo 155

Photo 156 Photo 157

Photo 158

Sediment Depth .25in-2in

Percentage of Sediment Coverage 90%

Field Sketch of Sediment Coverage

Photo 159 Photo 160 Photo 161

Clarity of Water Fair

Quality of Water Good

Water Temperature Hot (88 degrees or greater)

Water Depth (Maximum) 20ft

Water Depth (Actual) 17ft

Additional Notes

Inspector

15.07.2026 15:34 CDT

Ground Tank Inspection - ROV

City of DeSoto Inspection #5 / South Complete

Flagged items 2

Inspection Title City of DeSoto Inspection #5

Client Specific Tank Name South

Conducted on 06.07.2026 14:03 CDT

Recommended Maintenance 2 flagged

Condition of Vent Screen Non-Compliant

Recommend a new 16-gauge fine mesh screen be installed

Recommend the 1/4 in-2 in, 100% coverage, of sandy silt sediment be removed from the floor plates

External Inspection 1 flagged

Facility Type Ground

Facility Construction Metal- Welded

Capacity 5MG

Height 20ft

Diameter 210ft

Does Facility Extend Underground? No

Tank Builder Advance Tank and Construction Inc

Year Built 1987

Serial/ID Number 7886

Photo 5

Photo 6

Photo 11

Photo 12

Photo 17

Photo 18

Overflow Diameter 25in

Condition of External Plumbing NA

Photo 29

Photo 30

Photo 35

Photo 36

Photo of Side Manway Access Hatch

Size of Manway Access Hatch 31in and 36in

Was Manway Access Hatch Labeled 'Confined Space?' Yes

Condition of External Ladder Good

Photo 48

Photo 49

Width of External Ladder 18.75in

Length of External Ladder 20ft

Length of Standoff 4in

Does External Ladder Have Cage? No

Photo 55

Photo 56

Condition of Anode Plates Compliant

Size of Water Access Hatch 31 in

Photo 66

Photo 67

Vent Circumference 110 in

Vent Screen Opening Height 11 in

Condition of Vent Screen Non-Compliant

Recommend a new 16-gauge fine mesh screen be installed

Deficiency No screen

Photo of Deficiency

Photo 74

Photo 79

Photo 80

Width of Water Access Ladder 19 in

Length of Standoff 19 in

Photo 86

Photo 87

Photo 93

Photo 94

Photo 99

Condition of Roof Plates (SSPC Rating) 8

Condition of Water Level Indicator System NA

Photo 104

Photo 105

Condition of Cathodic Protection Good

Photo of Cathodic Protection

Photo 110

Photo 111

Photo 116

Photo 121

Photo 122 Photo 123

Photo 124

Photo 127

Photo 128 Photo 129

Photo 130

Photo 131

Photo 132 Photo 133

Photo 134 Photo 135

Photo 136

Photo 137

Photo 138

Photo 139 Photo 140

Photo 141 Photo 142

Photo 143

Photo 144

Photo 145 Photo 146

Photo 147

Photo 148

100% sediment coverage

Photo 149

Photo 150 Photo 151

Photo 152 Photo 153

Photo 154

Photo 155

Photo 156 Photo 157

Photo 158 Photo 159

Photo 160

Photo 161

Photo 162 Photo 163

Photo 164 Photo 165

Sediment Depth .25-2in

Photo 166

Photo 167 Photo 168

Photo 169

Water Depth (Maximum) 20ft

Water Depth (Actual) 16ft

15.07.2026 16:01 CDT

Clearwell Inspection - ROV

City of DeSoto Inspection #6 / N Hampton Complete

Inspection Title City of DeSoto Inspection #6

Client Specific Tank Name N Hampton

Conducted on 07.07.2026 07:56 CDT

Facility Type Clearwell

Facility Construction Concrete

Capacity 3MG

Height 2ft

Diameter 220ft

Does Facility Extend Underground? Yes

Tank ID Plate? No

Condition of Foundation NA

Water Level Indicator Type(s) Not Available

Condition of Water Level Indicator(s) NA

Condition of Overflow No Overflow

Condition of Sidewall Protective Coating (SSPC Rating) N/A

Photo 5

Photo 6

Photo 11

Photo 12

Condition of Side Manway Access Hatch NA

Condition of External Ladder NA

Photo 17

Photo 18

Photo 23

Photo 24

Condition of Roof Coating (SSPC Rating) N/A

Photo 31

Size of Water Access Hatch 57 x 57 in

Was Water Access Hatch Labeled 'Confined Space?' No

Type of Roof Vent Box

Photo 36

Photo 37

Vent Circumference 53 x 53 in

Vent Screen Opening Height 13 x 53 in

Photo 43

Photo 44

Width of Water Access Ladder 26 in

Diameter of Rung 2 in

Condition of Fall Protection System NA

Photo 50

Photo 51

Photo 56

Photo 57

Photo 65

Photo 66

Photo 71

Photo 72

Condition of Roof Plates (SSPC Rating) N/A

Condition of Water Level Indicator System Good

Photo of Water Level Indicator System

Condition of Overflow NA

Condition of Cathodic Protection NA

Photo 80

Condition of Sidewall Plates (SSPC Rating) N/A

Condition of Side Manway Access NA

Photo 85

Photo 86

100% sediment coverage

Photo 95

Sandy Silt Silt

Photo 100

Sediment Depth .125-2in

Level of Staining Inside Facility None

Clarity of Water Fair

Water Depth (Maximum) 16ft

Water Depth (Actual) 14ft

15.07.2026 16:10 CDT

Pressure Tank City of DeSoto Inspection #7 / 30K PT Complete

Inspection Title City of DeSoto Inspection #7

Client Specific Tank Name 30K PT

Conducted on 07.07.2026 09:23 CDT

Recommend the 1/8 in-1 in, 20% coverage, of sandy silt sediment be removed from the floor plates

Facility Type Mild Steel

Facility Construction Metal Welded

Capacity 30K

Height 10ft

Diameter 8ft Dia x 50ft L

Condition of Intruder Fence Good

Photo 5 Photo 6

Condition of Plumbing Good

Photo 10

Photo 11

SSPC Rating 7

Photo of Manway Access Hatch

Size of Manway Access Hatch 20in x 16in

Was Manway Access Hatch labeled 'Confined Space?' Yes

Internal Inspection 2 flagged

Did Client Drain Tank for Internal Inspection? Yes

Condition of Access Hatch Good

Condition of Internal Coating (SSPC Rating) 7

Photo 27

Photo 28

Recommend the 1/8 in-1 in, 20% coverage, of sandy silt sediment be removed from the floor plates

Sediment Depth .125-1in

Percentage of Sediment Coverage 20%

Water Temperature Cool

Additional Notes Recommend additional hatch on other end by drain to make inspection more effective

15.07.2026 16:25 CDT

Recommended Maintenance
External Inspection
Internal Inspection
Media summary
City of DeSoto_N Hampton_3MG _CW_#6.pdf
Recommended Maintenance
External Inspection
Internal Inspection
Media summary
City of DeSoto_South_5MG _GST_#5.pdf
Recommended Maintenance
External Inspection
Internal Inspection
Media summary
City of DeSoto_North_5MG _GST_#4.pdf
Recommended Maintenance
External Inspection
Internal Inspection
Media summary
City of DeSoto_Biarwood Hydropillar_2MG _EST_#3.pdf
Recommended Maintenance
External Inspection
Lower Level
Upper Level
Internal Inspection
Media summary
City of DeSoto_Parkerville EST_1.5MG _EST_#2.pdf
Recommended Maintenance
External Inspection
Lower Level
Upper Level
Internal Inspection
Media summary
City of DeSoto_Parks EST_1.5MG _EST_#1.pdf
0BRecommended Maintenance
1BExternal Inspection
2BLower Level
3BUpper Level
4BInternal Inspection
5BMedia summary