City_Approved_Plans_-_Pines_BLVD_Crossing_Only_8-27-24.pdf
PDF 2 MB Posted
- Attached to
- Fiber Installation
- Solicitation number
- TS-25-14
- Issued by
- Broward County, Florida
About this file
This document is a comprehensive engineering design and construction permit set for a fiber optic infrastructure project by KMV FiberTelecom Inc., involving the City of Pembroke Pines and the Florida Department of Transportation (FDOT). The project, identified as KMV-PP-24-002, involves installing underground fiber optic conduit from Fire Station 89 to Walter Young Middle School, with a directional bore spanning approximately 217 linear feet along NW 129th Avenue and Pines Boulevard (SR 820). The project is scheduled for submission on 05/28/24, with specific FDOT permit requirements, and encompasses detailed site plans, utility mapping, construction notes, and photographic documentation of the proposed installation route.
The project involves installing a single 1.5" HDPE conduit with a 6-count fiber optic cable, maintaining a minimum 120-inch cover depth and utilizing directional boring techniques with a maximum 4" back reamer size. The construction will navigate multiple existing utilities, including water mains, storm sewers, gas lines, and telecommunications infrastructure, with strict adherence to FDOT standards for utility placement, restoration, and environmental compliance. The project area spans multiple utility easements referenced in local plat books, and requires comprehensive safety measures, including utility locates, erosion control, and careful navigation of right-of-way constraints. The total project length is approximately 217 linear feet, running from station 2+35 to 4+52, with specific requirements for surface restoration, pedestrian access, and minimal disruption to existing infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NAME:
CHECKED BY:
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
UG FIBER - PROPOSED
CONDUIT - EXISTING
AERIAL FIBER - EXISTING
STRAND - EXISTING
INNERDUCT - EXISTING
UG FIBER - EXISTING
AERIAL FIBER - PROPOSED
STRAND - PROPOSED
CONDUIT - PROPOSED
INNERDUCT - PROPOSED
SANITARY SEWER (SEW)
GAS
WATER
TELEPHONE
ELECTRIC
STEAM
STORM DRAIN
FENCE
CABLE TV
UNKNOWN UTILITY
OIL
LINETYPES
RIGHT OF WAY
EDGE OF PAVEMENT
FOC
STREET LIGHT
FORCE MAIN
TRAFFIC
RECLAIMED WATER
EASEMENT
ASBUILT CONDUIT
SITE LOCATION
CONFIDENTIAL/PROPRIETARY
SHEET: OF 01 06
STA 2+35 START
PROJECT: KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG MIDDLE SCHOOL 4-2-24
ADDRESS: 901 NW 129TH AVE, PEMBROKE PINES, FL 33028 - FDOT PERMIT
CONTACTS
KMV
Fibertelecom
FTGJOB DESCRIPTION
SUMMARY DATA
217'DIRECTIONAL BORE
TWP : RNG : SEC :
PLAT BOOK : PAGE :
51S 40E 14
DATE SUBMITTED
05/28/24
PEMBROKE PINES
JOHN L.ENGLAND
DESIGN ENGINEER
PHONE: (954) 518-8905
JENGLAND@PPINES.COM
KMV FIBERTELECOM INC
SANDRA KARINA VARGAS
10604 NW 48TH ST
CORAL SPRINGS FL 33076
PHONE: 954-937-5239
KARINAV@KMVFIBERTELECOM.COM
Know what's below.
before you dig.Call
R
STA 4+52 END
JURISDICTION:
* FDOT
01 OF 06 - COVER SHEET/SITE LOCATION
02 OF 06 - OVERALL MAP
03 OF 06 TO 04 OF 06 - CONSTRUCTION NOTES
05 OF 06 TO 05A OF 06 - PLAN VIEWS & PROFILES
06 OF 06 - PHOTOGRAPHS
SITE INDEX
PERMITTING
SCALE: NTS
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
CONFIDENTIAL/PROPRIETARY
SHEET: OF 02 06
Know what's below.
before you dig.Call
R
N
W
T
H
A
V
E
END
4+52
CITY OF PEMBROKE PINES
PERMIT
SCALE: NTS
PINES BLVD / SR 820
FDOT PERMIT
MOT INDEX 102 - 602
MOT INDEX 102 - 660
FDOT MILEPOST: 7.495
START
2+35
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
CONSTRUCTION NOTES
TYPICAL UNDERGROUND CONSTRUCTION:
- RESTORE ALL SURFACES TO EQUAL OR BETTER CONDITION.
- CONTRACTOR TO VERIFY ALL MEASUREMENTS AND DISTANCES PRIOR TO CONSTRUCTION.
- CONTRACTOR TO VERIFY LOCATION AND CONDITION OF EXISTING CONDUIT PRIOR TO CONSTRUCTION.
- CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE AND IMMEDIATELY NOTIFY THE ENGINEER IN
WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK.
- MAINTAIN MINIMUM 24" VERTICAL AND HORIZONTAL SEPARATION BETWEEN PROPOSED BY PEMBROKE PINES DUCTS & EXISTING UTILITIES.
- MAINTAIN A MIN BENDING RADIUS OF 5' ON ALL DUCT CONFIGURATION.
- ANY CHANGES ON PROPOSED RUNNING LINE HAVE TO GET APPROVAL FROM PEMBROKE PINES CONSTRUCTION MANAGER.
FOR CONSTRUCTION:
- EXTREME CAUTION TO BE TAKEN TO CONTAIN SLURRY AROUND WORK AREAS NEAR WETLANDS TO AVOID ANY WATER QUALITY ISSUES!
- LOCATIONS, ELEVATIONS LOCATIONS, ELEVATIONS AND DIMENSIONS OF EXISTING UTILITIES, STRUCTURES AND OTHER SITE FEATURES SHOWN
ON THE DRAWINGS ARE BASED ON LIMITED INVESTIGATION TECHNIQUES AND SHOULD BE CONSIDERED APPROXIMATE ONLY. PLEASE CONTACT
SUNSHINE STATE ONE-CALL AT 1-800-432-4770
- CAUTION: EXISTING UNDERGROUND UTILITIES IN AREA. NO ELEVATION RECORDS FOR EXISTING UTILITIES AVAILABLE. CONTRACTOR SHOULD
CONTACT SUNSHINE 811, LOCATE ALL UTILITIES AND VERIFY ALL DEPTHS PRIOR TO CONSTRUCTION
DESIGN TICKET
#121405467
CONFIDENTIAL/PROPRIETARY
SHEET: OF 03 06
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
CONSTRUCTION NOTES - FDOT
· EXISTING F.D.O.T. DRAINAGE SYSTEM SHALL BE PROTECTED AT ALL TIMES BY THE PERMITTEE. ANY DAMAGE TO THE F.D.O.T. DRAINAGE SYSTEM (STRUCTURES OR PIPES) SHALL BE REPAIRED/REPLACED BY THE PERMITTEE AT NO COST TO THE DEPARTMENT.
· EXISTING GAS MAIN SHALL BE PROTECTED AT ALL TIMES DURING EXCAVATION, DRILLING AND CONDUIT INSTALLATION ACTIVITIES. UTILITY GAS COMPANY SHALL BE PRESENT AT THE PRE-CONSTRUCTION MEETING AND GIVE WRITTEN CLEARANCE PRIOR TO COMMENCEMENT OF ANY PERMIT
OPERATIONS.
· ANY DAMAGE TO CONCRETE SIDEWALK, CURB AND GUTTER, PEDESTRIAN CURB RAMPS, AND TRAFFIC SEPARATORS SHOULD BE RESTORED PER FDOT STANDARDS PLANS INDEX NO. 522-001, 520-001, 522-002, AND 520-020, ADA STANDARDS, AND FDOT STANDARD SPECIFICATION 522.
DAMAGED SIDEWALK, CURB AND GUTTER, AND TRAFFIC SEPARATORS SHALL BE RESTORED WITH FULL FLAGS/JOINT TO JOINT AT THE PERMITTEES EXPENSE; PATCHING IS NOT PERMITTED. IMPACTED PEDESTRIAN RAMPS SHALL BE REPLACED COMPLETELY; HANDHOLES MUST NOT BE LOCATED WITHIN PEDESTRIAN RAMPS. MAKE SURE TO FURNISH APPROPRIATE EXPANSION JOINTS PER FDOT STANDARDS PLANS INDEX 350-001. IMPACTED DETECTABLE WARNING SURFACES NEED TO BE RESTORED IN ACCORDANCE WITH FDOT STANDARD PLANS INDEX NO. 522-002 AND SPECIFICATION
527.
· HANDHOLES AND PULL BOXES SHALL NOT BE INSTALLED WITHIN THE FOOTPRINT OF EXISTING PEDESTRIAN ADA CURB RAMP NEITHER DRIVEWAY ENTRY AREA. REFER TO PPM, VOL. 2, CH. 8, SECTION 8.3.2 REGARDING NONSLIP TOP SURFACE IF THE HAND HOLE IS PROPOSED WITHIN PEDESTRIAN CURB RAMP. DO NOT INSTALL NEW HH AT LEAST 10' FROM ADA CURB RAMPS, FIRE HYDRANTS, BUS BOOTH-BENCHES
· WHERE PEDESTRIAN FACILITIES ARE DETOURED, BLOCKED, OR CLOSED DURING THE WORK, PLEASE ENSURE TO PROVIDE SAFE ALTERNATE ACCESSIBLE ROUTES THROUGH OR AROUND THE WORK ZONE THAT MEETS THE REQUIREMENTS OF THE ADA STANDARDS AND FDOT STANDARD PLAN
INDEX 102-660.
· RESTORATION OF SODDING AND TURF SHOULD BE DONE ACCORDING TO FDOT 2023-2024 STANDARD INDEX No 570-001.
· PROVIDE PROTECTION TO THE EXISTING TREES AND AVOID ANY IMPACT TO THE ROOTS. WHEN CONSTRUCTION AFFECTS TREE ROOTS OR CANOPY, PROVIDE TRIMMING PER FDOT STANDARD PLANS INDEX 110-100.
· PROVIDE APPROPRIATE EROSION CONTROL DEVICES DURING CONSTRUCTION.
· LANDSCAPING, TREES, SOD SHALL BE REPLACED AT THE COST OF THE PERMITTEE
· THE CONTRACTOR SHALL COORDINATE WITH BROWARD COUNTY DEPARTMENT OF TRANSPORTATION AND PUBLIC WORKS (DTPW), TRAFFIC SIGNALS & SIGNS DIVISION AT LEAST 5 WORKING DAYS PRIOR TO ANY WORK DONE AT SIGNALIZED INTERSECTIONS , WHICH
EITHER CLOSE ANY LANES, NEED CHANGES IN THE SIGNAL OPERATION OF TIMING, DAMAGE OR HINDER ANY SIGNAL SENSOR, OR DAMAGE ANY CABLE OR SIGNAL EQUIPMENT.
· PERMITTEE IS RESPONSIBLE FOR LOCATING ALL UNDERGROUND FACILITIES PRIOR TO DIRECTIONAL DRILLING/TRENCH WORK AND ASSUMES ALL RESPONSIBILITY FOR ANY DAMAGE DONE TO UNDERGROUND FACILITIES AND ABOVE GROUND FACILITIES. DIRECTIONAL
BORING SHALL BE CONDUCTED ACCORDING TO LATEST SECTION 555 OF FDOT'S STANDARD SPECIFICATIONS AND 3.16.9.1 OF THE 2017 U.A.M. OPEN TRENCH SHALL BE CARRIED OUT PER 3.16.4. OF 2017 U.A.M
· CONDUIT INSTALLATION SHALL ADHERE TO THE LATEST FDOT STANDARD PLANS INDEX NO. 630-001
· ACCORDING TO SECTION 3.10 OF 2017 U.A.M, WHEN UNDERGROUND AND AERIAL UTILITIES OCCUPY THE SAME ROADSIDE, UNDERGROUND UTILITIES SHALL NOT BE PLACED WITHIN THREE (3) FEET OF THE R/W LINE.
· DAMAGED SIDEWALK, CURB AND GUTTER, AND TRAFFIC SEPARATORS SHALL BE RESTORED WITH FULL FLAGS/JOINT TO JOINT AT THE PERMITTEES EXPENSE; PATCHING IS NOT PERMITTED. RESTORATION SHALL MATCH EXISTING CONCRETE PATTERN, PAVERS, AND
COLOR. IMPACTED PEDESTRIAN RAMPS AND DRIVEWAYS SHALL BE REPLACED COMPLETELY. INCLUDE 1 FOOT OF LEVEL EMBANKMENT FOR EROSION AND ENSURE TO NOT CREATE ANY DROP OFF HAZARDS AS SHOWN ON FDM FIGURE 222.4.1. IMPACTED DETECTABLE
WARNING SURFACES NEED TO BE RESTORED IN ACCORDANCE WITH FDOT STANDARD PLANS INDEX NO. 522-002 AND SPECIFICATION 527
· PROPOSED HANDHOLES MUST ADHERE TO LATEST FDOT STANDARD PLANS INDEX NO. 635-001”. ENSURE ALL HANDHOLE LIDS ON SIDEWALK ARE FLUSH AND ADA COMPLIANT. MAINTAIN THE TEMPORARY PATCHES AROUND THE HANDHOLE BOX EDGES AND/OR
ANYWHERE ELSE WHERE SIDEWALK HAS BEEN IMPACTED/DAMAGED BY THE DB WORK OR UTILITY INSTALLATION, SO IT PROVIDES A SMOOTH -ALL WEATHER SURFACES ALWAYS. ONCE THE HANDHOLE IS INSTALLED THE LID MUST BE KEPT IN PLACE, BOLTED, AND SECURED.
· TEMPORARY BARRIERS FOR PEDESTRIAN DETOURS MUST COMPLY WITH THE LATEST FDOT STANDARD PLANS INDEX NO. 102-100.
· RESTORATION OF SODDING AND TURF SHOULD BE DONE ACCORDING TO FDOT 2023-24 DESIGN STANDARDS INDEX 570-010.
· PERMITTEE MUST TAKE PICTURES OF THE EXISTING STREET LIGHTNING SYSTEM WORKING-DURING NIGHT-TIME-WITHIN THE LIMITS OF THIS PROPOSED JOB PRIOR TO BEGIN SAID WORK. TO AVOID FUTURE DISPUTE ABOUT UNFORESEEN DAMAGES TO THE LIGHTNING
SYSTEM.
· CONTAMINATED SITES LOCATED WITHIN A 500-FOOT RADIUS OF THE PROJECT AREA THAT COULD IMPACT THE FDOT ROW HAVE BEEN IDENTIFIED. THE PERMITTEE SHALL ASSURE THAT ANY ACTIONS CARRIED OUT ARE IN ACCORDANCE WITH ALL ENVIRONMENTAL
REGULATORY REQUIREMENTS.
· ANY ABOVEGROUND FEATURES THAT MAY BE IMPACTED BY PROPOSED WORK MUST BE IDENTIFIED TO BE ADJUSTED/RELOCATED/REPLACED. IF SIGNS ADD ARE DAMAGED, THESE MUST BE REPLACED ACCORDING THE LATEST FDOT STANDARD
PLANS INDEX NO. 700-101. ENSURE LATERAL OFFSET AND CLEAR ZONE STANDARDS ARE BEING ADHERED TO.
SHEET: OF 04 06
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
0+00 0+50 1+00 1+50
2+00 2+50 3+00
4+503+50 4+00 5+00 5+50 6+00 6+50 7+00
T R
F
T R
F
T R
F
TRFTRFTRFTRFTRF
TRF TRF TRF TRF TRF
#13000
#12890
#900
NW 129TH AVE
P I N
E S
B
L V
D
S
R
T R
F
T R
F
T R
F
T
R
F
200' FDOT ROW
100'
100'
C/L
10' UE
12' UE
200' FDOT ROW
100'
100'
C/L
10' UE
12' UE
R
O W
C L
U
E
U
E
U
E
30" STORM
SEWER
18" STORM SEWER
12" WATER MAIN
12" WATER
MAIN
16" WATER
MAIN
24" WATER MAIN
TELEPHONE
FOC
STORM SEWER
6" GAS
FORCE MAIN
FOC
GAS
48" STORM SEWER
FOC
FOC TELEPHONE 14" FORCE
MAIN
ELECTRIC CATV
16" FORCE MAIN
TRAFFIC
FOC
12" WATER
MAIN
16" FORCE
MAIN
GAS
FOC
12" FORCE MAIN
18" STORM SEWER
FOC
10' UTILITY EASEMENT
REF.: PLAT 78-36
10' UTILITY EASEMENT
REF.: PLAT 78-36
12' UTILITY EASEMENT
REF.: PLAT 104-18
12' UTILITY EASEMENT
REF.: PLAT 158 - 29
12' UTILITY EASEMENT
REF.: PLAT 158 - 29
C L
12" FORCE MAIN
6" GAS
24" WATER MAIN
U
E
R
O W
FOC
8'
40'
DIRECTIONAL BORE
MAX BACK REAMER SIZE = 4''
INSTALL (1) 1.5'' HDPE CONDUIT
PULL (1) 6CT FOC
120" MINIMUM COVER
2+35 - START FDOT
PERMIT
4+52 - END FDOT
PERMIT
102' 105'
LEGEND PROJECT ID 446200-1-52-01
MILLING & RESURFACING
4" CONCRETE
6" CONCRETE
FUTURE EOP
FUTURE SIDEWALK
PROP. ELECTRICAL POLE
FUTURE STREET LIGHT
CONSTRUCT DETECTABLE WARNING
FUTURE
STREET LIGHT
FUTURE TRAFIC
CONFIDENTIAL/PROPRIETARY
SHEET: OF 05 06
Know what's below.
before you dig.Call
R
PLAN VIEW
SCALE: 1"=50'
FDOT MILEPOST: 7.495
FDOT CONSTRUCTIONS NOTES
* NO DEWATERING WILL BE PERFORMED OUT IN THIS PROJECT.
* CONTRACTOR MUST HAVE CURRENT LOCATES DUE TO OTHER UTILITIES IN THIS AREA.
* PLEASE BE AWARE THAT IF ANY TREE IMPACTS (REMOVALS, RELOCATIONS, TRIMMING, ROOT
PRUNING) DO BECOME PROPOSED, COORDINATION WITH FDOT PRIOR TO WORK WILL BE REQUIRED.
* ENSURE APPROPRIATE EROSION CONTROL DEVICES ARE IN PLACE BEFORE ANY CONSTRUCTION
BEGINS AND ARE USED THROUGHOUT THE DURATION OF CONSTRUCTION.
* ANY DAMAGE PRODUCED BY THIS PROPOSED WORK SHALL BE RESTORED BY THE PERMITTEE AT NO
COST TO THE DEPARTMENT.
* THE CONTRACTOR AND CONSTRUCTION MANAGER OF CROWN CASTLE MUST ENSURE THAT ALL
PRODUCTS COMPLY WITH THE LATEST FDOT APPROVED PRODUCTS LIST (APL).
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
08.00
07.00
06.00
05.00
04.00
03.00
02.00
01.00
00.00
-01.00
-02.00
-03.00
-04.00
-05.00
-06.00
-07.00
-08.00
-09.00
-10.00
6+50 7+002+50 3+50 4+50 5+503+00 4+00 5+00 6+002+00
-11.00
-12.00
PROFILE - NW 129TH AVE (LOOKING WEST)
HORIZONTAL SCALE: 1''=50'
VERTICAL SCALE: 1''=5'
GRADE LEVEL
16" WATER
MAIN
48" STORM SEWER
16" FORCE MAIN
24"WATER MAIN
FOC
TRAFFIC
VARIES' FDOT ROW
100' VARIES'
C/L
10' UE 12' UE
M
I N
DIRECTIONAL BORE
MAX BACK REAMER SIZE = 4''
INSTALL (1) 1.5'' HDPE CONDUIT
PULL (1) 6CT FOC
120" MINIMUM COVER
PINES BLVD / SR 820
M
I N
TELEPHONE
18'
2+35 - START FDOT PERMIT
4+52 - END FDOT
PERMIT
M
I N
M
I N
M
I N
ELECTRIC
FUTURE STREET LIGHT
TRAFFIC
12" FORCE
MAIN
TELEPHONE
FOC
FOC
FOC
GAS
TRAFFIC
GAS
TRAFFIC
CONFIDENTIAL/PROPRIETARY
SHEET: OF 05A 06
RECORD ON UTILITY PLANS
CONSTRUCTION CONTRACTOR
SHALL CALL LOCATES AND SOFT DIG TO DETERMINE
UTILITY ELEVATION BEFORE CONSTRUCTION.
Know what's below.
before you dig.Call
R
ENGINEERING FIRM:
PROJECT NUMBER:
LOCATION:
KMV-PP-24-002 - FIRE STATION 89 TO WALTER YOUNG
MIDDLE SCHOOL 4-2-24.dwg
NO.
GIULIANO LEON
KMV FIBERTELECOM INC
KMV-PP-24-002
901 NW 129TH AVE
PEMBROKE PINES, FL 33028
STA 4+52 DIRECTIONAL BORE2
STA 2+35 DIRECTIONAL BORE
PHOTOGRAPHS
DIRECTIONAL BORE
MAX BACK REAMER SIZE = 4''
INSTALL (1) 1.5'' HDPE CONDUIT
PULL (1) 6CT FOC
120" MINIMUM COVER
DIRECTIONAL BORE
MAX BACK REAMER SIZE = 4''
INSTALL (1) 1.5'' HDPE CONDUIT
PULL (1) 6CT FOC
120" MINIMUM COVER
ON PINES BLVD / SR 820
STA 2+35
LOOKING NORTH
(SEE PAGE 05 OF 06)
ON PINES BLVD / SR 820
STA 4+52
LOOKING NORTH
(SEE PAGE 05 OF 06)
SHEET: OF 06 06