CHS VOR Roof Drawings Signed-Portfolio.pdf
PDF 4 MB Posted
- Attached to
- Roof Replacement Charleston SC Federal contract opportunity
- Solicitation number
- 6973GH-21-R-00050
About this file
This is a solicitation for roof replacement services at a Federal Aviation Administration facility located in Charleston, South Carolina. The contractor will provide all labor, materials, equipment, insurance, permits, and supervision to replace the roof in accordance with the attached scope of work and plans. Questions are due by February 29, 2021, with proposals due by March 5, 2021. The contract will be a firm-fixed-price construction contract awarded according to the Acquisition Management System. The contractor must be registered in the System for Award Management and comply with site visit and safety requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0002.pdf | ||
| Charleston Amendment 0001.pdf | ||
| CHS VOR Scope of Work 11-18-2020.pdf | ||
| Wage Determination.pdf | ||
| 6973GH-21-R-00050.pdf | ||
| Contractor Release Form.doc | DOC document | |
| Experience Information Form.pdf | ||
| Performance Bond.pdf | ||
| Payment Bond.pdf | ||
| CHS VOR Roofing Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader c h s -1
-a
.d g n
/1
/2
:2
:5
A
M P lo tt e d b y S
R V
C -C
E
G -E
D
O
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
NOTES:
SOLDERING NOTES:
A002
IS
U
VOR
SC
CHARLESTON AFB/INTL AIRPORTCHARLESTON
ENGINEERING SERVICES
INFRASTRUCTURE
CHS-1400248-A001
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
1400248
NEW ROOF PLAN
ROOF REPLACEMENT
08/05/2020
ATTACHMENT CLEAT
NOT TO SCALE
A001
SIGNAGE
PANEL SEAMING
PANEL FOLDING
PANEL ATTACHMENT
NEW ROOF INSTALL
SCALE: 3/16" = 1'-0" A001
SCALE: 3/16" = 1'-0"
WALKWAY LAYOUT
ACCORDANCE WITH CDA GUIDELINES OR ROOFING MANUFACTURERS INSTRUCTIONS.
5. THE CONTRACTOR SHALL FLUX FOUR SIDES, CLOSE UP THE HEM, AND FULLY SOLDER IN
PRIOR TO FLUXING AND SOLDERING.
THE CONTRACTOR SHALL USE SCOTCHBRITE (OR EQUAL) TO REMOVE THE OXIDATION
4. PANS MUST BE KEPT DRY ESPECIALLY AFTER PRE-TINNING. IF OXIDATION OCCURS,
OR WITHIN 24 HOURS TO PREVENT THE ACCUMULATION OF EXCESSIVE OXIDATION.
3. CONTRACTOR MUST SOLDER QUICKLY AFTER PRE-TINNING USUALLY THE SAME DAY
HEM OF APPROXIMATELY 60 DEGREES.
2. COPPER PANS SHALL BE PRE-BENT FROM SHOP LEAVING A GAP IN THE
1. CONTRACTOR SHALL PRE-TIN THE PANS EDGES TO 1 1/2".
ENTIRE ROOF SURFACE
ROOFING MATERIAL OVER
LIQUID APPLIED
INSIDE ANTENNA SHELTER
(SEE NOTE 13)
APPLIED ROOFING
(OR EQUAL) TO LIQUID
ADHERE SARNATRED
AND WALKWAY WITH TEEPEE DOOR
ALIGN LADDER SUPPORT
INSTALL SARNAFIL SARNATRED
NAILS
8D COMMON GRACE ULTRA, OR EQUAL
BUTYL UNDERLAYMENT
ROSIN PAPER (SEE NOTE 14)
SEE NOTE 1, THIS SHEET
SECTION A
PER SHEET A002,
INSTALL EDGE TRIM
(SEE 2/A003)
BONDING SEGMENTS
RE-INSTALL 50 DOPPLER ANTENNAS
CONTRACTOR TO ASSIST FAA TO
BASEPLATES AND PITCH POCKETS.
CONTRACTOR TO INSTALL ANTENNA
52'-6" DIAMETER
OR EQUAL
ROOF COATING (TRUCO INC)
INSTALL ELASTOMERIC
1. THE CONTRACTOR SHALL INSTALL A COPPER METAL ROOF IN ACCORDANCE
WITH CDA PUBLICATION A4050-04/18, COPPER IN ARCHITECTURE DESIGN HANDBOOK.
ALONG THE ROOF PERIMETER, EDGE CLEAT SHALL EXTEND 3/4" BEYOND THE
CLEAT SHALL BE FASTENED ALONG THE HORIZONTAL EDGE EVERY 4", OR
2. ROOFING SHALL BE 20 OZ. COPPER OR STAINLESS STEEL.
BOTTOM OF THE WOOD BLOCKING TO PROVIDE A DRIP EDGE. DRIP EDGE SHALL BE
THE COPPER PLATE SHALL BE INTERLOCKED WITH EDGE STRIP
TRIMMED AS NEEDED AT MONITOR ANTENNA MOUNT ASSEMBLIES. THE EDGE
AS IN ACCORDANCE WITH COPPER MANUFACTURERS INSTRUCTIONS SO AS TO
PROVIDE I-90 UPLIFT WIND RATINGS. SEE DETAIL 1 ON DRAWING A002.
3. ROOFING PANELS SHALL BE LAID OUT IN RUNNING BOND PATTERN (CONTRACTOR
SHALL STAGGER CROSS JOINTS).
4. CONTRACTOR SHALL USE MIN OF 3 DEDICATED CLEATS PER PANEL.
5. CONTRACTOR SHALL ASSUME 500 SQ FT OF DECK REPLACEMENT FOR BID.
SUBMIT ON DECK MATERIAL.
6. NEW ROOFING SHALL EXTEND UNDER TEEPEE TO VOR ANTENNA PEDESTAL
PLATE ROOF OPENING (SEE SHEET E001, DETAIL 1/SHEET A003, DETAIL A).
7. ELASTOMERIC SHALL EXTEND FROM EDGE DETAIL TO OUTSIDE RADIUS OF VOR
ANTENNA BASE PLATE BONDING SEGMENT. APPLY ELASTOMERIC TO HORIZONTAL
SURFACE ONLY.
8. COPPER PLATE BONDING SEGMENTS SHALL OVERLAP VOR ANTENNA PEDESTAL
PLATE A MINIMUM OF 3 INCHES. (SEE A003).
9. CONTRACTOR SHALL RE-ESTABLISH FACILITY NORTH POINT. THE CONTRACTOR
SHALL LAY OUT MONITOR ANTENNA SUPPORT ASSEMBLY LOCATIONS FOR
INSTALLATION BY REGISTERED LAND SURVEYOR (RLS). CENTER ASSEMBLIES ON
22.5° RADIALS FROM FACILITY NORTH POINT +/- 0.1°. ASSEMBLY SHALL BE
PERPENDICULAR TO A RADIAL LINE LAID OUT FROM THE CENTER OF THE VOR ANTENNA
PLATE. ANGLE BRACKETS SHALL BE ADJUSTED LEVEL, AND PLUMB. ALL BRACKETS
SHALL BE AT THE SAME RELATIVE ELEVATION.
NEEDED), 3/4" CDX T&G PLYWOOD, BUTYL UNDERLAYMENT (GRACE ULTRA, OR EQUAL),
STANDARD WEIGHT ROSIN PAPER, COPPER PANEL ROOFING (FULLY SOLDERED), EDGE
TRIM WITH NEW WOOD NAILER AND ELASTOMERIC (LIQUID APPLIED), WALKWAY PADS,
AND MONITOR ANTENNA SUPPORT ASSEMBLY INSTALLATION.
APPROVED BY ROOFING MANUFACTURER) AND A MINIMUM 3 POUND SOLDERING
IRONS TO COMPLETE THE WORK.
CONSTRUCTED OF BUTYRATE PLASTIC BACKED WITH 20 GAUGE GALVANIZED STEEL
AND FURNISHED WITH 1/4" EYELETS IN EACH CORNER. SIGN SHALL HAVE A
YELLOW BACKGROUND AND BLACK LETTERS. SIGNS CAN BE PURCHASED FROM
"SAMSEL SUPPLY COMPANY", 1285 OLD RIVER ROAD, CLEVELAND, OHIO, 44113,
TEL 800-892-8012.
1/4" SEAM AT JOINTS AND AROUND THE ANTENNA SHELTER. ATTACH WALKWAY MAT
WITH "SARNAFIL" SARNACOL 2170 ADHESIVE, OR EQUAL. HOT-AIR WELD ALL
SEAMS AND JOINTS WHERE ACCESSIBLE AND APPROVED BY ELASTOMERIC
MANUFACTURER. CONFIGURE TO PREVENT PONDING OR TRAPPED WATER.
ATTACH ROSIN PAPER TO DECK, THIS SERVES AS SLIPSHEET BETWEEN
UNDERLAYMENT AND SHEET METAL.
IN BOND PATTERN
3/4" CDX T&G PLYWOOD
INSTALL 4'x8' SHEETS OF
PLANKING (SEE NOTE 5)
2" x 6" TONGUE-AND-GROOVE
AS NECESSARY WITH SIMILAR
EXISTING WOOD DECKING, REPAIR
(SEE NOTE 6)
(TEEPEE) 10' DIA
ENCLOSURE
OF ANTENNA
OUTER LIMITS
AND SHEET E001, DETAIL 1
SEE SHEET A003, DETAILS A & B
VOR ANTENNA PEDESTAL PLATE,
SEE DETAILS 2 THRU 5, THIS SHEET
CREATE A CONTINUOUS COPPER PLATE
AND FULLY SOLDER TO
INSTALL 18" x 24" 20 OZ SHEETING, INSTALL 3 CLEATS PER PANEL
SOLDER JOINT
CONTINUOUS
DIRECTION OF FLOW
COPPER ALLOY NAILS
COPPER OR
LARGE FLAT HEAD
UPSLOPE
ABOVE
FOLD LINES
BENEATH
DIRECTION OF FLOW
12" O.C. MIN CENTER
.C
IN
6" O.C. MIN EDGE
.C
1"
14"
18"
"3/4"
10. ROOF REPLACEMENT SHALL INCLUDE INSTALLATION OF WOOD DECKING (AS
11. CONTRACTOR SHALL USE JOHNSON E127 PURE TIN FLUX-N-SOLDER (OR SOLDER
12. INSTALL ONE SAFETY SIGN AT THE STAIRS. SIGNS SHALL BE
13. WALKWAY MAT MATERIAL SHALL BE "SARNAFIL" SARNATRED, OR EQUAL. ALLOW
14. ROSIN PAPER AS RECOMMENDED BY COPPER METAL MANUFACTURER. DO NOT
DT#18953
FASTENER SPACING IN 3/4"
PRESSURE-TREATED PLYWOOD
04' 4' 8' 12' chs-1400248-a001
2020-08-11T08:24:05-0400
VI V HO
2020-08-11T06:57:37-0400
SHANE CHRISTIAN HARVEY
:5 lo tt e
ROOF EDGE DETAILS
CHS-1400248-A002
SOLDERED FOLDED SEAM
FLUXED AND FULLY
COPPER PANEL (TYP.)
DOPPLER POSITIONER BRACKET
TOP VIEW OF THE
ANTENNA CIRCLE
44'-0" DIAMETER
TO ANTENNA CIRCLE
PLATE SYM. ABOUT TANGENT
4" DIA. HOLE
(50 REQUIRED)
GALVANIZED STEEL PLATE
1'-2"x 1'-2"x 1/2" THICK
(6 REQUIRED)
9/16" DIA. HOLE
CENTER OF VOR COUNTERPOISE
PLATE SYM. ABOUT RADIAL LINE THROUGH
1 1/2" DIA. HOLE
1'-2"
7"
5 1/2"
3"3"
/8
/4
DOPPLER POSITIONER BRACKET
WOOD DECKING
COUPLING
1'' GALVANIZED
1'' RIGID GALV. CONDUIT
THE WOOD ROOF
APPROXIMATELY 9'' BELOW
VINYL SOFFIT LOCATED
4 REQUIRED PER ROD.
1/2" DIA. HEX NUT.
STAINLESS STEEL
4 REQUIRED PER ROD
WASHER WITH A 9/16" HOLE.
STEEL 3'' DIA. x 3/16" THICK
SEE DETAIL 3
1 1/2'' LEVELING PLATE
PITCH POCKET
TOP OF COPPER PLATE
COLD GALVANIZED COMPOUND
ENDS OF NIPPLES TREATED WITH
SEAL
ENSURE WATERTIGHT
THREADED ROD. 4 REQ'D.
STAINLESS STEEL 1/2" DIA.
STAR WASHERS
CONDUIT BRACKET
TO CABLE TRAY OR
1'' DIA. CONDUIT LOCKNUT
THICK WASHER
4'' O.D. x 1-5/8'' I.D. x 3/16''
DOPPLER BRACKET PITCH POCKET
1 1/2" 15"
13"
ROSIN PAPER
SEAM (FULLY SOLDERED)
COPPER PLATE
EQUAL
GRACE ULTRA OR APPROVED
3/4" PLYWOOD
EXISTING WOOD DECK
EDGE CLEAT
NEW WOOD BLOCKING
DRIP EDGE
ROOFING
ELASTOMERIC
MANUFACTURER
OR AS APPROVED BY ROOFING
VERTICAL CLEAT AND DRIP EDGE
HORIZONTAL, TO FORM CURVED
BACK CUT, AS REQUIRED ON
ROLLED COPPER
20 OZ. COLD
FABRICATE FROM 20 OZ COPPER ROOF STOCK
6"
3/4"
90°
4"
AX
AS NEEDED
BLOCKING,
ADDITIONAL
OF NEW NAILER (FURR AS NEEDED)
TO BE FLUSH WITH BOTTOM
RE-INSTALL SOFFIT. LOWER
TO PROVIDE MINIMUM 2" X 6" AT EDGE
BOARD WIDTH WILL VARY. RADIAL CUT
6" X 4" EDGE CLEAT
COPPER ROOF
PER NOTE 2 UNDER
FASTEN CLEAT
NECESSARY, FOR NEW LOCATION
NEW NAILER. PROVIDE STRAPPING/BLOCKING, AS
REMOVE AND REINSTALL EXISTING SOFFIT BELOW
FLASHING AND MONITOR BRACKET INSTALLATION.
PROVIDE A MINIMUM 2" X 6" MEMBER FOR
ADD TWO BY NAILER: SIZED AS NECESSARY TO
MANUFACTURER'S INSTRUCTIONS
TERMINATE ELASTOMERIC PER
COPPER
T&G PLYWOOD
NEW 3/4" CDX
COPPER METAL ROOFING
(EXISTING)
WOOD DECK
FULLY ENGAGE CLEAT)
(BENT AT EDGE TO
COPPER ROOFING
AT 4" SPACINGS (TYP)
INSTALL FASTENERS
3/4"
6"
MONITOR ANTENNA ASSEMBLY ATTACHMENT
STRUCTURE FOR EDGE TRIM (FASCIA) AND
NAILER WILL PROVIDE SUFFICIENT
THE UNDERSIDE OF THE ROOF DECKING.
THE 2 X 6 BLOCKING, INSTALLED ALONG
DASHED LINE REPRESENTS THE EDGE OF
ROOF EDGE
ACCORDANCE WITH CDA INSTRUCTIONS
TO DECK, SOLDERED TOGETHER IN
18"x 24" COPPER PANEL, CLEATED
EDGE FLASHING
VERTICAL ROOF
COPPER PANELS
TRUCO INC. (OR EQUAL) OVER
WHITE ELASTOMERIC ROOF COATING,
/4
FOLDED SEAM
SCALE: 1 1/
A002 2" = 1'-0"
SCALE: 6" = 1'-0"
ROOF EDGE CLEAT
THAT IS COMPATIBLE WITH ROOFING MANUFACTURER.
5. INSTALL NEW PITCH POCKETS PER DETAIL 5/A002 AND 7/A002 AT EACH BRACKET. FILL PITCH POCKETS WITH A RUBBERIZED MATERIAL
AND STORE FOR RE-USE.
4. CAREFULLY REMOVE ALL 50 MUSHROOM ANTENNAS AND STORE THEM IN A CLEAN DRY LOCATION. REMOVE PLATES AND BRACKETS
3. FABRICATE DOPPLER BRACKET PITCH POCKETS OUT OF 24 GAUGE GALVANIZED SHEET METAL. PROVIDE 50 PITCH POCKETS.
SHALL REMAIN UNSOLDERED.
SHALL DROP BELOW THE SOFFIT TO FORM A DRIP EDGE. LAP ENDS OF EDGE CLEAT A MINIMUM OF 1 INCH (1") AND THIS LAP JOINT RATINGS. SEE DETAIL 1 ON THIS DRAWING. THE ROOF PANELS SHALL CURVE OVER THE 3/4" LIP OF THE EDGE CLEAT. THE EDGE CLEAT HORIZONTAL ROOF DECK AS IN ACCORDANCE WITH COPPER MANUFACTURERS INSTRUCTIONS SO AS TO PROVIDE I-90 UPLIFT WIND PANELS. SHAPE THE EDGE CLEAT AS SHOWN AND FASTEN, USING 1" LONG STAINLESS STEEL RING-SHANKED NAILS, EVERY 4" TO THE THE ROOF EDGE SHALL CONSIST OF AN EDGE CLEAT FORMED FROM 20 OZ. COPPER AND LOCATED BENEATH THE ROOF COPPER 2.
SPECIFICATIONS.
SOLDERED FOLDED SEAM FOR THE COR PRIOR TO INSTALLATION OF THE ROOF. IN ACCORDANCE WITH THE CONTRACT CLEAT INSTALLATION, FOLDED SEAM FORMATION AND SOLDERING TECHNIQUES. CONTRACTOR SHALL DEMONSTRATE A FULLY SOLDERED FOLDED SEAMS. INSTALLATION SHALL FOLLOW MANUFACTURER'S RECOMMENDATION AND C.D.A. GUIDELINES, INCLUDING COPPER PANELS SHALL BE FASTENED TO DECK HEMMED BY ENGAGING EDGE CLEAT AND ATTACHED TO EACH OTHER USING FULLY 1.
(SCALE: 1/2" = 1")
3" 0 3" 9"6"
SCALE: 3" = 1'-0"
1' 0 1'3"6"9"
SCALE: 1 1/2" = 1'-0"
2" 0 2" 4" chs-1400248-a002
2020-08-11T08:30:12-0400
VI V HO
2020-08-11T06:57:07-0400
SHANE CHRISTIAN HARVEY
HOLE.
" PILOT 16
3DRILLWASHER.
TAPPING SCREW WITH FLAT
STAINLESS STEEL, SELF
#14 HEX HEAD, TYPE 2,
TO FULLY SOLDERING
SURFACE OF COPPER PANEL PRIOR
AREA TO BE CLEANED ON TOP
PANEL DECK, PRIOR TO TINNING
TOP SURFACE OF COPPER
AREA TO BE CLEANED ON
SEGMENTS
COPPER PLATE BONDING
1"
NEW COPPER PANEL
PEDESTAL PLATE EVERY 3"
SEGMENTS TO VOR ANTENNA
ATTACH COPPER BONDING
PREPARE AND MECHANICALLY
ROOF OPENING
INNER EDGE OF ROOF
PLATE
ANTENNA PEDASTAL
OUTER EDGE OF
PEDASTAL PLATE
ANTENNA
TEEPEE AND BONDING SEGMENT INSTALLATION
CHS-1400248-A003
GASKET (TYP)
RUBATEX
GALV STEEL
1/8" THICK
(2 PLACES)
5/8" DIA HOLE
(2 PLACES)
45° CHAMFER
3/8" PLYWOOD
CEILING
1'-2 1/4"
/8
2"
1 1/8"
3" MIN. OVERLAP
BONDING SEGMENT
SCALE: 1 1/2" = 1'-0"A003
BONDING SEGMENT LAYOUT
SCALE: 1 1/2" = 1'-0"A003
SECTION - BONDING AT BASE PLATE
SCALE: 6" = 1'-0"A003
SECTION THRU ROOF
SCALE: 3/4" = 1'-0"A003
FASTENING STRIP (GFM)
SCALE: 6" = 1'-0"A003
BONDING SEGMENT INSTALLATION:
TEEPEE INSTALLATION NOTES:
01' 1' 3'2'
SCALE: 3/4" = 1'-0"
:0 lo tt e
TO A MAXIMUM OF 7
9. DETAIL 2 IS FOR INFORMATIONAL PURPOSES ONLY, SEGMENT LENGTHS MAY VARY
8. SOLDER BONDING SEGMENTS ALL AROUND PERIMETER.
7. TIGHTEN SCREWS ON ANTENNA BASE PLATE.
SCREWS AND WASHERS SO THAT SEGMENTS WILL NOT BUCKLE WHILE SOLDERING.
6. REPLACE ALL SEGMENTS AND FASTEN IN PLACE, LIGHTLY, WITH SELF TAPPING
BONDING SEGMENTS AND TIN USING ROSIN FLUX. (SEE SECTION B)
5. CLEAN AREA ON ADJOINING COPPER PANEL DECK WHICH IS TO BE COVERED BY
CIRCLE.
4. LOCATE ALL BONDING SEGMENTS IN PLACE AND DRILL PILOT HOLES ON INNER
PLATE.
OR EQUAL) LUBRICANT BETWEEN THE BONDING SECTIONS AND THE PEDESTAL
APPLY ANTI-SEIZE COMPOUND TO THE SCREWS AND ANTI-CORROSION (NOALOX
VIA 1/2 " LONG STAINLESS STEEL SELF-TAPPING PAN SCREWS AT 3" SPACINGS.
SOLDERED LAP SEAMS. ATTACH THE BONDING SECTIONS TO THE PEDESTAL PLATE
SHALL BE ATTACHED TO THE ROOF PANS AND TO EACH OTHER VIA FULLY
LEAVING A 3/8 " GAP AT THE BASE FOR EXPANSION. BONDING SECTIONS
3. ATTACH BONDING SECTIONS TO THE VOR ANTENNA PEDESTAL PLATE AS SHOWN,
PLATE A MINIMUM OF 3 INCHES.
2. COPPER PANEL BONDING SEGMENTS SHALL OVERLAP VOR ANTENNA PEDESTAL
SEGMENT. (SEE SECTION B).
(NOALOX OR EQUAL) PRIOR TO MECHANICALLY ATTACHING COPPER BONDING
SURFACE. COAT WITH NON-CORROSIVE, ELECTRICALLY CONDUCTIVE GREASE
PLATE, REMOVE PAINT, SOLDER, RUST, AND ANY OTHER IMPURITIES FROM
1. CONTRACTOR SHALL CLEAN AND PREPARE OVERLAP AREA OF ANTENNA PEDESTAL
COPPER PANEL DECK COVERING
BONDING OF SEGMENTS TO
CONTINUOUS SWEAT SOLDER 3/4"
PROPER LAP
UNTINNED END FOR
CUT ONE SEGMENT AT
3/4" LAP (TYP)
(MAXIMUM)
7 BONDING
MOUNTING STRIPS.
3/8"X 3", S.S., HEX HEAD LAGS, SS WASHERS, AND THE (GFM)
FILL WITH CAULK PRIOR TO SECURING THE TEEPEE WITH
ALL ALIGNED, THE CONTRACTOR SHALL DRILL PILOT HOLES AND
H. WITH THE TEEPEE, GASKET MATERIAL, AND COPPER PANEL HOLES
COPPER PANEL ROOF.
TAKING CARE TO ALIGN THE TEEPEE WITH THE HOLES CUT IN THE
TEEPEE TO THE PREVIOUSLY APPROVED AND MARKED LOCATION
G. THE CONTRACTOR SHALL THEN REPOSITION THE REFURBISHED
PENETRATION.
OR SIMILAR METHOD TO CLEAR GASKET MATERIAL FROM THE
HOLES LOCATED IN THE BASE OF THE TEEPEE USING A STEPBIT
CONTRACTOR WILL THEN DRILL OUT THE GASKET FOR THE 36 BOLT
CONTACT ADHESIVE TO BE USED AS/IF REQUIRED. THE
FIRMLY HOLD IN PLACE. THE CONTRACTOR SHALL SUPPLY THE
MAY REQUIRE THE APPLICATION OF CONTACT ADHESIVE TO
TYPICALLY COMES WITH PRESSURE SENSITIVE ADHESIVE, BUT
TO THE UNDERSIDE OF THE TEEPEE. NOTE: THE GASKET MATERIAL
F. THE CONTRACTOR WILL THEN APPLY THE TEEPEE GASKET MATERIAL
CLEANING AND REMOVING ANY OLD GASKET MATERIAL, IF ANY.
ATION OF THE (GFM) TEEPEE GASKET BY THOROUGHLY
PREPARE THE BOTTOM SURFACE OF THE TEEPEE FOR INSTALL-
AND MARKED MOUNTING LOCATION, THE CONTRACTOR SHALL
E. JUST PRIOR TO SETTING THE TEEPEE BACK IN THE APPROVED
WITH CARE NOT TO DAMAGE WOOD DECK BELOW THE COPPER.
THE HOLES SHALL BE DRILLED THROUGH THE COPPER ROOF ONLY
LOCATIONS MARKED IN STEP B, AND DESCRIBED IN NOTE 1.
D. THE CONTRACTOR SHALL DRILL TEEPEE MOUNTING HOLES AT
ASIDE.
C. THE CONTRACTOR WILL THEN REMOVE THE TEEPEE AND SET IT
AT THIS TIME.
REQUIRED TEEPEE ATTACHMENT BOLTS SHALL ALSO BE MARKED
PREPARATIONS DESCRIBED BELOW. THE LOCATION OF THE 36
AND ORIENTATION AFTER REMOVAL FOR FURTHER ANCHORING
LOCATION SO IT CAN BE RETURNED TO THE EXACT LOCATION
B. THE CONTRACTOR SHALL THEN MARK THE APPROVED TEEPEE
ORIENTATION.
FAA WILL APPROVE THE FINAL LOCATION AND RADIAL
TEEPEE ON THE NEW ROOF. ONCE POSITIONED CORRECTLY, THE
A. THE CONTRACTOR SHALL TEMPORARILY PLACE REFURBISHED
2. TEEPEE INSTALLATION SEQUENCE:
PLATE CLEAT FASTENERS.
FOR PAN EXPANSION AND APPLY TO TEEPEE AND ANTENNA PEDESTAL
DIAMETER PLUS 3/4". THESE OVERSIZED OPENINGS ARE REQUIRED
BY 3/8" EACH SIDE, I.E. OPENING DIAMETER SHALL BE FASTENER
FASTENER INSTALLATION. THESE OPENINGS SHALL BE OVERSIZED
PANS, OPENINGS SHALL BE CREATED IN THE PANS PRIOR TO
1. FOR TEEPEE INSTALLATION, ALL FASTENERS PASSING THROUGH
A003
COPPER PLATE BONDING SEGMENT
ELASTOMERIC TO STOP AT
ELASTOMERIC COATING
SEGMENT ATTACHMENT
COMPOUND PRIOR TO BONDING
APPLY NOALOX DIELECTRIC (OR EQUAL)
WITH TSP (OR EQUAL)
OF ANTENNA PLATE AND CLEAN
TOP SURFACE
CLEAN AND PREPARE AREA ON
PLATE (EXISTING)
VOR ANTENNA PEDESTAL
T
ID
'-6
ID
PANEL SHEETS
COPPER
CUT FROM 20 OZ.
(7 MAXIMUM)
3/4" TINNED STRIPS
(CENTER POLE)
PEDESTAL
POLARIZER
STRIP (GFM)
FASTENING
(SEE 1/A003)
CONTRACTOR
INSTALLED BY
BY FAA
INSTALLED
PEDESTAL
VOR ANTENNA
AND CLEATS
BLOCKING
EXISTING
(MAY VARY)
ROOF STRUCTURE
TRIM TO OUTLOOKERS (2 LOCATIONS)
CONTRACTOR SHALL RE-INSTALL
E001
AS NEEDED
NEW NAILER, FURR DOWN,
RE-INSTALL SOFFIT UNDER
STRAPPING
3/4" X 2"
AROUND EDGE
1X TRIM TYPICAL
ACCESS HOLE PATCH
INSULATION (TYP.)
SPRAY FOAM
(8 PLACES)
CLAMP (GFM)
HOLD DOWN
AND ELASTOMERIC COATING. SEE DETAILS
UNDERLAYMENT, ROSIN PAPER, COPPER ROOFING,
NEW ROOF DECK (WHERE REQUIRED) 3/4" T & G CDX PLYWOOD
SIDING
1/4"/FT TYP SLOPE (MAY VARY)
(SHEET G003/NOTE 16)
INSTALLED BY FAA
(TEEPEE)
ANTENNA ENCLOSURE
COPPER ROOF
OF BONDING SEGMENT
END AT OUTER RADIUS
ELASTOMERIC COATING
12'-1/2" (TYPICAL FLAT)
20'-2 3/4" (TYPICAL SLOPE = 1/4" PER FOOT = APPROX 5")
chs-1400248-a003
2020-08-11T08:32:01-0400
VI V HO
2020-08-11T06:56:38-0400
SHANE CHRISTIAN HARVEY
(TYP OF 50)
AND MOUNTING BRACKETS
DOPPLER ANTENNAS
SYSTEM
DOPPLER COUNTERPOISE
GALVANIZED STEEL
AND 48' METAL EXTENSION
36'x 36' VOR BUILDING WITH 52' DIAMETER WOOD ROOF
D001
04' 4' 8' 12'
SITE SPECFIC
140048
-d
DEMOLITION PLAN
CHS-1400248-D001
REMOVED BY FAA (APPROX. 800 LBS)
TACAN ANTENNA
REMOVED BY FAA (APPROX. 300 LBS)
TACAN COLLAR
(APPROX 800 LBS)
REMOVED BY FAA
VOR TEEPEE
ASSEMBLIES (SEE NOTE 6)
SHALL REMOVE MOUNTING BRACKET
REMOVED BY FAA. CONTRACTOR
EXISTING DOPPLER ANTENNAS TO BE
ROOFING/COUNTERPOISE
REMOVE ORIGINAL TERNE PLATE SHEET
PERIMETER BEAMS BELOW
DOUBLE 2" X 12" STRUCTURAL
(SEE NOTE 3)
REPAIR AS NEEDED
DECK BOARDS REMAIN
ORIGINAL 2" T&G
TAPERED TO EDGE
C10'S WITH 4X6 NAILERS
STEEL ROOF FRAMING BELOW,
BELOW
BUILDING LINE
SEE NOTE 4
INSULATOR ACCESS
INSIDE TEEPEE
120V FLOOR RECEPTACLE
REMOVE EXISTING
9 AND 10)
ANTENNAS (SEE NOTES
VOR AND TACAN
FAA WILL REMOVE
1" POLYISO INSULATION (TYP)
REMOVE EXISTING ROOF WITH
52'-6" DIAMETER
(IF APPLICABLE)
RUBBER WALKWAY
REMOVE
(SEE NOTE 8)
LADDER HOLD BOLTS
TEEPEE ENCLOSURE
FAA SHALL REMOVE
3" BATT INSULATION
1/2" LAG BOLTS
BOLTED TO C10 WITH
4" X 6" TAPERED NAILERS
CEILING
3/8" PLYWOOD
INSULATION
SINGLE PLY ROOF
TERMINATION BAR
REMOVE TERNE ROOFING
(SOLDERED AND SCREWED) SEE NOTE 7
CLAMPS FROM ANTENNA PEDESTAL PLATE
REMOVE TERNE PLATE AND HOLD DOWN
VOR ANTENNA PEDESTAL PLATE
MATERIAL (VARIES)
OTHER ROOFING
2 X 6 WOOD DECK
METAL TERNE ROOFING
ROSIN PAPER, BOARD INSULATION, AND SINGLE PLY MEMBRANE
ASPHALTIC SURFACED TERNE PLATE ROOF/COUNTERPOISE,
CONTRACTOR TO REMOVE:
SLOPE 1/4"/FT (TYP.)
2"X6" T&G DECKING
C10 X 8.5
PERFORATED VINYL SOFFIT (EXISTING)
BUILDING EXTERIOR WALL
BREAK METAL
ALUMINUM SOFFIT
REMOVE AND REUSE
FASCIA AND SOFFIT
ALUMINUM
CONDUIT. SEE NOTE 11
CONTRACTOR SHALL
BOLTED TO C10 VIA CLIP ANGLES
DOUBLE 2 X 12 PERIMETER BEAM
VINYL SIDING
VOR ANTENNA ENCLOSURE
FASTENING STRIP AND WASHERS
ROOF SECTION
ROOF PLAN
N
4'-0"
10'-0"
VARIES
DIM
VORTAC FACILITY
10. FAA COR WILL COORDINATE TEEPEE REMOVAL WITH CONTRACTOR. SEE NOTE 16 ON G003
PROVIDE LABOR ASSISTANCE. PLAN TWO PEOPLE FOR EIGHT (8) HOURS ON EACH PICK.
CONTRACTOR SHALL PROVIDE CRANE AND OPERATOR. THE CONTRACTOR SHALL ALSO
9. FAA WILL PROVIDE LABOR, AND TRANSPORT, TO REMOVE EXISTING TEEPEE OFFSITE.
8. CONTRACTOR SHALL REMOVE LADDER HOLD BOLTS THEN SEAL HOLES WITH CAULK.
THE WORK.
SHALL NOT REMOVE MORE THAN THREE ANTENNA HOLD-DOWN CLAMPS AT ONE TIME TO EXECUTE
7. CONTRACTOR SHALL TAKE PRECAUTIONS NOT TO MOVE ANTENNA BASE PLATE. THE CONTRACTOR
6. NOT USED.
5. CONTRACTOR TO ASSIST FAA TO DISCONNECT COAX CABLING AND REMOVE ANTENNAS.
CEILING.
4. CONTRACTOR SHALL REMOVE EXISTING 3" BATT INSULATION FROM ABOVE PLYWOOD
3. REPLACE ALL REMOVED WOOD DECK MATERIAL WITH 2" X 6" T & G TO MATCH EXISTING.
CONTRACTING OFFICER.
REPLACEMENT DUE TO ROT. IF QUANTITY EXCEEDS 500 SF, IMMEDIATELY NOTIFY
EXPECTED THAT APPROXIMATELY 500 SF OF WOOD ROOF DECK WILL REQUIRE
2. REMOVE ALL ROOFING MATERIALS DOWN TO THE EXISTING WOOD DECK. IT IS
EPDM ROOF MEMBRANE.
ASPHALTIC ROOF COATING, 1" POLYISOCYANURATE INSULATION BOARD, AND AN
COATED METAL (TERNE PLATE ROOFING WHICH CONTAINS LEAD) TOPPED WITH AN
1. EXISTING ROOF OVER 2"X6" WOOD ROOF DECK MAY INCLUDE: ROSIN PAPER, TIN-
-d
:4 lo tt e chs-1400248-d001
2020-08-11T08:37:11-0400
VI V HO
2020-08-11T06:56:07-0400
SHANE CHRISTIAN HARVEY
-e
:1 lo tt e
GROUNDING DETAILS
CHS-1400248-E001
-e
(LOCATED NEAR EACH CORNER OF BUILDING)
4. THE CONTRACTOR SHALL PROVIDE NEW DOUBLE BOLT COPPER LUGS.
IN DETAIL 3, THIS SHEET.
TERNE METAL SHALL BE 20 OZ. PLATE FABRICATED AS SHOWN
CONNECTOR LUGS IF TINNED STAINLESS STEEL IS USED FOR ROOF MATERIAL.
3. THE CONTRACTOR SHALL PROVIDE AND INSTALL DOUBLE BOLT ALUMINUM
DOWN CLAMPS AT ONE TIME TO EXECUTE THE WORK.
2. THE CONTRACTOR SHALL NOT REMOVE MORE THAN TWO ANTENNA HOLD
MECHANICALLY ATTACHING TERNE PLATE.
SURFACE. COAT WITH NON-CORROSIVE (NOALOX OR EQUAL) PRIOR TO
PLATE, REMOVE PAINT, SOLDER, RUST, AND ANY OTHER IMPURITIES FROM
1. CONTRACTOR SHALL WIRE BRUSH OVERLAP AREA OF ANTENNA PEDESTAL
METAL GROUNDING PLATE
(FULLY SOLDERED)
TERNE PLATE SEAM
TO SOLDERING
PRE-TIN PRIOR
VAPOR BARRIER
METAL TERNE PLATE
(3 SIDES)
PLATE TO TERNE PLATE
FULLY SOLDER GROUND
SOFFIT
J-TRIM
HOLES
1/4"
PLATE
SOLDER TO COPPER
2"x 6"
SOLDER TO
80 LOCATIONS
COUNTERPOISE/ROOF
ALL AROUND
#6 BSDC AT 2'
POST CONNECTOR
BURNDY SERVIT
TYPE KC1781
MESH
OF METAL TERNE PLATE)
GROUNDING PLATE (FULLY SOLDERED ATOP
COPPER PANEL
WOOD DECKING
GROUND PLATE
TERNE ROOF
(SEE NOTES 3 & 4)
GROUND PLATE (TYP 4)
GROUND LUG, FASTENED TO
WIRE IN NEW DOUBLE BOLT
EXISTING #2 BARE GROUND
USE NOALOX
CRIMPED FITTING
HYDRAULIC COMPRESSION
SHALL BE 12 TON
CLAMP
HOLD DOWN
AT BASE PLATE
5/8" OPEN GAP
ANTENNA PEDESTAL PLATE
SEGMENTS TO EDGE OF VOR
TERNE PLATE BONDING
3" (MIN) FROM EDGE OF
SEGMENT
BONDING
ANTENNA BASE PLATE
NOT SHOWN FOR CLARITY)
(ELASTOMERIC ROOFING
TERNE PLATE PANS
SEGMENT
EDGE OF BONDING
STOP AT OUTER
ELASTOMETRIC TO
BONDING
AFTER INSTALLATION
(SEE NOTE 2) CAULK
HOLD-DOWN CLAMP (TYP 8)
VOR ANTENNA PEDESTAL PLATE
EVERY 3", SEE NOTE 1
ANTENNA PEDESTAL PLATE
BONDING SEGMENTS TO
MECHANICALLY FASTEN
HOLD DOWN CLAMP
ROOF OPENING/GAP
BASE PLATE
4" MIN
5"
2 1/
105°
1/2"
1 1/2"
3" (M
(SCALE: 1/2" = 1")
01" 1" 2"
SCALE: 1" = 1"
COPPER GROUNDING CONNECTION
EDGE OF ROOF
COUNTERPOISE
MESH
COUNTERPOISE
GROUNDING PLATE WITH EXISTING CONDUCTOR
SCALE: 1" = 1"
VOR ANTENNA BASE PLATE1
E001 2" = 1'-0"SCALE: 1 1/
GROUNDING PLATE/TERNE PLATE
(FOUR REQUIRED)
SHEET 0.021" THICK X 4" WIDE x 4" LONG
20 OZ COPPER OR STEEL (OR THICKER)
GROUNDING PLATE - ISOMETRIC VIEW
chs-1400248-e001
2020-08-11T08:38:10-0400
VI V HO
2020-08-11T06:55:38-0400
SHANE CHRISTIAN HARVEY
-g
:3 lo tt e
AVIA
I
L
TRAT
IO
SI
NI
T OF TRANSPO
T A
IO
IC
OF
STATES
IT
TM
EN
COVER SHEET
CHS-1400248-G001
VICINITY MAP
ELASTOMERIC AND COPPER PANNELIZED ROOF SYSTEM
CHS DOPPLER VORTAC FACILITY
chs-1400248-g001
2020-08-11T08:39:27-0400
VI V HO
2020-08-11T07:41:43-0400
SHANE CHRISTIAN HARVEY
lo tt e s g
140024808/05/2020
DRAWING INDEX, ABBREVIATIONS, AND LEGEND
CHS-1400248-G002
SECTION REFERENCE LETTER
SECTION IS LOCATED
SHEET NUMBER WHERE
SUBTITLE REFERENCE
SYMBOLS LEGEND DRAWING INDEX ABBREVIATIONS
FACILITY COORDINATES
(PLAN, DETAIL/ELEVATION, SECTION)
REFERENCE NUMBER/LETTER
X
XXXX SCALE: X=XXX
XXXXXXXXXXX
SCALE
ELEVATION, SECTION OR DETAIL IS/ARE LOCATED
SHEET NUMBER(S) WHERE CALLOUT(S) TO PLAN,
ELEVATION REFERENCE LETTER
ELEVATION CALLOUT REFERENCE
ELEVATION IS LOCATED
XXXX
SECTION CALLOUT REFERENCE
DETAIL REFERENCE NUMBER
DETAIL CALLOUT REFERENCE
DETAIL IS LOCATED
DRAWING PREFIXES
GXXX - GENERAL
AXXX - ARCHITECTURAL
EXXX - ELECTRICAL/ELECTRONIC
DXXX - DEMOLITION
CXXX - CIVIL
SXXX - STRUCTURAL
ELEVATION
LONGITUDE
LATITUDE
39.0 MSL
080 02' 16.131"W
32 53' 39.549"N
DRAWING NUMBER DRAWING TITLE
CHS-1400248-E001
CHS-1400248-A003
CHS-1400248-A002
CHS-1400248-A001
CHS-1400248-D001
CHS-1400248-G003
CHS-1400248-G002
CHS-1400248-G001
GROUNDING DETAILS
TEEPEE AND BONDING SEGMENT INSTALLATION
ROOF EDGE DETAILS
NEW ROOF PLAN
DEMOLITION PLAN
GENERAL NOTES AND GFM LIST
DRAWING INDEX, ABBREVIATIONS, AND LEGEND
COVER SHEET
XMTR - TRANSMITTER
XFMR - TRANSFORMER
WS - WIND SOCK
W/ - WITH
VOR - VERY HIGH FREQUENCY OMNI RANGE
VHF - VERY HIGH FREQUENCY
V - VOLT
UPS - UNINTERRUPTIBLE POWER SOURCE/SUPPLY
TYP - TYPICAL
TSA - TAXIWAY SAFETY AREA
TOS - TOP OF STEEL
TOC - TOP OF CONCRETE
TH - THRESHOLD
TELCO - TELEPHONE COMPANY
TEL - TAXIWAY EDGE LIGHTS
TACAN - TACTICAL AIR NAVIGATION
T/W - TAXIWAY
T - TELEPHONE
STA - STATION
SSC - SYSTEM SUPPORT CENTER (FAA)
SS - STAINLESS STEEL
SP - SINGLE-POINT (GROUND)
SMO - SYSTEM MANAGEMENT OFFICE (FAA)
SEC - SECONDARY
SCH - SCHEDULE
RVR - RUNWAY VISUAL RANGE
RTR - REMOTE TRANSMITTER/RECEIVER
RT - REMOTE TRANSMITTER
RSA - RUNWAY SAFETY AREA
RRCS - REMOTE RADIO CONTROL SYSTEM
RMC - REMOTE MONITORING SUBSYSTEM
RMMS - REMOTE MAINTENANCE MONITORING SYSTEM
RMM - REMOTE MAINTENANCE MONITORING
RLS - REGISTERED LAND SURVEYOR
RF - RADIO FREQUENCY
REQ - REQUIRED
REL - RUNWAY EDGE LIGHTS
REIL - RUNWAY END IDENTIFIER LIGHTS
RAIL - RUNWAY ALIGNMENT INDICATOR LIGHTS
R/W - RUNWAY
PVC - POLYVINYL CHLORIDE
PRIM - PRIMARY
PR - PAIR
PNL - PANEL
PLC - PLACES
PAPI - PRECISION APPROACH PATH INDICATOR
P - POWER
OM - OUTER MARKER (ILS)
OFA - OBJECT FREE AREA
OC - ON CENTER
OB - OBSTRUCTION
NWS - NATIONAL WEATHER SERVICE
NTP - NOTICE TO PROCEED
NOTAM - NOTICE TO AIRMEN
NIC - NOT IN CONTRACT
NEC - NATIONAL ELECTRIC CODE
NDB - NON -DIRECTIONAL BEACON
NAS - NATIONAL AIRSPACE SYSTEM
N/A - NOT APPLICABLE
N - NEUTRAL
MSL - MEAN SEA LEVEL
MP - MULTI-POINT (GROUND)
MIN - MINIMUM
MHZ - MEGAHERTZ
MAX - MAXIMUM
MASLR - MALS WITH RUNWAY ALIGNMENT INDICATOR LIGHTS (MALS-RAIL)
MASLF - MALS WITH SEQUENCED FLASHERS
MALS - MEDIUM INTENSITY APPROACH LIGHT SYSTEM
LOM - LOCATOR OUTER MARKER (NDB & OM)
LOC - LOCALIZER (ILS)
LIR - LOW IMPACT RESISTANCE
LHA - LAMP HOUSING ASSEMBLY (PAPI)
KVA - KILOVOLT AMPERE
KV - KILOVOLT
KHZ - KILOHERTZ
INSUL - INSULATED
IN - INCH
ILS - INSTRUMENT LANDING SYSTEM
HZ - HERTZ
HH - HAND HOLE
GS - GLIDE SLOPE (ILS)
GRSC - GALVANIZED RIGID STEEL CONDUIT
GND - GROUND
GFM - GOVERNMENT FURNISHED MATERIAL
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
GC - GROUND CHECK (LOCALIZER)
GALV - GALVANIZED
GA - GENERAL AVIATION
FT - FEET
FOD - FOREIGN OBJECT DEBRIS
FDN - FOUNDATION
FBO - FIXED BASE OPERATOR
FAA - FEDERAL AVIATION ADMINISTRATION
EXIST - EXISTING
EOR - END OF RUNWAY
EMT - ELECTRIC METALLIC TUBING
EL - ELEVATION
EES - EARTH ELECTRODE SYSTEM
DWG - DRAWING
DU - DISTRIBUTION UNIT
DPU - DATA PROCESSING UNIT
DME CO - DME CORPORATION
DME - DISTANCE MEASURING EQUIPMENT
DISC - DISCONNECT
DIA ( ) - DIAMETER
DEB - DIRECT EARTH BURIAL
CW - COURSE WIDTH (LOCALIZER)
COR - CONTRACTING OFFICER'S REPRESENTATIVE (FAA)
CO - CONTRACTING OFFICER (FAA)
CND - CONDUIT (DUCT)
CKT - CIRCUIT
CFW - CENTERFIELD WIND
CDA - COPPER DEVELOPMENT ASSOCIATION
C-C - CENTER TO CENTER
C - CONTROL
BSCU - BARE SOLID COPPER
BLD - BUILDING
AWG - AMERICAN WIRE GAUGE
ATCT - AIR TRAFFIC CONTROL TOWER
ASOS - AUTOMATED SURFACE OBSERVATION SYSTEM (NWS)
ARP - AIRPORT REFERENCE POINT
AOA - AIR OPERATIONS AREA
ALS - APPROACH LIGHT SYSTEM
AIP - AIRPORT IMPROVEMENT PROGRAM (FAA)
AGL - ABOVE GROUND/GRADE LEVEL
A-G - AIR TO GROUND
ACM - ASBESTOS CONTAINING MATERIAL
A - AMP
chs-1400248-g002
2020-08-11T08:40:09-0400
VI V HO
2020-08-11T06:54:46-0400
SHANE CHRISTIAN HARVEY
lo tt e
GENERAL NOTES AND GFM LIST
GENERAL NOTES:
SITE WORK:
ELECTRICAL WORK:
ELECTRICAL GROUNDING:
GOVERNMENT FURNISHED MATERIALS (GFM) NOTES:
AOA SPECIFIC SITE DETAIL NOTES:
CHS-1400248-G003
4A
4B
5340-01-623-0186
5985-01-573-3161
5985-01-363-1755
5999-01-509-6453
5975-00-867-4780
5411-01-325-1940 REFURBISHED VOR ANTENNA ENCLOSURE (TEEPEE)
TACAN ANTENNA
TACAN COLLAR
RTA2 TACAN ANTENNA HARNESS
LPTA TACAN ANTENNA HARNESS
FIBERGLASS DOPPLER ANTENNA COVER
CL-1 HOLD DOWN CLAMPS
TEEPEE FASTENING STRIPS
TEEPEE LOWER AND UPPER GASKET MATERIAL
1 EACH
50 EACH
8 EACH
18 EACH
DESCRIPTION
GFM MATERIAL LIST
NSNITEM QUANTITY
REQUIREMENTS FOR FACILITIES AND ELECTRONIC EQUIPMENT".
"LIGHTNING AND SURGE PROTECTION, GROUNDING, BONDING AND SHIELDING
1. GROUNDING AND LIGHTNING PROTECTION SHALL MEET LATEST VERSIONS OF FAA STANDARD 019,
2. THE CONTRACTOR SHALL MAKE ALL POWER SERVICE TERMINATIONS (IF APPLICABLE), AND GROUND TERMINATIONS.
AND IN NO CASE SHALL VIOLATE THE NATIONAL ELECTRIC CODE (NFPA 70, NEC).
1. ALL ELECTRICAL WORK SHALL CONFORM TO LATEST VERSIONS OF FAA-C-1217 AND FAA-C-1391
APPROVED BY THE FAA COR.
3. ALL DISTURBED AREAS SHALL BE RESTORED TO PRIOR CONDITION. FINAL CONDITION SHALL BE
AND SHALL CONDUCT REPAIRS AT CONTRACTOR'S EXPENSE.
2. THE CONTRACTOR SHALL IMMEDIATELY REPAIR UTILITIES DAMAGED DURING EXCAVATION ACTIVITIES.
VERIFIED IN THE FIELD BY THE CONTRACTOR.
1. DIMENSIONS, ELEVATIONS, CONTOURS AND HEIGHTS INDICATED ARE APPROXIMATE AND SHALL BE
MAY BE REUSED.
5. ALL ABOVE LISTED GFM ITEMS MAY NOT BE APPLICABLE. SOME ITEMS ARE EXISTING AND
THE PICK.
CONTRACTOR SHALL SUPPLY OTHER STRAPS AND RIGGING TO EXECUTE
4. THE FAA WILL FURNISH TACAN ANTENNA HARNESS TO REMOVE AND REPLACE TACAN.
SHALL ASSIST IN SETTING THE TEEPEE ON THE VOR SHELTER.
IS RESPONSIBLE FOR PROVIDING THE CRANE TO OFFLOAD THE TEEPEE. THE CONTRACTOR
3. THE NEW FIBERGLASS TEEPEE IS GOVERNMENT FURNISHED MATERIAL. THE CONTRACTOR
RESPONSIBLE FOR THE GFM WHILE STORED ON SITE.
THE GFM WILL BE TRANSFERRED (VIA FAA SUPPLIED 4650-12 FORM). THE CONTRACTOR SHALL BE
2. THE GFM SHALL BE INVENTORIED BY THE CONTRACTOR AND THE FAA COR AT WHICH TIME
1. GFM WILL BE DELIVERED TO THE SITE BY THE GOVERNMENT.
LIFTS NOT EASILY TRANSPORTED SUCH AS SCISSORS LIFTS MAY BE BOOMED DOWN AND STORED ON SITE UNDER VOR ROOF EVE.
OF CONSTRUCTION DEBRIS AND OTHER FOREIGN OBJECT DEBRIS (FOD) WHICH MAY BLOW ONTO THE RUNWAYS.
BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT. THE CONTRACTOR SHALL KEEP THE WORK SITE FREE
6. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK SITE. FOR PROJECTS WITHIN THE AOA, EQUIPMENT AND MATERIAL SHALL
AIR TRAFFIC ON THE APPROPRIATE FAA FREQUENCIES.
5. IF REQUIRED BY THE AIRPORT AUTHORITY, THE CONTRACTOR'S VEHICLES SHALL BE EQUIPPED WITH A RADIO TO MONITOR
MAY INCLUDE: A ROTATING BEACON AND/OR FLAG.
4. CONTRACTOR VEHICLES SHALL BE MARKED IN ACCORDANCE WITH THE AIRPORT AUTHORITIES REQUIREMENTS WHICH
AIRFIELD. SECURITY BADGES MUST BE DISPLAYED AT ALL TIMES WHILE ON THE AIRFIELD.
3. THE CONTRACTOR SHALL COMPLY WITH AIRPORT SECURITY BADGING AND ACCESS REQUIREMENTS TO WORK ON THE
PAVEMENT AND BE INGESTED INTO JET ENGINES.
ON THE AOA. THE CONTRACTOR SHALL BE VIGILANT TO REMOVE DIRT, MUD OR OTHER FOD WHICH MAY TRACK ONTO THE AOA
2. THE CONTRACTOR SHALL ALSO CONDUCT FOD INSPECTIONS OF ALL VEHICLES PRIOR TO DRIVING
INDIVIDUAL BADGED FOR DRIVING ON THE AOA.
VEHICLE MOVEMENT BY CONTRACTOR WITHIN THE AOA SHALL BE MADE ONLY WITH ESCORT BY THE FAA COR, OR OTHER
1. THE WORK ASSOCIATED WITH THE VOR SHELTER ROOF REPLACEMENT IS WITHIN THE AIRPORT OPERATIONS AREA (AOA), TABLE - GOVERNMENT FURNISHED MATERIAL (GFM)
G003
18. WHERE CAULKING IS SPECIFIED, CONTRACTOR SHALL USE 3M 5200 CAULKING OR APPROVED EQUAL.
17. THE CONTRACTOR SHALL USE ANTI-SEIZE COMPOUND ON ALL THREADED PARTS.
REMOVAL AND INSTALLATION OF EQUIPMENT.
16. CONTRACTOR SHALL PLAN AT LEAST TWO DAYS LABOR FOR TWO MEN (IN ADDITION TO CRANE OPERATOR) TO ASSIST FAA IN
AND ONE TO INSTALL EQUIPMENT.
15. CONTRACTOR SHALL PLAN AT LEAST TWO DAYS FOR THE CRANE AND MAN LIFT, ONE TO REMOVE
14. CONTRACTOR SHALL SECURE DUNNAGE AND TIE DOWNS TO PROTECT TEEPEE AND TACAN ANTENNA WHILE STORED ON SITE.
ON INSULATION MUST BE TREATED WITH FLAME RETARDANT OR MEET FIRE CODE FOR FOR FLAME SPREAD.
FOAM INSULATION. MINIMUM R-VALUE SHALL BE MET FOR PROJECT AREA PER LOCAL BUILDING CODE. EXPOSED SPRAY
SPECIFICATION. AT SITES WITHOUT FALSE CEILING, UNDERSIDE OF DECK SHALL BE PREPPED AND SPRAYED WITH CLOSED CELL
13. THE CONTRACTOR SHALL SPRAY IN NEW INSULATION ABOVE THE PLYWOOD CEILING IN ACCORDANCE WITH THE CONTRACT
INSTALLING NEW INSULATION, IF APPLICABLE, EXPOSED SPRAY-ON SHALL MEET FIRE CODE.
12. THE CONTRACTOR SHALL REMOVE EXISTING INSULATION FROM ABOVE PLYWOOD CEILING PRIOR TO
SHALL NOTIFY THE CONTRACTING OFFICER (CO) AND COR PRIOR TO PROCEEDING WITH CONSTRUCTION.
11. IF CONDITIONS ARE DIFFERENT THAN THOSE INDICATED IN THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR
THE FAA.
10. THE CONTRACTOR SHALL LEGALLY DISPOSE OF ALL MATERIALS AND EQUIPMENT NOT RETURNED TO OR RETAINED BY
SHALL PROVIDE ALL LABOR AND EQUIPMENT TO EXECUTE THE WORK, UNLESS OTHERWISE INDICATED.
9. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS UNLESS DESIGNATED AS GFM. THE CONTRACTOR
SUSPEND THE PROJECT SHOULD HE OR SHE DETERMINE THAT AN UNSAFE CONDITION EXISTS.
8. THE CONTRACTOR SHALL COMPLY WITH OSHA REGULATIONS. THE C.O. AND/OR COR RESERVES THE RIGHT TO
THE TACAN MOUNTING COLLAR MUST BE SEPARATED FROM THE TEEPEE FOR TRANSPORTATION.
TEEPEE. THE CONTRACTOR SHALL SUPPLY A 150 FOOT (MIN) TELESCOPING BOOM LIFT CAPABLE OF REACHING THE TACAN ANTENNA
THE CRANE SHALL SAFELY LIFT THE APPROXIMATE 800 LB TACAN ANTENNA (LOCATED ATOP THE TEEPEE) AND THE APPROXIMATE 800 LB
VOR ANTENNA SHELTER (TEEPEE). THE CONTRACTOR SHALL PROVIDE THE PROPER CRANE AND A MANLIFT TO EXECUTE THE WORK.
7. THE CONTRACTOR WITH FAA ASSISTANCE SHALL REMOVE THE EXISTING TACAN ANTENNA, MOUNTING COLLAR, AND
(SIGNED AND STAMPED) BY AN RLS.
6. CONTRACTOR TO PROVIDE ROOF SKETCH OF FINAL FACILITY NORTH POINT RELATIVE TO TRUE NORTH AND MONITOR ANTENNA LOCATIONS
ALL ELECTRONICS PRIOR TO THE CONTRACTOR BEGINNING WORK. FOR ADDITIONAL INFORMATION SEE DRAWING D001.
ROOF. THE BRACKETS ARE BOLTED THROUGH THE ROOF MATERIALS AND THE WOOD DECK BELOW. THE FAA WILL DISCONNECT AND REMOVE
FIFTY DOPPLER ANTENNA MOUNTING BRACKETS AND ASSOCIATED HARDWARE WHICH ARE LOCATED AROUND THE PERIMETER/EDGE OF THE
5. AFTER THE OFFSET FOR THE NORTH MONITOR BRACKET HAS BEEN ESTABISHED BY THE RLS, THE CONTRACTOR AND FAA SHALL REMOVE
ALONG EDGE OF ROOF. CONTRACTOR SHALL PROVIDE TEMPORARY STORAGE FACILITY FOR THE ANTENNAS.
ASSIST THE FAA IN REMOVING THE EXISTING VOR ANTENNAS, (INSIDE TEEPEE) AND THE VOR DOPPLER ANTENNAS
4. THE FACILITY (VOR AND TACAN) WILL BE SHUT DOWN FOR THE DURATION OF THE CONSTRUCTION. THE CONTRACTOR SHALL
LEAST 1 WEEK IN ADVANCE.
SHUTDOWN OR OTHER PROVISIONS. COORDINATE ALL SUCH ACTIVITIES AND REQUIRED SHUTDOWNS WITH THE COR AT
3. ANY ACTIVITIES INVOLVING CRANES OR OTHER EQUIPMENT EXCEEDING 15 FEET IN HEIGHT MAY REQUIRE
PRIOR TO CONSTRUCTION START.
2. CONTRACTOR SHALL USE ACCESS ROUTES, STAGING AREAS, AND EMPLOYEE PARKING AREAS APPROVED
THIS FACILITY HAS A TACAN ANTENNA AND COLLAR INSTALLED ON TOP OF THE TEEPEE.
1. THIS DRAWING PACKAGE INDICATES WORK REQUIRED FOR THE REPLACEMENT OF DOPPLER VOR EQUIPMENT SHELTER ROOF.
chs-1400248-g003
2020-08-11T08:42:19-0400
VI V HO
2020-08-11T06:54:09-0400
SHANE CHRISTIAN HARVEY
File details come from the government source that posted it. Updated .