Pre-Bid_RFI_W912L6-17-B-0001_Log_04-27-17.xlsx
XLSX spreadsheet 11 KB Posted
- Attached to
- Chiller and Installation Building 316
- Solicitation number
- ChillerBuilding316
About this file
This document contains questions sent in regard to this solicitation as well as the answers provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pre-Bid_RFI_W912L6-17-B-0001_Log_05-11-2017.pdf | ||
| 17-B-0001-0002_Clause_52.228-1.pdf | ||
| Pre-Bid_RFI_W912L6-17-B-0001_Log_04-27-17.pdf | ||
| Solicitation_Modification_W912L6-17-B-0001-0001.pdf | ||
| STATEMENT_OF_WORK-21_Feb_2017_Bldg316_Chiller.doc | DOC document | |
| Pre-Bid_RFI_W912L6-17-B-0001_Log_04-27-17.xlsx | XLSX spreadsheet | |
| ChillerPics.pdf | ||
| Pre-Bid_RFI_W912L6-17-B-0001_Log_04-27-17.xlsx | XLSX spreadsheet | |
| Site_Visit_Sign_In.pdf | ||
| Solicitation_W912L6-17-B-0001.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 Pre-Bid RFI Log for W912L6-17-B-0001 Bldg 316 Chiller, XHZG201501230
| Date: | RFI No. | RFP Reference (Sect/Para/Page) | QUESTION | GOVERNMENT RESPONSE |
| 4/27/17 | 1 | N/A | Does the chilled water system have glycol in it? If so, what type of glycol and how much percentage does it have? | Yes, the chilled water system has propylene glycol in it. It is a 30%, protected to 0° mixture, but has been diluted. |
4/27/17 2 N/A Are the chilled water pumps able to handle the capacity for this type of Carrier chiller model, 30RAP1156D-06314?
| Unknown if pumps can handle new chiller. Current pumps installed: Aurora centrifugal, No. 04-1069291, Type 341A BF, Size 2.5x3x9, GPM 207, Head feet 70, RPM 1750 / Motor: HP 7.5, RPM1750, 208-230/460 volt 3ph, Enclosed DP, Frame 213JM | ||||
| 4/27/17 | 3 | N/A | Who is the chemical treatment company that your base uses? | Brainerd Chemical, but we can use anyone. |
| 4/27/17 | 4 | N/A | Is the chilled water system chemical treatment maintained? | Yes, the chilled water system chemical treatment is maintained. |
| 4/27/17 | 5 | N/A | Are there any plans for your system that can be shared with us? | Plans for the system that can be shared - Not Available |
| 4/27/17 | 6 | N/A | Can I come and walk the site at a select scheduled time? | Please contact me at 918-833-7118 and we will arrange a site visit. |
| 4/27/17 | 7 | N/A | If I cannot come and walk the site, may we have a couple of photos of the chiller and associated piping from the pumps to the chiller? | |
| We will arrange a site visit but if you still need the photos we will work with our internal customer to arrange photos. |