CC-622-260-003A BCCC Mechanical Replacement @ LSB Bid Set Rev I - Bid Set - Drawings - signed.pdf
PDF 4 MB Posted
- Attached to
- CC-622-260-003A
- Solicitation number
- BPM059257
- Issued by
- Maryland
About this file
This is a bid set containing architectural and mechanical drawings for the Mechanical Replacement project at the Life Sciences Building (LSB) at Baltimore City Community College in Maryland, prepared under contract number CC-622-260-003A. The project involves the replacement of mechanical systems at the Life Sciences Building facility. The bid set documents, designated as Revision I, provide detailed technical drawings and specifications necessary for bidders to prepare competitive proposals for the mechanical replacement work. The drawings appear to be signed, indicating they represent finalized design documents ready for bidding purposes.
The document serves as the primary technical reference for contractors interested in bidding on this mechanical replacement project. Specific details regarding bid submission deadlines, site visit requirements, pre-bid meetings, contract award dates, and the contract term are not detailed within this drawing set itself, as bid sets typically focus on technical specifications and visual representations of the work scope. Contractors should reference the associated bid documents and solicitation materials for information regarding pricing requirements, bid deadlines, bonding requirements, insurance provisions, and other commercial terms governing the project delivery and contract execution.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mechanical Replacement at the
LIFE SCIENCES BUILDING
2901 Liberty Heights Avenue Baltimore, Maryland 21215
Department of General Services
PROJECT NO. CC-622-260-003
June 16 2026 Bid Set
VICINITY MAP
N
LOCATION MAP
N
MEP:
HENRY ADAMS, LLC
600 Baltimore Avenue, Suite 400 Baltimore, Maryland 21204 Phone: (410) 296-6500
COST ESTIMATING:
FORELLA GROUP, LLC
5180 Parkstone Dr., Suite 250 Chantilly, VA 20151 Phone: (703) 560-2200
STRUCTURAL ENGINEER:
ONYX DESIGN AND CONSULTING, LLC
55 S Queen St., Suite 01 York, PA 17403 Phone: (717) 852-1260
USING AGENCY APPROVAL
NAME DATE
TITLE
DEPARTMENT OF GENERAL SERVICES
APPROVAL
PROJECT MANAGER DATE
CHIEF ARCHITECT PROJ. MGMT. & DESIGN DATE
G-001
GENERAL COVER
SHEET
PROJECT SITE PROJECT SITE
THE CONTRACT DOCUMENTS
FOR THE INDICATED PUBLIC
IMPROVEMENT WERE
PREPARED UNDER BY
SUPERVISION AND, TO THE
BEST OF MY KNOWLEDGE,
INFORMATION AND BELIEF,
THEY COMPLY WITH THE
RELEVANT BUILDING CODES
OF THE STATE OF MARYLAND.
STATE OF MARYLAND
DEPARTMENT OF GENERAL SERVICES
ATIF CHAUDHRY, SECRETARY
301 WEST PRESTON STREET
BALTIMORE, MARYLAND 21201
BOARD OF PUBLIC WORKS
WES MOORE, GOVERNOR
BROOKE ELIZABETH LIERMAN, COMPTROLLER
DERECK E. DAVIS, TREASURER
SCOPE OF WORK:
REPLACE EQUIPMENT, COMPONENTS, AND UTILITIES
DAMAGED IN THE FIRE.
Michael Thomas (Jul 20, 2026 06:28:37 EDT) 07/20/2026
Vice President
07/20/2026
Courtney League (Jul 20, 2026 06:37:43 EDT) Courtney League 07/20/2026
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
G-002
CEL
G-002.DWG
DRAWING INDEX AND
GENERAL INFORMATION
APPLICABLE CODES AND STANDARDS
2021 INTERNATIONAL GREEN CONSTRUCTION CODE
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL FUEL GAS CODE
2017 INTERNATIONAL ELECTRICAL CODE
2019 ASHRAE 90.1
2019 DGS PROCEDURE MANUAL
DRAWING LIST
DRAWING TITLE
1 G-001 GENERAL COVER SHEET
2 G-002 DRAWING INDEX AND GENERAL INFORMATION
3 S-001 GENERAL NOTES AND LOADING INFORMATION
4 S-101 ROOF - STRUCTURAL - NEW WORK
5 P-001 PLUMBING COVER SHEET
6 PD-105 ROOF - PLUMBING - DEMOLTION
7 PD-301 PLUMBING PART PLANS - DEMOLITION
8 P-105 ROOF - PLUMBING - NEW WORK
9 P-301 PLUMBING PART PLANS - NEW WORK
10 P-501 PLUMBING DETAILS AND SCHEDULE
11 P-601 PLUMBING RISER DIAGRAMS
12 M-001 MECHANICAL COVER SHEET
13 MD-105 ROOF - DUCTWORK - DEMOLITION
14 MD-205 ROOF - MECHANICAL PIPING - DEMOLITION
15 MD-301 MECHANICAL PART PLANS - DEMOLITION
16 MD-302 MECHANICAL PART PLANS - DEMOLITION
17 MD-303 MECHANICAL PART PLANS - DEMOLITION
18 M-105 ROOF - DUCTWORK - NEW WORK
19 M-106 ROOF - DUCTWORK - NEW WORK
20 M-205 ROOF - MECHANICAL PIPING - NEW WORK
21 M-301 MECHANICAL PART PLANS - NEW WORK
22 M-302 MECHANICAL PART PLANS - NEW WORK
23 M-501 MECHANICAL DETAILS
24 M-701 AUTOMATIC TEMPERATURE CONTROLS
25 M-702 AUTOMATIC TEMPERATURE CONTROLS
26 M-703 AUTOMATIC TEMPERATURE CONTROLS
27 M-801 MECHANICAL SCHEDULES
28 E-001 ELECTRICAL COVER SHEET
29 E-002 ELECTRICAL COVER SHEET
30 ED-105 ROOF - ELECTRICAL - DEMOLITION
31 ED-301 ELECTRICAL PART PLANS - DEMOLITION
32 E-105 ROOF - ELECTRICAL - NEW WORK
33 E-301 ELECTRICAL PART PLANS - NEW WORK
34 E-601 ELECTRICAL RISERS
35 E-801 ELECTRICAL SCHEDULES
36 E-802 PANELBOARD SCHEDULES
37 E-803 MOTOR CONTROL CENTER SCHEDULES
38 E-804 MOTOR CONTROL CENTER SCHEDULES
39 E-805 MOTOR CONTROL CENTER SCHEDULES
EKD
PHASING NOTES
1. ALL PHASING SHALL BE COORDINATED WITH COR.
2. REPLACE FUEL OIL DAY TANK AND FUEL OIL PIPING PRIOR TO REPLACING THE
BOILERS AND DWH'S.
3. IF BOILER REPLACEMENT (INCLUDING ASSOCIATED PIPING, PUMPS, AND
ELECTRICAL REPLACEMENT) OCCURS WHEN OUTDOOR TEMPERATURE IS BELOW
80 DEGREES F, TEMPORARY BOILER(S) WILL BE REQUIRED. COORDINATE WITH
COR.
4. CHILLED WATER PIPE MAINS SHALL BE REPLACED OVER COR APPROVED
SHUTDOWNS. CHILLED WATER RUNOUTS TO CHILLERS SHALL OCCUR ONE AT A
TIME WHILE OTHER CHILLER(S) REMAIN OPERATIONAL.
5. REPLACE DWH'S OVER OWNER APPROVED SYSTEM SHUTDOWNS.
6. SEE MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL
PHASING REQUIREMENTS.
7. PHASING IS NOT REQUIRED FOR THE STRUCTURAL WORK, BUT INSTALLATION
SHALL BE COORDINATED WITH ALL MEP WORK.
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
DESIGN DATA
1. THE EXISTING FRAMING HAS BEEN EVALUATED FOR NEW LOADING BASED ON LOADS DICTATED BY THE 2021 BUILDING CODE, AND LOADS PROVIDED BY "NEW LIFE SCIENCES FACILITY" CONSTRUCTION
DRAWINGS, DATED 03/17/95.
2. NEW CONSTRUCTION LOADS:
A. ROOF LOADS:
a. DEAD LOAD = 20 PSF (SELF WEIGHT AND SUPERIMPOSED)
b. LIVE LOAD = 30 PSF
B. WIND LOAD:
a. BASIC WIND SPEED (3-SECOND GUST) = 113 MPH
b. WIND IMPORTANCE FACTOR, Iw = 1.0
c. RISK CATEGORY = II
d. EXPOSURE CATEGORY = C
e. INTERNAL PRESSURE COEFFICIENT, GCpi = ±0.18
f. WIND DESIGN PRESSURE = 33 PSF
C. SNOW LOAD:
a. MINIMUM DESIGN SNOW LOAD = 30 PSF
b. GROUND SNOW LOAD, Pg = 25 PSF
c. BALANCED ROOF SNOW LOAD, Pb = 17.5 PSF
d. SNOW EXPOSURE FACTOR, Ce = 1.0
e. SNOW LOAD IMPORTANCE FACTOR, Is = 1.0
f. THERMAL FACTOR, Ct = 1.0
D. EARTHQUAKE DESIGN DATA:
a. RISK CATEGORY = II
b. SEISMIC IMPORTANCE FACTOR, Ie = 1.0
c. MAPPED SPECTRAL RESPONSE ACCELERATIONS:
1) Ss = 0.141
2) S1 = 0.043
d. SITE CLASS = D
e. SPECTRAL RESPONSE COEFFICIENTS:
1) SDS = 0.151
2) SD1 = 0.069
f. SEISMIC DESIGN CATEGORY = B
g. BASIC SEISMIC FORCE-RESISTING SYSTEM = LIGHT-FRAME (COLD-FORMED STEEL)
WALLS SHEATHED WITH STEEL PANELS
h. DESIGN BASE SHEAR = .021W
i. SEISMIC RESPONSE COEFFICIENT, Cs = 0.021
j. RESPONSE MODIFICATION FACTOR, R = 2.5
k. ANALYSIS PROCEDURE = EQUIVALENT LATERAL FORCE PROCEDURE
STRUCTURAL SPECIFICATIONS AND GENERAL CONDITIONS
1. WHERE THESE SPECIFICATIONS CONFLICT WITH OTHER PROJECT SPECIFICATIONS, THESE
SPECIFICATIONS SHALL GOVERN.
2. ONYX DESIGN & CONSULTING WILL ASSUME NO RESPONSIBILITY AND/OR LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS, AND THE DESIGN INTENT THEY CONVEY OR FOR PROBLEMS WHICH ARISE FROM OTHERS’ FAILURE TO OBTAIN AND/OR FOLLOW
THE ENGINEER’S GUIDANCE.
3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH LOCAL APPLICABLE CODES AND
REGULATIONS AND APPROPRIATE SAFETY MEASURES SATISFYING LOCAL AND OSHA REQUIREMENTS
SHALL BE PROVIDED.
4. PROPER TEMPORARY BRACING AND SHORING OF ALL CONSTRUCTION WORK IN PROGRESS IS THE CONTRACTOR’S RESPONSIBILITY. THE CONTRACTOR SHALL SUBMIT ENGINEERED DRAWINGS THAT BEAR THE STAMP AND SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE
STATE IN WHICH THE PROJECT IS LOCATED TO THE OWNER FOR REVIEW AND APPROVAL.
5. IF DURING DEMOLITION EXISTING CONDITIONS DO NOT AGREE WITH INFORMATION SHOWN ON THE
DESIGN DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE LOCATION AND PROTECTION OF ALL EXISTING
UTILITIES DURING CONSTRUCTION AND THE REPAIR OF ANY DAMAGED FACILITIES.
7. SECTIONS AND DETAILS SHOWN, WHILE DRAWN FOR SPECIFIC LOCATIONS, ARE INTENDED TO
ESTABLISH THE GENERAL TYPES OF DETAILS TO BE USED THROUGHOUT.
8. DRAWINGS SHOULD NOT BE SCALED. CONTACT THE ENGINEER FOR CLARIFICATION OF ANY
DIMENSION IN QUESTION.
9. ANCHOR BOLT LAYOUT SHALL BE PERFORMED UNDER THE DIRECTION OF A PROFESSIONAL LAND
SURVEYOR.
10. ALL DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. LAYOUT SHALL BE CHECKED AND
COORDINATED BETWEEN ALL CONSTRUCTION DOCUMENTS AND SPECIFICATIONS PRIOR TO THE
START OF WORK.
11. SHOP DRAWINGS PREPARED BY THE SUBCONTRACTORS, SUPPLIERS, ETC. SHALL BE REVIEWED BY THE ENGINEER FOR CONFORMANCE WITH DESIGN CONCEPT ONLY. EACH SHOP DRAWING SUBMITTED
SHALL BE STAMPED, INITIALED AND DATED AS BEING REVIEWED BY THE CONSTRUCTION
MANAGER/GENERAL CONTRACTOR. WORK SHALL NOT BEGIN WITHOUT THE REVIEW BY THE
ENGINEER.
12. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW OR RECORD SHALL BEAR THE STAMP AND SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE
STATE IN WHICH THE PROJECT IS LOCATED.
STRUCTURAL STEEL
1. ALL STEEL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, (AISC 360), THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, THE CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, (AISC 303) AND
THE AISC STEEL CONSTRUCTION MANUAL, 16TH EDITION.
2. ALL WELDING SHALL BE PERFORMED IN ACCORDANCE WITH THE REQUIREMENTS OF THE AWS D1.1 STRUCTURAL WELDING CODE -STEEL, LATEST EDITION, AND AISC SPECIFICATIONS USING THE PROPER ELECTRODE FROM AWS D1.1 TABLE 3.1 AND PERFORMED ONLY BY QUALIFIED WELDERS.
3. STRUCTURAL STEEL SHALL CONFORM TO THE REQUIREMENTS OF ASTM A992, WITH A MINIMUM YIELD STRESS OF 50 KSI FOR ALL WIDE FLANGE AND WT SHAPES. ALL OTHER SHAPES, MISCELLANEOUS
PLATES, AND CONNECTION MATERIAL SHALL CONFORM TO ASTM A36.
4. SQUARE OR RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A500, GRADE C, WITH A MINIMUM YIELD STRESS OF 50 KSI.
5. ROUND HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO THE REQUIREMENTS OF ASTM
A500, GRADE C, WITH A MINIMUM YIELD STRESS OF 50 KSI.
6. STRUCTURAL STEEL PIPE SHALL CONFORM TO THE REQUIREMENTS OF ASTM A53, TYPE S, GRADE B, WITH A MINIMUM YIELD STRESS OF 35 KSI.
7. SHOP DRAWINGS FOR THE FABRICATION AND ERECTION OF ALL STRUCTURAL STEEL SHALL BE
SUBMITTED TO AND APPROVED BY THE ENGINEER PRIOR TO FABRICATION.
8. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY FABRICATION OR ERECTION ERRORS OR
DEVIATIONS AND RECEIVE WRITTEN APPROVAL BEFORE FIELD CORRECTIONS ARE MADE.
9. BOLTED CONNECTIONS OF STRUCTURAL STEEL SHALL BE MADE USING HIGH STRENGTH STEEL BOLTS
CONFORMING TO ASTM A325. BOLTS SHALL BE ¾” DIAMETER U.N.O.
10. SIMPLE SHEAR CONNECTIONS SHALL BE STANDARD DOUBLE ANGLES U.N.O. ALL BOLTED
CONNECTIONS SHALL HAVE MINIMUM 2 BOLTS.
11. ALL HIGH STRENGTH BOLTS SHALL BE SNUG TIGHT U.N.O. A SNUG TIGHT CONDITION IS AS DEFINED IN
SECTION 1.2.2 IN THE AISC DESIGN GUIDE 16.
12. ANCHOR BOLTS SHALL BE HEADED BOLTS THAT CONFORM TO THE REQUIREMENTS OF ASTM F1554, WITH A MINIMUM YIELD STRENGTH OF 36 KSI U.N.O. BOLTS SHALL BE ¾” IN DIAMETER U.N.O. ALL
COLUMNS SHALL HAVE A MINIMUM OF 4 ANCHOR BOLTS U.N.O.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE TEMPORARY BRACING OF ALL STEEL DURING
ERECTION AND UNTIL CONSTRUCTION IS COMPLETE.
14. THE CONTRACTOR SHALL FURNISH ALL PLATES, CLIP AND SEAT ANGLES, AND CONNECTIONS FOR COMPLETION OF THE STRUCTURE, EVEN IF SUCH ITEMS ARE NOT SPECIFICALLY CALLED FOR ON THE
STRUCTURAL DRAWINGS.
15. STRUCTURAL AND MISCELLANEOUS STEEL FABRICATORS SHALL BE RESPONSIBLE FOR OBTAINING ALL
FIELD DIMENSIONS NECESSARY FOR THE COMPLETION OF THEIR WORK.
16. MINIMUM SIZE OF FILLET WELDS IS TO BE 3/16" FILLET U.N.O. CHIP, WIRE BRUSH CLEAN, AND PRIME
PAINT ALL FIELD WELDS.
17. SUMMARY OF PAINT SYSTEM (REFERENCE STEEL STRUCTURES PAINTING COUNCIL - A GUIDE TO THE SHOP PAINTING OF STRUCTURAL STEEL). COORDINATE PAINT REQUIREMENTS WITH ARCHITECTS
SPECIFICATIONS:
A. FOR ALL WORK TEMPORARILY EXPOSED TO WEATHER FOR SIX (6) MONTHS OR LESS: NO PAINT
B. FOR ALL WORK TEMPORARILY EXPOSED TO WEATHER FOR GREATER THAN SIX (6) MONTHS:
1) SURFACE PREPARATION = SSPC-SP 2
2) PRETREAT = NONE REQUIRED
3) PAINT APPLICATION = SSPC-PA 1
4) NUMBER OF COATS = ONE
5) PRIMER = SSPC-PAINT 15
6) TOUCH-UP = AS PER MANUFACTURER SPECIFICATIONS
7) DRY FILM = 2.0 MILS
C. FOR ALL WORK PERMANENTLY EXPOSED TO WEATHER:
1) SURFACE PREPARATION = SSPC-SP 3
2) PRETREAT = NONE REQUIRED
3) PAINT APPLICATION = SSPC-PA 1
4) NUMBER OF COATS = THREE MINIMUM
5) PRIMER = SSPC-PAINT 25
6) TOUCH-UP = AS PER MANUFACTURER SPECIFICATIONS
7) 2ND COAT = SSPC PAINT 21
8) FINISH COAT = SSPC PAINT 21
9) DRY FILM THICKNESS = FIRST COAT= 1.5 TO 2.0 MILS
SECOND COAT= 2.0 MILS
FINISH COAT= 2.0 MILS
TOTAL = 5.5 TO 6.0 MILS
D. SURFACES WITHIN 2" OF WELDS SHALL BE FREE OF MATERIAL THAT WOULD PREVENT PROPER
WELDING OR PRODUCE OBJECTIONABLE FUMES WHILE WELDING IS BEING DONE.
STRUCTURAL ENGINEERING
ONYX DESIGN AND CONSULTING, LLC
1215 E FORT AVE, SUITE 200
BALTIMORE, MD 21230
(717) 852-1261
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
06/16/2026
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
MPG
RLB
PROFESSIONAL CERTIFICATION: I HEREBY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO. 47011, EXPIRATION DATE: 07/08/2027
S-001
GENERAL NOTES AND LOADING
INFORMATION
BID S
SHEET 3 OF 39
BID SET
W8X13
S-101
S-101
E
F
G
D.6
D
111098 12
V.I.F.
8' - 11"
20' - 0" 20' - 0" 20' - 0" 20' - 0"
HSS3x3x1/4, TYP.
EX. SCREEN WALL
AND ROOFTOP
CHILLERS, TYP.
EX. HSS TRUSS, TYP.
W8X13
V .I .F
V .I
.F
V .I .F
2' - 0" 12' - 0" 7' - 0" 5"
W4X13 ROOF BM @ EA. EX. HSS
TRUSS, TYP. (SEE NOTE 1)
NOTES:
1. CONTRACTOR OPTION TO PROVIDE LL4X3X5/16" AS ROOF BEAM.
2. DO NOT SUSPEND EQUIPMENT FROM ROOF MEMBERS.
3. PROVIDE SUPPORT FROM BELOW FOR ALL DUCTS, CONDUITS,
AND EQUIPMENT.
S-101
E
F
G
D.6
D
111098
20' - 0" 20' - 0" 20' - 0" 20' - 0"
V.I.F.
8' - 11"
EX. ABANDONED
DUNNAGE, SEE MECH.
EX. ABANDONED
DUNNAGE, SEE MECH.
BOILER, SEE MECH.
EX. SCREEN WALL
AND ROOFTOP
CHILLERS, TYP.
V .I
.F
V .I .F
V .I .F
V .I .F
V .I
.F
BOILER, SEE MECH.
EX. BOILER CURB, TYP., V.I.F.
EX. 12" MASONRY CURB,
TYP. AT INTERIOR, V.I.F.
EX. MECH. PLATFORM
STEEL CURB, V.I.F.
EX. 8" MASONRY CURB,
TYP. AT EXTERIOR, V.I.F.
2' - 0" 12' - 0" 5"
EX. STEEL
PLATE, V.I.F.
NOTES:
1. MISCELLANEOUS PIPE AND MECHANICAL
EQUIPMENT SUPPORTS NOT SHOWN FOR CLARITY
S-101
HSS3x3x1/4, TYP.
S-101
V A
R
IE
S
ROOF BM, SEE PLAN
EX. TRUSS BTM CHORD & WEB
EX. TRUSS TOP CHORD
1/8
TYP. @ EA.
PURLIN
EX. INSULATION
EX. SHEATHING, V.I.F.
EX. LIGHT GAUGE
PLATE, V.I.F.
EX. PURLIN ON 2' - 0" GRID
NOTES:
1. CONTRACTOR OPTION TO PROVIDE LL4X3X5/16"
AS ROOF BEAM.
2. CONTRACTOR MAY INSTALL ROOF BEAM ON
EITHER SIDE OF EXISTING TRUSS.
3. CONTRACTOR TO VERIFY IN FIELD PURLIN TO
TRUSS CONNECTION ARE ADEQUATE.
EX. CONN. OF PURLIN TO TRUSS
ROOF GIRDER, SEE PLAN
3/8" SHEAR TAB, TYP.
3/16
CL OF GIRDER =
CL OF EX. MECH PLATFORM STEEL CURB =
CL OF EX. MASONRY CURB
EX. TRUSS NOT
SHOWN FOR CLARITY
ROOF BM, SEE PLAN
3/8" GUSSET PL, TYP.
EX. INSULATION
EX. SHEATHING, V.I.F.
EX. LIGHT GAUGE
PLATE, V.I.F.
EX. PURLIN ON 2' - 0" GRID
ROOF GIRDER, SEE PLAN
3/16
CL
1/2" THK x 0' - 5" SQ
A36 STL BPL.
EX. PURLIN ON 2' - 0" GRID
EX. TRUSS NOT
SHOWN FOR CLARITY
HSS3x3x1/4 COL, SEE PLAN
EX. INSULATION
EX. SHEATHING, V.I.F.
EX. LIGHT GAUGE
PLATE, V.I.F.
EX. 12" MASONRY CURB, V.I.F.
EX. MECH. PLATFORM STEEL
CURB, V.I.F.
EX. STEEL PLATE, V.I.F.
3/16
1/4" CAP PLATE, TYP.
GC TO PROVIDE
SHIMS AS REQ'D
3/8" SHEAR TAB, TYP.
CL
1/2" THK x 0' - 5" SQ
A36 STL BPL.
HSS3x3x1/4 COL, SEE PLAN
EX. 12" MASONRY CURB, V.I.F.
EX. MECH. PLATFORM STEEL
CURB, V.I.F.
EX. STEEL PLATE, V.I.F.
3/16
GC TO PROVIDE SHIMS
AS REQ'D
STRUCTURAL ENGINEERING
ONYX DESIGN AND CONSULTING, LLC
1215 E FORT AVE, SUITE 200
BALTIMORE, MD 21230
(717) 852-1261
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
06/16/2026
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
MPG
RLB
PROFESSIONAL CERTIFICATION: I HEREBY CERTIFY THAT
THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MARYLAND.
LICENSE NO. 47011, EXPIRATION DATE: 07/08/2027
S-101
ROOF - STRUCTURAL - NEW WORK
BID SUBMISSION
SCALE: 1/8" = 1'-0"S-101
2 MECH. PENTHOUSE ROOF FRAMING PLAN
SCALE: 1/8" = 1'-0"S-101
1 MECH. PENTHOUSE PLATFORM FRAMING PLAN
SCALE: 1" = 1'-0"S-101
6 SECTION AT NEW ROOF BEAM - HSS
PLAN NOTES:
1. EXISTING CONDITIONS ARE BASED ON LIMITED SITE OBSERVATIONS BY ONYX ON 3/20/2026, AND BY "NEW LIFE SCIENCES FACILITY" CONSTRUCTION DRAWINGS, DATED 03/17/95. CONTRACTOR SHALL CONTACT E.O.R. IF FIELD CONDITIONS DIFFER FROM THAT SHOWN ON DESIGN DOCUMENTS.
2. ALL DIMENSIONS WITH RESPECT TO EXISTING CONDITIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION OF ANY STRUCTURAL FRAMING MEMBERS.
3. TEMPORARY SHORING OF EXISTING FRAMING SHALL BE THE CONTRACTOR'S RESPONSIBILITY. CONTRACTOR SHALL CONTACT E.O.R. IMMEDIATELY IF ANY
EXISTING WALL IS FOUND TO BE LOAD BEARING AND DIFFERS FROM EXISTING CONDITIONS SHOWN.
4. ALL ELEVATIONS SHOWN THUS (+X' - X") ARE REFERENCED TO TOP OF MECHANICAL PENTHOUSE FLOOR ELEVATION 420.71' (0' - 0"). CONTRACTOR TO VERIFY IN
FIELD.
5. TOP OF EXISTING PENTHOUSE ROOF STEEL FRAMING IS ASSUMED TO BE (+11' - 0"), V.I.F.
6. ALL NEW HSS POST TO BE ANCHORED TO THE MECHANICAL PENTHOUSE FLOOR SHALL BE ATTACHED AT LOCATIONS WHERE BEARING ALIGNS ONTO MASONRY
CURB WALLS BELOW, V.I.F..
7. ALL WORK PERFORMED SHALL MAINTAIN THE EXISTING ROOFING INSULATION AND WATERPROOFING SYSTEM AND REPAIRS MADE WHERE REQUIRED.
SCALE: 1" = 1'-0"S-101
5 SECTION AT NEW ROOF GIRDER
SCALE: 1" = 1'-0"S-101
4 SECTION AT NEW ROOF GIRDER
SCALE: 1" = 1'-0"S-101
3 SECTION AT NEW COLUMN BEARING
SHEET 4 OF 39
BID SET
AS AIR SEPARATOR
BFP BACKFLOW PREVENTER
BLR BOILER
BWF BYPASS WATER FILTER
COR CONTRACTING OFFICERS REPRESENTATIVE
CW COLD WATER
CX CONNECT TO EXISTING
D DAMPER/DEEP / DRAIN / DIAMETER
DIA DIAMETER
DN DOWN
DT DAY TANK
DWG DRAWING
DWH DOMESTIC WATER HEATER
ELEV ELEVATOR
ELEC ELECTRICAL
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EX EXISTING
FCU FAN COIL UNIT
FD FLOOR DRAIN
FLR FLOOR
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FT FEET / FOOT
G GAS
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT / HIGH
HB HOSE BIBB
HW HOT WATER
HWR HOT WATER RETURN
HZ HERTZ
IN INCH
L LENGTH
LWT LEAVING WATER TEMPERATURE
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MIN MINIMUM
N NORTH
NO NUMBER
P PLUMBING/PUMP
PD PLUMBING DEMOLITION
PH PHASE
RX REMOVE EXISTING
S SANITARY
SG STEAM GENERATOR
STM STEAM
T TEMPERATURE SENSOR
TYP TYPICAL
W WIDTH / WASTE / WATTS / WIDE
V VOLTS
GENERAL NOTES:
(APPLICABLE TO ALL PLUMBING DRAWINGS)
1. THE LOCATION OF EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES
OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES.
2. RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED. HORIZONTAL
VENT PIPING SHALL BE GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY GRAVITY.
3. ELEVATIONS NOTED ARE TO CENTERLINES OF PIPES FOR ALL PRESSURE LINES AND TO INVERT
FOR ALL GRAVITY FLOW LINES.
4. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE
FOR INSULATION IF REQUIRED.
5. INSTALL PIPING SO THAT ALL VALVES ARE ACCESSIBLE.
6. COORDINATE ALL PLUMBING WORK WITH FIRE PROTECTION WORK, MECHANICAL WORK,
ELECTRICAL WORK, AND WORK OF OTHER TRADES, SHOWN ON OTHER DRAWINGS.
7. MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL AND ELECTRICAL ROOMS.
8. CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.
9. WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES
REQUIRE CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO CHECK FOR THE PRESENCE OF EXISTING MECHANICAL AND/OR ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION AND EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO HIS PERSONNEL
DUE TO CONTACT WITH SAME. WHERE PRACTICAL, SUCH EXISTING SERVICES SHALL BE
TEMPORARILY DISCONNECTED DURING THE CUTTING OPERATION. SUCH OUTAGES IN SERVICE SHALL
BE SCHEDULED IN ADVANCE WITH THE COR.
10. FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT. VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. ADDITIONAL VALVES, PRESSURE GAUGES, ETC. SHALL BE PROVIDED AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON
FLOW SCHEDULES AND RISER DIAGRAMS.
11. INFORMATION SHOWN ON THE PLUMBING DRAWINGS PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS
AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING
CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR
PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF
WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE
COR IN WRITING AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
12 REMOVE ALL EXISTING PIPING, FIXTURES, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR
RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND
EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO
REMAIN THE PROPERTY OF GOVERNMENT SHALL BE DELIVERED BY THE CONTRACTOR WHERE
DIRECTED BY THE COR. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL
BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR
FROM THE PREMISES.
13. DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR
OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR
NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR
SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO
EXISTING PIPING SHALL BE LEFT UNSEALED VALVE ALL TERMINATED PRESSURE PIPE.
14 EXISTING PLUMBING PIPING, FIXTURES, EQUIPMENT, AND MATERIALS AFFECTED BY
DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE
RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL
WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE COR AND AT NO ADDITIONAL
CONTRACT COST.
15. ALL PIPING AND EQUIPMENT WITHIN THE PENTHOUSE SHALL BE SUPPORTED FROM THE FLOOR.
PLUMBING ABBREVIATIONS
(APPLICABLE TO ALL PLUMBING DRAWINGS)
SYMBOL DESCRIPTION
HW
FOS
D
P-100
PLUMBING LEGEND
(APPLICABLE TO ALL PLUMBING DRAWINGS)
DRAIN PIPING
HOT WATER
FUEL OIL SUPPLY
CONNECT TO EXISTING
END OF DEMOLITION
SHUTOFF VALVE
SECTION DESIGNATION
TOP - SECTION REFERENCE
BOTTOM - REFERENCED DRAWING
HOSE BIBB
FLOOR DRAIN
CW COLD WATER
FOR FUEL OIL RETURN
G GAS
STM STEAM
HWR HOT WATER RETURN
CAP (PIPE OR DUCT)
THERMOMETER
UNION
RELIEF VALVE
PLUMBING DESIGN CRITERIA
TOTAL BUILDING DOMESTIC WATER DEMAND: 800 GPH
DESIGN HOT WATER LOAD: 798 MBH
MAXIMUM DESIGN NATURAL GAS CONSUMPTION: 8,558 MBH
MAXIMUM DESIGN FUEL OIL CONSUMPTION: 66 GPH
CHECK VALVE
STRAINER
PRESSURE GAUGE
BALANCING VALVE
SOLENOID VALVE
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
P-001
P-001.DWG
PLUMBING COVER SHEET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed
MECH
PENTHOUSE
PD-301
ROOF ROOF
ROOF
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
PD-101
ROOF - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0" 0 4 16 24 FT8
1/8" = 1' - 0"
N
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY DASHED WEIGHT LINE,
3. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS
BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL
OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK.
SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS
INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF
DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING
AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
PD-105
PD-105.DWG
ROOF - PLUMBING -
DEMOLITION
EX WATER
SYSTEM AND
TANKS
EX AIR TANK
SYSTEM
EX FCU
MECH
PENTHOUSE
EX ABANDONED
DUNNAGE
EX ABANDONED
DUNNAGE
RX AS
RX SG-1
EX P-2 EX P-1
EX ABANDONED
DUNNAGE
EX LAB
AIR
SYSTEM
EX P-7
EX P-8
EX BWF
RX FCU-2
EX 4" G DN
RX 4"
RX 2"
RX
G
EX 2" HW DN
EX 1" HWR DN
EX 3" CW DN
EX CW DN TO AIR COMPRESSOR
EX
H
W
EX
C
W
EX HW
EX HWR
EX CW
RX BFPEX CW
EX CW
RX
C
W
RX HB
RX
C
W
EX
C
W
EX
H
WR
EX STM
EX HW
EX CW
EX CW
EX HW
EX STM
EX CW
EX HW
EX STM
EX FD
EX FD
EX FD
EX FD
EX FD
EX FD
EX FD EX FD
EX FD EX FD
EX FDEX FD
EX
D
EX D ON FLR
EX
D
EX HB
RX BLR-2
RX BLR-1EX
H
WR
RX G
RX FOSRX FOR
RX CW
EX ABANDONED
DUNNAGE
EX HWR
PUMP
(PMP-13)
EX FD
EX
S
TM
EX
C W
EX COLD ROOM
CONDENSING UNITS
RX 3"
RX 3/4"
RX 3/4"
RX 3"
RX 3/4"
EX HEATING COIL
EX COOLING COIL
EX HEATING COIL
EX COOLING COIL
EX HUMIDIFIERS
EX STM
EX HUMIDIFIER
EX STM
RX FCU-3
RX DWH-1
RX DWH-224
RX FUEL OIL DAY TANK
EX
H
W 3
EX FOS/FOR DN
CAP
RX D
EX D
EX D
RX D
RX FLASH TANK5
RX 3" D RX 1" CW
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
PD-301
PENTHOUSE - PLUMBING - ENLARGED PLAN - DEMOLITION PLAN
3/16" = 1'-0"
N
0 2 8 12 FT4
3/16" = 1' - 0"
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY DASHED WEIGHT LINE,
3. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS
BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR
DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING
CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD
CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS
INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF
DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING
AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
4. COORDINATE ALL DOMESTIC WATER SHUTDOWNS WITH COR.
5. COORDINATE ALL PHASING WITH COR.
5.1. REPLACE FUEL OIL DAY TANK AND FUEL OIL PIPING PRIOR TO REPLACING
BOILERS AND DWH'S.
5.2. REPLACE DWH'S OVER OWNER APPROVED SYSTEM SHUTDOWNS.
6. PRESSURE TEST ALL EXISTING DOMESTIC WATER PIPING WITHIN PENTHOUSE.
PROVIDE AN ALLOWANCE TO REPLACE ANY JOINTS AS REQUIRED.
SEE MECHANICAL DRAWINGS FOR MORE INFORMATION.
EXISTING DRAIN PAN TO REMAIN.
COORDINATE PHASING OF BOILER REPLACEMENT WITH COR.
COORDINATE PHASING OF DWH REPLACEMENT WITH COR.
RX VENT UP TO 6" BELOW ROOF AND CAP. ENSURE THE EXISTING ROOF
PENETRATION IS SEALED AIR AND WATER TIGHT.
VALVE AND CAP.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
PD-301
PD-301.DWG
PLUMBING PART PLANS -
DEMOLITION
P-301
ROOF ROOF
ROOF
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
P-105
ROOF - PLUMBING - NEW WORK PLAN
1/8" = 1'-0" 0 4 16 24 FT8
1/8" = 1' - 0"
N
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
P-105
CEL
P-105.DWG
ROOF - PLUMBING - NEW
WORK
EKD
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed
EX WATER
SYSTEM AND
TANKS
EX AIR TANK
SYSTEM
EX FCU
MECH
PENTHOUSE
EX ABANDONED
DUNNAGE
EX ABANDONED
DUNNAGE
AS
EX ET
EX P-2 EX P-1
EX ABANDONED
DUNNAGE
EX LAB
AIR
SYSTEM
EX P-7
EX P-8
EX BWF
FCU-2
EX 4" G DN
4"
2"
G
EX 2" HW DN
EX 1" HWR DN
EX 3" CW DN
EX CW DN TO AIR COMPRESSOR
EX
H
W
EX
C
W
EX HW
EX HWR
EX CW
BFP-1EX CW
EX CW
CW
HB
CW
EX STM
EX HW
EX CW
EX CW
EX HW
EX STM
EX CW
EX HW
EX STM
EX FD
EX FD
EX FD
EX FD
EX FD
EX FD
EX FD EX FD
EX FD EX FD
EX FDEX FD
D
EX D ON FLR
D
EX HB
BLR-2
BLR-1
EX
H
W
EX
C W
EX
H
WR
G
FOSFOR
CW
EX ABANDONED
DUNNAGE
EX HWR
PUMP
(PMP-13)
EX FD
EX
S
TM
EX
C W
EX COLD ROOM
CONDENSING UNITS
3"
3/4"
3/4"
3"
3/4"
EX HEATING COIL
EX COOLING COIL
EX HEATING COIL
EX COOLING COIL
EX HUMIDIFIERS
EX STM
EX HUMIDIFIER
EX STM
24 DWH-2DWH-1
FCU-3
DT-1
EX
H
WR
FO
R
FO
S
EX 3/4" FOS/R DN
3/4"
2 4
1" D
EX D
1" D
EX D
1-1/2" CW
3/4"
3/4"
7 7 Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
P-301
PENTHOUSE - PLUMBING - ENLARGED PLAN - NEW WORK
3/16" = 1'-0"
N
0 2 8 12 FT4
3/16" = 1' - 0"
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS
BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR
DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING
CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD
CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS
INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF
DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING
AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
4. COORDINATE ALL DOMESTIC WATER SHUTDOWNS WITH COR.
5. COORDINATE ALL PHASING WITH COR.
5.1. REPLACE FUEL OIL DAY TANK AND FUEL OIL PIPING PRIOR TO REPLACING
BOILERS AND DWH'S.
5.2. REPLACE DWH'S OVER OWNER APPROVED SYSTEM SHUTDOWNS.
6. ALL PIPING AND EQUIPMENT WITHIN THE PENTHOUSE SHALL BE SUPPORTED FROM
THE FLOOR.
7. PRESSURE TEST ALL EXISTING DOMESTIC WATER PIPING WITHIN PENTHOUSE.
PROVIDE AN ALLOWANCE TO REPLACE ANY JOINTS AS REQUIRED.
SEE MECHANICAL DRAWINGS FOR MORE INFORMATION
MOUNT IN EXISTING DRAIN PAN.
COORDINATE PHASING OF BOILER REPLACEMENT WITH COR
COORDINATE PHASING OF DWH REPLACEMENT WITH COR
MOUNT ON FLOOR.
SEAL PIPE PENETRATIONS THROUGH WALL.
NEW STRUCTURAL COLUMN. ROUTE PIPING AROUND COLUMN.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
P-301
P-301.DWG
PLUMBING PART PLANS -
NEW WORK
at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
GAS VENT TO OUTDOORS
REGULATOR
PRESSURE GAGE
CONCENTRIC REDUCER CONTROL LINE
RELIEF VALVE
RELIEF
VENT
TO
OUTDOORS
TEST PORT
G
GAS PRESSURE REGULATOR PIPING
NOTE: EXTEND REGULATOR VENT AND RELIEF VENT TO OUTDOORS INDEFINITELY. TERMINATE VENTS IN ACCORDANCE WITH CODE REQUIREMENTS FOR CLEARANCES FROM LOT LINES, WALKWAYS, OUTDOOR AIR INTAKES (NATURAL AND MECHANICAL), OPERABLE OPENINGS, ETC., VENT SIZING AND QUANTITY BY
REGULATOR MANUFACTURER.
HWR
CW
140 HW
12"
DWH-1
0 H W
NO
1/2" HB
G
1-1/2"
DRAIN, PIPE TO NEAREST FLOOR DRAIN
VACUUM RELIEF VALVE. INSTALL ABOVE
THE TOP OF THE WATER HEATER.
T
CWHW
R
THERMOMETER,
TYPICAL (TYP)
12"
FULL SIZE DIRT LEG TYP)
GAS TRAIN (TYP)
TEMPERATURE AND PRESSURE
RELIEF VALVE (TYP)
PIPE TO NEAREST
FLOOR DRAIN, TYPICAL (TYP)
DWH-2
0 H
W
NO
1/2" HB
G
1-1/2"
3/4"
CWHW
R
SPECIAL NOTE:
1 GAS RELIEF VENT TO OUTDOORS. QUANTITY AND SIZE AS REQUIRED FOR GAS TRAIN.
1.
GENERAL NOTE:
MAINTAIN MANUFACTURER'S REQUIRE CLEARANCE
ABOVE AND ON ALL SIDES OF WATER HEATER.
1-1/2"
EX 140 HW
140 HW
DUAL-FIRED DOMESTIC WATER HEATER PIPING
GENERAL NOTES: (APPLICABLE TO ALL PLUMBING SCHEDULES)
1. UNIT NUMBERS ARE INDICATED WHERE ALL UNITS ARE LISTED AND NUMBERED
INDIVIDUALLY.
2. UNIT SYMBOLS ARE INDICATED WHERE ALL UNITS ARE NOT LISTED AND NUMBERED
INDIVIDUALLY.
3. UNIT TYPES ARE DESCRIBED IN THE SPECIFICATIONS.
4. TEMPERATURE VALUES ARE LISTED IN DEGREES FAHRENHEIT.
5. FLUID PRESSURE VALUES ARE LISTED IN FEET OF WATER GAGE.
6. PIPE SIZES ARE LISTED IN SINGLE-NUMBER INCHES OF NOMINAL DIAMETER OR MULTIPLE
NUMBER INCHES OF INDICATED PARAMETER. CONNECTION SIZES ARE BRANCH SIZES FROM
MAINS TO UNIT INLETS. SINGLE PIPE SIZE IS TYPICAL FOR SUPPLY AND RETURN.
REPLACE TEMPERATURE SENSOR. CONNECT TO BAS, TYP.
EX 1" HWR
EX 2" CW
EX 2" 140 HW
3/4"
P-501
P-501.DWG
PLUMBING DETAILS AND
SCHEDULES
COMBUSTION AIR INTAKE
DAMPER (D-1), TYP OF 2
2. WHEN A DWH IS ENERGIZED, D-1 SHALL OPEN. SEE DWG
M-701 FOR MORE INFORMATION.
FOS/R FOS/R
(5.0 GPM)
(5.0 GPM)
EX PUMP-13. REBALANCE TO 10 .0 GPM
EX DRAIN PAN EX DRAIN PAN
VENT CONNECTION
RUPTURE BASIN
3/4" FOS
3/4" FOR
TANK FILL
OVERFLOW
TANK DRAIN
RUPTURE BASIN DRAIN. PIPE TO
NEAREST FLOOR DRAIN
VENT CONNECTION
3/4" FOS 3/4" FOR
TANK FILL OVERFLOW
RUPTURE BASIN DRAIN. PIPE TO
NEAREST FLOOR DRAIN
SIDE VIEW
TOP VIEW
DAY TANK DETAIL
PITCH
DEPTH OF SEAL AS
REQUIRED TO OVERCOME
OPERATING STATIC
PRESSURE DIFFERENTIAL.
SIZE AS INDICATED,
EXCEPT NO SMALLER
THAN DRAIN PAN
NIPPLE.
CLEANOUT PLUG
PER
MANUFACTURER'S
REQUIREMENT
DRAIN PAN
FCU CONDENSATE DRAIN TRAP
ROOF ROOF
PENTHOUSE PENTHOUSE
BLR-1
(4,119 CFH)
G
EX
G
EX 4"
4"
3"
2"
14"1 PSI BLR-1
(4,119 CFH)
3"
14"1 PSI DWH-2
(399 CFH)
1"
14"1 PSI DWH-2
(399 CFH)
1"
14"1 PSI
ROOF ROOF
PENTHOUSE PENTHOUSE
DT-1
DWH-1EX
FO
S
EX
FO
R
FOS
FOREX 3/4"
3/4" 3/4" 3/4"
3/4"
DWH-2
3/4"
BLR-2
3/4"
BLR-1
3/4"
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
P-601
NATURAL GAS RISER DIAGRAM
NOT TO SCALE
P-601
FUEL OIL RISER DIAGRAM
NOT TO SCALE
P-601
PLUMBING RISER
DIAGRAMS
at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
GENERAL MECHANICAL NOTES
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
1. COORDINATE ALL MECHANICAL WORK WITH PLUMBING WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES SHOWN ON OTHER DRAWINGS.
2. RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED.
3. INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE PER INTERNATIONAL MECHANICAL CODE SECTION 306.
4. UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AND DUCTWORK OVERHEAD, TIGHT TO UNDERSIDE OF SLAB OR STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.
5. MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL AND
ELECTRICAL ROOMS.
6. CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN DUCTWORK AND PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC
LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.
7. WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE
CUTTING OPERATION. SCHEDULE SERVICE OUTAGES IN ADVANCE WITH THE COR.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS.
INCLUDE THIS INFORMATION IN THE OUTAGE PLAN AND SUBMIT TO COR FOR APPROVAL.
9. PROVIDE AN AUTOMATIC AIR VENT AT THE TOP OF ALL RISERS AND AT THE HIGH POINT OF EACH DROP IN THE HEATING AND CHILLED WATER SYSTEMS.
10. PROVIDE HOSE END DRAIN VALVES AT BOTTOM OF ALL RISERS AND LOW POINTS.
11. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION INDICATORS AND MAXIMUM ADJUSTABLE MEMORY STOPS.
12. UNION AND OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT TO PERMIT DISASSEMBLE FOR ALTERATIONS AND REPAIRS.
13. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATIONS ISOLATION EXCEPTS WATER
COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.
14. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE
ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS.
15. PROVIDE FLEXIBLE CONNECTIONS AT ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT
WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTORS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
16. THE LOCATION OF EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING
WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES.
17. FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT. VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. ADDITIONAL VALVES, PRESSURE GAUGES, ETC. SHALL BE PROVIDED AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS
AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER DIAGRAMS.
18. INFORMATION SHOWN ON THE MECHANICAL DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK.
SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
19. REMOVE ALL EXISTING PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE GOVERNMENT, OR ARE INDICATED TO REMAIN THE PROPERTY OF GOVERNMENT SHALL BE DELIVERED BY THE CONTRACTOR WHERE DIRECTED BY THE COR. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE
CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.
20. DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT UNSEALED. VALVE ALL TERMINATED PRESSURE PIPE.
21. EXISTING MECHANICAL PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE COR
AND AT NO ADDITIONAL CONTRACT COST.
22. REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE DEMOLISHED TO MATCH EXISTING ADJACENT SURFACES.
23. PROVIDE UNIONS FOR ALL VALVES, STRAINERS, ETC. UNIONS SHALL BE INDEPENDENT OF VALVE, STRAINER, ETC.
24. ALL DUCTWORK, PIPING, AND EQUIPMENT WITHIN THE PENTHOUSE SHALL BE SUPPORTED FROM THE FLOOR. ACCESS SHALL BE MAINTAINED.
25. COORDINATE EXACT PHASING OF EQUIPMENT REPLACEMENT WITH COR.
MECHANICAL ABBREVIATIONS
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
ACV AUTOMATIC CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFM AIRFLOW MONITOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
ATC AUTOMATIC TEMPERATURE CONTROLS
ATU AIR TERMINAL UNIT
BAS BUILDING AUTOMATION SYSTEM
BLR BOILER
BWF BYPASS WATER FILTER
C CARBON MONOXIDE SENSOR
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
COR CONTRACTING OFFICERS REPRESENTATIVE
CO2 CARBON DIOXIDE
CS CURRENT SENSOR
D DAMPER / DEPTH / DIAMETER / DRAIN
DB DRY BULB / DECIBEL
DIA DIAMETER
DN DOWN
DPS DIFFERENTIAL PRESSURE SWITCH
DWH DOMESTIC WATER HEATER
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EFT ENTERING FLUID TEMPERATURE
ELEC ELECTRICAL
ESS EMERGENCY SHUTDOWN SWITCH
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FD FLOOR DRAIN
FM FLOW METER
FOS FUEL OIL SUPPLY
FOR FUEL OIL RETURN
FPD FLUID PRESSURE DROP
FS FLOW SWITCH
FT FEET / FOOT
G GAS
GAL GALLON
GPM GALLONS PER MINUTE
H HEIGHT / HUMIDISTAT / HUMIDITY SENSOR
HC HEATING COIL
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HR HEATING WATER RETURN
HS HEATING WATER SUPPLY
MECHANICAL LEGEND
HS HOT WATER HEATING SUPPLY
HOT WATER HEATING RETURN
CHS
CHR
CHILLED WATER SUPPLY
CHILLED WATER RETURN
COMBINATION TEMPERATURE/HUMIDITY/OCCUPANCY SENSOR
OUTDOOR AIR OR SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
CALLOUT DESIGNATION
TOP - VIEW REFERENCE
BOTTOM - REFERENCED DRAWING
END POINT OF REMOVAL
CONNECT TO EXISTING
M-301
DESCRIPTIONSYMBOL
HR
SMOKE DETECTOR
VOLUME DAMPER
MOTOR OPERATED DAMPER
FIRE DAMPER
SHUTOFF VALVE
BALANCING VALVE
TWO WAY AUTOMATIC CONTROL VALVE
UNION
CAP (PIPE OR DUCT)
PRESSURE GAUGE
THERMOMETER
AIR VENT
PRESSURE REDUCING VALVE
PIPE ANCHOR
CARBON DIOXIDE SENSOR
CHECK VALVE
STRAINER
RELIEF VALVE
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HZ HERTZ
IN INCH
L LENGTH
LAT LEAVING AIR TEMPERATURE
LFT LEAVING FLUID TEMPERATURE
LLS LIQUID LEVEL SENSOR
LWT LEAVING WATER TEMPERATURE
M MECHANICAL
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MD MECHANICAL DEMOLITION
MIN MINIMUM
MOD MOTOR OPERATED DAMPER
N NORTH
NC NORMALLY CLOSED
NO NUMBER
NTS NOT TO SCALE
OA OUTDOOR AIR
P PRESSURE
PH PHASE
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRV PRESSURE REDUCING VALVE
RA RETURN AIR
RHC REHEAT COIL
RLF RELIEF AIR
RPM ROTATIONS PER MINUTE
RV RELIEF VALVE
RX REMOVE EXISTING
S SMOKE DETECTOR / SWITCH
SA SOUND ATTENUATOR / SUPPLY AIR
SENS SENSIBLE
SG STEAM GENERATOR
SP STATIC PRESSURE
SPSS STATIC PRESSURE SENSING STATION
STM STEAM
T THERMOSTAT / TEMPERATURE SENSOR
TYP TYPICAL
UH UNIT HEATER
V VALVE / VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFMC VARIABLE FREQUENCY MOTOR CONTROLLERS
W WIDE / WIDTH
WB WET BULB
WG WATER GAGE
WPD WATER PRESSURE DROP
M-001
M-001.DWG
MECHANICAL COVER
SHEET
MECHANICAL DESIGN CRITERIA
TOTAL BUILDING HEATING LOAD: 6,450 MBH
DESIGN OUTDOOR AMBIENT TEMPERATURE (HEATING): 0 DEGREES F
DESIGN INDOOR HEATING SPACE SETPOINT: 70 DEGREES F
MAXIMUM DESIGN NATURAL GAS CONSUMPTION: 8,558 MBH
MAXIMUM DESIGN FUEL OIL CONSUMPTION: 66 GPH
FOS
FOR
FUEL OIL SUPPLY
FUEL OIL RETURN
SOLENOID VALVE
G
D
NATURAL GAS
DRAIN
MD-301
ROOFROOF
ROOF
PENTHOUSE
Mechanical Replacement at the Life Sciences Building
Baltimore City
Community College
2901 Liberty Heights Ave, Baltimore, MD 21215
SHEET OF 39
BID SET
Professional Certification: I certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland.
License No:36608 Expiration Date:12/23/2027
Mechanical, Electrical, Plumbing, Fire Protection Engineering Henry Adams, LLC 600 Baltimore Avenue, Suite 400, Baltimore, MD 21204 Office: (410) 296-6500
06/16/2026
DESCRIPTIONDATEMARK
PROJECT NO.:
DATE:
CHK'D BY:
DRAWN BY:
CAD DWG FILE:
CC-622-260-003DGS PROJECT NO.:
25-B017
Cost Estimating Forella Group, LLC 5580 Parkstone Drive, Suite 250, Chantily, VA 20151 Office: (703) 540-2230
CEL
EKD
Structural Engineering Onyx Design and Consulting, LLC 55 S Queen St Suite 01, York, PA 17403 Office: (717) 852-1260
MD-105
ROOF - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0" 0 4 16 24 FT8
1/8" = 1' - 0"
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY DASHED WEIGHT LINE,
3. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAS
BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL
OR DIMENSION. EXISTING…