The shared file is a comprehensive set of construction documents for the Seminole County Fire Training Center Shower Building Addition project, prepared by KMA Design Group, LLC and dated April 3, 2023. The project involves constructing a new shower building addition at the Seminole County Fire Training Center located at 201 Valentine Way in Longwood, Florida. The documents include architectural, civil, structural, mechanical, electrical, and plumbing plans covering a multi-room shower facility with detailed specifications for construction, including site plans, floor plans, elevations, utility connections, and technical details for various building systems.
The project documents indicate a total project budget estimated around $225,000, with specifications for a certified general contractor to complete the work. The plans detail a facility with multiple shower rooms, mechanical spaces, and associated infrastructure, including specific requirements for electrical, plumbing, and mechanical systems. The documents provide extensive technical specifications, including building code compliance, material specifications, installation requirements, and detailed drawings for each discipline of construction. The project appears to be funded through Seminole County and is designed to enhance the fire training facility's amenities and functionality.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REVISIONS:
Mark A. Kaiser, AIA
AR 92267
Date:
Project No.:
04/03/2023
23-01002
SEALCONSULTANTS
100% Construction Docs voice 407.697.0336 www.kmadg.net
AR 92267 CS1
Seminole County Fire Training Center Fire Training Center - Shower Building Addition
FTC Shower Building Addition
SC
F ire T ra in in g
C en te r -
S ho w er
B ui ld in g A dd iti on
Specialty Consultant n/a
Valentine Way
Seminole County Fire Training Center 201 Valentine Way
Longwood, FL 32750
Mechanical, Electrical, Plumbing & Fire Protection Engineer
SGM Engineering Inc.
935 Lake Baldwin Lane
Orlando, FL 32814 407.767.5188
Structural Engineer
Alba Engineering P.O. Box 547774
Orlando, FL 32854 407.421.4866
Civil Engineer
Klima Weeks Civil Engineering 385 Douglas Ave
Suite 2100 Altamonte Springs, FL 32714
407.478.8750
X
X
X
XXXX
X
X
ARCHITECTURAL GENERAL NOTES
SYMBOLS LEGEND
X
X
X
XXXX
X
X
WALL TYPES WITH PLAN IDENTIFICATION
BUILDING CODE INFORMATIONABBREVIATIONS
TYPICAL MOUNTING HEIGHTS
A001 General Notes & Code Info.
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
C-001
GENERAL NOTES
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i c e w w w k m a d g n e t
A R
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
FL P.E. #49945
GEOMETRY NOTES:
GRADING AND DRAINAGE NOTES:
EROSION CONTROL NOTES
GENERAL NOTES:
VERTICAL DATUM NOTE:
UTILITY NOTES:
STORM LEGEND: WATER / SEWER LEGEND:
DEWATERING NOTES:
0'
GRAPHIC SCALE IN FEET
25 50 100
C-100
OVERALL SITE PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
FL P.E. #49945
LEGEND:
10 20 40
C-101
SITE PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
10 20 40
C-200
DEMOLITION &
EROSION CONTROL PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
FL P.E. #49945
DEMOLITION LEGEND
TREE BARRIER DETAIL
SLICING METHOD
TRENCHING METHOD
SILT FENCE BARRIER INSTALLATION
INLET PROTECTION DETAIL
10 20 40
C-300
GEOMETRY PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
FFE:
26.45
0'
GRAPHIC SCALE IN FEET
10 20 40
C-400
GRADING &
DRAINAGE PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
FFE:
26.45
0'
GRAPHIC SCALE IN FEET
10 20 40
C-500
UTILITY PLAN
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
C-600
CIVIL DETAILS
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023 23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
v o i w w w k m a d g n e t
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
AR 92267
Seal
JAY A. KLIMA, P.E.
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
02/24/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
90% Construction Docs
Sh o w er
B ui ld in g A dd it io n
M ar k A
. K ai se r, A
IA
A R
AutoCAD SHX Text
1. BUILDING CODES A. ALL CONSTRUCTION SHALL CONFORM WITH THE 2020 (7th EDITION) FLORIDA 2020 (7th EDITION) FLORIDA (7th EDITION) FLORIDA 7th EDITION) FLORIDA EDITION) FLORIDA BUILDING CODE - BUILDING BUILDING B. IN ADDITION, ALL CONSTRUCTION SHALL CONFORM WITH THE GOVERNING LOCAL BUILDING CODE OR LOCAL JURISDICTIONAL REQUIREMENTS. 2. DESIGN LOADS A. THE DESIGN DEAD LOADING FOR ALL FRAMING IS BASED ON THE CONSTRUCTION MATERIALS SHOWN ON THE DRAWINGS AND INDICATED IN THE SPECIFICATIONS. ALL FRAMING IS DESIGNED FOR THE FOLLOWING UNIFORM DEAD LOADS APPLIED IN ADDITION TO STRUCTURE SELF WEIGHT: MECH., ELECT., PLUMBING, CEILING, ETC.................15PSF ROOFING....................................................................5PSF B. THE MINIMUM DESIGN UNIFORMLY DISTRIBUTED LIVE LOADING FOR ALL NEW FRAMING SHALL BE AS FOLLOWS: FLOOR LIVE LOADS UNINHABITABLE ATTICS WITHOUT STORAGE..........10PSF UNINHABITABLE ATTICS WITHOUT STORAGE..........10PSF UNINHABITABLE ATTICS W/ STORAGE..................20PSF UNINHABITABLE ATTICS W/ STORAGE..................20PSF SLEEPING AREAS...................................................30PSF ALL OTHER AREAS INCL. STAIRS.........................40PSF ROOF LIVE LOAD.....................................................20PSF C. HANDRAIL/GUARDRAIL LIVE LOADS HANDRAIL/GUARDRAIL LIVE LOADS GUARDS AND HANDRAILS (HIGHER OF) 200LB PT LOAD OR 50PLF. GUARD PICKET/INFILL COMPONENTS 50PSF OVER A 1 SQ. FT. AREA. D. THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR THE METHOD OF THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR THE METHOD OF CONSTRUCTION AND SHALL PROVIDE ALL TEMPORARY BRACING AND SHORING REQUIRED TO MAINTAIN THE STABILITY OF THE STRUCTURE AND TO SUPPORT CONSTRUCTION LOADS DURING CONSTRUCTION, INCLUDING SOILS ON WALLS FROM BACKFILLING PRIOR TO PLACING SLABS ON GRADE. DESIGN OF ALL BRACING IS THE CONTRACTORS RESPONSIBILITY. ANY SHORING OR BRACING ENGINEERING SHALL BE BY OTHERS. 3. MISCELLANEOUS A. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT DOCUMENTS MUST BE SUBMITTED BY THE CONTRACTOR OR OWNER FOR REVIEW BY THE ENGINEER. B. THE CONTRACTOR SHALL REVIEW THE ARCHITECTURAL, MECHANICAL, ELECTRICAL PLUMBING AND STRUCTURAL DRAWINGS FOR LOCATION AND DIMENSION OF CHASES, INSERTS, OPENINGS, SLEEVES, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS. C. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS SHOWN ON THE CONTRACT DRAWINGS BEFORE PROCEEDING WITH CONSTRUCTION. ALL DISCREPANCIES AND OMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE DESIGN PROFESSIONALS. D. SCALES SHOWN ON THE CONSTRUCTION DOCUMENTS ARE FOR GENERAL INFORMATION ONLY. DIMENSIONAL INFORMATION SHALL NOT BE OBTAINED BY SCALING THE DRAWINGS. 4. SPREAD FOOTING FOUNDATIONS A. THE BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE LOCATED AS INDICATED ON THE DRAWINGS. C. ALL FILL PLACED UNDER SPREAD FOOTINGS SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95 PERCENT OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D 698 OR ALTERNATIVE REQUIREMENTS PROVIDED BY A GEOTECHNICAL ENGINEER. D. ALL EXISTING SOIL CONTAINING GRAVEL, CONSTRUCTION OR DEMOLITION DEBRIS, ORGANIC SUBSTANCES, OR OTHER FOREIGN OBJECTS SHALL BE REMOVED FROM THE REGION WITHIN THE FOOTPRINT OF THE STRUCTURE. 5. STRUCTURAL FILL A. NEW FILL MATERIAL AND EXISTING BASE MATERIAL SHALL BE FREE OF ALL REFUSE, DEBRIS, AND ORGANIC MATTER AND SHALL BE APPROVED FOR USE BY A GEOTECHNICAL ENGINEER. B. FILL MATERIAL SHALL BE DEPOSITED IN 8 INCH MAXIMUM LOOSE LIFTS AND COMPACTED TO A DRY DENSITY OF AT LEAST 95 PERCENT OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D 698 OR ALTERNATIVE REQUIREMENTS PROVIDED BY A GEOTECHNICAL ENGINEER. 6. SLABS ON GRADE SLABS ON GRADE A. ALL SLABS ON GRADE SHALL CONSIST OF A 4 INCH THICK 2500 PSI (MIN) SLAB PLACED OVER A 6 MIL (MIN.) POLYETHYLENE VAPOR RETARDER OVER CLEAN COMPACTED FILL REINFORCED WITH POLYPROPOLENE FIBERS OVER CLEAN COMPACTED FILL REINFORCED WITH POLYPROPOLENE FIBERS (FIBERMESH OR EQUAL), MIN. 1-1/2" LONG AT A RATE OF 1.5 LBS/ CY OF CONCRETE. ALL EDGES OF VAPOR RETARDER SHALL BE LAPPED 6 INCHES MIN. AND TAPED AT ALL JOINTS/PENETRATIONS. B. ANY TERMITE TREATMENT SPECIFIED AND PERMITTED BY FBC-1816 ANY TERMITE TREATMENT SPECIFIED AND PERMITTED BY FBC-1816 IS ACCEPTABLE, INCLUDING: SOIL TREATMENT WITH REGISTERED TERMITICIDE, OR BAITING SYSTEMS (SENTRICON OR APPROVED EQUAL), OR PESTICIDES APPLIED TO WOOD (BORA-CARE OR APPROVED EQUAL) C. SLABS ON GRADE SHALL BE SCREEDED, FLOATED, AND STEEL SLABS ON GRADE SHALL BE SCREEDED, FLOATED, AND STEEL TROWELED TO FORM A SMOOTH, DENSE, AND PLANE SURFACE. D. PLACE CONCRETE PER ACI 302. CONTRACTOR SHALL READ, UNDERSTAND PLACE CONCRETE PER ACI 302. CONTRACTOR SHALL READ, UNDERSTAND FOLLOW GUIDELINES SET FORTH FOR PREPARING SUBGRADE, PLACING, CONSOLIDATING, FINISHING AND CURING CONCRETE SLABS. E. EXTEND SLAB 1-1/2" INCHES AT DOOR OPENINGS, EXTEND SLAB 1-1/2" EXTEND SLAB 1-1/2" INCHES AT DOOR OPENINGS, EXTEND SLAB 1-1/2" INCHES AT SLIDING GLASS DOORS AND RECESS " FOR TRACKS. 34" FOR TRACKS. F. SAWCUT CONTROL JOINTS IN CONCRETE SLAB RECOMMENDED AT 12'-0" O.C. MAX SAWCUT CONTROL JOINTS IN CONCRETE SLAB RECOMMENDED AT 12'-0" O.C. MAX X
AutoCAD SHX Text
%%UROOF
AutoCAD SHX Text
%%UWALL
AutoCAD SHX Text
ZONE 1
AutoCAD SHX Text
ZONE 2
AutoCAD SHX Text
ZONE 3
AutoCAD SHX Text
ZONE 3
AutoCAD SHX Text
ZONE 4
AutoCAD SHX Text
ZONE 5
AutoCAD SHX Text
NOTE: RECOMMENDED SPACING OF CONTROL JOINTS NOT TO EXCEED MAX. SPACING OF 12'-0"
AutoCAD SHX Text
1/3 OF "D"
AutoCAD SHX Text
7. CAST IN PLACE CONCRETE A. ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301)"; AND TO THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318)". B. IN ADDITION TO THE ABOVE, ALL CONCRETE WORK SHALL CONFORM TO THE FOLLOWING: 1. REC. PRACTICE FOR HOT WEATHER CONCRETING (ACI 305). 2. REC. PRACTICE FOR COLD WEATHER CONCRETING (ACI 306). 3. REC. PRACTICE FOR CONCRETE FORMWORK (ACI 347). C. ALL CONCRETE EXPOSED TO PUBLIC VIEW SHALL CONFORM TO THE REQUIREMENTS FOR ARCHITECTURAL CONCRETE CONTAINED IN ACI 301. D. ALL CONCRETE; UNLESS NOTED OTHERWISE, SHALL BE STONE AGGREGATE CONCRETE HAVING THE FOLLOWING MINIMUM 28 DAY COMPRESSIVE STRENGTHS: FOUNDATIONS 3000 PSI SLABS ON GRADE 3000 PSI BEAMS/COLUMNS/ELEVATED SLABS 4000 PSI ALL CONCRETE EXPOSED TO WEATHER SHALL HAVE AN AIR ENTRAINMENT OF 5% +/- 1%. NO ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL BE PERMITTED. MAXIMUM AGGREGATE SIZE SHALL BE 1", AND MAXIMUM SLUMP SHALL BE 4", 3" FOR SLABS ON GRADE. ALL CONCRETE EXCEPT FOOTINGS SHALL CONTAIN A WATER REDUCING ADMIXTURE. PORTLAND CEMENT SHALL CONFORM TO ASTM C 150 AND NORMAL WEIGHT AGGREGATES SHALL CONFORM ASTM C 33. E. ALL REINFORCING BARS SHALL BE NEW BILLET STEEL CONFORMING TO GRADE 60 MIN. GRADE 40 ACCEPTABLE FOR FOUNDATIONS. ALL WELDED WIRE FABRIC (W.W.F.) SHALL CONFORM TO ASTM A 185. LAP ALL REINFORCING BARS A MINIMUM OF 48 BAR DIAMETERS (30" FOR #5 REINF.) AND ALL W.W.F. A MINIMUM OF TWO FULL GRIDS, UNLESS OTHERWISE INDICATED. G. ALL REINFORCING SHALL BE DETAILED, FABRICATED AND PLACED IN ACCORDANCE WITH THE CRSI "MANUAL OF STANDARD PRACTICE", ACI 315" DETAILS AND DETAILING OF CONCRETE REINFORCEMENT", ACI SP 66 "DETAILING MANUAL". H. GROUND BLAST FURNACE SLAG MAY BE USED TO REPLACE UP TO 50 PERCENT OF THE PORTLAND CEMENT IN A CONCRETE MIX, AND FLY ASH OR POZZOLAN MAY BE USED TO REPLACE UP TO 25 PERCENT OF PORTLAND CEMENT, SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER AND SHALL CONFORM TO ASTM C 989. L. MINIMUM COVER FOR ALL REINFORCING SHALL BE AS FOLLOWS UNLESS OTHERWISE INDICATED: FOUNDATIONS 3 INCHES SLABS ON GRADE 2 INCHES (TOP) ALL OTHER CONCRETE ACI STANDARDS 8. CONCRETE MASONRY A. ALL MASONRY CONSTRUCTION SHALL CONFORM TO THE "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530/ASCE 5/TMS 402)" AND TO THE "SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1/ASCE 6/TMS 602)". B. ALL CONCRETE MASONRY SHALL HAVE A SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f'm = 1500 PSI. C. ALL WALLS SHALL BE CONSTRUCTED OF NORMAL WEIGHT HOLLOW LOAD BEARING UNITS CONFORMING TO ASTM C90 WITH A NET COMPRESSIVE STRENGTH OF 1900 PSI. D. ALL EXTERIOR WALLS AND BEARING WALLS SHALL BE CONSTRUCTED WITH TYPE "S" CEMENT LIME MORTAR ABOVE GRADE, AND TYPE "M" BELOW GRADE. ALL MORTAR SHALL CONFORM TO ASTM C270 WITH TYPE "S" MORTAR OBTAINING AN AVERAGE COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS AND TYPE "M" MORTAR OBTAINING AN AVERAGE COMPRESSIVE STRENGTH OF 2500 PSI AT 28 DAYS. E. ALL FILL FOR CONCRETE MASONRY SHALL BE GROUT CONFORMING TO ASTM C 476 WITH A COMPRESSIVE STRENGTH OF 2500 PSI AT 28 DAYS. F. ALL MASONRY WALLS SHALL BE REINFORCED WITH 9 GA LADDER TYPE GALVANIZED HORIZONTAL JOINT REINFORCING CONFORMING TO ASTM A 82 AND SPACED VERTICALLY AT 16" O.C., UNLESS OTHERWISE INDICATED. PROVIDE CORNER AND TEE PIECES AT ALL INTERSECTIONS. LAP ALL JOINTS 6" MINIMUM. LADDER REINF. IS RECOMMENDED FOR SHRINKAGE CRACK CONTROL, HOWEVER, AT GENERAL CONTRACTOR DISCRETION THE LADDER REINFORCING MAY BE ELIMINATED AND IS NOT A FBC MANDATED REQUIREMENT. G. ALL REINFORCING BARS FOR MASONRY SHALL BE NEW BILLET STEEL ALL REINFORCING BARS FOR MASONRY SHALL BE NEW BILLET STEEL CONFORMING TO GRADE 40 MIN H. ALL VERTICAL REINFORCING SHALL BE LAP SPLICED A MINIMUM OF 48 BAR DIAMETERS (30" FOR #5 REINF.) UNLESS OTHERWISE INDICATED. ALL MASONRY CORES CONTAINING VERTICAL REINFORCING SHALL BE GROUTED SOLID. I. IF VERTICAL REINF. IS MISSING/MISPLACED, REPLACEMENT REINF. MAY IF VERTICAL REINF. IS MISSING/MISPLACED, REPLACEMENT REINF. MAY BE DOWELLED INTO FOOTING 5" MIN. WITH EPOXY. 9. EPOXY A. ALL EPOXY CALLED FOR IN PLANS TO BE SIMPSON SET (CONCRETE OR MASONRY), ALL EPOXY CALLED FOR IN PLANS TO BE SIMPSON SET (CONCRETE OR MASONRY), SIMPSON HP-ET, (CONCRETE OR MASONRY), HILTI HIT-RE 500 V3 (CONCRETE), OR HILTI HIT-HY 270 (MASONRY). 10. SOFFITS SOFFITS 11. PRE-ENGINEERED WOOD TRUSSES (**NOT-IN-USE**) A. WOOD TRUSSES SHALL DESIGNED FOR THE LOADS INDICATED ON THE WOOD TRUSSES SHALL DESIGNED FOR THE LOADS INDICATED ON THE CONTRACT DOCUMENTS. ALL TRUSS TO TRUSS CONNECTIONS SHALL BE DESIGNED AND SPECIFIED BY THE TRUSS SUPPLIER. B. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND DESIGN THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND DESIGN CALCULATIONS FOR ALL WOOD TRUSSES INCLUDING TRUSS LAYOUT, WOOD SPECIES AND GRADE, MEMBER SIZES, TRUSS BEARING CONNECTION DETAILS WITH CLEARLY INDICATED REACTIONS, AND THE DESIGN AND LOCATION OF ALL REQUIRED BRACING AND BRIDGING. THE TRUSSES SHALL BE DESIGNED IN A MANNER THAT AVOIDS ADDITIONAL MEMBER BRACING. THE CALCULATIONS AND SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF FLORIDA. CONTRACTOR TO VERIFY THAT TRUSS DESIGN MATCHES ROOF PLAN PRIOR TO FABRICATION.
AutoCAD SHX Text ALL EXTERIOR SOFFITS TO BE SUPPORTED AT 12" O.C. MAX. UNLESS FLORIDA APPROVED MANUFACTURER SPEC. PROVIDED
AutoCAD SHX Text
12. WOOD A. ALL STRUCTURAL SHEATHING SHALL CONFORM TO THE DESIGN SPECIFICATIONS OF THE AMERICAN PLYWOOD ASSOCIATION. APA PS 1. PLYWOOD SHALL HAVE A MINIMUM OF THREE CONTINUOUS SPANS WITH FACE GRAIN PERPENDICULAR TO SUPPORTS. ALL SHEATHING SHALL BE SPAN RATED FOR THE LOADS AND FRAMING SPACING AS INDICATED ON THE DRAWINGS. B. FLOOR SHEATHING: USE 23/32" PLYWOOD (MIN.) FOR FLOOR SHEATHING. FASTEN PLYWOOD TO FLOOR TRUSSES W/ #8 SCREWS AT 6" O.C. AND GLUE. C. ROOF SHEATHING: ROOF SHEATHING: USE 19/32" (5/8") CDX. OR ZIP OR OSB (MIN.) FOR ROOF SHEATHING. FASTEN TO ROOF FRAMING W/ 8d RING SHANK NAILS (ASTM F1667 RSRS-03) AT 4" O.C. AT ALL PANEL EDGE SUPPORTS AND 6" O.C. AT ALL INTERIOR SUPPORTS. REDUCE NAIL SPACING TO 4" O.C. WITHIN 4'-0" OF ALL ROOF EDGES PER DIAGRAM SHOWN BELOW (ZONES 2 AND 3). IN EXPOSURE B AREAS CONTRACTOR PERMITTED TO SUBSTITUTE 15/32" (1/2") CDX OR 7/16" ZIP/OSB USING PLYWOOD SHEATHING CLIPS AND WITH OWNER'S APPROVAL. IN EXPOSURE B AREAS FASTENERS MAY BE INSTALLED AT 6" O.C. AT ALL LOCATIONS. ROOF SHEATHING SHALL NOT CANTILEVER MORE THAN 9" BEYOND A GABLE END WALL UNLESS SUPPORTED BY GABLE OVERHANG FRAMING. D. VERTICAL WALL SHEATHING (INC. GABLES, TRUSS HEELS ETC.): VERTICAL WALL SHEATHING (INC. GABLES, TRUSS HEELS ETC.): USE 15/32" CDX. OR 7/16" OSB/ZIP (MIN.) FOR WALL SHEATHING. FASTEN SHEATHING TO STUDS W/ 8d NAILS @ 6" O.C. AT ALL EDGE SUPPORTS AND 6" O.C. AT ALL INTERIOR SUPPORTS. (MIN. PENETRATION 1-1/2") E. WOOD GRADE SHALL BE REGULAR SOUTHERN PINE NO. 2, 19% MOISTURE CONTENT MAX., Fb = 1400psi MIN. 2x4 STUDS MAY BE SPRUCE, PINE OR FIR. F. ALL MANUFACTURED/GLULAM/POWERBEAM/LVL MEMBERS TO HAVE A MINIMUM BENDING STRESS OF Fb = 2250psi AND COMPLY WITH FBCR 802.1.2. AND COMPLY WITH FBCR 802.1.2. G. ALL DOUBLE BEAMS TO BE CONNECTED WITH 12d NAILS AT 16" O.C. STAGGERED, MIN. ALL TRIPLE AND QUADRUPLE BEAMS TO BE CONNECTED WITH " DIA. LAG SCREWS AT 16" O.C. ON BOTH FACES OF BEAM. WITH " DIA. LAG SCREWS AT 16" O.C. ON BOTH FACES OF BEAM. 316" DIA. LAG SCREWS AT 16" O.C. ON BOTH FACES OF BEAM. H. ALL SIMPSON CONNECTORS TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS, INCLUDING NUMBER, LENGTH AND DIAMETER OF FASTENER. WHERE CONNECTOR HAS MULTIPLE OPTIONS FOR NUMBER OF NAIL HOLES TO BE FILLED, THE MAX. NUMBER OF NAIL HOLES SHOULD BE FILLED U.N.O. I. ALL WOOD IN CONTACT WITH THE GROUND AND THAT SUPPORTS PERMANENT ALL WOOD IN CONTACT WITH THE GROUND AND THAT SUPPORTS PERMANENT STRUCTURES INTENDED FOR HUMAN OCCUPANCY SHALL BE APPROVED PRESERVATIVE TREATED WOOD (FBC R317.1.2.). FASTENERS IN CONTACT WITH PRESERVATIVE TREATED WOOD TO COMPLY WITH FBC R317.3.1. FBC R317.3.1. J. INTERIOR NON-LOAD BEARING STUD WALLS TO BE 2x4 STUDS SPACED AT 24" ON INTERIOR NON-LOAD BEARING STUD WALLS TO BE 2x4 STUDS SPACED AT 24" ON CENTER. 13. WIND LOADING:
AutoCAD SHX Text B. ALL FOUNDATIONS HAVE BEEN DESIGNED FOR A NET ALLOWABLE SOIL BEARING PRESSURE OF 2500 PSF. PER THE GEOTECHNICAL REPORT PREPARED BY ECS, (ECS PROJECT NUMBER 56:1575) AND DATED JUNE 27, 2022. ALL SOIL PREPARATION SHOULD BE BE PERFORMED IN ACCORDANCE WITH THESE RECOMMENDATIONS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(ROOF ANGLE 0 - 7 )
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PRESSURE
AutoCAD SHX Text +12.1, -25.7
AutoCAD SHX Text +12.1, -30.1
AutoCAD SHX Text +12.1, -36.2
AutoCAD SHX Text +12.1, -40.8
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +25.7, -27.7
AutoCAD SHX Text +24.4, -26.6
AutoCAD SHX Text +23.0, -25.0
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text +21.8, -24.0
AutoCAD SHX Text
AutoCAD SHX Text
ZONE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
AutoCAD SHX Text
WALL
AutoCAD SHX Text
TRIBUTARY AREA
AutoCAD SHX Text DESIGN WIND SPEED Vult = 140 MPH (Vasd = 108 MPH)
AutoCAD SHX Text
BUILDING RISK CATEGORY = II
AutoCAD SHX Text
WIND EXPOSURE CATEGORY = C
AutoCAD SHX Text
INTERNAL PRESSURE COEFF. (ASCE ENCLOSED BLDG) = %%P 0.18
AutoCAD SHX Text
COMPONENTS AND CLADDING
AutoCAD SHX Text
WIND PRESSURE SCHEDULE
AutoCAD SHX Text +12.1, -34.2
AutoCAD SHX Text +12.1, -40.2
AutoCAD SHX Text +12.1, -47.9
AutoCAD SHX Text +12.1, -53.8
AutoCAD SHX Text +12.1, -34.2
AutoCAD SHX Text +12.1, -46.0
AutoCAD SHX Text +12.1, -61.6
AutoCAD SHX Text +12.1, -73.3
AutoCAD SHX Text +25.7, -34.2
AutoCAD SHX Text +24.4, -31.9
AutoCAD SHX Text +23.0, -28.9
AutoCAD SHX Text +21.8, -26.6
AutoCAD SHX Text Vasd VALUES
AutoCAD SHX Text
ALL WINDOWS AND DOORS TO BE SELECTED FROM WALL PRESSURE
AutoCAD SHX Text
TABLES. ZONES 2, 3 & 5 WITHIN 4'-0" OF CORNERS/EDGES.
AutoCAD SHX Text S-1
AutoCAD SHX Text
STRUCTURAL GENERAL NOTES
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text All designs, plans, arrangements, and ideas represented or indicated by this drawing belong to and are the property of KMA Design Group, LLC and were created and developed for use on and in connection with the specified project. None of the designs, plans, arrangements, or ideas shall be used by or disclosed to any person, firm, or corporation for any purpose whatsoever whithout the written consent of KMA Design Group, LLC. Written dimensions shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and KMA Design Group, LLC must be notified of any variation from the dimensions and conditions shown by these drawings.
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text
AR 92267
AutoCAD SHX Text
AutoCAD SHX Text dsout Textbox 04/03/2023 dsout Textbox 100%
8"x8" MASONRY BOND
BEAM, FILL WITH SOLID
GROUT.
#5 CONT.
1'-0"
8" 8"
1x OR 2x P.T. SECURE TO BLOCK W/
1/4" TAPCONS (MIN. EMBEDMENT 1
4") WITHIN 8" OF EACH END & 12"
O.C. MAX SPACING
8" CMU
1"X4" OR 1"X2" P.T. NAILER
WINDOW ATTACH TO BUCK PER
MANUFACTURER DETAILS.
ALTERNATIVE MANUFACTURER
INSTALLATION THROUGH BUCKING
TO BLOCK ALSO ACCEPTABLE
DOOR CASING
2X4:
SECURE TO BLOCK W/ 1/4"
TAPCONS STAGGERED
(MIN. EMBEDMENT 1 14") WITHIN
8" OF EACH END & 12" O.C. MAX
SPACING.
2X6:
SECURE TO BLOCK W/
1/4" TAPCONS STAGGERED
(MIN. EMBEDMENT 1 14") WITHIN
8" OF EACH END & 12" O.C. MAX
SPACING.
DOOR JAMB ATTACH TO 2X
PER MANUFACTURERS
DETAILS.
DRYWALL PER ARCH
1"X4" OR 1"X2" P.T. NAILER
8" CMU
BLOCK WALL CONNECTIONA N.T.S.
WINDOW JAMB TO
BLOCK WALL CONNECTIONB N.T.S.
DOOR JAMB TO
2X8:
SECURE TO BLOCK W/
2 ROWS 1/4" TAPCONS MIN.
(EMBEDMENT 1 14") WITHIN 8"
OF EACH END & 12" O.C. MAX
SPACING.
SOLID GROUTED CELL
SOLID GROUTED CELL
DRYWALL PER ARCH
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
02/24/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
90% Construction Docs
Sh o w er
B ui ld in g A dd it io n
M ar k A
. K ai se r, A
IA
A R
AutoCAD SHX Text P.T. 2x ANCHORED TO BLK. WALL W/ HILTI DRIVE PINS (.145 X 3") @ 24" O/C. OR 316"x3-1/4" TAPCONS @ 16" O.C. OR 12" DIA. x 8" ANCHOR BOLTS AT 2'-0" IF CELL IS SOLID.
AutoCAD SHX Text
1/2" GYP. BOARD ON WOOD STUDS
AutoCAD SHX Text 1/2" GYP BOARD ON 1x P.T. FURRING STRIPS W/ INSULATION PER ENERGY CALCS
AutoCAD SHX Text
CMU WALL
AutoCAD SHX Text
%%UBB1
AutoCAD SHX Text
TYPICAL CMU WALL CONSTRUCTION DETAIL
AutoCAD SHX Text
BOND BEAM REINFORCEMENT:
AutoCAD SHX Text LAP ALL HORIZ. BARS 30" MIN. USE ACI 90 DEG. BENDS AT ALL CORNERS. ALL PIERS, BOND BEAMS AND LINTELS SHALL BE FILLED SOLID WITH GROUT
AutoCAD SHX Text
BOND BEAM DETAILS
AutoCAD SHX Text
VERT. REINF. IN SOLID GROUTED CELL
AutoCAD SHX Text STANDARD ACI 90deg HOOK TIED TO FOOTING REINFORCING
AutoCAD SHX Text
FOOTING, SEE PLAN
AutoCAD SHX Text
FOOTING REINFORCING
AutoCAD SHX Text
BOND BEAM- SEE PLAN
AutoCAD SHX Text UNLESS STATED OTHERWISE ON THE PLANS: CLEANOUT REQUIRED FOR EVERY 10'-0" (MIN.) OF WALL.
AutoCAD SHX Text
CLEANOUT REQ'D. @ EVERY FILLED CELL.
AutoCAD SHX Text
PRE-CAST LINTEL, SEE PLAN
AutoCAD SHX Text
PROVIDE PRECAST SILL OR BOND BEAM
AutoCAD SHX Text
AT BOND BEAM STEP, LAP REINFORCING 25" MIN.
AutoCAD SHX Text
CONT. BARS PER BOND BEAM SCHEDULE
AutoCAD SHX Text
STD ACI 90 DEG HK BAR TO MATCH CONT BARS
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text
CONT. BARS PER BOND BEAM SCHEDULE
AutoCAD SHX Text
CONT. BARS PER BOND BEAM SCHEDULE
AutoCAD SHX Text
CONT. BARS PER BOND BEAM SCHEDULE
AutoCAD SHX Text
BOND BEAM CORNER DETAILS
AutoCAD SHX Text UP TO 4" DIA. SLEEVE PIPE LOCATED AT CENTER MAY BE ACCOMODATED IN 12" DEEP FOUNDATION. (4" FROM BOTTOM). UP TO 6" DIA. SLEEVE PIPE LOCATED AT CENTER MAY BE ACCOMODATED IN 16" DEEP FOUNDATION. (4" FROM BOTTOM). FOR LARGER PIPES/ ALTERNATE PIPE ELEVATIONS SEE BELOW.
AutoCAD SHX Text PROVIDE 2 (#5) x 3'-0" REINFORCING AT TOP OF FOUNDATION ABOVE SLEEVE LOCATION.
AutoCAD SHX Text PROVIDE 2 (#5) x 3'-0" REINFORCING ABOVE PIPE LOCATION 2" CLEARANCE.
AutoCAD SHX Text
STEP FOUNDATION AND REINFORCEMENT AROUND SLEEVED PIPE.
AutoCAD SHX Text
SLEEVED FOUNDATION DETAIL
AutoCAD SHX Text IF SLEEVE IS LOCATED WITHIN STEM WALL. LOCATE AT NON-FILLED CELL LOCATION BUT GROUT AROUND SLEEVE.
AutoCAD SHX Text S-2
AutoCAD SHX Text
FRAME TO CMU DET.
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
TYPICAL CMU WALL CONSTRUCTION
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
JAMB/BUCK DETAILS
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text All designs, plans, arrangements, and ideas represented or indicated by this drawing belong to and are the property of KMA Design Group, LLC and were created and developed for use on and in connection with the specified project. None of the designs, plans, arrangements, or ideas shall be used by or disclosed to any person, firm, or corporation for any purpose whatsoever whithout the written consent of KMA Design Group, LLC. Written dimensions shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and KMA Design Group, LLC must be notified of any variation from the dimensions and conditions shown by these drawings.
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text
AR 92267
AutoCAD SHX Text
AutoCAD SHX Text dsout Textbox 04/03/2023 dsout in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
02/24/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
90% Construction Docs
Sh o w er
B ui ld in g A dd it io n
M ar k A
. K ai se r, A
IA
A R
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
FOUNDATION SCHEDULE
AutoCAD SHX Text
REINFORCEMENT
AutoCAD SHX Text
MARK
AutoCAD SHX Text W x L
AutoCAD SHX Text
DEPTH
AutoCAD SHX Text
T.O. FTG. EL.
AutoCAD SHX Text
2- #5 CONT. BOT.
AutoCAD SHX Text 1'-4" x CONT.
AutoCAD SHX Text 1'-8"
AutoCAD SHX Text
T.O. SLAB
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
1- #5 CONT. BOT.
AutoCAD SHX Text
TE1
AutoCAD SHX Text 0'-8" x CONT.
AutoCAD SHX Text 0'-8"
AutoCAD SHX Text
T.O. SLAB
AutoCAD SHX Text
2- #5 CONT. BOT.
AutoCAD SHX Text 1'-4" x CONT.
AutoCAD SHX Text
T.O. SLAB
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text NOTES SEE GENERAL NOTES FOR CONCRETE SLAB CRITERIA PROVIDE SAWCUT CONTROL JOINTS IN FLOOR SLAB AT 12'-0" (SUGGESTED), COORD. WITH OWNER FOR FLOOR FINISHES. SEE GENERAL STRUCT. NOTES SHEET. CONTRACTOR SHALL COORDINATE EXACT PLUMBING FIXTURE LOCATIONS. ALL INTERIOR FOOTINGS TO EXTEND 8" MIN. PAST END OF BEARING WALL U.N.O. PROVIDE BOND BEAM BB1 OR PRECAST CONCRETE SILL BELOW ALL MASONRY WINDOW OPENINGS. ALL MASONRY WINDOW OPENINGS. MASONRY WINDOW OPENINGS. PROVIDE BOND BEAM BB1 AT TOP OF ALL CMU WALLS, SEE DETAILS SHEET. 8" CMU WALL WITH #5 REINFORCING IN CENTER OF SOLID GROUTED CELLS AS SHOWN, AT 4'-0" O.C. MAX. AND AT ALL CORNERS AND JAMBS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 4- #5s EACH WAY, BOT.
AutoCAD SHX Text F3
AutoCAD SHX Text 2'-8"x2'-8"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text
-1'-4" MIN.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
SIM.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text wh
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TF1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TE1.5
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
SIM.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
SIM.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
THICKENED SLAB FTG (INT. WALL)
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text MISSED OR MISPLACED ANCHOR BOLTS MAY BE SUBSTITUTED WITH 12" WEDGE ANCHORS OR " 12" THREADED ROD IN SIMPSON SET OR HP-ET EPOXY (EMBED 4" MIN.)
AutoCAD SHX Text 2x P.T. SILL PLATE WITH 1/2" DIA. J BOLTS AT 32" O.C. AND WITHIN 8" OF ALL CORNERS, JAMBS AND END OF WOOD SECTION.
AutoCAD SHX Text
#5 REINF. CONTINUOUS, BOTTOM. SEE PLAN FOR QUANTITY
AutoCAD SHX Text
AT GARAGE/STEP DOWN BEARING WALL
AutoCAD SHX Text
TOP OF SLAB
AutoCAD SHX Text
TOP OF SLAB
AutoCAD SHX Text
TOP OF SLAB
AutoCAD SHX Text
#5 CONT.
AutoCAD SHX Text
THICKENED EDGE FTG DETAIL
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
3" COVER TYP.
AutoCAD SHX Text
TOP OF SLAB
AutoCAD SHX Text
STANDARD ACI 90 DEG. HOOKED BAR, DIA. TO MATCH WALL REINF.
AutoCAD SHX Text
EQUAL
AutoCAD SHX Text
PROVIDE CLEANOUT AT EACH GROUTED CELL
AutoCAD SHX Text
#5 REINF. CONTINUOUS, BOTTOM. SEE PLAN FOR QUANTITY
AutoCAD SHX Text
PROVIDE LAP SPLICE ACCORDING TO STRUCT. NOTES
AutoCAD SHX Text
VERT. REINF. IN SOLID GROUTED CELL. REFER TO PLAN FOR SIZE AND SPACING
AutoCAD SHX Text
GRADE 8" BELOW INTERIOR FINISHED FLOOR
AutoCAD SHX Text
TOP OF SLAB
AutoCAD SHX Text
#5 CONT.
AutoCAD SHX Text
SLAB THICKENED EDGE
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
THICKENED SLAB FTG (INT. WALL)
AutoCAD SHX Text
SCALE: NTS
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text
#5 PERIMETER BAR
AutoCAD SHX Text
STANDARD ACI 90 DEG. HOOKED BAR, DIA. TO MATCH J-BOLTS AT 32" OC
AutoCAD SHX Text S-3
AutoCAD SHX Text
FOUNDATION PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text S-3
AutoCAD SHX Text All designs, plans, arrangements, and ideas represented or indicated by this drawing belong to and are the property of KMA Design Group, LLC and were created and developed for use on and in connection with the specified project. None of the designs, plans, arrangements, or ideas shall be used by or disclosed to any person, firm, or corporation for any purpose whatsoever whithout the written consent of KMA Design Group, LLC. Written dimensions shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and KMA Design Group, LLC must be notified of any variation from the dimensions and conditions shown by these drawings.
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text
AR 92267
AutoCAD SHX Text
AutoCAD SHX Text dsout Textbox 04/03/2023 dsout in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
02/24/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
90% Construction Docs
Sh o w er
B ui ld in g A dd it io n
M ar k A
. K ai se r, A
IA
A R
AutoCAD SHX Text
D-5DR
AutoCAD SHX Text wh
AutoCAD SHX Text
D-5DR
AutoCAD SHX Text
D-5DR
AutoCAD SHX Text
D-5DR
AutoCAD SHX Text
D-5DE
AutoCAD SHX Text
D-5DE
AutoCAD SHX Text
D-5DE
AutoCAD SHX Text
D-5DE
AutoCAD SHX Text
D-8DR
AutoCAD SHX Text NOTES PROVIDE BOND BEAM AT TOP OF ALL WALLS WITH (1)#5, U.N.O., SEE TYPICAL CMU WALL DETAILS SEE LINTEL TABLES ON THIS SHEET. TABLES SHOWN ARE "QUALITY PRECAST", LOTT'S PRECAST AND CAST-CRETE LINTELS ARE ALSO ACCEPTABLE. ADDITIONAL ALTERNATIVE LINTEL MANUFACTURERS MAY ALSO BE USED PROVIDED LOAD TABLES MEET OR EXCEED VALUES PROVIDED ON THESE PLANS. SPECIFIED LINTEL DEPTH IS THE MINIMUM ACCEPTABLE. ANY EXTRA COURSES OF BLOCK ABOVE LINTEL ARE ACCEPTABLE AS LONG AS ALL COURSES ABOVE PRECAST LINTEL ARE FILLED WITH GROUT. ALL DOORWAY LINTELS (NOT SLIDING GLASS DOORS) ARE CALLED OUT ON LINTEL PLAN WITH 2" RECESSED LINTELS (DE, DR AND DX). CONTRACTOR RESPONSIBILITY TO VERIFY WITH DOOR MANUFACTURER FOR ACTUAL DOORWAY HEAD HEIGHT REQUIREMENTS PRIOR TO BEGINNING WORK. CONTRACTOR TO VERIFY ALL ROUGH OPENING ALL ROUGH OPENING ROUGH OPENING DIMENSION REQUIREMENTS WITH DOOR/WINDOW MANUFACTURER PRIOR TO BEGINNING WORK.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TC1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TC1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TC2
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
FRAMING CONNECTOR SCHEDULE
AutoCAD SHX Text
CALLOUT
AutoCAD SHX Text
CONNECTOR
AutoCAD SHX Text
ALLOWABLE UPLIFT LOAD
AutoCAD SHX Text
TC1
AutoCAD SHX Text
META16
AutoCAD SHX Text
1450 LB
AutoCAD SHX Text
TC7
AutoCAD SHX Text
MGT
AutoCAD SHX Text
3965 LB
AutoCAD SHX Text
TC3
AutoCAD SHX Text
TC4
AutoCAD SHX Text
1000 LB
AutoCAD SHX Text
MTS12
AutoCAD SHX Text
TC5
AutoCAD SHX Text
600 LB
AutoCAD SHX Text H2.5A
AutoCAD SHX Text
TC2
AutoCAD SHX Text
META16 @ 4'-0" O.C.
AutoCAD SHX Text
1450 LB
AutoCAD SHX Text
LSTA16 @ 4'-0" O.C.
AutoCAD SHX Text
1110 LB
AutoCAD SHX Text
TC6
AutoCAD SHX Text
VCT-R
AutoCAD SHX Text
370 LB
AutoCAD SHX Text
TC8
AutoCAD SHX Text
HTS20
AutoCAD SHX Text
1320 LB
AutoCAD SHX Text META16 CONNECTORS MAY BE REPLACED WITH HETA16 (1810 LB). ANY MISSING META16s MAY BE REPLACED WITH HTSM16s. ALL FRAMING TO CMU WALL CONNECTIONS, META16 (TC1) U.N.O. ALL FRAMING TO WOOD FRAME WALL CONNECTIONS, MTS12 (TC3) U.N.O.
AutoCAD SHX Text
TC9
AutoCAD SHX Text
HTT4
AutoCAD SHX Text
4235 LB
AutoCAD SHX Text
TC10
AutoCAD SHX Text
HTT5
AutoCAD SHX Text
5090 LB
AutoCAD SHX Text
TC11
AutoCAD SHX Text
(2)META16
AutoCAD SHX Text
1 PLY 1985 LB, 2PLY+ 1900 LB
AutoCAD SHX Text
TC12
AutoCAD SHX Text
TC13
AutoCAD SHX Text
(2)HETA16
AutoCAD SHX Text
1 PLY 2035 LB, 2PLY+ 2500 LB
AutoCAD SHX Text
DETAL20
AutoCAD SHX Text
1 PLY ONLY 2480 LB
AutoCAD SHX Text
TC15
AutoCAD SHX Text
1375 LB
AutoCAD SHX Text
MSTAM24
AutoCAD SHX Text
TC14
AutoCAD SHX Text
1110 LB
AutoCAD SHX Text
HTSM16
AutoCAD SHX Text NOTES: : TOP OF WALL ELEVATION/TRUSS BEARING ELEVATION, SEE ELEVATION SHEETS SEE GENERAL STRUCTURAL NOTES FOR ROOF SHEATHING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 2x10 @ 24" O.C.
AutoCAD SHX Text wh
AutoCAD SHX Text 2x8 WOOD STUD BLOCKING AT 16" O.C. HEIGHT VARIES FOR RAKED WALL
AutoCAD SHX Text FINISH, SEE ELEVATIONS AND TYPICAL SECTIONS) OVER PLYWOOD SHEATHING (SEE GENERAL STRUCT. NOTES)
AutoCAD SHX Text
SEE DETAILS FOR INTERFACE BETWEEN WOOD AND CMU BLOCK WALLS
AutoCAD SHX Text PROVIDE PT 2x8 SILL PLATE CONNECT TO TOP OF WALL WITH 1/2" DIA. x 8" ANCHOR BOLTS AT 32" O.C. OR A36 THREADED ROD EMBED 5" MIN. IN BOND BEAM WITH EPOXY.
AutoCAD SHX Text
BOND BEAM PER PLANS
AutoCAD SHX Text
DOUBLE 2X8 TOP PLATE
AutoCAD SHX Text
SP8 EACH STUD
AutoCAD SHX Text
RAKED WOOD INFILL WALL
AutoCAD SHX Text
BOND BEAM, (1) #5 REINFORCING IN SOLID GROUT, U.N.O.
AutoCAD SHX Text
1/2" GYPBOARD ON 3/4" P.T. FURRING. SEE ENERGY CALCS FOR INSULATION
AutoCAD SHX Text
8" CMU WALL, SEE PLANS FOR #5 REINFORCING SPACING
AutoCAD SHX Text
SEE ELEV.
AutoCAD SHX Text
AutoCAD SHX Text
FASCIA
AutoCAD SHX Text
DRIP EDGE
AutoCAD SHX Text 2x10 RAFTERS SEE FRAMING PLAN
AutoCAD SHX Text
PRECAST LINTEL, SEE LINTEL PLAN
AutoCAD SHX Text
ROOF SHEATHING SEE GENERAL STRUCTURAL NOTES
AutoCAD SHX Text
EMBEDDED UPLIFT STRAP META16, U.NO., SEE FRAMING PLAN
AutoCAD SHX Text
SEE FOUNDATION PLAN FOR SIZE AND REINFORCING
AutoCAD SHX Text
4" CONC. SLAB, SEE PLAN SHEETS
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text S-4
AutoCAD SHX Text
LINTEL PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text S-4
AutoCAD SHX Text All designs, plans, arrangements, and ideas represented or indicated by this drawing belong to and are the property of KMA Design Group, LLC and were created and developed for use on and in connection with the specified project. None of the designs, plans, arrangements, or ideas shall be used by or disclosed to any person, firm, or corporation for any purpose whatsoever whithout the written consent of KMA Design Group, LLC. Written dimensions shall have precedence over scale dimensions. Contractors shall verify and be responsible for all dimensions and conditions on the job and KMA Design Group, LLC must be notified of any variation from the dimensions and conditions shown by these drawings.
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text
AR 92267
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FRAMING PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text S-4
AutoCAD SHX Text
EXTERIOR WALL SECTION
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text S-4 dsout Textbox 04/03/2023 dsout
Demolition Plan
AD101
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
ARCHITECTURAL GENERAL NOTES
ARCHITECTURAL KEY NOTES
004 008
003 007
002 006
001 005
S2
S1S1
M1
M1
S1
M1
CEILING LEGEND
Partial Site Plan, Floor Plan
A101 & Reflected Ceiling Plan
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
001 002 003 004
008 007 006 005
004 008
S2
M1
M1
S1
S1
S1
S1 S1
T10
T4 T2
T1
T5
T11
T10
T10
T10
T4T2
T1
T5
T11
T6 T6
T3 T3
T9T8T7 T9T8T7
A B C D
T3T4
T11 T6
T11
T4
T3
T1
T7 T8 T9T7 T8 T9T7 T8 T9
T10 T10 T5
T2
Enlarged Floor Plan, Int.
A201 Elevations, Elevations & Sections
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
MECHANICAL
B
SHOWER
A
Door Schedule & Details
A301
Se m in ol e C ou nt y Fi re T ra in in g
C en te r
V al en tin e W ay Lo ng w oo d, F L
MAK
04/03/2023
23-01002
MAK
Checked By:
Date:
Project No.:
Drawn By:
REVISIONS:
vo ic e
7.
7.
w w w
.k m ad g.
ne t
AR
100% Construction Docs
Sh o w er
B ui ld in g A dd it io n
Mark A. Kaiser, AIA
TV
TV
LIGHTING FIXTURES
-SINGLE RECEPTACLE
-JUNCTION BOX
-DUPLEX RECEPTACLE
-DISCONNECT SWITCH
-DOOR BELL PUSH BUTTON
-EQUIPMENT CONNECTION
-SPECIAL PURPOSE RECEPTACLE
-DOUBLE DUPLEX (QUAD) RECEPTACLE
-MOTOR STARTER
-SHUNT TRIP
-PHOTOCELL
-DOOR BELL
-TIMECLOCK
-TRANSFORMER
-DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
-DUPLEX RECEPTACLE, GROUND FAULT
-SINGLE 250V, NON-LOCKING TYPE RECEPTACLE
-ABOVE COUNTER DUPLEX RECEPTACLE
-DUPLEX RECEPTACLE, HALF SWITCHED
-MOTOR
-120/208V PANELBOARD, SURFACE MOUNT
-277/480V PANELBOARD, SURFACE MOUNT
-POWER/DATA POLE
-PULL BOX
-CEILING MOUNTED RECEPTACLE
-RECESSED FLOOR RECEPTACLE
-FLOOR MOUNTED JUNCTION BOX
-120/208V PANELBOARD, RECESSED
-277/480V PANELBOARD, RECESSED
-FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
-STARTER/DISCONNECT SWITCH
-GENERATOR
-CLOCK
-LOCKBOX
-DUPLEX RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM WEATHERPROOF "IN USE"
COVER
-DUPLEX RECEPTACLE, GROUND FAULT
LOCATE WITHIN ELECTRIC WATER COOLER PER MANUFACTURER'S
INSTRUCTIONS
-BLACK DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION
-DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF, LOCATE IN
COMMON BOX WITH CCTV
-DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF, UNLESS NOTED
OTHERWISE
-GROUND BUS BAR
-5/8"Ø X 30'L GROUND ROD WITH TEST INSPECTION WELL
-PIR-WALL SWITCH DECORATOR MOTION SENSOR, 120/277 VAC,
800/1200W, WATTSTOPPER PW-100 OR EQUAL
-DUAL ULTRASONIC/PIR-WALL SWITCH DECORATOR MOTION SENSOR,
120/277VAC, 800/1200W, WATTSTOPPER DW-100 OR EQUAL
-*DUAL ULTRASONIC/PIR-CEILING MOUNT SENSOR, 24 VDC/VAC, 35mA, WATTSTOPPER DT-305 OR EQUAL
-*DUAL ULTRASONIC/PIR-WALL MOUNT SENSOR, 24 VAC/VDC, 35mA, WATTSTOPPER DT-205 OR EQUAL
-POWER PACK 120/277 VAC; 20 AMPS, 225mA SECONDARY, WATTSTOPPER BZ-150 OR EQUAL
-*PIR-WALL MOUNT SENSOR, LOW TEMP, 24 VDC/AC, 20mA, WATTSTOPPER CB-100 OR EQUAL
-*PIR-CEILING MOUNT SENSOR 24 VDC/VAC, 11mA, WATTSTOPPER
CI-205 OR EQUAL
-QUAD RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM WEATHERPROOF "IN USE"
COVER
-TRACK FIXTURE
-CEILING MOUNTED RECESSED, DOWN LIGHT
-EMERGENCY LIGHT FIXTURE
-2'x4' FLUORESCENT FIXTURE
-1'x4' FLUORESCENT FIXTURE
-2'x2' FLUORESCENT FIXTURE
-SURFACE MOUNTED LIGHTING FIXTURE
-2'x4' FLUORESCENT FIXTURE, BATTERY/EMERGENCY
-2'x2' FLUORESCENT FIXTURE, BATTERY/EMERGENCY
-1'x4' FLUORESCENT FIXTURE, BATTERY/EMERGENCY
-FLOOD LIGHT FIXTURE
-BOLLARD OR PENDANT LIGHT FIXTURE
POWER DISTRIBUTION
LIGHTING CONTROL DEVICES
1R1-1,3,5
1M1-1:3:5
1R1-1
1M1-1:3
1R1-1,3
-4' WALL MOUNT FLUORESCENT LUMINAIRE
-4' WALL MOUNT FLUORESCENT LUMINAIRE, EMERGENCY
-CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT
-BOLLARD OR PENDANT LUMINAIRE, EMERGENCY
-WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY
-POLE MOUNTED LUMINAIRE
-SINGLE POLE MOUNT LUMINAIRE, RECTANGLES INDICATE
NUMBER OF FIXTURES
-HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT: (2)
12 AWG + (1) 12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE
NOTED. PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
-HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: (4) 12
AWG + (1) 12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
-HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS: (3) 12 AWG
+ (1) 12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
-HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE CIRCUIT: (2)
12 AWG + (1) 12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE
NOTED. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
-HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: (3) 12 AWG
+ (1) 12 AWG GND IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
F
WP
WP
EWC
-CEILING MOUNTED RECESSED, WALL WASHER (ARROW
INDICATES DIRECTION OF WASH)
-SINGLE FACE EXIT LIGHT FIXTURE, ARROW INDICATES
DIRECTION OF EGRESS
-DOUBLE FACE EXIT LIGHT FIXTURE, ARROW INDICATES
DIRECTION OF EGRESS
-POLE MOUNTED SITE LIGHTING FIXTURE, RECTANGLES
INDICATE NUMBER OF FIXTURES
PC
TC
C
-QUAD RECEPTACLE, GROUND FAULT
C
J
J
PB
C
ST
CH
G
P
PD
T
SPD -SURGE PROTECTION DEVICE, SEE SPECIFICATIONS
LT
R9
PP
W
CI
DT
D1
C -*ULTRASONIC-CEILING CORRIDOR MOTION SENSOR, 24 VDC/VAC,
40mA, WATTSTOPPER WT-2250 OR EQUAL
-SWITCH LEG a FOR CONTROL OF THE INBOARD LAMP IN NORMAL AND
EMERGENCY POWERED LUMINAIRE
-SWITCH LEG b FOR CONTROL OF THE OUTBOARD LAMP IN NORMAL
AND EMERGENCY POWERED LUMINAIRE
-SWITCH, KEYSWITCH
P
-SWITCH
a
-SWITCH, 2 POLE
-SWITCH, 3-WAY
b
-SWITCH, 4-WAY
K
-SWITCH - PILOT LIGHT
M -MOTOR RATED SWITCH
-SWITCH, 3-WAY, LEG a FOR CONTROL OF THE INBOARD LAMP IN
NORMAL AND EMERGENCY POWERED LUMINAIRE
-SWITCH, 3-WAY, LEG b FOR CONTROL OF THE OUTBOARD LAMP IN
NORMAL AND EMERGENCY POWERED LUMINAIRE
-SWITCH, KEYSWITCH, 3-WAY
TS
SWITCHES
-SWITCH - LINE VOLTAGE TIMER, 120/277 VAC. WATTSTOPPER TS-400
OR EQUAL
-DUAL ULTRASONIC/PIR-DUAL RELAY WALL SWITCH DECORATOR
MOTION SENSOR, 120/277VAC, 800/1200W, WATTSTOPPER DW-200 OR
EQUAL
D2
-DUAL ULTRASONIC/PIR-MULTI-WAY WALL SWITCH DECORATOR
MOTION SENSOR, 120/277VAC, 800/1200W, WATTSTOPPER DW-103 OR
EQUAL
D3
-SWITCH, EXPLOSION PROOF
-BLACK QUAD RECEPTACLE FOR COMPUTER WORKSTATION
C
-4' FLUORESCENT STRIP FIXTURE
-4' FLUORESCENT STRIP FIXTURE, BATTERY/EMERGENCY
-4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED
-4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED,
BATTERY/EMERGENCY
3a
3b
3K
EXP
LB
-ELECTRIC STRIKE
ELECTRICAL SYMBOLS LEGEND
-*FOR LOW VOLTAGE OCCUPANCY SENSORS, PROVIDE POWER
PACK(S) 120/277 VAC; 20 AMPS, 225mA SECONDARY AS NEEDED FOR
ZONE/AREA CONTROL, WATTSTOPPER BZ-150 OR EQUAL.
POWER DEVICES ABBREVIATIONS
-AMPERES
-ABOVE FINISHED FLOOR
-ABOVE FINISHED GRADE
-BELOW FINISHED GRADE
-ELECTRIC UNIT HEATER
-ELECTRIC WATER COOLER
-ELECTRIC WATER HEATER
-ELECTRICAL METALLIC TUBING
-BELOW FINISHED CEILING
EWH
FLUOR
FA
EXIST
EXH
EQUIP
EWC
EUH
EMT
EF
-FLUORESCENT
-FIRE ALARM
-EXHAUST
-EXISTING
-EXHAUST FAN
-EQUIPMENT
CLG
DISC
DWG
EA
CU
CL
CAB
CKT
BFG
-CEILING
-CENTERLINE
-DISCONNECT(ING)
-DRAWING(S)
-EACH
-COPPER
-CABINET
-CIRCUIT
-CONDUIT
AFG
BFC
A
AFF
FLA -FULL LOAD AMPERES
-ABOVE FINISHED CEILINGAFC
GFCI -GROUND FAULT CIRCUIT INTERRUPTER
-CURRENT TRANSFORMERSCT's
C
AIC -AMPERES INTERRUPTING CAPACITY
-AMERICAN WIRE GAUGEAWG
EXP -EXPLOSION PROOF
-AUDIO ENHANCEMENTAE
-ALUMINUMAL
ECB -ENCLOSED CIRCUIT BREAKER
-NATIONAL ELECTRICAL CODENEC
MTR
MTG
MTD
MISC
MIN -MINIMUM
-MISCELLANEOUS
-MOUNTED
-MOUNTING
-MOTOR
-HEATING, VENTILATING, & AIR CONDITIONING
-KILO-VOLTS-AMPERES
-KILO-WATT-HOURS
-MOTOR CONTROL CENTERMCC
MH
MFR
MAX
LTG
kVA kWH kW kV
JB
-METAL HALIDE
-LIGHTING
-MANUFACTURER
-MAXIMUM
-JUNCTION BOX
-KILO-VOLTS
-KILO-WATTS
HVAC
HV
INC
HP -HORSEPOWER
-HIGH VOLTAGE
-INCANDESCENT
-KILO-VOLTS-AMPERES REACTIVEkVAR m -METER mm -MILLIMETER
MCB -MAIN CIRCUIT BREAKER
MCP -MOTOR CIRCUIT PROTECTOR
-HAND-OFF-AUTOMATIC
-HIGH INTENSITY DISCHARGE
-HIGH PRESSURE SODIUM
HID
HOA
HPS
GND
HGT
-GROUND
-HEIGHT
GFP -GROUND FAULT PROTECTION
MMS -MANUAL MOTOR STARTER SWITCH
-NOTIFICATION APPLIANCE CIRCUITNAC
-NIGHT LIGHT, UNSWITCHEDNL
-UNLESS OTHERWISE NOTED
XFMR
V
WP
VA
TEL
UON
-TRANSFORMER
-TELEPHONE
-VOLT-AMPERES
-WEATHER PROOF
-VOLTS
REC -RECEPTACLE
W -WATTS
TYP -TYPICAL
RGS -RIGID GALVANIZED STEEL
VFD -VARIABLE FREQUENCY DRIVE
SPD -SURGE PROTECTION DEVICE
-POLYVINYL CHLORIDEPVC
-PULL STATION INSIDEPSI
PNL -PANEL
MOUNTING 3" ABOVE COUNTER OR BACK SPLASH
C
1. DATA JACKS:
EACH RJ45 CAT6 JACK FOR DATA SHALL BE CONNECTED TO A DEDICATED
UTP 4 PR CAT6 CABLE
COMMUNICATIONS "INFORMATION OUTLET" MOUNTED. AT RECEPTACLE HEIGHT
UNLESS OTHERWISE NOTED. MODULE AND FACEPLATENX
X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE ADAPTER (P)OLE,
(R)ACEWAY, (D)OUBLE GANG FLUSH, (PD) PEDESTAL
N = # OF DATA JACKS
WALL TELEPHONE OUTLET FOR HOUSE PHONE. MOUNTED AT 52" ABOVE
FINISHED FLOOR TO TOP.
SPECIAL NOTES:
3/4" PLYWOOD BACKBOARD, FIRE RETARDANT.
IDF - 2 POST RACK
WALL DATA OUTLET. SURFACE MOUNTED AT 48" ABOVE FINISHED FLOOR TO
TOP OF BACKBOX. X = # OF DATA JACKS
WIRELESS ACCESS POINT. PROVIDE CAT 6 CABLE HOMERUN TO IDF AND
TERMINATE WITH RJ45 JACK FLUSH CEILING MOUNTED, WITH 10' OF COILED
CABLE ABOVE CEILING.
WIRELESS ACCESS POINT WALL MOUNTED 10'-0" TO 12'-0" ABOVE FINISHED
FLOOR PROVIDE CAT 6 CABLE HOMERUN TO IDF AND TERMINATE TO RJ45 JACK
FLUSH ON WALL.
FLOOR BOX DATA OUTLET. DATA OUTLET INSTALLED IN FLOOR BOX WITH UTP
HOMERUN TO COMM ROOM. X = # OF DATA JACKS
WAP
SX
W F1
PREMISE DISTRIBUTION SYSTEM
WAP
TELEVISION OUTLET, RG6 CABLE TO COMMUNICATIONS ROOM
-SWITCH, DIMMING 0-10VD
TO THE BEST KNOWLEDGE AND
UNDERSTANDING OF THE EOR, THESE
DRAWINGS AND SPECIFICATIONS HAVE ALL THE
INFORMATION REQUIRED BY FAC 61G15-33.005,
INCLUDING BUT NOT LIMITED TO:
1) COMMUNICATIONS SYSTEMS ARE
DESIGNED IN THE DRAWINGS AND
SPECIFICATIONS PER FBC SIXTH EDITION
AND OTHER CODES AND STANDARDS
LISTED IN SPECIFICATION SECTIONS 27 26
26 PART 1.1 AND 27 41 33 PART 1.5.
2) DRAWING AND SPECIFICATIONS CONTAIN:
a) SYSTEM RISERS (SHEET E601).
b) SYMBOL LEGEND (E001).
c) CABLING REQUIREMENTS (27 26 26 PART 2
AND 27 41 33 PART 1.3, 2.4)
d) DEVICE TYPE AND LOCATIONS (E203, E203A AND 27 26 26 PART 2, 27 41 33 PART
2.2).
e) BACKUP POWER SOURCES ARE OWNER
PROVIDED ON THIS PROJECT.
f) INSTALLATION, IDENTIFICATION, AND
TESTING REQUIREMENTS (27…