C05__Attachment_3_-_AquaLogic_MT-10_Water_Chiller_Drawing.PDF

PDF 266 KB Posted

Attached to
NCAO Livingston Stone National FH Chiller Units
Solicitation number
140R2022Q0026
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

H

24" 1/4"

AIR OUTLET KEEP CLEAR

* SEE NOTES

FRONT VIEW

DETAIL

"A"

ELECTRICAL AND

REFRIGERANT

COMPONENT

SERVICE PANEL ACCESS

FIELD INSTALL

FLOW SWITCH

3" WATER

OUTLET

DIGITAL

TEMPERATURE

CONTROLLER

MAIN POWER

IN

3" WATER

INLET

TITANIUM TUBE

COIL

INSULATED 8" SCH 40 PVC

HEAT EXCHANGER SHELL.

W

L

INSTALLATION

CLEARANCE

*SEE NOTES

304 STAINLESS

STEEL STAND

10 x

DIAMETER

6 x

DIAMETER

MT-9 THRU MT-12

SPECIFICATIONS

MT-9 THRU MT-12 SPECIFICATION

FOR INDOOR OR OUTDOOR FRESH AND SALT

WATER APPLICATIONS

*NOTES:

· TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100 INCHES MINIMUM.

· UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT.

· MINIMUM CLEARANCE FOR PROPER OPERATION IS 36 INCHES FROM WALLS, SHRUBBERY, FENCES, ETC.

· MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72 INCHES.

· ALL DIMENSIONS ARE APPROXIMATE AND CAN CHANGE AT ANY TIME.

PLAN VIEW

*NORMAL OPERATING AMBIENT AIR TEMPERATURE: 50 F - 115 F.

*ADD LOW AMBIENT HEAD PRESSURE CONTROL FOR OPERATING IN AMBIENT AIR TEMPERATURES FROM 0 F TO 50 F.

CONSULT AQUA LOGIC IF OPERATING AT TEMPERATURES OUTSIDE THESE RANGES.

1:29

PDF-0051

MULTI TEMP AIR COOLED WATER CHILLER

IMPORTANT!

·DETAIL "A"

· FLOW SWITCH MUST BE FIELD INSTALLED

HORIZONTALLY WITH NO LESS THAN 10

TIMES THE DIAMETER OF STRAIGHT PIPE

ON THE INLET SIDE AND NO LESS THAN 6

TIMES THE DIAMETER ON THE OUTLET

SIDE.

OPTIONS:

· SCH 80 SHELL CONSTRUCTION.

· 316 STAINLESS STEEL STAND AND HARDWARE.

· LOW AMBIENT HEAD PRESSURE CONTROL.

· HAIL GUARDS TO PROTECT CONDENSER FINS.

· COASTAL MARINE CONDENSER COATING.

*INLET, OUTLET AND FLOW SWITCH ARE 3" (SLIP) CONNECTIONS.

MULTI-TEMP WATER CHILLERS

MODEL NO. NOMINAL

TONS / BTUH / KW

VOLTS /

PHASE

AMPS

RLA / LRA

WATER

FLOW RATE

(GPM)

AIR

OULET

(CFM)

MCA

MAX FUSE /

CIRCUIT

BREAKER

L W H

SHIPPING

WEIGHT

(~lbs.)

MT-9 7.5 / 90K / 26.3 208 - 240 / 3 28 / 164 60 / 120 5100 34 50 51" 42" 68" 670

MT-9-460 7.5 / 90K / 26.3 460 / 3 15 / 100 60 / 120 5100 17 25 51" 42" 68" 675

MT-10 10 / 120K / 35.1 208 - 240 / 3 35 / 225 60 / 120 7500 46 70 61" 46" 68" 815

MT-10-460 10 / 120K / 35.1 460 / 3 19 / 114 60 / 120 7500 25 40 61" 46" 68" 815

MT-12 12.5 / 150K / 43.9 208 - 240 / 3 50 / 149 60 / 120 7800 55 70 61" 46" 74" 965

MT-12-460 12.5 / 150K / 43.9 460 / 3 27 / 75 60 / 120 7800 26 35 61" 46" 74" 965

DATEDRAWN BY

* COPYRIGHT *

These drawings including design idea and construction techniques herin are the sole property of Aqua Logic Inc. They shall not be revised, copied, or reproduced in any manner without the written consent of Aqua Logic Inc..

2/13/2019 1 OF 1

SHEET #

SHEET TITLE

SCALE

DESCRIPTION

REVISION

DRAWING #

9558 Camino Ruiz, San Diego, CA 92126

Arnaldo Guzman

Sheet1
Drawing View1
Drawing View2
Drawing View3
Drawing View5

File details come from the government source that posted it. Updated .