This document is a software design document outlining the human-machine interface and programmable logic controller controls for a fish hatchery spawning treatment system. The system will maintain water levels in two tanks using a motorized valve, with alarms for high and low levels. The interface includes status screens, trend graphs, I/O mapping and alarm logs. It also details login procedures, email alarm settings, two modes of motorized valve control, IP addresses and battery maintenance. Technical support contact information is provided.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Nimbus Fish Hatchery Project
Converse Construction LLC Revision 2
Prepared By:
John Cokeley 6617 SW Walnut Terrace Tigard, OR 97223 Cell (530) 524-6546 cokeley@gmail.com
Revision Log:
1 – June 2018 – Draft 2 – As Commissioned
Attachment 5 - OM Nimbus Gate Spawning Design Document
Nimbus Hatchery Spawning Treatment Software Design Document
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 2 of 17
Table of Contents
1 OVERVIEW
2 HMI INTERFACE
2.1 MAIN SCREEN SPAWNING
2.1.1 Status Points
2.1.2 Alarm Screen
2.1.3 Alarms
2.2 MAIN SCREEN TOWNER
2.2.1 Status Points
2.2.2 Alarm Screen
2.2.3 Alarms
2.3 TREND SCREEN
2.4 PLC IO SCREEN
2.5 TECH SCREEN
2.6 LOGIN
3 EMAIL ALARM SETTINGS
4 PLC CONTROLS
4.1 OVERVIEW
4.1.1 Operation Modes
5 IP MAPPING
6 NOTE ON BATTERIES
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 3 of 17
1 Overview
This document covers the Nimbus hatchery spawning treatment software design.
The control panel main function is to operate a motor operated vale (MOV) to maintain a water level in Tank 2 set by the operator. It also has local and remote alarms from the drum filter and ultra violet treatment tanks.
Contact Info for Tech Support – Leslie Converse 530-378-5591 20553 Sunset Lane Redding, CA 96002
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 4 of 17
2 HMI Interface
2.1 Main Screen Spawning
2.1.1 Status Points
MOV Status in local or remote MOV Mode in auto or manual MOV position
Tank 1 level with high/low alarms The bar graph color is
Yellow below the low SP Red above the high SP Green with operating SP
Tank 2 level with high/low alarms The bar graph color is
Yellow below the low SP Red above the high SP
Any current alarms are scrolled in the lower right box.
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 5 of 17
2.1.2 Alarm Screen
2.1.3 Alarms
NHS-Tank 1 High Alarm NHS-Tank 1 Low Alarm NHS-Tank 2 High Alarm NHS-Tank 2 Low Alarm NHS-MOV Position Tracking Alarm NHS-MOV Not in Remote NHS-MOV Fault NHS-Drum Filter 3 High Level NHS-Drum Filter 4 High Level NHS-UVS-1 Common Alarm NHS-UVS-2 Common Alarm NHS-Power/PS Fault NHS-Battery OK MOV Position Transducer Fault Tank 1 Level Transducer Fault Tank 2 Level Transducer Fault
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 6 of 17
2.2 Main Screen Towner
2.2.1 Status Points
MOV Status in local or remote MOV Mode in auto or manual MOV position
Tank 1 level with high/low alarms The bar graph color is
Yellow below the low SP Red above the high SP Green with operating SP
Any current alarms are scrolled in the lower right box.
2.2.2 Alarm Screen
Printed - 8/13/2018 SDD Rev 4 Page 7 of 17
2.2.3 Alarms
NHS-Tank 1 High Alarm NHS-Tank 1 Low Alarm NHS-MOV Position Tracking Alarm NHS-MOV Not in Remote NHS-MOV Fault NHS-Power/PS Fault NHS-Battery OK MOV Position Transducer Fault Tank 1 Level Transducer Fault
It is recommended that reducing flows from the down should be done slowly for the PLC to process the changes and prevent over topping the tower.
Printed - 8/13/2018 SDD Rev 4 Page 8 of 17
2.3 Trend Screen
Spawning trend shows MOV position, Tank 1 and Tank 2 levels.
Tower trend shows MOV position and Tank 1 Level
Printed - 8/13/2018 SDD Rev 4 Page 9 of 17
2.4 PLC IO Screen
This screen shows the digital status of the 16-point input card along with operator controllable setpoints. When an operator is logged in the setpoints will not be grayed out. By pressing on any yellow boxed setting will popup a numeric screen to enter a new value.
The operator adjustments are displayed in yellow boxes. By pressing the number, the operator can enter a new value.
By pressing on the Horn of Beacon button the operator can enable or disable the beacon light and horn on top of the control panel.
Printed - 8/13/2018 SDD Rev 4 Page 10 of 17
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 11 of 17
Below is the screen as show when a Tech is logged in. This will allow a tech to adjust system setpoints. By pressing the Tech button, the Tech screen will be displayed.
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 12 of 17
2.5 Tech Screen
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 13 of 17
2.6 Login
Logging In.
When logging in as Operator press the Login button. A login screen will be displayed.
Then press the Login Operator and then enter the password using the keypad.
User Password Note Tech 4321 Master User Operator 1234 Local Operator with Control
After entering the information press Enter. The Logged Out will change to Logged In if the correct password is entered.
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 14 of 17
3 Email Alarm settings.
Not included.
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 15 of 17
4 PLC Controls
4.1 Overview
The AD2000 is programmed to perform automatic control functions for the MOV to maintain a water level setpoint. It also provides a manual mode to position the MOV to any position from 0% to 100%.
The AD200 software is developed using Productivity Suite 2.4.2.2. This software runs under Microsoft Windows and can be downloaded from www.automationdirect.com for free.
4.1.1 Operation Modes
The operation mode is chosen using the selector switch located on the HMI Main screen. The two modes are Manual and Auto. The operation modes are described below.
Manual Operation Mode In this mode, the MOV position is control by a manual setpoint entered by the operator. When placed in this position the MOV will move to the setpoint. By entering a 0% setpoint, the valve will close, and water will stop flowing
Auto Operation Mode In this mode control of the PLC will control the MOV setpoint to maintain a level in Tank 2. The level setpoint is the elevation in feet.
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 16 of 17
5 IP Mapping
NFH IP Address 2000 PLC Spawning 192.168.1.50
Maple HMI Spawning 192.168.1.51
2000 PLC Tower 192.168.1.60 Maple HMI Tower 192.168.1.61
August 2018
Printed - 8/13/2018 SDD Rev 4 Page 17 of 17
6 Note on Batteries
The internal batteries will maintain the alarm during a power outage for approximately two hours. They should be check once a year to make sure no corrosion builds up on the terminals. Every two to three years they will need to be replaced.