HVAC Exhaust Replacement for USDA ARS in Corvallis, OR
Solicitation number
1232SA26Q0648
Issued by

About this file

This document set comprises the design drawings and specifications for a laboratory exhaust system upgrade project at the USDA Agricultural Research Services facility in Corvallis, Oregon (3420 NW Orchard Avenue). The project involves adding a new laboratory exhaust fan and re-balancing building airflows to maintain proper pressure relationships in laboratory areas while coordinating with existing facility operations and systems.

The primary scope includes installation of a new rooftop exhaust fan (EF-10) rated at 8,470 CFM with 1.75 inches water column static pressure, served by a 7.5 HP motor requiring 208V/3-phase power with a 30-amp breaker. The system incorporates two variable-volume exhaust terminal units (ETU-01 and ETU-02) on the first and second floors respectively, connected to existing ductwork. The contractor is responsible for final crane lift planning and site restoration, including preparation and repair of sprinklers, sidewalks, and asphalt. Construction work requires careful coordination with laboratory staff and facilities teams regarding HVAC shutdowns. The project includes structural roof modifications, mechanical ductwork connections, controls integration with the existing Building Automation System via BACnet, and differential pressure sensors to maintain negative pressurization in laboratory spaces. All work must comply with SMACNA standards, NFPA 90A and 90B, and current NEC codes as adopted by the State of Oregon. Equipment schedules specify an insulated roof curb, birdscreen, isolation damper, and NEMA 4X VFD controller, with basis-of-design equipment identified for mechanical and electrical components.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT SUMMARY

THE USDA RESEARCH LAB IN CORVALLIS WAS CONSTRUCTED IN 1971, EXPANDED IN 1993, AND RECENTLY HAD SEVERAL ROOFTOP UNITS REPLACED. THIS PROJECT WILL ADD A NEW LABORATORY EXHAUST FAN AND RE-BALANCE THE BUILDING AIRFLOWS TO MAINTAIN PRESSURE RELATIONSHIPS

IN LABORATORY AREAS.

THE CONTRACTOR SHALL COORDINATE CAREFULLY WITH THE LABORATORY STAFF AND FACILITIES

TEAM REGARDING THE VARIOUS BUILDING HVAC SHUTDOWNS REQUIRED TO COMPLETE THE

PROJECT.

THE ELECTRICAL DRAWINGS DETAIL THE ELECTRICAL-SPECIFIC REQUIREMENTS IN ACCORDANCE

WITH THE ABOVE.

THE FINAL CRANE LIFT PLAN SHALL BE THE RESPONSIBILITY OF THE AWARDED CONTRACTOR. THE CRANE SHALL UTILIZE WOOD OR SIMILAR TO DISTRIBUTE THE OUTRIGGER POINT LOADS WHERE

THEY ARE LOCATED OVER UNDERGROUND UTILITIES. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR PREPARING THE GROUND FOR THE CRANE AND RESTORING THE SITE TO ORIGINAL CONDITION

AS AGREED-UPON AT TIME OF AWARD TO INCLUDE ANY NECESSARY REPAIRS TO SPRINKLERS,

SIDEWALKS, ASPHALT, ETC.

PROJECT AREA

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:2

:2

A M

02/04/2026

TAH

PJTM

230612

G-001

COVER SHEET

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

USDA AGRICULTURAL

RESEARCH SERVICES

LABORATORY EXHAUST

HORTICULTURAL CROPS RESEARCH LAB

3420 NW ORCHARD AVE.

CORVALLIS OR, 97331

BENTON COUNTY

OREGON STATE

BENTON COUNTY STREET VIEW

01 16

PROJECT SHEET INDEX

SHEET NUMBER SHEET NAME

G-001 COVER SHEET

STRUCTURAL

S-001 GEN. STRUCTURAL NOTES

S-101 EXISTING ROOF FRAMING PLAN

MECHANICAL

M-001 MECHANICAL LEGENDS AND ABBREVIATIONS

MD-101 FIRST FLOOR PLAN WEST MECHANICAL DEMO PLAN

MD-102 SECOND FLOOR PLAN WEST MECHANICAL DEMO PLAN

MD-103 MECHANICAL ROOF DEMO PLAN

M-201 FIRST FLOOR WEST ZONE PLAN

M-202 SECOND FLOOR WEST ZONE PLAN

M-203 FIRST FLOOR WEST MECHANICAL PLAN

M-204 SECOND FLOOR WEST MECHANICAL PLAN

M-205 MECHANICAL ROOF PLAN

M-501 MECHANICAL DETAILS

M-701 MECHANICAL CONTROLS

M-702 MECHANICAL SCHEDULES

ELECTRICAL

E-001 ELECTRICAL LEGEND, SECOND FLOOR & ROOF WEST PLANS & SCHEDULES

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

HORTICULTURAL

CROPS RESEARCH LAB

3420 NW ORCHARD

AVE., CORVALLIS, OR

97331

USDA ARS

LABORATORY

EXHAUST

230612

02/04/26

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

E

E

2 3 4 5 6

2 3 4 5 6

FINAL TURNOVER

21P:

\S

PO

\23

JO

BS

\23

C

OR

VA

LL

IS

A

RS

A

HU

R

EP

LA

CE

ME

NT

S\ 0.0

D W

GS

\S

\23

_S

-0

.D W

G.

_S -0

: C

LIN

E, K

EV

IN

: L

AS

T

SA

VE

D:

Ja nu ar y 9 , 2

6 :

P

LO

T

DA

TE

: 2

/3/ www.coffman.com ph 509.328.2994

10 N. Post Street, Spokane, WA 99201 Suite 500

CEI# 230612

(A) ABOVE

AB ANCHOR BOLT

AC ASPHALT CONCRETE

ACI AMERICAN CONCRETE INSTITUTE

ADDL ADDITIONAL

ADH ADHESIVE

ADJ ADJACENT

ADESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL

AFF ABOVE FINISHED FLOOR

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

AISI AMERICAN IRON AND STEEL INSTITUTE

ALT ALTERNATE

ALUM ALUMINUM

ARCH ARCHITECTURAL

ASPH ASPHALT

ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS

ASNT AMERICAN SOCIETY OF NON-DESTRUCTIVE TESTING

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

AWS AMERICAN WELDING SOCIETY

(B) BELOW

BLKG BLOCKING

BLDG BUILDING

BOC BOTTOM OF CONCRETE

BOD BOTTOM OF DECKING

BOS BOTTOM OF STEEL

BOT BOTTOM

BP BASE PLATE

BRNG BEARING

BS BOTH SIDES

BTWN BETWEEN

CANT CANTILEVER

CBF CONCENTRIC BRACED FRAME

CFS COLD FORMED STEEL

CHAN CHANNEL

CIP CAST IN PLACE

CJ CONTROL OR CONSTRUCTION JOINT

CJP COMPLETE JOINT PENETRATION

CL CENTER LINE

CLR CLEAR, CLEARANCE

CM CUBIC METER

CMP CORRUGATED METAL PIPE

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CP COMPLETE PENETRATION

CTR CENTER, CENTERED

CY CUBIC YARD

D BEAM DEPTH

DP DEEP

DBA DEFORMED BAR ANCHOR

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DET DETAIL

DIAA DRILLED IN ADHESIVE ANCHOR

DIAG DIAGONAL

DIAM,Ø DIAMETER

DIEA DRILLED IN EXPANSION ANCHOR

DIM DIMENSION

DISA DRILLED IN SCREW ANCHOR

DIST DISTANCE

DN DOWN

DO DITTO

DWG DRAWING(S)

DWL DOWEL

E EAST, MODULUS OF ELASTICITY

(E) EXISTING

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATION OR ELEVATOR

EMBED EMBEDMENT

ENGR ENGINEER

EQ EQUAL

EQUIP EQUIPMENT

ES EACH SIDE

ESC ESCALATOR

EW EACH WAY

EXIST EXISTING

EXP EXPANSION, EXPOSURE

EXT EXTERIOR

F'c CONCRETE COMPRESSIVE STRENGTH

FCAW FLUX CORED ARCH WELDING

FDN FOUNDATION

FEMA FEDERAL EMERGENCY MANAGEMENT AGENCY

FIN FINISH

FLG FLANGE

F'm CONCRETE MASONRY COMPRESSIVE STRENGTH

FLR FLOOR

FP FIREPROOFING, FULL PENETRATION

FRD FACILITIES REQUIREMENTS DOCUMENT

FS FAR SIDE

FT FEET OR FOOT

FTG FOOTING

GA GAGE OR GAUGE

GALV GALVANIZED

GEN GENERAL

GLB GLUED LAMINATED BEAM

GR GRADE

GWB GYPSUM WALLBOARD

GYP GYPSUM

H HIGH

HAS HEADED ANCHOR STUD

HDR HEADER

HGR HANGER

HORIZ HORIZONTAL

HS HEADED STUD

HSB HIGH STRENGTH BOLT

HSS HOLLOW STRUCTURAL SECTION

HT HEIGHT

HVAC HEATING/VENTILATING/AIR CONDITIONING

I MOMENT OF INERTIA

IBC INTERNATIONAL BUILDING CODE

ICBO INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS

ICC INTERNATIONAL CODE COUNCIL

ID INSIDE DIAMETER

IE INVERT ELEVATION

IF INSIDE FACE

IJ ISOLATION JOINT

IN INCHES

INFO INFORMATION

INSUL INSULATE, INSULATION

INV INVERT

J JOULES

JST JOIST

JT JOINT

K KIP (1,000 POUNDS)

KSI KIPS PER SQUARE INCH

L LENGTH

LB POUND

LD REINF DEVELOPMENT LENGTH

LDh REINF DEVELOPMENT LENGTH (HOOKED BARS)

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LO LOW

LOC LOCATION

Ls REINF TENSION LAP SPLICE

LS LANDSCAPE

LSH LONG SLOTTED HOLE

LT LIGHT

LVF LOW VELOCITY FASTENER

LVL LEVEL, LAMINATED VENEER LUMBER

M METER

MAS MASONRY

MAX MAXIMUM

MECH MECHANICAL

MEZZ MEZZANINE

MF MOMENT FRAME

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MM MILLIMETER

MT MAGNETIC PARTICLE TEST

(N) NEW

N NORTH

NA NOT APPLICABLE

NAAMM NATIONAL ASSOCIATION OF ARCH METAL MANUFACTURERS

NFS NON FROST SUSCEPTABLE

NIC NOT IN CONTRACT

NIP NOT IN PERMIT

NO NUMBER

NORM NORMAL

NS NEAR SIDE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OF OUTSIDE FACE

OH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OVS OVERSIZE

OWJ OPEN WEB JOIST

PAF POWDER ACTUATED FASTENER

PC PRECAST

PCF POUND PER CUBIC FOOT

PEN PENETRATION

PIL PILASTER

PJP PARTIAL JOINT PENETRATION

PL PLATE

PLCS PLACES

PLWD PLYWOOD

PLF POUNDS PER LINEAR FOOT

PLWD PLYWOOD

PNL PANEL

PP PARTIAL PENETRATION

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT POINT, PENETRANT TEST, POINT OF TANGENCY

PRESSURE TREATED

R RADIUS

RAD RADIUS

RD ROOF DRAIN

REF REFERENCE

REINF REINFORCE, REINFORCING

REQD REQUIRED

RO ROUGH OPENING

RT RADIOGRAPHIC TEST

S SOUTH, SECTION MODULUS

SB STRAP BEAM

SC SLIP CRITICAL

SCBF SPECIAL CONCENTRIC BRACED FRAME

SCHD SCHEDULE

SD SNOW DRIFT

SDI STEEL DECK INSTITUTE

SEC SECTION

SFRS SEISMIC FORCE RESISTING SYSTEM

SHT SHEET

SHTG SHEATHING

SIM SIMILAR

SJ SEISMIC JOINT

SJ SLAB JOINT

SJRO SEISMIC JOINT ROUGH OPENING

SL SLOPE

SLB SNOW LOAD, BALANCED

SLRS SEISMIC LOAD RESISTING SYSTEM

SMAW SHIELDED METAL ARC WELDING

SOG SLAB ON GRADE

SPCS SPACES

SPEC SPECIFICATION

SQ SQUARE

SS STAINLESS STEEL

SSH SHORT SLOTTED HOLE

SSMA STEEL STUD MANUFACTURERS ASSOCIATION

STD STANDARD

STIFF STIFFENER

STL STEEL

STRUCT STRUCTURAL

SW SHEAR WALL

SYM SYMMETRICAL

TBC THREADED BAR COUPLER

TBD TO BE DETERMINED

TBR TO BE REMOVED

TC TENSION/COMPRESSION CHORD

TEMP TEMPORARY, TEMPERATURE

Tf FLANGE THICKNESS

THK THICK

TL TOTAL LOAD

T.A. TOP OF

TOC TOP OF CONCRETE

TOD TOP OF DECKING

TOF TOP OF FOOTING

TOS TOP OF STEEL, TOP OF SLAB

TOW TOP OF WALL

TS TUBE STEEL

Tw WEB THICKNESS

TYP TYPICAL

T&B TOP AND BOTTOM

UBC UNIFORM BUILDING CODE

UNO UNLESS NOTED OTHERWISE

UT ULTRASONIC TESTING

VERT VERTICAL

W WIDTH, WEST, WIDE FLANGE DESIGNATION

WF WIDE FLANGE

WHS WELDED HEADED STUD

WP WORK POINT, WATER PROOFING

WT WEIGHT

WWF WELDED WIRE FABRIC

W/ WITH

W/C WATER/ CEMENT RATIO

W/CM WATER/ CEMENTITIOUS MATERIALS RATIO

W/O WITHOUT

ABBR

STANDARD STRUCTURAL ABBREVIATIONS

DESCRIPTION

REVISION CLOUD AND REVISION NUMBER

ELEVATION SYMBOL

SECTION CUT LINE INDICATOR

GENERAL LEGEND

DETAIL SYMBOL:

SECTION SYMBOL:

B

SYMBOL

B

IDENTIFYING LETTER

SHEET WHERE SECTION IS SHOWNB =

A =

IDENTIFYING NUMBER

SHEET WHERE DETAIL IS SHOWN

A B

DESCRIPTION

INDICATES STEP IN ELEVATION

INDICATES STEP IN FOOTING ELEVATIONSS

INDICATES DECK SPAN DIRECTION

INDICATES MOMENT CONNECTION

DRAWING INDEX

DWG. NO. TITLE

S-001 GENERAL STRUCTURAL NOTES

S-101 EXISTING ROOF FRAMING PLAN

CMU (CONCRETE MASONRY UNIT) WALL (PLAN VIEW)

INDICATES DIAGONAL BRACING (PLAN VIEW)

ABBR DESCRIPTION

X INDICATES FOOTING MARK, SEE PLAN AND SCHEDULE

1 INDICATES PIER/PEDESTAL MARK, SEE PLAN AND SCHEDULE

INDICATES SHEAR WALL MARK, SEE PLAN AND SCHEDULEXXX

INDICATES GRADE BEAM MARK, SEE PLAN AND SCHEDULEGB1

GENERAL:

THE STRUCTURAL CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE STRUCTURE IS DESIGNED TO BE A STABLE UNIT AS A COMPLETED WHOLE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DESIGN, ERECT AND INSPECT TEMPORARY SHORES, BRACES, ETC. TO SUPPORT THE STRUCTURE AGAINST ALL ANTICIPATED LOADS INCLUDING GRAVITY, WIND AND LATERAL EARTH PRESSURE UNTIL ITS COMPLETION. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THESE METHODS OF CONSTRUCTION.

CONSTRUCTION MATERIAL SHALL BE PLACED ON FRAMED FLOORS AND ROOFS SUCH THAT THE DESIGN LIVE

LOADS ARE NOT EXCEEDED.

WORKMANSHIP AND MATERIALS SHALL COMPLY WITH THE EDITIONS OF THE INTERNATIONAL BUILDING CODE AND TESTING STANDARDS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION AND APPLICABLE AT THE TIME THE

PROJECT WAS PERMITTED.

NOTES AND DETAILS ON THE DRAWINGS TAKE PRECEDENCE OVER THE GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS. WHERE NOTES AND DETAILS ON DRAWINGS AND THESE GENERAL NOTES AND TYPICAL DETAILS ARE IN CONFLICT WITH THE PROJECT SPECIFICATION, THE MOST STRINGENT SHALL APPLY. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT SUBJECT TO REVIEW BY THE ARCHITECT AND ENGINEER. "TYPICAL" DETAILS ARE NOT FLAGGED ON THE DRAWINGS, BUT APPLY

UNLESS NOTED OTHERWISE.

FRAMING MEMBERS WHICH ARE NOT DIMENSIONED SHALL BE ASSUMED EQUALLY SPACED BETWEEN

DIMENSIONED POINT OF MEMBERS SUBJECT TO REVIEW BY THE ARCHITECT AND ENGINEER.

COORDINATION:

ALL DRAWINGS ARE CONSIDERED TO BE PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE STRUCTURAL DRAWINGS AND SPECIFICATIONS WITH THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER DISCIPLINES, INCLUDING BUT NOT LIMITED TO ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, FIRE PROTECTION, AND AMONG THE SUBCONTRACTORS PRIOR TO START OF CONSTRUCTION. ANY DISCREPANCIES THAT ARE FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO START OF CONSTRUCTION. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT HIS OWN EXPENSE

AND AT NO EXPENSE TO THE OWNER OR DESIGN TEAM.

THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS PRIOR TO STARTING

CONSTRUCTION. RESOLVE ANY DISCREPANCY WITH THE ENGINEER.

COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO, VERIFYING THE LOCATION AND WEIGHT OF ALL MECHANICAL AND ELECTRICAL EQUIPMENT, AS WELL AS, THE SIZE AND LOCATION OF ALL MECHANICAL OPENINGS IN ROOFS, FLOORS AND WALLS. UNLESS OTHERWISE NOTED ON THE DRAWINGS, DO NOT PENETRATE ANY STRUCTURAL ELEMENTS SUCH AS BEAMS, COLUMNS, WALLS, HEADERS, JAMBS, SLABS, ETC. WITHOUT PRIOR

WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.

SPECIAL INSPECTIONS:

THE OWNER WILL EMPLOY AN ICC CERTIFIED SPECIAL INSPECTOR TO PROVIDE INSPECTION OF REQUIRED ITEMS

PER IBC CHAPTER 17 AND THE REQUIREMENTS OF THE APPROPRIATE LOCAL JURISDICTION:

POST INSTALLED ANCHORS; SEE INFORMATION THIS SHEET.

CODE:

2022 EDITION OF THE OREGON STRUCTURAL SPECIALTY CODE.

DESIGN LOADS:

ROOF SNOW LOAD---------------------------------------------------------------------- SEE SNOW LOADS BELOW

RISK CATEGORY------------------------------------------------------------------------- II

WIND:

WIND SPEED (3 SECOND GUST) -------------------------------------------------- 96 MPH EXPOSURE CATEGORY--------------------------------------------------------------- B INTERNAL PRESSURE COEFFICIENT GCpi------------------------------------- +/- 0.18

SEISMIC:

IMPORTANCE FACTOR (Ie) ---------------------------------------------------------- 1.0 Ss -------------------------------------------------------------------------------------------- 0.885 S1 -------------------------------------------------------------------------------------------- 0.468 Sds ------------------------------------------------------------------------------------------ 0.676 Sd1 ------------------------------------------------------------------------------------------ 0.571 SITE CLASS-------------------------------------------------------------------------------- D

SEISMIC DESIGN CATEGORY------------------------------------------------------- D

SEISMIC FORCE RESISTING SYSTEM ------------------------------------------ REINFORCED MASONRY SHEAR

WALLS

RESPONSE MODIFICATION COEFFICIENT (Rp) ----------------------------- 6 SEISMIC RESPONSE FACTOR (Fp) ----------------------------------------------- 0.20 Wp OVERSTRENGTH FACTOR (Ω) ----------------------------------------------------- 2.5 ANALYSIS PROCEDURE ------------------------------------------------------------- EQUIVALENT LATERAL FORCE

SNOW:

GROUND SNOW LOAD --------------------------------------------------------------- 14 PSF FLAT ROOF SNOW LOAD ------------------------------------------------------------ 25 PSF SNOW EXPOSURE FACTOR (Ce) ------------------------------------------------- 1.0 SNOW LOAD IMPORTANCE FACTOR (Is) -------------------------------------- 1.0 THERMAL FACTOR (Ct) --------------------------------------------------------------- 1.0 SLOPE FACTOR ------------------------------------------------------------------------- 1.0

COLD-FORMED STEEL:

ALL COLD-FORMED STEEL FRAMING SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF "SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" BY THE AMERICAN IRON AND STEEL INSTITUTE AND IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

STEEL FOR ALL 54 MIL OR GREATER STUDS AND JOISTS, TRACK AND ALL THICKNESS OF DIAGONAL TENSION STRAPS SHALL HAVE A MINIMUM YIELD STRENGTH Fy = 50 KSI. STEEL FOR ALL 43 AND 33 MIL STUDS AND JOISTS, TRACK, AND ALL THICKNESS OF BRIDGING AND ACCESSORIES SHALL HAVE A MINIMUM YIELD STRENGTH Fy = 33 KSI.

STEEL SHALL BE GALVANIZED AT LOCATIONS EXPOSED TO WEATHER AND WHENEVER NOTED ON THE DRAWINGS IN ACCORDANCE WITH ASTM A653, GRADE D, FOR Fy = 50 KSI AND ASTM A653, GRADE A, FOR Fy = 33 KSI.

ALL STUDS SHALL BE SECURELY SEATED FOR FULL END BEARING ON TOP AND BOTTOM TRACK. SPLICING OF STUDS SHALL NOT BE PERMITTED. UNLESS NOTED OTHERWISE, PROVIDE DOUBLE STUDS AT ALL BEAM BEARINGS, JAMBS, WALL CORNERS AND INTERSECTIONS. UNLESS NOTED OTHERWISE, ALL TRACK SHALL BE OF THE SAME MATERIAL AND GAGE AS THE STUDS. BRIDGING SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS WITH THE

FOLLOWING MINIMUM REQUIREMENTS:

FOR NON-BEARING WALLS, PROVIDE BRIDGING AT MID-HEIGHT FOR WALLS LESS THAN OR EQUAL TO 10'-0" HIGH AND 5'-0" OC MAXIMUM FOR WALLS GREATER THAN 10'-0" HIGH. FOR BEARING WALLS, PROVIDE BRIDGING EQUALLY SPACED AT 4'0" OC MAXIMUM. IN ADDITION, BRIDGING SHALL BE PROVIDED AT ROOF LINES, FLOOR LINES AND ELSEWHERE AS SHOWN ON THE DRAWINGS. SOLID BLOCKING SHALL BE INSTALLED IN LIEU OF

BRIDGING WHERE NOTED ON THE DRAWINGS.

ALL WELDING SHALL BE PERFORMED BY AWS CERTIFIED WELDERS EXPERIENCED IN LIGHTGAGE STEEL FRAMING

WORK. USE E60 (MINIMUM) SERIES LOW HYDROGEN RODS.

STUDS SHOWN ARE NOTED USING STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) DESIGNATIONS AND SHALL

MEET THE MINIMUM REQUIREMENTS SHOWN IN THE LATEST EDITION OF THE SMA CATALOG.

FASTENERS:

HOT-DIPPED ZINC COATED STEEL FASTENERS CONFORMING TO THE REQUIREMENTS OF THE CURRENT EDITION OF

ASTM A153. SUBMIT TECHNICAL INFORMATION SHOWING CONFORMANCE.

FRAMING CONNECTORS:

FRAMING CONNECTORS SHALL BE ZINC COATED SHEET STEEL (GALVANIZED) BY THE HOT-DIP OR MATTE FINISH PROCESS. THE CORROSION RESISTANT COATING SHALL BE 1.25 OZ. POT YIELD COMMERCIAL CLASS HOT-DIPPED ZINC COATING, OR 0.625 OZ. MATTE FINISH HOT-DIPPED ZINC COATING EACH SIDE AND MAY BE APPLIED TO THE STEEL SHEET BEFORE THE CONNECTOR IS STAMPED OUT. FASTENERS FOR USE WITH THE FRAMING CONNECTORS

SHALL CONFORM WITH THE REQUIREMENTS ABOVE.

BASIS OF DESIGN IS SIMPSON STRONG-TIE OR SCAFCO PRODUCTS.

WOOD:

GENERAL:

DO NOT NOTCH OR DRILL JOISTS, BEAMS OR LOAD BEARING STUDS WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT. DOUBLE UP FLOOR JOISTS UNDER PARTITIONS. PROVIDE 1 x 3 OR METAL CROSS BRIDGING AT MIDSPAN OF ALL JOISTS. UNLESS NOTED OTHERWISE IN DRAWINGS OR DETAILS, DOUBLE UP STUDS AT JAMBS, AT GIRDER TRUSSES, AND UNDER BEAMS IN BEARING WALLS, STACKED CONTINUOUS TO FOUNDATION. AT BEAMS PERPENDICULAR TO BEARING WALLS, PROVIDE BUNDLED STUDS FOR FULL WIDTH OF BEAM STACKED CONTINUOUS TO FOUNDATION UNLESS NOTED OTHERWISE. PROVIDE 2 X SOLID BLOCKING AT MID-HEIGHT OF LOAD BEARING STUD WALLS. ALL NAILS SHALL BE COMMON NAILS. ALL NAILING NOT NOTED SHALL BE IN ACCORDANCE WITH TABLE 2304.10.1 OF THE LATEST EDITION OF THE INTERNATIONAL BUILDING CODE. ALL FRAMING ANCHORS AND CONNECTORS SHALL BE AS MANUFACTURED BY SIMPSON COMPANY OR OTHER APPROVED EQUAL WITH ICC CERTIFICATION. ALL NAIL HOLES IN FRAMING ANCHORS AND CONNECTORS SHALL BE FILLED WITH NAILS PER MANUFACTURERS PUBLISHED NAIL SIZES. ALL BOLTS SHALL BE

ASTM A307 BOLTS INSTALLED WITH STEEL WASHERS.

FRAMING LUMBER:

JOISTS

BEAMS

4x MEMBERS (MAX) 6x AND OVER

POSTS

4x MEMBERS (MAX) 6x AND OVER

STUDS

LEDGERS, TOP

AND BOT PLATES

1,350

1,200

1,600,000

1,600,000 1,600,000

1,600,000 1,600,000 1,600,000

1,600,000

1,350

1,350

1,350 1,000 1,350

1,350

DOUG FIR-LARCH #2

DOUG FIR-LARCH #2

DOUG FIR-LARCH #1

DOUG FIR-LARCH #2

DOUG FIR-LARCH #1

DOUG FIR-LARCH #2

DOUG FIR-LARCH #2

MEMBER Fb (PSI) Fv (PSI) E (PSI) Fc// (PSI). SPECIES & GRADE

ROOF 5/8" 32/16 8d @ 6" OC 8d @ 12" OC

ITEM THICKNESS

SPAN/INDEX

RATIO

EDGE

NAILING

INTERMEDIATE

NAILING

STRUCTURAL SHEATHING PROPERTIES AND ATTACHMENT

STRUCTURAL SHEATHING INCLUDES ALL-VENEER PLYWOOD:

ALL STRUCTURAL SHEATHING SHALL BE APA RATED SHEATHING WITH AN EXTERIOR OR EXPOSURE 1 DURABILITY CLASSIFICATION AND SHALL BEAR THE STAMP OF AN APPROVED TESTING AGENCY. LAY UP FLOOR AND ROOF WITH THE LONG DIMENSION PERPENDICULAR TO SUPPORTS AND PROVIDE PANEL LENGTHS TO BE CONTINUOUS OVER TWO OR MORE SUPPORTS. ALL WEATHER WOOD PLYWOOD SHALL BE BONDED WITH AN EXTERIOR GLUE AND BE GRADE MARKED INDICATING CONFORMANCE WITH THE CURRENT EDITION OF U.S. DEPARTMENT OF COMMERCE PRODUCT STANDARD PS 1 "STRUCTURAL PLYWOOD (WITH TYPICAL APA TRADEMARKS)", AND

STAMPED WITH AN APA GRADE MARK.

PRESSURE TREATMENT OF LUMBER AND PLYWOOD:

ALL LUMBER TO BE PRESERVATIVE TREATED SHALL BE PRESSURE TREATED IN ACCORDANCE WITH AMERICAN WOOD PRESERVERS BUREAU STANDARD AWPB-FDN AND BEAR THE QUALITY MARK OF AN APPROVED INSPECTION AGENCY PER AWPB-FDN. PLATES AND STUDS WITH ENDS CUT AFTER PRESSURE TREATING AND PLACED BELOW GRADE SHALL HAVE THE ENDS BELOW GRADE BRUSHED, DIPPED OR SOAKED WITH PRESERVATIVE UNTIL THE WOOD ABSORBS NO MORE PRESERVATIVE. USE THE FOLLOWING PRESERVATIVE FOR FIELD TREATMENT:

COPPER NAPHTHENATE CONTAINING A MINIMUM OF 2 PERCENT METALLIC COPPER IN SOLUTION.

ALL WEATHER WOOD FASTENERS:

NAILS: HOT-DIPPED ZINC COATED STEEL NAILS CONFORMING TO THE REQUIREMENTS OF THE CURRENT EDITION

OF ASTM A153. SUBMIT TECHNICAL INFORMATION SHOWING COMPLIANCE.

FRAMING ANCHORS:

FRAMING ANCHORS SHALL BE OF ZINC COATED SHEET STEEL (GALVANIZED) BY THE HOT-DIP OR MATTE FINISH PROCESS. THE CORROSION RESISTANT COATING SHALL BE 1.25 OZ. POT YIELD COMMERICAL CLASS HOT-DIPPED ZINC COATING, OR 0.625 OZ. MATTE FINISH HOT-DIPPED ZINC COATING EACH SIDE, AND MAY BE APPLIED TO THE STEEL SHEET BEFORE THE ANCHOR IS STAMPED OUT. NAILS/SCREWS FOR USE WITH FRAMING ANCHORS SHALL

CONFORM WITH THE REQUIREMENTS ABOVE. BASIS OF DESIGN ANCHORS ARE SIMPSON.

STEEL JOIST HANGERS SHALL BE TESTED AND APPROVED IN ACCORDANCE WITH IBC SECTION 1709.

SUBSTITUTIONS:

CONTRACTOR REQUESTED CHANGES OR SUBSTITUTIONS MUST BE SUBMITTED IN WRITING TO THE ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON THE SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. CONTRACTOR WILL BE RESPONSIBLE FOR ANY ADDITIONAL ENGINEERING EFFORT AND ASSOCIATED FEES REQUIRED FOR REVIEW AND APPROVAL OF REQUESTED CHANGES AND

SUBSTITUTIONS.

1. MECHANICAL EQUIPMENT CURBS.

SHOP DRAWINGS:

SUBMIT SHOP DRAWINGS FOR STRUCTURAL ENGINEER REVIEW PRIOR TO FABRICATION/ERECTION/INSTALLATION.

THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS PRIOR TO ENGINEERING REVIEW.

ENGINEERS REVIEW IS ONLY FOR GENERAL CONFORMANCE WITH WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. SUBMIT ELECTRONIC COPY FOR ENGINEERING REVIEW THAT INCLUDES CONTRACTOR'S REVIEW COMMENTS. DOCUMENT WILL BE

MARKED AND RETURNED ELECTRONICALLY.

THE CONTRACTOR SHALL ALLOW 2 WEEKS FOR ENGINEER'S REVIEW OF SUBMITTALS. COMMENTS

OR MARKS ON SUBMITTALS ARE A NORMAL AND EXPECTED PART OF THE SUBMITTAL PROCESS AND SHALL NOT BE USED AS A BASIS FOR CHANGE ORDERS. TIME REQUIRED TO REVISE AND SUBMIT ANY SUBMITTAL SHALL BE CONSIDERED INHERENT TO THE SUBMITTAL REVIEW PROCESS AND SHALL NOT BE DEEMED A CHANGE ORDER.

RE-SUBMITTALS SHALL HAVE ALL REVISIONS CLEARLY IDENTIFIED WITH DRAWINGS CLOUDS AND REVISION DATES.

THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE REVIEW OF ANY UNMARKED REVISIONS.

SHOP DRAWINGS SHALL BE SUBMITTED FOR THE FOLLOWING ITEMS IN ADDITION TO ANY SUBMITTAL

REQUIREMENTS SPECIFIED ON THESE PLANS OR IN THE PROJECT SPECIFICATIONS:

DOUG FIR/LARCH (NORTH) IS NOT AN ACCEPTABLE ALTERNATIVE TO DOUG FIR/LARCH LUMBER. CONTRACTOR TO SUBMIT A SUBSTITUTION REQUEST TO THE ENGINEER OF RECORD PRIOR TO START OF CONSTRUCTION IF DOUG

FIR/LARCH (NORTH) SUBSTITUTION IS DESIRED.

FRAMING LUMBER SHALL COMPLY WITH THE LATEST EDITION OF THE GRADING RULES OF THE WESTERN WOOD PRODUCTS ASSOCIATION (WWPA) OR THE WEST COAST LUMBER INSPECTIONS BUREAU (WCLIB). ALL SAWN LUMBER SHALL BE STAMPED WITH THE GRADE MARK OF AN APPROVED GRADING AGENCY. MOISTURE CONTENT

SHALL NOT EXCEED 19%.

STRUCTURAL SHEATHING:

POST-INSTALLED ANCHORAGE:

REBAR

HILTI HIT-RE 500 V3

SIMPSON SET-XP

DEWALT PURE 110+

EXPANSION ANCHORS

HILTI KWIK BOLT TZ2

SIMPSON STRONG-BOLT 2

DEWALT PURE 110+

ADHESIVE ANCHORS

HILTI HIT-HY 200 V3

SIMPSON SET-XP OR AT-XP

DEWALT PURE 110+

SCREW ANCHORS

HILTI KWIK KH-EZ

SIMPSON TITEN HD

DEWALT SCREW-BOLT+

ANCHORAGE TO GROUT FILLED CMU

EXPANSION ANCHORS

HILTI KWIK BOLT TZ2

STRONG BOLT 2

DEWALT POWER-STUD+SD1

SCREW ANCHORS

HILTI KWIK KH-EZ

SIMPSON TITEN HD

DEWALT SCREW-BOLT+

ADHESIVE ANCHORS

HILTI HIT-HY 270

SIMPSON SET-XP OR AT-XP (AT-XP CANNOT BE USED FOR ANCHORS IN THE TOP OF THE WALL) DEWALT

AC+100 GOLD

REBAR

HILTI HIT-HY 270

SIMPSON SET-XP

POWDER ACTUATED FASTENERS (SHOT PINS) IN CONCRETE OR GROUT FILLED CMU

HILTI X-U AND X-U 15 (0.157 ” )

SIMPSON PDP SERIES (0.145 ” MIN)

INSTALLATION AND SPECIAL INSPECTION:

ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-14 17.1.2) AND IN GROUTED MASONRY THAT HAS REACHED IT'S MINIMUM SPECIFIED COMPRESSIVE STRENGTH.

ADHESIVE ANCHORS INSTALLED IN HORIZONTAL OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS SHALL BE CONTINUOUSLY INSPECTED DURING INSTALLATION BY AN INSPECTOR SPECIALLY APPROVED FOR THAT PURPOSE BY THE BUILDING OFFICIAL (ACI 318-14 17.8.2.4) PROVIDE SPECIAL INSPECTION FOR ALL MECHANICAL AND ADHESIVE ANCHORS PER THE APPLICABLE

BUILDING CODE AND PER THE CURRENT ICC-ES REPORT (IBC 2018 TABLE 1705.3 NOTE B).

ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF CONCRETE OR CMU. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE

CLEARANCES INDICATED ON THE DRAWINGS.

EXISTING REINFORCING BARS IN THE CONCRETE OR CMU STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE OR CMU ANCHORS, BY HILTI FERROSCAN, GPR, X-RAY OR OTHER MEANS APPROVED BY ENGINEER OF RECORD. DO NOT CUT REBAR, RELOCATE ANCHOR, OR REDUCE EMBEDMENT WITHOUT WRITTEN APPROVAL BY THE ENGINEER OF

RECORD.

THREADED RODS FOR ADHESIVE ANCHORS SHALL BE CLEAN THREADED ROD. FOR USE IN INTERIOR LOCATIONS THREADED ROD TO BE ASTM F1554, GRADE 36. THREADED ROD FOR USE IN INTERIOR APPLICATIONS WITH HILTI ADHESIVE TO CONCRETE AND WITH DEWALT ADHESIVE TO GROUTED MASONRY SHALL HAVE A 0.0002-INCH THICK ZINC ELECTROPLATED COATING COMPLYING WITH ASTM B633 SC 1. THREADED ROD USED AT EXTERIOR CONDITIONS OR WHERE THE ANCHOR IS IN CONTACT WITH PRESERVATIVE-TREATED OR FIRE -RETARDANT-TREATED LUMBER SHALL BE EITHER STAINLESS STEEL OR SHALL HAVE A ZINC COATING. STAINLESS STEEL THREADED RODS SHALL CONFORM TO ASTM A193, GRADE B6, B8, OR B8M FOR SIMPSON ADHESIVE PRODUCTS TO MASONRY AND WITH REBAR TO CONCRETE AND SHALL CONFORM TO ASTM F593 (AISI 304 OR 316) FOR HILTI AND DEWALT ADHESIVE PRODUCTS AND FOR SIMPSON

ADHESIVE WITH THREADED ROD TO CONCRETE. ZINC COATING ON THREADED RODS SHALL BE

HOT-DIPPED IN ACCORDANCE WITH ASTM A153 CLASS C OR D COATING.OATING.

GENERAL STRUCTURAL NOTES

SWH

KLC

GENERAL STRUCTURAL

NOTES

S-001

2-3-2026

02 16 http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com

75'-0"

'-0

(E ) 2 x1 2 D

F

JO

IS

TS

" O C

SP

AC

IN

G

(T

YP

D E

D.2 D.5 D.7

(E) 5/8" PLYWOOD

SHEATHING (TYP)

THROUGHOUT

(E) ROOF HATCH

(E) SKYLIGHT

(E ) 1 x3 B

RI

DG

IN

G

(T

YP

(E) RTU-2

(E) RTU-4

(E) RTU-1

(E) DUCT OPENINGS

TO BE RE-USED

(E) RTU-3

(E) SKYLIGHT

A B C

(E) ELEVATOR

CAP

(E) HCP

CONCRETE

ROOF

36'-3" 17'-8" 20'-8" 20'-0"9'-3"41'-6"

36'-3"

'-0

'-0

152'-9"

'-0

'-0

'-9

1/ 4"

'-9

1/ 4"

(E) RTU-6

(E) 5" PIPE COLUMN,

TYP (3) PLACES

(E ) 1

4B x2

(E ) 1

4B x2

(E

) 1 4B x2

(E ) 1

4B x2

(E

) 1 4B x2

16'-8"

(E) RTU-5

(E) STEEL DECK OVER

LIGHTGAGE STEEL ROOF JOISTS

(E) WALLS BELOW

(E) 14FJ1200 JOISTS

(E) 12FJ1200 JOISTS @ 4'-0" OC

(E ) 1

2x

FJ

JO

IS

TS

2' -0

" O C

(E ) W x

(E ) 1

2x

FJ

JO

IS

TS

" O

C (E

) L

IG

HT

G

AU

GE

S

TE

EL

R

OO

F

TR

US

SE

S

(E ) 1

4F J1

0 J

OI

ST

S

" O

C

(E) W14x22

(E) W14x22

(E) INFILLED

ROOF TO REMAIN

(E) 2x6 @ 16" OC

D ED.2 D.5 D.7A B C

(E) 26 GA METAL B DECK

(E ) 2

6 G A

ME

TA

L B D

EC

K

(E ) W x

(E) STEEL DECK OVER

LIGHTGAGE STEEL ROOF JOISTS

DEMO (E) ROOF SYSTEM

FOR NEW EHAUST

OPENING

(N) EF-10

3'-9 7/8"

3'- 9 7

/8"

(N) 2x6 EA END

OF UNIT

S-101

S-101

CONTRACTOR TO SUBMIT

PROPOSED METHOD OF

SUPPORTING AND BRACING

NEW EXHAUST TERMINAL

UNITS BELOW ROOF AND 2ND

FLOOR FOR APPROVAL BY

STRUCTURAL ENGINEER

(N) ETU-02

(E) 3" RIGID INSULATION

(E) 2 1/2" CONC TOPPING

SLAB

(E) 8" CONC HOLLOW CORE

PLANK

SIMPSON LUS26 HANGER

(TYP)

(E) DECKING AND MEMBRANE

CONT 2x6 LEDGER W/ 1/2" x 6"

SCREW ANCHORS @ 16" OC

(TYP)

SHEATHING

PER PLAN

8" 2 1 /2"

3"

ADD 3" RIGID INSULATION

AND SHEATHING TO MATCH (E)

AT INFILLED OPENING

10d NAILS

@6" OC (TYP)

(E) WOOD JOIST

PER PLAN

SCALE:1 SECTION: INFILL DETAIL @ ROOF OPENING (AS REQUIRED)

3/8" = 1'-0" SCALE:2 FUME EXHAUST UNIT SUPPORT

3/8"=1'-0" HOLLOW CORE PLANK CONCRETE ROOF

(E) COVERBOARD &

ROOF MEMBRANE

(E) 3" RIGID INSULATION

3'-9"

(E) 8" CONC HOLLOW

CORE PLANK

DEMO (E) INFILLED ROOF

STRUCTURE AS REQ'D FOR

NEW EXHAUST DUCT

(N) EXHAUST

FUME UNIT

TOTAL WT

1,466 LBS

1'- 6"

(N) UNIT CURB BY OTHERS.

SUBMIT STAMPED DRAWING

OF CURB AND STAMPED

STRUCTURAL CALCULATIONS

FOR CURB

2 1 /2"

1 7/16" 1 7/16"

3'-9 7/8"

3'-7" 1" 1"

DUCT TRANSITION AS REQ'D,

BY MECH CONTRACTOR TYP

(E) 2 1/2" CONC

TOPPING SLAB

CONNECTION TO CURB BY

MECH CONTRACTOR, TYP

5" 5"

(E) 3" RIGID INSULATION

(E) ROOFING MEMBRANE,

REPAIR, INSULATE, FLASH,

AND SEAL AROUND CURB

AS REQUIRED FOR A

WATERPROOF ROOF

3'-7"

CURB CONNECTION TO CONCRETE ROOF

STRUCTURE BY CURB DESIGNER. SUBMIT

STAMPED STRUCTURAL CALCULATIONS

FOR CURB CONNECTION TO ROOF

STRUCTURE. NOTE THAT CONCRETE

ANCHORS REQUIRE SPECIAL INSPECTION

REV DATE DESCRIPTION

PROJ. NO.

DRAWN

CHECKED

DATE

SHEET OF

COFFMAN ENGINEERS INC.C

HORTICULTURAL

CROPS RESEARCH LAB

3420 NW ORCHARD

AVE., CORVALLIS, OR

97331

USDA ARS

LABORATORY

EXHAUST

230612

02/04/26

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

E

E

2 3 4 5 6

2 3 4 5 6

FINAL TURNOVER

21P:

\S

PO

\23

JO

BS

\23

C

OR

VA

LL

IS

A

RS

A

HU

R

EP

LA

CE

ME

NT

S\ 0.0

D W

GS

\S

\23

_S

-1

.D W

G.

_S -1

: C

LIN

E, K

EV

IN

: L

AS

T

SA

VE

D:

F eb ru ar y 3

, 2

6 :

P

LO

T

DA

TE

: 2 /3/ www.coffman.com ph 509.328.2994

10 N. Post Street, Spokane, WA 99201 Suite 500

CEI# 230612

SCALE:

PROJECT

NORTH 3/16" = 1'-0"

ROOF FRAMING PLAN

0 2 4 8 12 16

3/16"=1'-0"

SWH

KLC

EXISTING ROOF

FRAMING PLAN

S-101

2-3-2026

03 16 http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com

GENERAL HVAC NOTES

1. SHEET METAL DUCTWORK AND COMPONENTS INCLUDING HANGING, SEALING, PLENUMS, & ACCESSORIES SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS FOR HVAC DUCT CONSTRUCTION, NFPA 90A, & 90B STANDARDS.

2. ALL DUCTWORK OPENINGS SHALL BE COVERED DURING CONSTRUCTION.

3. ALL DAMPERS SHALL BE SET FULLY OPEN PRIOR TO BALANCING.

4. CONTRACTOR TO PROVIDE TRANSITION TO CONNECT TO ALL MECHANICAL EQUIPMENT. PROVIDE FLEXIBLE CONNECTION ON INTAKE AND DISCHARGE

OF ALL MECHANICAL EQUIPMENT.

5. DUCT DIMENSIONS SHOWN ARE INSIDE SHEET METAL DIMENSIONS OR CLEAR OPENING INSIDE LINED DUCT.

6. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND

PROVIDE ALL NECESSARY OFFSETS.

7. PROVIDE 1" THICK DUCT LINER IN ALL TRANSFER AIR DUCTWORK UNLESS NOTED OTHERWISE.

8. ALL ELBOWS SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE, OR SHALL HAVE TURNING VANES WHERE INDICATED ON PLANS. NO SQUARE

THROAT OR ZERO RADIUS ELBOWS ALLOWED.

9. ALL DUCT BRANCH CONNECTIONS TO DIFFUSER OR GRILLES, TO OR FROM MAIN DUCTS, SHALL INCLUDE MANUAL VOLUME DAMPERS. ALL SPIN-IN FITTINGS SHALL BE CONICAL, RECTANGULAR BRANCH DUCT TAKEOFFS SHALL HAVE 45° TAKEOFFS.

10. PROVIDE CONCEALED DAMPER REGULATORS OR ACCESS DOORS FOR ALL MANUAL VOLUME DAMPERS LOCATED THAT ARE INACCESSIBLE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO

INSTALLATION.

11. 24"x24" ACCESS DOORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE GYPSUM BOARD CEILINGS. ALL FINAL ACCESS

DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.

12. PROVIDE DIFFUSER AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES AND COORDINATE LOCATIONS WITH THE

ARCHITECTURAL REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING LAYOUT.

13. ALL DUCTWORK VISIBLE THROUGH RETURN OR SUPPLY GRILLES TO BE PAINTED FLAT BLACK.

14. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTS SHALL HAVE THE TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS

SEALED AIRTIGHT WITH DUCT SEALANT (SMACNA SEAL CLASS "A").

15. COORDINATE EXACT LOCATIONS OF ALL ROOM THERMOSTATS AND/OR ROOM TEMPERATURE SENSORS WITH ARCHITECT/OWNER PRIOR TO

INSTALLATION.

16. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A COPY OF THE BALANCE REPORT TO THE ENGINEER FOR REVIEW.

GENERAL ABBREVIATIONS

ø ROUND or DIAMETER

AAV AUTOMATIC AIR VENT

ABV ABOVE

AD ACCESS DOOR

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

AL ACOUSTIC LINED

AP ACCESS PANEL

APD AIR PRESSURE DROP

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AWT AVERAGE WATER TEMPERATURE

BB BASEBOARD

BBD BACKDRAFT DAMPER

BFF BELOW FINISH FLOOR

BHP BRAKE HORSEPOWER

BG BELOW GROUND/GRADE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

C CENTIGRADE

CC COOLING COIL

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CG CEILING GRILLE

CI CAST IRON

CLG CEILING

CO CLEANOUT

COG CLEANOUT TO GRADE

CMU CONCRETE MASONRY UNIT

CM CONDENSATE METER

CONC CONCRETE

CONN CONNECT or CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION

(D) DEMOLISH

DB DECIBEL or DRY BULB

DDC DIRECT DIGITAL CONTROL

DIA DIAMETER

DIM DIMENSION

DN DOWN

DOAS DEDICATED OUTDOOR AIR SYSTEM

DPR DAMPER

DPS DIFFERENTIAL PRESSURE SWITCH

DWG DRAWING

(E) EXISTING

EA EACH

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

ELEC ELECTRIC or ELECTRICAL

ELEV ELEVATION

EMCS ENERGY MANAGEMENT CONTROL

SYSTEM

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXST EXISTING

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCU FAN COIL UNIT

FD FLOOR DRAIN

FD FIRE DAMPER

FFD FUNNEL FLOOR DRAIN

FF FINAL FILTER

FLR FLOOR

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD COMBINATION FIRE/SMOKE DAMPER

FT FOOT/FEET

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAGE or GAUGE

GAL GALLON

GALV GALVANIZED

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRD GRILLE, REGISTER, OR DIFFUSER

H HEIGHT

HB HOSE BIBB

HD HEAD

HP HORSEPOWER

HRV HEAT RECOVERY VENTILATOR

HTG HEATING

HVAC HEATING, VENTILATION AND

AIR CONDITIONING

HWG HIGH WALL GRILLE

HWR HIGH WALL REGISTER

HZ HERTZ

ID INSIDE DIAMETER

IE INVERT ELEVATION

IN INCH or INCHES

INSUL INSULATION

INV INVERT

KH KICKSPACE HEATER

KW KILOWATT

KWH KILOWATT HOUR

L LENGTH

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LF LINEAR FOOT/FEET

LVG LEAVING

LWG LOW WALL GRILLE

LWR LOW WALL REGISTER

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MAV MANUAL AIR VENT

MBH 1000 BRITISH THERMAL UNITS

PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MCC MOTOR CONTROL CENTER

MFR MANUFACTURER

MOP MAXIMUM OVERCURRENT

PROTECTION

MUA MAKEUP AIR UNIT

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

MTG MOUNTING

(N) NEW

(NL) NEW LOCATION

N/A NOT APPLICABLE

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NC NOISE CRITERIA

N.I.C. NOT IN CONTRACT

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

O/C ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

PVC PRESSURE CONTROL VALVE

PD PRESSURE DROP

PH PHASE

PLCS PLACES

POC POINT OF CONNECTION

POUA POINT OF USE ALARM

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH (GAGE)

(REL) RELOCATE

RA RETURN AIR

RAG RETURN AIR GRILLE

REQD REQUIRED

R.O. ROUGH OPENING

RPBP REDUCED PRESSURE BACKFLOW

PREVENTER

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SD SMOKE DETECTOR

SF SUPPLY FAN

SHT SHEET

SIM SIMILAR

SL SOUNDLINING

SP STATIC PRESSURE

SQ SQUARE

SQ FT SQUARE FOOT/FEET

SS STAINLESS STEEL

STD STANDARD

TAB TESTING, ADJUSTING & BALANCING

THK THICK

TP TRAP PRIMER or TEST PLUG

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

TU TERMINAL UNIT

UBC UNIFORM BUILDING CODE

UFC UNIFORM FIRE CODE

UMC UNIFORM MECHANICAL CODE

UPC UNIFORM PLUMBING CODE

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

VA VALVE

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

VTR VENT THRU ROOF

W WIDE

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER COLUMN

WCO WALL CLEANOUT

WG WATER GAGE

WGE WASTE GAS EVACUATION

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WT WEIGHT

HVAC DUCTWORK LEGEND

DUCTWORK

24x12 S/A

RECTANGULAR DUCT

SIZE (INCHES) FIRST

DIMENSION IS SIDE OF

DUCT SHOWN

DUCT SIZES SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS OF DUCT. DUCT SIZE

SHOWN DOES NOT INCLUDE INSULATION OR LINING UNLESS NOTED OTHERWISE. SEE

BELOW FOR DUCT SIZE TAG LEGEND.

DUCT SIZE

DUCT SYSTEM ABBREVIATION

(NOT ALWAYS BE SHOWN)

INSULATED DUCT

SOUND LINED DUCT

24x12ø

FLAT OVAL DUCT

SIZE (INCHES) FIRST

DIMENSION IS SIDE OF

DUCT SHOWN

24ø ROUND DUCT

18ø24x12

CHANGE IN DUCT SIZE

AND/OR SHAPE

SUPPLY AIR (SA)

OUTSIDE AIR (OSA)

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

RETURN AIR (RA)

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

EXHAUST AIR (EA)

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

DAMPERS

VOLUME/BALANCING

DAMPER

FIRE DAMPER (FD)

SMOKE DAMPER (SD)

FIRE/SMOKE DAMPER

(FSD)

BACKDRAFT DAMPER

MOTORIZED DAMPER

DUCT SYSTEM ABBREVIATIONS

M

SUPPLY AIRSA

OUTSIDE AIROSA

COMBUSTION AIRCA

RETURN AIRRA

TRANSFER AIRTA

EXHAUST AIREA

FLEXIBLE DUCT

DUCT SYMBOLS

DUCT END CAP

DUCT ACCESS DOOR

AD

SUPPLY AIR (SA)

TERMINAL

RETURN AIR (RA) OR

TRANSFER AIR (TA) TERMINAL

AIR TERMINAL

IDENTIFICATION

EXHAUST AIR (EA) TERMINAL

GRILLE, REGISTER, OR OPEN

DUCT

X

CFM

AIRFLOW DIRECTION

SOUND ATTENUATOR

OR X-CFM

PIPING LEGEND

CS

CR

CWS

CWR

CONDENSER

WATER SUPPLY

CONDENSER

WATER RETURN

CHILLED WATER

SUPPLY

CHILLED WATER

RETURN

HWS

HWR

HEATING HOT

WATER SUPPLY

HEATING HOT

WATER RETURN

HGS

HGR

HEATING GLYCOL

SUPPLY

HEATING GLYCOL

RETURN

FOS

FOR

FUEL OIL SUPPLY

FUEL OIL RETURN

SMS

SMR

SNOWMELT

GLYCOL SUPPLY

SNOWMELT

GLYCOL RETURN

RL

REFRIGERANT

LIQUID LINE

RS

REFRIGERANT

SUCTION LINE

HRS

HIGH PRESSURE

REFRIGERANT

SUCTION LINE

GWS

GWR

GEOTHERMAL

WATER SUPPLY

GEOTHERMAL

WATER RETURN

G NATURAL GAS

PG PROPANE GAS

LPG

LIQUID PETROLEUM

GAS

CA COMPRESSED AIR

LPS

LOW PRESSURE

STEAM SUPPLY

LPR

LOW PRESSURE

STEAM RETURN

LPC

LOW PRESSURE

CONDENSATE

MPS

MEDIUM PRESSURE

STEAM SUPPLY

MPR

MEDIUM PRESSURE

STEAM RETURN

MPC

MEDIUM PRESSURE

CONDENSATE

HPS

HIGH PRESSURE

STEAM SUPPLY

HPR

HIGH PRESSURE

STEAM RETURN

HPC

HIGH PRESSURE

CONDENSATE

D

CONDENSATE

DRAIN (D)

VAC VACUUM (VAC)

PLUMBING/PIPING SYMBOLS LEGEND

VALVE

GATE VALVE

BALL VALVE

GLOBE VALVE

PLUG VALVE

BUTTERFLY VALVE

SPECIALTY VALVE

OS & Y VALVE

STOP COCK

PRESSURE REDUCING

VALVE

PRESSURE REGULATING

VALVE

CHECK VALVE

SPRING CHECK VALVE

STRAINER

STRAINER W/

BLOWDOWN

BACKFLOW PREVENTER

BALANCING VALVE

AUTOMATIC BALANCING

VALVE

A

RELIEF VALVE

FUEL ANTI-SIPHON

VALVE

F

FUSIBLE OIL SAFETY

VALVE

MOTORIZED VALVE

NEEDLE VALVE

M M

SOLENOID VALVE

S S

AUTOMATIC CONTROL

VALVE

FLOW SWITCH

PRESSURE SWITCH

FS

PS

PIPE ELBOW DOWN

(OR AWAY)

PIPE ELBOW UP

(OR TOWARDS)

PIPE TEE DOWN

(OR AWAY)

PIPE TEE UP

(OR AWAY)

FLOW DIRECTION

PIPE SLOPE

& DIRECTION

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

UNION

FLANGES

BLIND FLANGE

END CAP

PT PLUG (TEST PORT)

FLEX CONNECTOR/

COUPLING

EXPANSION JOINT

EXPANSION GUIDE

PIPE ANCHOR

HOSE QUICK

DISCONNECT

HOSE THREAD DRAIN

BALL VALVE

HOSE BIBB

WALL HYDRANT

HOSE THREAD DRAIN

VALVE

FIRE DEPARTMENT

CONNECTION

WATER HAMMER

ARRESTOR

THERMOWELL

THERMOMETER

DIAL THERMOMETER

T

PRESSURE GAUGE

W/ COCK

P

PRESSURE GAUGE

W/ COCK & SIPHON

P

AIR VENT

A - AUTOMATIC

C - COIN

M - MANUAL

H - HIGH VOLUME

A

BASKET STRAINER

AIR FILTER W/

COALESCER & DRAIN

AIR FILTER W/

COALESCER, DRAIN,

REGULATOR & GAUGE

PUMP (SYMBOLIC -

ARROW INDICATES

FLOW DIRECTION)

WATER METERM

WATER HAMMER

ARRESTOR (PLAN)

V#

S=2%

GENERAL LEGEND

THERMOSTAT. ADJACENT NUMBER

INDICATES TERMINAL UNIT CONTROLLED

HUMIDISTAT

SENSOR

CO2 SENSORCO2

T

H

S

PLUMBING FIXTURE TAG, SEE PLUMBING SCHEDULES

NOTES:

XX-X

SPECIFIC TO LOCATION(S) INDICATED.

A. NOTE APPLIES TO ENTIRE SHEET.

EXISTING

NEW

(E)

(N)

EXISTING (THIN)

NEW (MEDIUM)

POINT OF CONNECTION (POC)

EXISTING TO BE DEMOLISHED

MECHANICAL EQUIPMENT, SEE MECHANICAL SCHEDULES.XX-X

x

SD DUCT SMOKE DETECTOR

SP DUCT STATIC PRESSURE

LINETYPES:

B

A

A

B

DETAIL SYMBOL:

A = IDENTIFYING NUMBER

B = SHEET WHERE DETAIL IS SHOWN

SECTION SYMBOL:

A = IDENTIFYING NUMBER

B = SHEET WHERE DETAIL IS SHOWN

NEW LOCATION(NL)

RELOCATE(REL)

GENERAL NOTES

1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED PERMITS, LICENSES, AND INSPECTIONS FOR DURATION OF WORK UNLESS

DIRECTED OTHERWISE.

2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL APPLICABLE STATE AND LOCAL CODES, OR AUTHORITY HAVING

JURISDICTION.

3. SUBSTITUTIONS OF EQUIPMENT OTHER THAN AS SPECIFIED SHALL BE THE COMPLETE RESPONSIBILITY OF THE CONTRACTOR, ANY ADDITIONAL ELECTRICAL, STRUCTURAL, MECHANICAL, OR ARCHITECTURAL REQUIREMENTS SHALL BE PROVIDED AT NO ADDITIONAL EXPENSE TO THE OWNER.

4. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE ALL NECESSARY OFFSETS. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR CONSTRUCTION DETAILS.

5. REFER TO PROJECT MANUAL (SPECIFICATIONS) FOR ADDITIONAL REQUIREMENTS. PLANS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER.

PROVIDE ALL WORK CALLED FOR IN EITHER. IN CASE OF CONFLICT BETWEEN SPECIFICATIONS AND PLANS THE MORE STRINGENT SHALL APPLY.

6. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION SHALL BE COVERED AND PROTECTED FROM RAIN, DIRT, DUST, AND

DAMAGE.

7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/ GENERAL CONTRACTOR AND OTHER TRADES TO ALLOW FOR REQUIRED MECHANICAL EQUIPMENT CLEARANCES.

8. PROVIDE AN UNOBSTRUCTED PASSAGEWAY MEASURING NO LESS THAN 36" WIDE BY 80" HIGH FROM DOOR INTO THE SPACE TO SERVICEABLE MECHANICAL EQUIPMENT. A LEVEL WORKING SPACE MEASURING NO LESS THAN 30" WIDE BY 36" DEEP MUST BE PROVIDED IN FRONT OF CONTROL

SIDE OF EQUIPMENT FOR SERVICING.

9. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET

MECHANICAL WORK AS REQUIRED.

10. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION STANDARDS AND CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SHOP FABRICATION AND/OR FIELD INSTALLATION. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER.

11. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE PROVIDED BY THE CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE, INSTALLED, AND FULLY FUNCTIONAL PRIOR TO FINAL ACCEPTANCE OF THE WORK.

12. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. ANY CONFLICTS BETWEEN THE MANUFACTURERS DOCUMENTATION AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.

13. DO NOT ALLOW ANY WORK TO BE COVERED UP OR ENCLOSED UNTIL INSPECTED, TESTED AND APPROVED BY OWNER'S REPRESENTATIVE OR

AUTHORITY HAVING JURISDICTION.

14. MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY HEATING OR COOLING DURING CONSTRUCTION.

15. PIPES AND WIRING IN PLENUM SHALL BE RATED FOR PLENUM USE. PVC, ABS, AND PLASTIC PIPING IS NOT ACCEPTABLE IN PLENUM APPLICATIONS.

16. ALL DETAILS ARE TYPICAL UNLESS NOTED OTHERWISE.

DESIGN CONDITIONS

OUTDOORS

VENTILATION

INDOOR

ELEVATION

COOLING

HEATING

COOLING

HEATING

USDA ARS 242.1M 2024

250 FT ABOVE SEA LEVEL

LOCATION CORVALLIS, OR

CLIMATE ZONE 4C (BENTON COUNTY)

92.7°F DB / 67.0°F WB

11.8°F DB

72°F

68°F www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:1

:5

P

M

02/04/2026

TAH

PJTM

230612

M-001

MECHANICAL

LEGENDS AND

ABBREVIATIONS

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

MECHANICAL SHEET INDEX

SHEET NUMBER SHEET NAME

M-001 MECHANICAL LEGENDS AND ABBREVIATIONS

MD-101 FIRST FLOOR PLAN WEST MECHANICAL DEMO PLAN

MD-102 SECOND FLOOR PLAN WEST MECHANICAL DEMO PLAN

MD-103 MECHANICAL ROOF DEMO PLAN

M-201 FIRST FLOOR WEST ZONE PLAN

M-202 SECOND FLOOR WEST ZONE PLAN

M-203 FIRST FLOOR WEST MECHANICAL PLAN

M-204 SECOND FLOOR WEST MECHANICAL PLAN

M-205 MECHANICAL ROOF PLAN

M-501 MECHANICAL DETAILS

M-701 MECHANICAL CONTROLS

M-702 MECHANICAL SCHEDULES

04 16

M

A B C D

OFFICE

TECHNICIAN'S OFFICE

OFFICE

LAB

110 PREP ROOM

COLD ROOM

LAB

LAB

OFFICE

HALLWAY

EQUIPMENT ROOM

MECHANICAL ROOM

JANITOR

ELEVATOR EQUIP.

ELECTRICAL ROOM

RECEPTION/OFFICE

VESTIBULE

HALLWAY

MENS

WOMENS

(E) AIR SEPARATOR

FD

T

T

T

T T T HC-6HC-1

HC-2

HC-3

12x6

8ø

8ø x1 x1

10ø

8ø x6

12ø ø ø ø

36x14 24 x1 x1

12x6

24x18

8ø x1

6ø ø ø

10ø x1

8ø

24x10

12ø

12ø ø

9ø

10ø

6ø x1 x6

8ø

8ø

10ø

10ø

10ø 18x16 x1

18x10 12x8

S-190

S-320

T-190

S-160

S-430

S-430

S-430

S-430

S-170

S-170

S-410

S-600

S-230

S-200

T-300R-900

S-260

S-260

S-120

E-300

T-300

E-50

T-170

T-170

T-230

12x8

T-230

S-150

T-190

T-160

T-160

T HC-5

(E) HC-3

(E) HC-4

(E) SF-1 M

(E) HC-4

(E) HC-6

(E) HC-2

(E) HC-1

(E) B-1

(E) EF-3

(E) 12x12 LOUVER(E) 28x20 COMBUSTION

AIR LOUVERS (ONE

HIGH, ONE LOW)

(E) HC-5

(E) FILTER RACK

(E) 12x12 LOUVER

THIS UNIT

ABANDONED

IN PLACE

SP

6YCSTN

FUME HOOD

ENVIRO

CHAMBER

INCUBATOR

LAMINAR

FLOW HOOD

-80C

FREEZER

AUTOCLAVE

STEAM

WASHER

FRIDGES

FUME HOOD

BIOSAFETY

CABINET

INCUBATOR

ENVIRO

CHAMBER

FREEZER

M

(E) HWP-1

GENERAL NOTES

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER

PROVIDED RECORD DRAWINGS DATED 06-01-93 AND THROUGH

FIELD OBSERVATIONS. VERIFY EXISTING CONDITIONS AS THEY

APPLY TO THIS PROJECT AND INCLUDE IN BID A SUFFICIENT

ALLOWANCE TO COVER ANY DISCREPANCY BETWEEN THE

DRAWINGS AND THE ACTUAL CONDITIONS AS THEY CURRENTLY

EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS

SHOWN WITH BOLD BROKEN LINES, TYP.

C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL

EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE

USE.

D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS

WITH OWNER.

E. AIRFLOWS SHOWN ON DEMO SHEETS CORRESPOND WITH

PREVIOUS DESIGN AND TAB REPORTS.

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:1

:5

P

M

02/04/2026

TAH

PJTM

230612

MD-101

FIRST FLOOR PLAN

WEST MECHANICAL

DEMO PLAN

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

1/4" = 1'-0"

FIRST FLOOR PLAN WEST MECHANICAL DEMO PLAN

KEY NOTES

1 LOCATE AND DEMOLISH EXISTING MOTORIZED DAMPER AND

STATIC PRESSURE SENSOR. DUCT WILL BE RECONNECTED

WITH NEW EXHAUST TERMINAL UNIT.

05 16

OFFICE

TECHNICIANS OFFICE

OFFICE

STORAGE

LAB

LAB

LAB

PREP ROOM

COLD ROOM

EQUIPMENT ROOM

OFFICE

HALLWAY

CONFERENCE ROOM

HALLWAY

HALLWAY

12x8

12x6 x6

10ø

10ø x1 x1

8ø

8ø ø ø ø ø

12ø

8ø x6 ø x1

24x16 x1 x1

36x18 x1 x1

10ø 8ø x1 x1

9ø

18x10

18x10 x8

18x10 18x10

18x14 x1 x1 x1 ø

10ø ø ø ø

22x12

8ø

9ø ø

24x16 x1 x1

12ø

10ø ø

10ø

10ø 18x18

10ø

8ø

S-210

T-210

T-210

S-505

S-505

S-505

S-505

S-350

S-180

T-180

T-180

S-140 S-140

S-280

S-250

R-560

R-525

S-300

S-400

S-365S-365

S-170

R-730

R-0

R-0

8ø

THC-8

T

HC-7

T HC-12

T

HC-13

T

HC-10

T SF-2

THC-9

3/4"

3/4"

3/4"

1"

1 1/4"

2"

2"

3/4"

2"

3/4" 3/4"

HC-9

(E) HC-11

HC-10

(E) HC-8

(E) HC-7

(E) HC-13

(E) HC-14

S-275

S-240

T-240

T-240

S-630

S-500

S-170

T-170

T-170

M

UP TO

RTU-6

UP TO RTU-5

(E) HC-12

10" SS FUME HOOD

EXHAUST UP TO

ROOF, TYP. 7

(E) 12x12 LOUVER

(E) FILTER RACK

THIS UNIT

ABANDONED

IN PLACE

SP

INCUBATOR

FRIDGE/FREEZER

SAFETY

CABINET

SPECTROMETER

MICROWAVE

REACTION

SYSTEMFUME HOOD

ARGON

TANKS

CORROSIVE

STORAGE

FUME HOOD

FUME HOOD

LECO

TENNEY

EQUITY

LAMINAR

FLOW HOOD

GROW

RACK

FLAM

GENERAL NOTES

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER

PROVIDED RECORD DRAWINGS DATED 06-01-93 AND THROUGH

FIELD OBSERVATIONS. VERIFY EXISTING CONDITIONS AS THEY

APPLY TO THIS PROJECT AND INCLUDE IN BID A SUFFICIENT

ALLOWANCE TO COVER ANY DISCREPANCY BETWEEN THE

DRAWINGS AND THE ACTUAL CONDITIONS AS THEY CURRENTLY

EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS

SHOWN WITH BOLD BROKEN LINES, TYP.

C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL

EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE

USE.

D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS

WITH OWNER.

E. AIRFLOWS SHOWN ON DEMO SHEETS CORRESPOND WITH

PREVIOUS DESIGN AND TAB REPORTS.

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:1

:5

P

M

02/04/2026

TAH

PJTM

230612

MD-102

SECOND FLOOR

PLAN WEST

MECHANICAL

DEMO PLAN

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

1/4" = 1'-0"

SECOND FLOOR PLAN WEST MECHANICAL DEMO PLAN

KEY NOTES

1 EXISTING DUCT UP TO ROOF IS CURRENTLY CAPPED BELOW

ROOF INFILL. REMOVE CAP AND PREPARE THE DUCT TO

CONNECT TO NEW EXHAUST FAN.

2 LOCATE AND DEMOLISH EXISTING MOTORIZED DAMPER AND

STATIC PRESSURE SENSOR IN CEILING SPACE. DUCT WILL BE

RECONNECTED WITH NEW EXHAUST TERMINAL UNIT. REMOVE

EXISTING ACOUSTIC GPY. BOARD FROM AROUND DUCTWORK

AS NECESSARY TO REPLACE THE TERMINAL UNIT.

06 16

A B C D D.2 D.5 D.7 E

(E) ROOF DRAINS

(E) PLUMBING VENT(E) HYDRONIC

BOILER VENT

(E) PLUMBING

VENT

(E) ROOF DRAIN

(E) PLUMBING

VENT

(E) PLUMBING

VENT

(E) PLUMBING

VENT

(E) STEAM

BOILER FLUE

STACK

(E) PLUMBING

VENT

(E) CU

(E) PLUMBING

VENT

(E) PLUMBING

VENT

(E) PLUMBING

VENT

(E) EF-4

(E) EF-5

(E) EF-6

(E) EF-7

(E) EF-8

(E) EF-9

(E) RTU-6

(E) CU

(E) CU

(E) RTU-4

(E) CU

(E) RTU-2

(E) EF-2

(E) EF-4

(E) EF

(E) CU

(E) RTU-1

(E) EF-1(E) EF-3

(E) RTU-3

(E) RTU-5

GENERAL NOTES

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER

PROVIDED RECORD DRAWINGS DATED 06-01-93 AND THROUGH

FIELD OBSERVATIONS. VERIFY EXISTING CONDITIONS AS THEY

APPLY TO THIS PROJECT AND INCLUDE IN BID A SUFFICIENT

ALLOWANCE TO COVER ANY DISCREPANCY BETWEEN THE

DRAWINGS AND THE ACTUAL CONDITIONS AS THEY CURRENTLY

EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS

SHOWN WITH BOLD BROKEN LINES, TYP.

C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL

EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE

USE.

D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS

WITH OWNER.

E. AIRFLOWS SHOWN ON DEMO SHEETS CORRESPOND WITH

PREVIOUS DESIGN AND TAB REPORTS.

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:1

:5

P

M

02/04/2026

TAH

PJTM

230612

MD-103

MECHANICAL ROOF

DEMO PLAN

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

3/16" = 1'-0"

MECHANICAL ROOF DEMO PLAN

KEY NOTES

1 CREATE ROOF OPENING AS NECESSARY TO ACCESS EXISTING

CAPPED DUCTWORK AND INSTALL NEW EXHAUST FAN CURB.

07 16

OFFICE

TECHNICIAN'S OFFICE

OFFICE

LAB

LAB

LAB

OFFICE

EQUIPMENT ROOM

COLD ROOM

PREP ROOM

HALLWAY

JANITOR

ELEVATOR EQUIP.

MECHANICAL ROOM

ELECTRICAL ROOM

RECEPTION/OFFICE

VESTIBULE

HALLWAY

MENS

WOMENS

T

T

HC-02

HC-03 T HC-01

T HC-06

T SF-01

T HC-04

T HC-05

DP +-

(N) ETU-1

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:2

:2

A M

02/04/2026

TAH

PJTM

230612

M-201

FIRST FLOOR WEST

ZONE PLAN

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

1/4" = 1'-0"

FIRST FLOOR WEST ZONE PLAN

KEY NOTES

1 INSTALL NEW DIFFERENTIAL PRESSURE SENSOR ABOVE

EXISTING DOORWAY BETWEEN LABORATORY AND HALLWAY.

SENSOR SHALL CONNECT TO THE BAS AND WILL BE USED TO

CONTROL ETU AIRFLOW SETPOINT. SEE 4/M-501.

2 EXISTING THERMOSTAT FOR EXHAUST FAN

ABANDONED-IN-PLACE. SHOWN FOR CLARITY, NO SCOPE IN

THIS PROJECT.

08 16

OFFICE

TECHNICIANS OFFICE

OFFICE

LAB

LAB

LAB

OFFICE

EQUIPMENT ROOM

COLD ROOM

PREP ROOM

STORAGE

HALLWAY

HALLWAY

HALLWAY

CONFERENCE ROOM

T HC-08

T HC-09

T HC-07

T HC-12

T HC-14T HC-13

T SF-2

T HC-10

T HC-11

DP +-

(N) ETU-2

www.coffman.com

221 N. Wall Street, Suite 500

Spokane, WA 99201 ph 509.328.2994

SHEET OF

DATE

CHECKED

DRAWN

PROJ. NO.

A

B

D

54321

D

C

B

A

1 2 3 4 5

SHEET NO:

SHEET TITLE:

C

EE

COFFMAN ENGINEERS INC.C

/3

/2

:2

:2

A M

02/04/2026

TAH

PJTM

230612

M-202

SECOND FLOOR

WEST ZONE PLAN

FINAL

TURNOVER

HORTICULTURAL

CROPS RESEARCH

LAB

USDA ARS

LABORATORY

EXHAUST

3420 NW ORCHARD AVE.,

CORVALLIS, OR 97331

REV DATE DESCRIPTION

1/4" = 1'-0"

SECOND FLOOR WEST ZONE PLAN

KEY NOTES

1 INSTALL NEW DIFFERENTIAL PRESSURE SENSOR ABOVE

EXISTING DOORWAY BETWEEN LABORATORY AND HALLWAY.

SENSOR SHALL CONNECT TO THE BAS AND WILL BE USED TO

CONTROL ETU AIRFLOW SETPOINT. SEE 4/M-501.

2 EXISTING THERMOSTAT FOR EXHAUST FAN

ABANDONED-IN-PLACE. SHOWN FOR CLARITY, NO SCOPE IN

THIS PROJECT.

09 16

A. INSTALL NEW EXHAUST…