Building Descriptions and Structures 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf
PDF 909 KB Posted
- Attached to
- Timber Lake Job Corps Center Multiple Building Electrical System Evaluation Federal contract opportunity
- Solicitation number
- 1282A722Q0016
- Issued by
- Department of Agriculture Forest Service
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Revised Statement of Work 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf | ||
| SF 30 Amendment 0001 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf | ||
| Combined Synopsis Solicitation 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf | ||
| Vicinity Map 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf | ||
| Service Contract Act Wage Det1282A722Q0016 Timber Lake Job Corps Center Building. 1467 Freezer Cooler Door Replacement.pdf | ||
| Statement of Work 1282A722Q0016 Timber Lake JCC Multiple Building Electrical System Evaluation.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building Descriptions and Structures TIMBER LAKE Civilian Conservation Center
BUILDING 1637 - VOCATION
Building Descriptions Date: 04/12/2018Center : Timber Lake (01009) Page: 46 of 137
Building: 1637 - VOCATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Cast Concrete Stucco Wood Siding
Wall Roof Batt Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Factory/Industrial 12,648 10,821 1 Owned 1965 Not Evaluated
Comments: The entrance to Business Office Technology is not accessible. There are no audio/visual devices in the public toilet rooms.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
No
No
N/A
N/A
Yes
No
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
The remaining life expectancy is based on visual observation and condition of the roof during the November 2017 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1997 3 Gable Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Entire Building
Area Served
Page: 47 of 137
Building: 1637 - VOCATION
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Concrete Drywall Plywood
Metal Rollup - Metal Frame Metal Unit - Metal Frame
Wood Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Steps Comments: Concrete steps lead to east side entries
Metal Overhead - Metal Frame Metal Unit - Metal Frame Wood Overhead - Steel Frame
Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;
Sliding - Aluminum Frame; Single Glazing; Sliding - Vinyl Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plywood
Number of Deficiencies = 1
Exterior Doors5. Number of Deficiencies = 1
Windows6.
Floors1. Number of Deficiencies = 2
Interior Walls2.
3.
Interior Doors4.
Ceilings
Page: 48 of 137
Building: 1637 - VOCATION
Mechanical
Mechanical
Dust Collection
Restroom
Welding Booths
Shop Area
Comments:
Comments:
The sixteen welding shop booths have individual exhaust hoods and natural ventilation make-up air.
There are multiple roof-mounted exhaust fans such that each fan is connected to two hoods.
The system has nine branch drops, five of which are capped.
Ventilation Area Served
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Natural None Classrooms and Offices
Exhaust Ventilation
There is one heat pump system (Lennox #HP235131Y outdoor, #CB19512P indoor, 4 ton).Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The radiant heating units were manufactured by Radiant Optics, Inc.
There is one heat pump system (Lennox #HP235131Y outdoor, #CB19512P indoor) with an approximate capacity of 48 MBH. The heat pump also utilizes a 25 kW supplemental electric heater.
Comments:
Comments:
HVAC
Heat1.
Electric Resistance
Electric Resistance
Split Heat Pump (Air
Source)
Electric Resistance
Radiant Ceiling Units
Unit Heater
Single Duct
Wall Heater
None
None
Refrigerant
None
Electric
Electric
Electric
Electric
Natural
Natural
Natural
Natural
None
None
None
None
Shop Area
Shop Area
Classrooms and Offices
Classrooms and Offices
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 49 of 137
Building: 1637 - VOCATION
Cast Iron None None
Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Service Sink Sink Urinal Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: Overhead service is provided from a pole-mounted transformer located to the back of the building. Service terminates in the 1200A, 480V rated switchboard with four service rated switches, three 400A switches and one 200A switch, with two switches fused at 400A, one at 225A and one 200A switch. The 400A and 225A fused switches serve 400A and one 225A panels, providing 480V power for the welding shop. The 400A and 200A fused switches serves one 400A and one 200A, 480V panels located in the electrical room. The 400A and 200A panels, located in the electrical room, serves (2) 75 kVA transformers, providing 120/208V loads in the welding and carpentry shop, and one 45 kVA, and two 15 kVA transformers providing for 120/208V loads in the rest of the building. Carpentry shop has only by 120/208V power.
Copper Copper/Galvanized Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: The building-mounted site lighting is photocell controlled.
Switchboard 277/480V, 3-Phase, 4 Wire Switchboard, Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 7
Exterior Lighting1.
LIGHTING
Page: 50 of 137
Building: 1637 - VOCATION
FIRE ALARM
Comments: The fire alarm devices in the building are controlled and monitored by the fire alarm control/annunciator panel (Silent Knight SK-4) located in Building 2304.
Comments: The building is connected to the Center's LAN system. The telephone system intercom feature is utilized for public address notifications.
Audible Alarm Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None Connected to Main System TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Comments:
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T12 - Fluorescent
T12 and T8 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T5 - Fluorescent
T8 - Fluorescent
Offices
Offices
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Storage Rooms
Classrooms
Classrooms
Vocational
Vocational
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup Emergency Exit
Number of Deficiencies = 3
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 2
COMMUNICATION
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Type Location N/A N/A
There is no fuel operating equipment in the building.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
Page: 51 of 137
Building: 1637 - VOCATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Roof is nearing end of useful life.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Poor
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 2818 - PAINTER'S CLASSROOM
Page: 82 of 137
Building: 2818 - PAINTER'S CLASSROOM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 800 714 1 Owned 1990 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
N/A
Yes
N/A
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Roof has skylights in the classroom that occassionally leak. Roof also leaks. The remaining life expectancy is based on visual observation and condition of the roof during the November 2017 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1990 0 Gable Entire Building
Number of Deficiencies = 1
Comments:
3. Roof
Page: 83 of 137
Building: 2818 - PAINTER'S CLASSROOM
Comments: Seals are failing at thermo-pane window gaskets.
INTERIOR FINISH
Carpet Vinyl Tile
Drywall
Wood Unit - Wood Frame
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
Fixed - Wood Frame; Double Glazing; Skylight - Metal Frame; Single Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Office is served by a Freidrich window unit
The one heat pump (15 MBH) serves the one classroom which also utilizes a supplemental electric heater.
Comments:
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Electric Resistance
Through-The- Wall Unit
Wall Heater
None
None
Electric
Electric
Mechanical
Natural
None
None
Classrooms
Offices
Ventilation2.
Page: 84 of 137
Building: 2818 - PAINTER'S CLASSROOM
None None None
None
Comments: There is no drinking fountain.
None
None None ABC Type Fire Extinguisher
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Heat Pump (Air
Source)
Through-The- Wall Unit
Refrigerant Electric Natural None Classrooms
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Office is served by a Freidrich window unit
The one heat pump (1-1/4 ton) serves the one classroom
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
Page: 85 of 137
Building: 2818 - PAINTER'S CLASSROOM
Comments: Overhead service is provided from a pole-mounted transformer and utility meter with a 200A loadcenter in the same enclosure. The loadcenter has a 200A circuit breaker providing for a 200A MCB main panelboard located in Painter Classroom Building 2818. Two 20A circuit breakers in the pole-mounted loadcenter serve Flammable Storage Structure 2317 and Fuel Monitoring Structure 2957.
FIRE ALARM
Comments: The fire alarm devices in the building are controlled and monitored by the fire alarm control/annunciator panel (Silent Knight SK-4) located in Building 2304.
Comments: The building is connected to the Center's LAN system. The telephone system intercom feature is utilized for public address notifications.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None Connected to Main System TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Comments: The expiration date of the tritium gas exit sign is April 2019. Battery backup exit fixtures are also utilized.
Compact Fluorescent Light Emitting Diode (LED) Comments: Building-mounted site lighting is controlled by fixture-mounted photocells.
T12 - Fluorescent
T12 - Fluorescent
Offices
Classrooms
Area Recommended Level
Recorded Level Light Type
None Tritium Gas
Main Panelboard 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Electric Water Gas N/A N/AZone
BUILDING UTILITY METERING
Type Location N/A N/A
There is no fuel operating equipment in the building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Page: 86 of 137
Building: 2818 - PAINTER'S CLASSROOM
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Roof is leaking.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 2819 - PAINTER'S BUILDING
Page: 87 of 137
Building: 2819 - PAINTER'S BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Loadbearing Masonry Wood
Stucco
Wall Roof Unknown Batt
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business 1,030 739 1 Owned 1965 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
N/A
No
No
N/A
N/A
Yes
N/A
N/A
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The remaining life expectancy is based on visual observation and condition of the roof during the November 2017 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Asphalt Shingles Gutters and Downspouts 1997 3 Gable Entire Building
Comments:
3. Roof
Page: 88 of 137
Building: 2819 - PAINTER'S BUILDING
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
CMU Concrete Drywall
Metal Unit - Metal Frame Metal Unit - Wood Frame
Mechanical
Mechanical
Restroom
Paint Storage
Ventilation Area Served
VERTICAL CIRCULATION
None
Sliding - Aluminum Frame; Single Glazing;
Gypsum Board Plaster
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1. Number of Deficiencies = 3
Electric Hot Water Boiler
Single Duct Two-Pipe Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 1
Page: 89 of 137
Building: 2819 - PAINTER'S BUILDING
The water heater was built by Reliance (#6522ORT2, 50 gallon, 4.5 kW).Comments:
Cast Iron and Galvanized None None
Emergency Eye Wash Hose Bibb Lavatory Multi-Compartment Service Sink Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: Overhead service is provided from a pole-mounted transformer and utility meter and serves a 200A main panelboard with a 200A main circuit breaker located in the mechanical room. Explosion proof electrical air heater (FX5-208-260-150-WT-15 kW) is utilized in the paint shop area.
Copper/Galvanized Copper/Galvanized Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None None None None Natural None Entire Building
High Intensity Discharge (HID) Comments: Building-mounted site lighting is controlled by a time clock.
Main Panelboard 120/208V, 3-Phase, 4 Wire Service Equipment Only Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 2
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
LIGHTING
Page: 90 of 137
Building: 2819 - PAINTER'S BUILDING
FIRE ALARM
Comments: The fire alarm devices in the building are controlled and monitored by the fire alarm control/annunciator panel (Silent Knight SK-4) located in Building 2304. Explosion proof heat detectors and pull stations are utilized in the building. Audio/visual device is provided on the building exterior.
External Audible/Visual Alarm Heat Detector Manual Pull Station
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. In the paint shop and paint storage the light fixtures and light switches are explosion proof.
Comments: Explosion proof exit signs and battery backup explosion proof fluorescent light fixtures are utilized in the building. One photoluminescent type exit sign is provided above the paint shop south exit.
Incandescent+CFL
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Vocational
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Battery Backup Emergency Exit
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
15 KW electric heater was offline at the time of survey; replacement part had been ordered.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Good
Type Location N/A N/A
There is no fuel operating equipment in the building.
CARBON MONOXIDE DETECTION
Detection Required No
IMPAIRMENT
Page: 91 of 137
Building: 2819 - PAINTER'S BUILDING
IMPAIRMENT
Potentially Impaired
DOL Responded