Brand Name Justification.pdf
PDF 176 KB Posted
- Solicitation number
- 36C24826Q0138
About this file
This Justification for Other Than Full and Open Competition (JOFOC) details the Department of Veterans Affairs' procurement of brand-name Square D electrical distribution components for the Malcom Randall VA Medical Center in North Florida/South Georgia. The VA requires two Square D WA6AAR74A3CFFFWSXA 800A draw-out circuit breakers and six Square D S144A Micrologic 6.0A trip units to restore emergency electrical system redundancy after a water intrusion incident that damaged equipment in Main Switchgear B. The estimated procurement value is $72,054.00, and the acquisition will be conducted as an open-market commercial products procurement under FAR Part 12.
The document justifies sole-source procurement from Square D because its components are the only physically and electrically compatible parts for the existing switchgear, and using non-original equipment manufacturer (non-OEM) components would void UL ratings, violate safety standards, and potentially compromise critical hospital operations. Market research confirmed that only Square D components meet the facility's requirements, and while multiple authorized distributors exist, all must provide OEM parts. The contracting officer will seek competition among authorized Square D distributors to the maximum extent practicable and will evaluate pricing for fairness using historical data, OEM information, and competitive quotes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24826Q0138_1.docx | DOCX document | |
| RFQ Attachment.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JUSTIFICATION FOR OTHER THAN FULL AND OPEN COMPETITION
(FAR 6.303–2)
For Brand-Name Required, Open-Market Procurement
Malcom Randall VA Medical Center – NF/SGVHS
1. Agency and Contracting Activity
The Department of Veterans Affairs, Veterans Health Administration, North Florida/South
Georgia Veterans Health System, Malcom Randall VA Medical Center, submits this
Justification for Other Than Full and Open Competition (JOFOC) for the procurement of brand-name Square D electrical distribution components for Main Switchgear B.
2. Nature and/or Description of the Action Being Approved
This justification approves the use of other than full and open competition for the procurement of brand-name Square D WA6AAR74A3CFFFWSXA draw-out circuit breakers and Square D S144A Micrologic 6.0A trip units. These supplies are required to restore emergency electrical system redundancy at the Malcom Randall VA Medical Center. The acquisition will be conducted as an open-market commercial products procurement under
FAR Part 12.
3. Description of Supplies or Services Required
The VA requires brand-name Square D WA6AAR74A3CFFFWSXA 800A draw-out circuit breakers (2 each) and Square D S144A Micrologic trip units (6 each) to restore the emergency spare inventory consumed during restoration efforts following a water intrusion incident. These items are essential to ensuring safe operation of Main Switchgear B, which supports critical hospital electrical distribution systems. The estimated value of this procurement is $72,054.00.
4. Statutory Authority Permitting Other Than Full and Open Competition
This procurement is authorized under FAR 6.302-1, Only One Responsible Source and No
Other Supplies or Services Will Satisfy Agency Requirements. Only OEM Square D components are compatible with the facility’s existing Square D WA-series switchgear.
5. Demonstration That the Contractor’s Unique Qualifications or the Nature of the
Acquisition Requires Use of the Authority Cited
Square D is the original manufacturer of the switchgear installed at Malcom Randall VAMC.
Its breaker frames, control wiring, racking assemblies, trip units, and protective relay interfaces are proprietary. No other manufacturer produces physically or electrically compatible components. Use of non-OEM components would void UL ratings, violate NFPA
70 and NFPA 99, compromise arc-flash safety, and jeopardize critical hospital operations.
6. Description of Efforts Made to Solicit Offers From as Many Offerors as Practicable
Market research was conducted consistent with FAR Part 10. Research confirmed the items are not available on GSA or FSS contracts but can be purchased on the open market from multiple authorized distributors. Competition will be sought among authorized Square D distributors to the maximum extent practicable.
7. Determination of Fair and Reasonable Cost
The estimated cost of $72,054.00 is based on a market research quote from an authorized distributor. Additional quotes will be solicited from other authorized Square D vendors.
Pricing will be evaluated for fairness and reasonableness using historical pricing, OEM data, and competitive quotes.
8. Market Research
Market research confirmed that only brand-name Square D components are compatible with the existing switchgear. Multiple commercial distributors exist, but all must provide
OEM Square D components. No equal or substitute items exist.
9. Any Other Supporting Facts
A water intrusion event on October 27, 2025 damaged multiple breakers within Main
Switchgear B. The facility used its only OEM spare breakers to restore power and currently has no replacement units available. The absence of spares poses a significant risk to hospital operations and patient safety in the event of another electrical failure.
10. Statement of Actions to Remove Barriers for Future Competition
This brand-name restriction is due to existing proprietary equipment. Future switchgear upgrades may allow for open competition. No unnecessary barriers are created by this action.
11. Technical Certification
Engineering Service certifies that only OEM Square D components satisfy the facility’s technical and safety requirements for this application.
12. Contracting Officer Certification
The Contracting Officer certifies that this justification is accurate and complete to the best of their knowledge.
Approved By:
John H. Shultzaberger
Contracting Officer
| 2025-12-02T07:38:02-0500 | |
| JOHN SHULTZABERGER |
File details come from the government source that posted it. Updated .