Braidwood UPS Attachment A .xlsx
XLSX spreadsheet 20 KB Posted
- Attached to
- EMA - Braidwood GEMS Facility UPS - 20KVA
- Solicitation number
- 23-588IEMA-DIVNU-B-34496
- Issued by
- Illinois
About this file
This document contains the technical specifications for a 20 kVA / 18 kW Eaton 9355 uninterruptible power supply (UPS) system required for the Braidwood Nuclear Generating Station. The UPS system must have double conversion topology, a 208/120V 3-phase, 4-wire (plus ground) wye input and output, and be able to provide over 100 minutes of backup power at full load. The UPS must have a graphical LCD display, RS-232 and network communications capabilities, and be certified to ISO 9001 standards with a 1-year full parts and labor warranty including 24/7 on-site emergency response.
The vendor awarded this contract must be certified to perform the initial startup of the UPS system per the manufacturer's requirements. The UPS will be installed on-site at the Quad Cities Nuclear Generating Station. The vendor must provide 24/7 technical support for the UPS system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| COVID Standard Terms and Conditions v.20.1~46.pdf | ||
| standard-illinois-certifications-v.23.1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 GEMS UPS Technical Specifications
| Tech Specs | |
| Model | Eaton 9355 |
| Power | |
| Ratings | 20 KVA / 18W @ 0.9 P.F. |
| Topology | Double Conversion |
| Input | |
| Input Voltage | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Input Frequency | 60 Hz ± 5 Hz |
| Voltage Correction Range | 176-228.8V AC |
| Power Factor (Full Load) | 0.99 typical |
| Output | |
| Waveform (On-Line) | Sinewave |
| Waveform (On-Battery) | Sinewave |
| Output Voltage (RMS) | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Output Frequency | 60 Hz |
| Efficiency (Full Load / On-Line) | 91% typical |
| Voltage Regulation | ± 1% |
| Input Current Distortion | < 5% THD |
| Overload Capabilities | 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) |
| Battery | |
| Battery Type | VRLA, 9AH, maintenance free (Field replacable) |
| Typical Backup Time (Full Load) | > 100 min @ full load (> 10 hours @ 15% full load) |
| Operation / General | |
| Diagnostics | Full system self-test @ startup |
| UPS Bypass | Automatic on overload or UPS failure |
| On-Line Transfer Time | 1 ms typical |
| Audible Noise (Full Load @ 1m) | < 58 dBA |
| Communications | |
| Minimum Requirements | Graphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card |
| Network type | Factory Installed MS Network Card (SNMP) |
| Certifications | |
| Quality | ISO 9001 |
| Warranty | |
| Standard | 1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification. |
| Customer Service | |
| Initial Start Up | Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Quad Cities Nuclear Generating Station |
| Tech Support Availability | 24/7 (Unlimited) |