This document contains the technical specifications for a 20 kVA / 18 kW Eaton 9355 uninterruptible power supply (UPS) system required for the Braidwood Nuclear Generating Station. The UPS system must have double conversion topology, a 208/120V 3-phase, 4-wire (plus ground) wye input and output, and be able to provide over 100 minutes of backup power at full load. The UPS must have a graphical LCD display, RS-232 and network communications capabilities, and be certified to ISO 9001 standards with a 1-year full parts and labor warranty including 24/7 on-site emergency response.

The vendor awarded this contract must be certified to perform the initial startup of the UPS system per the manufacturer's requirements. The UPS will be installed on-site at the Quad Cities Nuclear Generating Station. The vendor must provide 24/7 technical support for the UPS system.

View the file

Other files

File Type Posted
COVID Standard Terms and Conditions v.20.1~46.pdf PDF
standard-illinois-certifications-v.23.1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Power
Ratings20 KVA / 18W @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion< 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 100 min @ full load (> 10 hours @ 15% full load)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Quad Cities Nuclear Generating Station
Tech Support Availability24/7 (Unlimited)